                                                                                                   P17/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.17/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

USER MANUAL 

ATS-I 

REV1 

 


background image

 

                                                                                                   P18/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.18/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

 

Index 

 
General description ......................................................................................................... 19

 

Electrical specifics ........................................................................................................... 19

 

Device operative logic ..................................................................................................... 20

 

Manual mode ............................................................................................................... 20

 

Automatic mode ........................................................................................................... 21

 

Alarms ......................................................................................................................... 21

 

Display......................................................................................................................... 22

 

Automatic transfer switch procedure mains-generator, generator-mains...................... 24

 

Parameters Programmation ......................................................................................... 26

 

Phase detection special function.................................................................................. 27

 

Mechanical Sizing ........................................................................................................... 28

 

Rear View........................................................................................................................ 29

 

Triple phase wiring diagram (230Vac, 400Vac, 440Vac) ................................................. 30

 

Single phase wiring diagram (230Vac) ............................................................................ 31

 

 

 


background image

 

                                                                                                   P19/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.19/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

General description 

 
ATS-I  controller  allows  an  automatic  transfer  switch  commutation  between  mains  and 
generator. 
In automatic mode, when faulty mains conditions are detected, the board sends a remote 
start signal to the engine; when generator is running, the phase sequence is checked, if 
voltage  and  frequency  measurements  are  compatible  with  programmed  values,  the 
changeover switch is activated towards generator side. 
When mains voltage returns back, transfer switch returns on mains side and generator is 
stopped. 

  

 

Electrical specifics 

 

Supply voltage (isolated) 

8 ÷ 30 Vdc 

Voltage measurements 

230Vac 1ph 
230Vac 3ph 
400Vac 3ph 
440Vac 3ph 

Frequency measurements 

45 ÷ 65 Hz 

Generator voltage range 

0 ÷ 500 Vac 

Mains voltage range 

0 ÷ 500 Vac 

Measurements precision 

± 2% 

Input LA 

10 ÷ 30 Vdc 

Input LM 

10 ÷ 30 Vdc 

Input LR 

0 ÷ 500 Vac 

Input LG 

0 ÷ 500 Vac 

Output  START GEN. 

5A, 10 ÷ 30 Vdc 

Output  TLR 

5A, 230 Vac 

Output  TLG 

5A, 230 Vac 

Maximum reaction time for VF measurements 

2 sec. 

Maximum phase detection delay 

1 sec. 

 

 


background image

 

                                                                                                   P20/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.20/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Device operative logic 

 
There are two operative modes:  
 

-  Manual 
-  Automatic 

 
At the startup, device selects automatically the correct operative mode in accordance with 
P13 parameter; “Aut/Man” key allows to change operative mode without restriction.  
 
Front view: 

 
Manual mode 
 
In manual mode all system is controlled by ATS-I operative panel, on the left side of the 
display, a label shows the actual operative mode of the device (“ MAN “ or “ AUTO “). 
Start Gen” button allows to start and stop the generator; in case of idle generator, when 
“Start Gen” button is pushed, a blinking key icon will appear near “MAN” indicator to signal 
a  starting  phase  for  generator;  when  running  engine  is  detected,  the  key  become 
permanent.  To  stop  the  engine  “Start  Gen”  key  must  be  pushed  again  (  key  icon  will 
disappear). 
 
To  switch  contactor  status from  mains  to  genset,  push  “Generator”  key:  Generator  icon 
will  appear  near  frequency  indicator,  this  icon  blinks  until  feedback  voltage  is  detected: 
from that moment, the icon becomes permanent. 
Push “Generator” key a second time to disconnect generator line without switching; push 
Mains”  key  to  switch  contactor  status  from  genset  to  mains,  a  icon  will  appear  near 
frequency indicator, this icon blinks until feedback voltage is detected: from that moment, 
the icon becomes permanent. 
On  display  is  possible  to  check  mains  line  voltages,  generator  line  voltages  and 
frequency. 
 

UP 

Aut/Man 

Generator 

Start Gen 

Select Mis 

Down 

LOCK 

Mains 

 


background image

 

                                                                                                   P21/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.21/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

To read mains voltages, push “Select Mis” key until “L” indication will appear on the left 
upper corner;  at this  point  mains  voltages  will  be showed  on  display.  Push “Select Mis” 
again  and  “G”  icon  will  appear;  generator  line  voltages  will  replace  mains  measure.  If 
generator  is  not  running,  “OFF”  icon  will  appear  which  means  unavailable  genset 
measurements. 
The  commutation  is  immediate  (500ms  delay  from  opening  a  contactor  and  closure  the 
other) and a phase sequence check is performed each switching procedure. 
In  manual  mode,  operative  generator  alarms  are  not  detected,  are  available  only 
indicators LA and LM. “M” letter on the right side means single-phase system. 
 
Automatic mode 
 
Automatic  mode  allows  to  manage  engine  and  transfer  switch  completely  by  software 
logic,  it’s  not  possible  to  start  the  generator  or  force  switching  through  operative  board, 
“AUTO” indication will appear on the low left corner. 
However  with  “Select  Mis”  is  still  possible  to  change  displayed  measurements  from  
generator  and  mains.  When  controller  commands  switching  on  mains  or  generator, 
automatically values visible on display change in accordance. 
Each phase is checked separately, so a phase failure will start the automatic intervention 
procedure. 
 
Alarms 
 
If mains measurements are selected, in case of alarm will be possible to see one of these 
messages on the left side of the display : 

-  “LOW VOLT” line voltage below programmed threshold ( P3 parameter ); 
-  “HIGH VOLT” line voltage over programmed threshold ( P4 parameter );  
-  “PH.SEQ.ERR” in case of wrong phase sequence; 

Both alarms cause an automatic intervention procedure. 
 
Generator starting procedure begins after a programmable delay (P7 parameter). 
With running generator, after another programmable timer ( P8 parameter), the controller 
checks  voltage  status  measured  on  alternator  and  in  case  of  anomaly,  one  of  these 
alarms will be showed on display: 

-  “ERROR 1” if generator’s phase voltage is out of limits. ( P5, P6 parameters ). 
-  “ERROR 2” if generator’s frequency is out of limits. ( P12 parameter ). 
-  “ERROR 3” if generator fails to start. 

 
If generator is working correctly, “ERROR 1” or “ERROR 2” alarms are showed if voltage 
or frequency values are out of limits for the duration of programmed time ( P15 parameter) 
 
To  reset  an  alarm  on  display  must  be  used  “Aut/Man”  with  locked  keyboard  (  “LOCK” 
key). The device returns on mains position and restarts commutation procedure towards 
generator. If generator alarm is active and mains voltage returns back, automatically the 
commutation will be switched on mains side. 
 

 


background image

 

                                                                                                   P22/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.22/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Display 
 
Display shows following indications: 

 
Line 1: 

(Example “G400  L1  L2  L3”) this code indicates which line is measured and 

 

the connection type for the device. 

 

 

L230M 

Mains, 230Vac single phase connection 

L230 

Mains, 230Vac three-phase connection 

L400 

Mains, 400Vac three-phase connection 

L440 

Mains, 440Vac three-phase connection 

G230M 

Generator, 230Vac single phase connection 

G230 

Generator, 230Vac three-phase connection 

G400 

Generator, 400Vac three-phase connection 

G440 

Generator, 440Vac three-phase connection 

  

Below the code are displayed the values of measured line voltage. 

 
Line 2: 

(Example  “Vac    384    387    383”)  On  this  line  are  showed  the  values  of  three 

 

measured  voltages,  at  the  beginning  of  the  line  is  displayed  the  unit  of 

 

measure . 

 
Line 3: 

(Example  “Hz    48  | 

   

  “)  on  this  line  is  showed  frequency  value  (Hz) 

 

measured on generator’s phase 1, then after separation bar “ | “ some status 

 

symbols are displayed. 

 

  Generator symbol: is used when commutation is on generator 

side, the icon blinks if feedback is not detected.  
Is alternative with Mains symbol. 

 

Mains  symbol:  is  used  when  commutation  is  on  mains  side, 
the icon blinks if feedback is not detected.  
Is alternative with Generator symbol. 

 

Pad  lock  symbol:  is  used  when  the  keyboard  is  locked  by 
LOCK”  button  keep  pushed  for  more  than  5  seconds,  to 
unlock the keypad, the procedure must be repeated. 

 


background image

 

                                                                                                   P23/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.23/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

 

Symbol input LA active: the symbol is connected with LA input 
which usually means a generator alarm.  

  Symbol  input  LM  active:  the  symbol  is  connected  with  LMA 

input which means running engine. 

 
Line 4: 

On this line are showed information about device’s operative modes. 

 

All available information are listed below: 

 

AUTO 

Indicates  automatic  operative  mode,  alternative  with  
MAN and PROG. 

MAN 

Indicates  manual  operative  mode,  alternative  with 
AUTO and PROG. 

PROG 

Indicates programmation mode, alternative with MAN 
and AUTO. 

 

When  MAN  or  AUTO  modes  are  selected,  indicates 
running generator, blinking during start phase. 

 

When  AUTO  mode  is  selected,  indicates  the 
programmed  delay  time  between  faulty  mains  and 
starting generator (P7 parameter) . 

Pxx xxx:xxx  When  PROG  mode  is  selected,  indicates  parameter 

type  “Pxx”  and  blinks  to  show  that  the  parameter  is 
going  to  be  modified,  the  old  values  (  “xxx:”  )  is 
showed on the left side of the colon, the new one  
( “:xxx” ) on the right side.  

Error 
message 

When AUTO mode is selected, alarm messages are 
displayed  in  accordance  with  chosen  visualization:  
“L” or “G”. 

Vb 

Supply battery voltage 

 

Generator  hour  meter  (AUTO),  enabled  start  signal 
(MAN) 

 

 P 

Generator  partial  hour  meter:  active  if  generator 
contactor is detected (load supplied by generator) 

 

 


background image

 

                                                                                                   P24/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.24/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Automatic transfer switch procedure mains-generator, generator-mains 
 
Initial configuration with mains OK (voltage values inside programmed thresholds) 
 
R = Mains 
G = Generator 
 

 
 
 
When  mains  voltage  is  outside  programmed  limits  (P3  and  P4  parameters)  for  a  delay 
time (P7 parameter), the intervention process starts; at the end of this period, the engine 
is  started  too  and  the  controller  waits  for  stable  measurements  for  a  delay  time  (P8 
parameter), otherwise a “ERROR 3” message will be displayed.  
 
With  stable  voltage  and  frequency  values,  after  a  delay  time  (P10  parameter)  the 
commutation  is  switched  on  generator  side;  if  voltage  check  fails,  “ERROR1”  occurs,  if 
frequency  check  fails,  “ERROR2”  occurs,  if  phase  sequence  detection  fails, 
“PH.SEQ.ERR” occur. In these cases the generator is stopped. Between mains contactor 
opening and generator contactor closure there is constant delay time of 500ms. 
 
Transfer switch remains on generator side until mains voltage returns in a stable way in 
accordance with programmed delay time (P10 parameter). 
 

Switching R-G 

TLR open 

TLG open 

START GEN closed

 

Mains OK 

TLR closed 

TLG open 

START GEN open

 

Starting engine 

TLR closed 

TLG open 

START GEN closed

 

Mains coupling 

TLR closed 

TLG open 

START GEN  closed

 

Generator OK 

TLR open 

TLG closed 

START GEN closed

 

Switching G-R 

TLR closed 

TLG open 

START GEN  closed

 

Mains KO + 
Delay P7 

Generator OK +  

Delay P9 

Delay 500ms 

Delay 500ms 

Mains OK + 

Delay P10 

Delay P11 

 


background image

 

                                                                                                   P25/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.25/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

 
With  mains  ok,  generator  contactor  opens  and  after  500ms  mains  contactor  is  closed. 
After cooling time (P11 parameter) the generator is stopped. 
 
With  running  generator,  if  voltage  and  frequency  value  are  outside  programmed 
thresholds ( P5, P6 and P12 parameters) for a delay time (P15 parameter), the device will 
show an error message and the generator is turned off. In this case with “Aut/Man” key or 
when  mains  returns  back,  the  device  returns  to  the  mains  OK  status  where  generator 
contactor is opened and mains contactor is closed.    

 


background image

 

                                                                                                   P26/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.26/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Parameters Programmation 
 
Parameters  programmation  can  be  performed  without  operative  mode  restriction.  Hold 
UP” and “DOWN” keys at the same time for 5 seconds to open programmation menu; the 
word “PROG” will be displayed with the indication relative to P1 parameter, with “UP” and 
DOWN” keys is possible to scroll all parameters and select the one you need to change 
with  “Select  Mis”  button.  The  chosen  parameter  begins  to  blink  and  will  be  possible  to 
edit  the  value  with  “UP”  or  “DOWN”  keys.  Each  increase/decrease  command,  the  value 
will be modified by 1 unit. Hold the button to raise inc/dec speed by 1 unit every 500ms, 
and after 30 step, by 10 units every second. The old values ( “xxx:” ) is showed on the left 
side of the colon, the new one ( “:xxx” ) on the right side.  
 
To confirm the new value push “Select Mis” key, the parameter finish to blink and will be 
possible to select another value. To exit programmation mode and save changes made, 
hold “UP” and “DOWN” keys at the same time.  
Below a comprehensive list with all parameters. 
 

Par. 

Values range 

(unit) 

Default 

values 

Description 

P1 

230

M

, 230, 400, 

440(V) 

400(V tri 

phase) 

Mains system type, shows nominal voltage and  
“M” symbol which indicates single phase system.  

P2 

50, 60(Hz) 

50(Hz) 

Mains nominal frequency 

P3 

0 ÷ -40(%) 

-15(%) 

Minimum mains voltage (percentage over nominal 
value) 

P4 

0 ÷ +40(%) 

+15(%) 

Maximum mains voltage (percentage over nominal 
value) 

P5 

0 ÷ -40(%) 

-15(%) 

Minimum generator voltage (percentage over 
nominal value) 

P6 

0 ÷ +40(%) 

+15(%) 

Maximum generator voltage (percentage over 
nominal value) 

P7 

1 ÷ 600(s) 

5(s) 

Generator start delay 

P8 

0 ÷ 600(s) 

120(s) 

Maximum engine running detection time 

P9 

1 ÷ 240(s) 

5(s) 

Switching on generator delay 

P10 

1 ÷ 240(s) 

10(s) 

Switching on mains delay 

P11 

1 ÷ 240(s) 

30(s) 

Generator cooling time 

P12 

1 ÷ 5(Hz) 

5(s) 

Generator frequency range 

P13 

0(Manual) 

1(Automatic) 

Operative mode selection at start up 

P14 

0(pad lock) 

1(pad unlock) 

Pad lock at start up 

P15 

1 ÷ 10(s) 

3(s) 

Faulty mains / faulty generator delay. An alarm 
generating condition must be detected for this time 
long.   

P16 

0(Disable) 

1(Enable) 

Phase detection function 

 


background image

 

                                                                                                   P27/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.27/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

 
Voltage threshold limits change with 1% step, delay time change with 1s step, frequency 
range change  with 1  Hz step,  all  other  parameters  have  editing  step  in  accordance  with 
their range values. 
 
 
Special functions: Phase sequence detection, hour meter, battery voltage 
 
Phase  detection  function  can  be  enabled  for  both  mains  and  generator  three-phase 
systems with a special parameter ( P16 parameter). 
The function, in case of the generator, is active both in automatic and manual mode. If in 
automatic, the message "PH.SEQ.ERR" appears and the closure of the relative contactor 
is  inhibited;  if  in  manual,  the  word  doesn’t  appear  but  the  "generator"  icon  remains 
flashing and the closure of the relative contactor is however inhibited. The same function, 
in  case  of  the  mains,  is  active  both  in  automatic  and  manual  mode  and  it’s  the same  in 
both cases: the "mains" icon remains flashing, the "PH.SEQ.ERR” message appears and 
the closure of the relative contactor is inhibited. To reset the alarm can be used “Select 
Mis
” key. Then the device repeats the whole control and switching procedure. 
 
WARNING!!!  If  the  supply  voltage  12/24Vdc  is  not  connected  to  the  board,  the  board 
turns-off; but if the mains voltage is present with board off, the mains contactor is closed 
even if the voltage values and/or the phase sequence are not correct. 
 
 
 

 


background image

 

                                                                                                   P28/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.28/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Mechanical Sizing 

 

 

 


background image

 

                                                                                                   P29/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.29/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Rear View 

 

   + 

8-30VDC 

LA   LM 

GEN.INPUT 

MAINS.INPUT 

T    S    R 

T    S    R 

L    N 

L    N 

START 
GEN. 

TLR 

TLG 

LR 

230-440VAC 

LG 

230-440VAC 

 


background image

 

                                                                                                   P30/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.30/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Three-phase wiring diagram (230Vac, 400Vac, 440Vac) 

 

 


background image

 

                                                                                                   P31/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.31/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

Single phase wiring diagram (230Vac) 

 

 


background image

 

                                                                                                   P32/32    Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc         

Tecnoelettra srl 

Dal 1985 

Via Vioni Dimo,5 42016 S.Rocco di Guastalla (RE) 

Tel.+39.0522.832004 – Fax.+39.0522.832012  P.32/32 

Internet :www.tecnoelettra.it   E-mail:info@tecnoelettra.it 

NOTES: