POOL HEATER 

MODELS: 

CE SERIES 

12, 15 & 18kW 

208V, 240V, 480V 

SINGLE & THREE PHASE 

CPH SERIES 

24 & 30kW 

208V, 240V, 480V 

SINGLE & THREE PHASE 

PHS SERIES 

36, 45, 54 & 57kW 

208V, 240V, 480V 

SINGLE & THREE PHASE 

WARNING 

 

Only qualified personnel, as defined by National Electric Code Article 

100, should install and maintain this equipment.  Unauthorized  

alteration or improper maintenance of this unit may release the  

manufacturer from any warranty claims.  The installation must be in 
accordance with the instructions in this manual and applicable local 

plumbing and electrical codes. 

CAUTION 

 

THE ELECTRICAL INSTALLATION MUST BE IN ACCORDANCE 

WITH ARTICLE 680 OF THE NATIONAL ELECTRICAL CODE. 

BEFORE YOU BEGIN 

 

CHECK ALL ELECTRICAL CONNECTIONS TO ALL COMPONENTS 

WITHIN THE HEATER FOR TIGHTNESS.  CONNECTIONS CAN  

BECOME LOOSE DURING SHIPMENT AND HANDLING. 

INSTALLATION, OPERATION  

AND MAINTENANCE 

Publication 2/06 

 


background image

 

 

INTRODUCTION 
 

This manual provides installation procedures, 
operating and maintenance instructions and a parts list 
for the Coates Pool Heater. 
 
Your Coates Electric Swimming Pool Heater has been 
designed and engineered to provide you with the most 
progressive quality heating system possible.  Its 
operation is efficient and pollution-free.  Models are 
available for every size or make of pool. 
 
To insure a long life of trouble-free service, your 
Coates Pool Heater should be carefully installed in 
accordance with the instructions given in this manual.  
Failure to do so may damage the pool heater and the 
pool equipment to which it is connected.  Only 
qualified personnel should install and maintain this 
unit, and, of course, local plumbing and electrical 
codes have precedence over these instructions. 
 
 

1.0 

DESCRIPTION

 

 
The Coates Swimming Pool Heater consists of a 
heating tank with external enclosure, and the electrical 
heating and control system.  In order to help maintain 
the heater in a satisfactory manner, a brief description 
of its components and their operation is included for 
the customer’s convenience. 
 
The pressure vessel and its enclosure comprise the 
main mechanical portion of the pool heater. 
 
The pressure vessel, in conjunction with the flow 
switch and heating element are the only portions of 
this equipment in contact with the water. 
 
The external enclosure is a sheet steel case totally 
enclosing the pressure vessel and electrical 
components.  The enclosure is coated with a rust 
inhibiting, powder coat finish.  
 
The electrical system, which is the heart of this unit, 
can be considered as three separate systems 
engineered to provide optimum use of energy.  They 
are as follows: 
 

(1)  

The heating elements

; mounted on a four-bolt 

flange.  There are 2, 3 or 4 elements. 
 
(2) 

The control system

; consists of the pilot switch, 

high limit thermostat, flow switch, temperature control, 
magnetic contactors, 120/24V transformer and 
sequencer (on some single phase units only).  These 
controls are wired into a control circuit designed to 
control the temperature of the water leaving the heater.  
The high-limit thermostat is designed to open the control 
circuit and cut off the power in the event of excessive 
temperature. 
 
A flow switch is built-in to prevent the pool heater from 
operating without water flow.   The flow switch will 
activate at flow rates of 20 GPM or greater. 
 
(3) 

The main current-carrying components

; are 

the contactors and fuses.  These are wired into circuits 
which carry the full amperage draw of the elements.  
The contactors function during a high temperature 
condition to de-energize the elements.   
 
The element fuses in these units are rated at 60 Amps 
and have an interrupting capacity of 100,000 Amps rms.  
These fuses provide supplemental circuit protection for 
the internal wiring of the heater. 
 
The heater has a temperature controller adjustable from 
70°F(21°C) to 104°F(40°C) and has one manual reset 
type high temperature limit thermostat set at 122°F     
(50°C). 

 

2.0 

LOCATION AND PLUMBING 

 

A.  

Installation: Location 

 
 
Coates swimming pool heaters are quiet, do not expel 
exhaust fumes, and may be conveniently located in shed 
or basement.  Normal positioning of the pool heater 
should be in close proximity to the pool filtration system.  
Select a location conveniently close to incoming 
electrical service and where excessively long piping runs 
are not required. 
 
Suggested clearance: 24 in. on right, 24 in. on left, 42 in. 
above, 12 in. on the back, and 36 in. on front. 

WARNING 

 

Only qualified personnel, as defined by National 
Electric Code Article 100, should install and 
maintain this equipment.  Unauthorized alteration 
or improper maintenance of this unit may release 
the manufacturer from any warranty claims.  The 
installation must be in accordance with the 
instructions in this manual and applicable local 
plumbing and electrical codes. 

2

 


background image

B.  

Installation: Plumbing

 

 
Pipe the heater as shown in Figure 2 to the inlet and 
outlet openings on the right side.  Connect the heater 
in line between the filter discharge and pool.  The 
water line coming from the filter should be connected 
to the heater 

inlet

, and the discharge line to the pool 

should be connected to the 

outlet

.  The pool will not 

heat properly unless it is plumbed correctly.  If plastic 
pipe is used, it should be suitable for at least 120°F 
(49 °C). 
 
A plumbing bypass around the pool heater is not 
necessary unless flow rate though the heater exceeds 
80 GPM.   A minimum flow rate of 20 GPM is required.  
Lack of sufficient flow will not allow the flow switch to 
activate the heater. 
 
It may be necessary, in larger Olympic-sized or public 
pools, to use two or more heaters to obtain sufficient 
KW capacity.  If so, the heaters must be placed in 
parallel, so that each heater takes equal flow. 
 
DRAINAGE:  A method of draining water away from 
the heater and other equipment is to be provided.  The 
heater should be flushed at the end of each swimming 
season.  During flushing or service, water may be 
spilled and could cause damage to the floor or other 
equipment.  A drain valve is to be installed in the 
INLET plumbing. 
 

3.0 ELECTRICAL 

INSTALLATION

 

 
First:  1. 

 Check nameplate rating to insure the 

heater matches your electrical supply. 

 2. 

CHECK ELECTRICAL CONNECTIONS 
TO ALL COMPONENTS

 within the heater 

for tightness.  These can become loose 
during shipment and handling. 

 

3.  Check components for any moisture, rust, 

or dust which may have accumulated 
during shipping, and clean or dry where 
necessary. 

 
All pool heaters covered in this manual have integral 
thermostats, transformers, contactors and sequencers 
where required. 
 
All other internal connections are completed and 
tested at the factory. 
 
Wiring diagrams on pages 6 through 15 show internal 
wiring and required field connections for various 
models.  Consult your local electrical code for proper 
wire and conduit sizes, and other local requirements. 
 
Do not connect the pool heater to, or operate at, a 
voltage other than the voltage rated on the nameplate. 
 
Bring wires of adequate size from a fused disconnect 
switch or circuit breaker with an ampere rating of 

125% of the ampere rating shown on heater nameplate.  
Refer to Table 1 for wire sizes.  Connect power 
conductors to the power distribution block inside the 
heater. 

Ground wires must be insulated copper conductor and 
the same size as supply wiring, but not less than #12 
AWG. 

 

Table 1 

 

WIRE SIZE: AWG 

KW

240V/1Ø 208V/3Ø 240V/3Ø 480V/3Ø

12 

6 8 8 12 

15 

4 6 8 10 

18 

3 6 6 10 

24 

1 4 4 8 

30 2/0 

36 3/0 

45 250MCM 

2/0 

1/0 

54 300MCM 

3/0 

2/0 

57 350MCM 

3/0 

2/0 

 

 

Suggested size for insulated copper conductor 
wires.  Based on 125% correction factor for wire 
with 75°C insulation. 

 

 
 

A. 

To Connect Pool Heater to Power Supply

 

 
These pool heaters have branch supplemental fusing 
already installed in the element circuitry; see wiring 
diagrams.  To connect to the power supply, one needs 
only to protect the main supply lines, either with a circuit 
breaker or fused disconnect switch (Figure 1). 

 

Suggested wire sizes are shown in Table 1. 

 

     

  

Figure 1

3

 


background image

B.  

Startup Procedure: 

 
1.  Make sure that the pump is on and that there is at 

least 20 GPM flow through the pool heater.  The 
heating elements will fail if allowed to operate dry. 

 
2.   Check temperature control setting, also, examine 

wiring for loose connections, etc. 

 
3.   Turn on power at main disconnect switch. 
 
4.  Turn on pilot switch on pool heater. 
 
When closing down the pool for any length of time, 
shut off the power at the main disconnect switch and 
drain the water from the system.  Water must not be 
allowed to freeze in the heater, as this will cause 
severe damage. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

4.0 MAINTENANCE

 

 
Element Inspection and Replacement: 
1.   Turn off power at main disconnect switch and turn 

off pump. 

2.  Drain pool heater. 
3.  Remove service access panel opposite inlet/outlet. 
4.  Disconnect element leads. 
5.  Remove the four (4) element flange retaining nuts 

and extract element. 

6.  Installation is the reverse of steps 1 through 5.  

(Reinstall element with new gasket) 

 

Annual Cleaning: 

Yearly, before winter, the pool heater should be drained 
and cleaned to remove any scale or sludge.  More 
frequent cleaning may be required if pool water contains 
sediment or any amount of foreign matter. 
1.  Turn off system at main disconnect switch. 
2.  Open drain valve. 
3.  Permit water to run until it is clear. 
4.   Close valve and restart normally. 
 
If high temperature causes manual reset high limit 
switch to shut off the heater, disconnect power at 
disconnect switch and determine the cause before 
resetting.  
 
 

4

 


background image

TOTAL

 kW 

PER

 H

E

A

T

ER

AM

PER

A

G

E A

T

 FUL

L

 L

O

AD

EL

EM

EN

TS PE

HE

ATER

kW PER

 E

L

EM

EN

T

FU

SE, 

F

-1

, SC

-6

0

, 60

A/4

80V

FU

SE, F

-5

SC

-2

, 2A/

480

V

FU

SE, 

F

-3

, SC

-3

0

, 30

A/4

80V

FUSE, 

F

-6

, FNM

-2,

 2A

/25

0

V

T5, XFM

R

 480

V/2

40V

-5

0V

A

T2, 

XFM

R

, 48

0, 2

4

0

, 20

8V/

120

, 2

4

V-

50

VA

T2, 

XFM

R

, 48

0, 2

4

0

, 20

8V/

120

, 2

4

V-

75

VA

T2, 

XFM

R

, 48

0, 2

4

0

, 20

8V/

120

, 2

4

V-

10

0V

A

T2, 

XFM

R

, 48

0, 2

4

0

, 20

8V/

120

, 2

4

V-

15

0V

A

CR-

1 TO CR-

5 CONTA

C

TOR 3

P

, 1

2

0

V

 COIL

CR-

6 CONTA

C

TOR 4

P

, 1

2

0

V

 C

O

IL

CR-

7 CONTA

C

TOR 3

P

, 2

0

8

/24

0

V

 COIL

AU

XI

LIAR

Y

 SW

ITC

H

RS

-1

 ROCK

ER S

W

ITCH

, L

IG

H

TED

 1

2

0

V

RS

-2

 ROCK

ER S

W

ITCH

, L

IG

H

TED

 2

4

0

V

TS

-1

 HI

GH

 TE

MP

. LI

MI

T

TS-

2

 P

OOL

 STAT

K5

 SEQ

UE

N

C

E

R

 1-

POL

E

K6

 SEQ

UE

N

C

E

R

 2-

POL

E

K1

 SEQ

UE

N

C

E

R

 3-

POL

E

PL

-1

 & 2

, P

ILOT 

LIGH

T, 

AM

BER

 1

20/2

4

0

V

PL

-3

, PI

LOT L

IGHT, A

M

B

E

R 48

0V

TB1

, TER

M

IN

AL 

BLO

C

K

, 30

A/3

00V

 2 

POL

E

TB1

, TER

M

IN

AL 

BLO

C

K

, 30

A/3

00V

 4 

POL

E

EL

EM

EN

T GAS

KET

FLOW

 S

W

ITCH

18

18

3

4

7

7

7

7

7

17

16

17

4

10

10

11

8

15

15

15

9

9

5

5

13

6

COMPONENTS

29

018

910

29

018

930

29

019

525

29

015

052

22

012

200

22

010

702

22

010

752

22

010

802

22

010

902

21

000

900

21

00

1

20

0

21

001

000

1

6

C

R

-8

 CO

NT

A

C

T

O

R 4P,

 208

/2

4

0

V

 C

O

IL

21

001

300

21

00

0

05

0

23

001

520

23

001

521

22

003

820

22

002

001

21

00

5

50

1

21

005

502

210

05

503

29

034

620

29

034

648

29

025

570

2

902

55

74

44

000

250

23

000

102

PAR

T N

o

.

1241

2CE

124

15

CE

124

18C

E

124

24

C

P

H

124

30

CP

H

124

36P

HS

124

45P

HS

124

54P

HS

12

45

7P

HS

SINGLE 

PHASE

    

     

   2

40V

12

15

18

3

6

2

4

30

45

54

5

7

3201

2CE

320

15

CE

32

01

8C

E

320

24C

P

H

320

30

C

P

H

320

36P

HS

320

45P

HS

320

54P

HS

32

057P

HS

THREE 

PHASE

    

     

    2

08

V

12

15

18

36

2

4

3

0

45

54

57

32

41

2C

E

324

15C

E

3241

8CE

32

424C

P

H

32430

CP

H

3243

6P

H

S

324

45

P

H

S

324

54

P

H

S

32

457

P

H

S

THREE 

PHASE

     

     

     

 24

0V

12

1

5

1

8

36

2

4

3

0

45

54

57

3481

2C

E

34

815C

E

3481

8CE

348

24C

P

H

3483

0CP

H

3483

6P

HS

348

45P

H

S

348

54P

H

S

34

85

7P

H

S

THREE 

PHASE

    

     

     

 48

0V

12

15

1

8

3

6

2

4

3

0

45

54

57

H

E

ATER

 M

O

D

E

No

.

ILLUSTRATIO

N ITEM

 No.

5

1

64

7

7

1

02

12

8

1

53

19

1

225

238

34

50

4

2

6

7

84

10

1

1

26

150

15

9

3

0

37

4

5

59

7

4

89

11

1

1

32

14

0

15

1

9

22

2

9

37

69

65

55

44

22

22

2

3

2

2

2

22

22

22

2

2

2

2

2

23

34

4

33

33

34

4

4

4

4

4

66

66

9

9

9

9

1

21

2

1

2

1

2

1

21

2

1

21

2

1

5

15

15

15

15

15

15

15

3

11

1

1

2

3

2

3

2

3

2

66

6

6

66

66

6

6

6

6

6

12

12

12

12

12

12

10

10

9

9

9

9

2

2

22

2

22

22

2

22

22

2

22

2

2

2

2

2

2

2

2

2

2

22

22

2

22

22

1

11

1

1

1

11

1

1

1

11

1

1

1

1

11

1

1

1

1

1

PO

O

L

 H

E

A

T

ER PA

RT

S LIS

T

-E

1

2

3

4

H

E

A

T

ER

S W

ITH

 M

U

L

T

IP

LE E

L

EM

EN

T SIZES

2 EA

C

H

 AT 12

kW 

& 2

 EAC

H

 AT 

15kW

1

 EA

CH

 A

T

 12

kW &

 3 

EAC

H

 AT 1

5

kW

1

 EA

CH

 A

T

 6kW

 & 

1 EA

C

H

 AT 9kW

SPEC

IA

L I

N

FO

RM

A

T

ION

NOT SHOW

N IN IL

LUSTRATIO

N

11

1

11

1

1

1

1

1

1

1

1

1

1

11

11

11

11

1

1

1

1

11

1

1

1

11

44

7

7

8

82

2

5

5

5

5

5

5

2

2

5

5

22

2

2

2

2

2

22

22

2

2

2

2

1

33

3

11

1

1

1

1

1

11

1

1

1

11

1

1

1

1

11

1

1

1

1

11

1

11

1

1

1

1

11

1

11

1

1

1

1

11

1

1

1

1

1

1

11

1

1

1

1

1

1

1

1

1

11

11

1

1

11

1

11

1

1

11

1

1

11

1

1

11

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

11

1

1

11

1

1

1

11

1

1

1

1

1

1

11

11

1

1

1

1

1

1

1

1

1

1

11

11

11

1

1

1

11

11

1

11

1

1

1

1

1

1

11

1

11

1

1

1

1

11

1

11

1

1

1

1

11

11

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

11

11

1

1

1

1

1

11

1

11

2

22

22

2

222

2

2

2

22

22

22

4

4

4

4

4

4

4

44

44

22

4

22

2

2

2

2

2

2

2

2

22

22

22

2

22

2

2

2

2

22

2

2

2

90

255

50

IS

OLATE

D

 BUS

4

4

4

4

4

11

1

1

11

11

1

1

1

1

POOL HEATER PARTS LIST

MODELS CE, CPH & PHS

11

1

1

1

5

 


background image

1

1. POWER 

D

ISTRI

B

UTION BLOCK

2. GROUND 

LU

G

3. CONTROL TRANSFORMER PRIMARY FUSI

N

G

4. C

ONTROL TRANSFORMER SEC

OND

ARY 

FU

SING

5. EXTERNAL CONTROL CONNECTION

6. FLOW 

SWITCH

7. C

ONTROL TRANSFORMER (

WHEN 

R

EQUIR

ED)

8. TEMPERATURE CONTROL

9. PI

LOT LI

G

H

TS 

"ELEMENT" 

AND 

“FLOW”

10. 

PILOT SWITCH, 

LI

GHTED 

"ON/OFF"

11. 

TEMPERATURE LIMIT SWITCH

12. 

HEATING ELEMENT

13. 

HEATING ELEMENT GASKET

14. 

SEQUENCER TRANSFO

RMER (WHEN REQUIRED)

15. 

SEQUENCER (WHEN 

R

EQUIRED)

16. 

CON

TA

C

TOR 

(4-POLE)

17. 

CON

TA

C

TOR 

(3-POLE)

18. 

HEATER 

C

IRCUIT FUSI

N

G

19. 

VESSEL

20

. ENCL

OS

URE

NOTE:

REFERENCE THE 

POOL 

H

EATER 

PARTS LIST FOR

COMPONENT 

PART NUMBE

R

S AND QUANTITIES.

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

9-

2-

91

DP

H-

IL

L

6

 


background image

TB1 FOR REMOTE TEMPERATURE 

CONTROL (IF USED).

FLOW SWITCH

CR7

CR7

PL2 "FLOW"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

SINGLE PHASE

208V – 12, 15 & 18kW

240V – 12, 15 & 18kW

3.

CO

IL

COI

L

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK 

R = RED 

LEGEND;

5.

W = WHITE 

HEATING ELEMENTS

TB1

TS2

ISOLATED BUS

PL1 "ELEMENT"

MODEL CE

F5

F5

6.        HEATING ELEMENT QTY/RATING;

12kW = 2 @ 6kW
15kW = 1 @ 6kW & 1 @ 9kW
18kW = 2 @ 9kW

1BC1218D

TS1

RS2

1

2

2

1

CR7

COI

L

W

W

R

B

R

B

W

W

R

B

R

B

#8

#8

#8

#8

#8

#8

#8

#8

#8

#8

#8

#8

#10

#10

#10

#10

#10

#10

F1

F1

F1

F1

F1

F1

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

TB1 FOR REMOTE TEMPERATURE 

CONTROL (IF USED).

FLOW SWITCH

CR1

CR1

PL2 

"FL

O

W"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

SINGLE PHASE

208V – 24 & 30kW

240V – 24 & 30kW

3.

CO

IL

CO

IL

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

HEATING ELEMENTS

TS2

PL1 

"EL

EMENT"

MODEL CPH

F5

F5

1BC2430E

TS1

RS1

1

2

2

1

CR1

CO

IL

W

W

R

B

R

B

W

W

R

B

R

B

#8

#8

#8

#8

#8

#8

#10

#10

#10

F1

F1

F1

F1

F1

F1

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

CR1

COI

L

#10

#10

#10

TB1

X3

X2

X1

24V

120V

T2

F6

K5

M1

M2

H2

H1

AUX1

#10

#10

#10

Yellow #14

Yellow #14

Y

e

llo

w #

1

4

XF

7

 


background image

TB1 F

O

R REMOT

E TEMPERAT

URE 

CO

N

TRO

L (

IF U

SED).

FLOW 

SWI

TC

H

PL2 "FLOW"

GR

OU

N

D

  POOL

GR

OU

ND

ENC

LO

S

URE

TE

RM

INA

L

HEAT

ER G

ROUND

SEE IN

S

TRU

CT

ION

 MANU

AL FOR C

OM

PON

E

NT

SINGLE PHAS

E

208V –

36

 & 45kW

240V –

36 & 45k

W

3.

ID

E

NTI

FICA

TI

O

N.

4.

ALL 

WIRING T

O B

E

 10

5°C

 INSULAT

E

D, MIN

IMUM

.

CO

NT

RO

L CI

RCU

IT WIR

ING

; 14 AWG

.

PO

WER

 CIR

CUIT

 WIR

ING

; AS NO

TED

.

B = BLA

C

K

R = RED

LEGE

N

D

;

5.

W = WH

IT

E

HEAT

IN

G ELEMENTS

TS2

PL1 

"E

LEMENT"

MODEL PHS

F5

F5

1B

C

3645

D

TS

1

RS1

1

2

2

1

W

W

RB

RB

WW

RB

RB

#8

#8

#8

F1

F1

F1

#2  

BR

A

SS

#1  

CO

PP

ER

#3  

AL

UM

INUM

TB1

X3

X2

X1

24

V

12

0V

T2

F6

Ye

llow #1

4

XF

#8

F1

#8

F1

#8

#8

#8

F1

F1

F1

#8

F1

#8

F1

CR

1

COIL

WW

RB

RB

AUX1

CR

1

COIL

CR

1

COIL

CR

1

COIL

CR1

COIL

CR1

COIL

CR

1

COIL

K6

M1

M2

H2

H1

M3

M4

Yello

w #1

4

Y #1

4

Y = YELLOW

#1

0

#10

#1

0

#1

0

#1

0

#

10

#1

0

8

 


background image

TB1 F

O

R REMOT

E TEMPERAT

URE 

CO

N

TRO

L (

IF U

SED).

FLOW 

SWI

TC

H

PL2 "FLOW"

GR

OU

N

D

  POOL

GR

OU

ND

ENC

LO

S

URE

TE

RM

INA

L

HEAT

ER G

ROUND

SEE IN

S

TRU

CT

ION

 MANU

AL FOR C

OM

PON

E

NT

SINGLE PHAS

E

208V –

54

 & 57kW

240V –

54 & 57k

W

3.

ID

E

NTI

FICA

TI

O

N.

4.

ALL 

WIRING T

O B

E

 10

5°C

 INSULAT

E

D, MIN

IMUM

.

CO

NT

RO

L CI

RCU

IT WIR

ING

; 14 AWG

.

PO

WER

 CIR

CUIT

 WIR

ING

; AS NO

TED

.

B = BLA

C

K

R = RED

LEGE

N

D

;

5.

W = WH

IT

E

HEAT

ING

 ELEMENT

S

TS2

PL1 

"E

LEMENT"

MODEL PHS

F5

F5

1B

C

5457

D

TS

1

RS1

1

2

2

1

W

W

R

B

RB

WW

RB

RB

#8

#8

#8

F1

F1

F1

#2  

BR

A

SS

#1  

CO

PP

ER

#3  

AL

UM

INUM

TB1

X3

X2

X1

24

V

12

0V

T2

F6

Ye

llow #1

4

XF

#8

F1

#8

F1

#8

#8

#8

F1

F1

F1

#8

F1

#8

F1

CR

1

COIL

WW

RB

RB

AUX1

CR1

COIL

CR

1

COIL

CR1

COIL

CR1

COIL

CR1

COIL

CR

1

COIL

Yello

w #1

4

Y #14

Y = YELLOW

CR

1

COIL

WW

RB

RB

K1

M1

M2

H2

H1

M3

M4

M5

M6

#8

F1

#8

F1

#1

0

#10

#1

0

#1

0

#1

0

#1

0

#1

0

#10

9

 


background image

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

208V – 18kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

TS2

ISOLATED BUS

PL1 "ELEMENT"

MODEL CE

F5

F5

B

R

B

R

W

W

3BC18C

TS1

RS2

1

2

2

1

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR7

CO

IL

CR7

CO

IL

CR8

CO

IL

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

#8

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

CR7

CR7

PL2 "FLOW"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

208V - 12 & 15kW

240V - 12, 15 & 18kW

3.

COI

L

CO

IL

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

TS2

ISOLATED BUS

PL1 "ELEMENT"

MODEL CE

F5

F5

B

R

B

R

W

W

6.        HEATING ELEMENT QTY/RATING;

12kW = 2 @ 6kW
15kW = 1 @ 6kW & 1 @ 9kW
18kW = 2 @ 9kW

#10

3BC1218C

TS1

RS2

1

2

2

1

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#10

#10

#8

#8

#8

#8

#8

#8

10

 


background image

TB1 FOR REMOTE TEMPERATURE 

CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

208V – 36 & 45kW

240V – 36 & 45kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

TS2

PL1 "ELEMENT"

MODEL PHS

F5

F5

B

R

B

R

W

W

3BC3645D

RS1

1

2

2

1

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

CR1

CO

IL

CR1

CO

IL

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

TS1

W

W

R

B

R

B

CR1

COI

L

F1

F1

F1

CR1

CO

IL

CR1

CO

IL

#8

#8

#8

#8

#8

#8

#8

#8 #8

X3

X1

120V

T2

F6

XF

FLOW SWITCH

PL2 "FLOW"

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

208V – 24 & 30kW

240V – 24 & 30kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

TS2

PL1 "ELEMENT"

MODEL CPH

F5

F5

B

R

B

R

W

W

3BC2430D

RS1

1

2

2

1

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR1

CO

IL

CR1

CO

IL

CR6

COI

L

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

#8

TS1

X3

X1

120V

T2

F6

XF

11

 


background image

TB1 F

O

R REMOT

E

 TEMPERATURE 

CO

NT

ROL

 (I

U

SED

).

FLO

W

 S

W

IT

CH

PL2 "FLOW"

GR

OU

N

D

  POOL

GR

OU

ND

EN

CL

OS

UR

E

TE

RM

INA

L

HEAT

ER G

ROUND

SEE INSTR

U

C

TION M

A

N

U

AL F

OR

 COMPONENT

TH

R

E

PH

AS

E

208V –

54 & 57kW

240V –

54 & 57kW

3.

WW

RB

RB

IDE

NT

IFIC

A

TIO

N.

4.

ALL WIRIN

G

 T

O BE 105°C

 INSU

LA

TED, M

INIMU

M.

CO

NT

RO

CI

R

C

U

IT 

W

IR

IN

G

; 1

AW

G.

POWER C

IRCU

IT WIR

ING; AS NOT

E

D.

B = BLACK

RED

LEG

E

ND;

5.

W = WH

IT

E

#8

HEAT

ING

 ELEMENT

S

TB1

2

TS

2

PL1 "ELEMEN

T"

MODEL PHS

F5

F5

B

R

B

R

W

W

3B

C

5457

E

RS1

1

2

1

C

B

A

#2  

BRA

S

S

#1  

C

O

PP

ER

#3  

AL

UM

INU

M

#8

#8

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

TS

1

WW

RB

RB

F1

F1

F1

#8

#8

#8

#8

#8

#8

#8

#8

#8

CR6

COIL

WW

RB

RB

F1

F1

F1

CR6

COIL

CR6

COIL

CR6

COIL

CR6

COIL

X3

X

1

120V

T2

F6

XF

12

 


background image

TB1 F

O

R REMOT

E

 TEMPERAT

UR

CO

NT

RO

(IF 

U

SED

).

FLOW 

SWI

TC

H

CR

7

CR

7

PL2 "FLOW"

GR

OU

ND

  POOL

GR

OU

N

D

EN

CL

O

S

UR

E

TER

M

IN

AL

HEAT

ER GRO

UND

SEE IN

STRU

CT

IO

N MANU

AL FO

R

 C

O

M

PON

E

NT

THRE

E PHASE

480V –

12, 15 & 18kW

3.

CO

IL

CO

IL

WW

RB

RB

ID

E

NT

IFIC

A

TIO

N.

4.

ALL WIRIN

G

 TO BE 105°C

 INSULATED, MIN

IMUM

.

CONT

ROL C

IRCU

IT WIR

ING; 14 AWG.

PO

WER CIR

C

U

IT WIR

ING

; AS NO

TED

.

B = BLACK

R = R

E

D

LEG

E

ND;

5.

W = WHITE

#8

HEAT

ING

 ELEMENT

S

TB1

TS

2

IS

OLATE

D BU

S

PL3 "ELEMENT"

MODEL CE

F5

F5

B

R

B

R

W

W

6.  

      HEAT

ING ELEMENT

 QT

Y/RAT

ING;

12kW =

 2 @ 6kW

15kW =

 1 @ 6kW & 1 @

 9kW

18kW =

 2 @ 9kW

#1

0

3J

121

8F

TS

1

RS

2

1

2

2

1

C

B

A

#2  

BR

A

SS

#1  

CO

PP

ER

#3  

A

L

UM

INUM

#8

#8

#1

0

#1

0

#8

#8

#8

#8

#8

#8

X3

X1

240

V

T5

F6

XF

13

 


background image

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

1

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

480V – 36kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

2

TS2

PL3 "ELEMENT"

MODEL PHS

F5

F5

B

R

B

R

W

W

3J36E

RS1

1

2

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR1

CO

IL

CR1

COI

L

#8

#8

#8

TS1

#10

#10

#10

B

R

B

R

W

W

X3

X1

120V

T2

F6

XF

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

1

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

480V – 24 & 30kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

2

TS2

PL3 "ELEMENT"

MODEL CPH

F5

F5

B

R

B

R

W

W

3J2430E

RS1

1

2

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR1

CO

IL

CR1

COI

L

#8

#8

#8

TS1

#10

#10

#10

X3

X1

120V

T2

F6

XF

14

 


background image

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

1

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

480V – 54 & 57kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

2

TS2

PL3 "ELEMENT"

MODEL PHS

F5

F5

B

R

B

R

W

W

3J5457E

RS1

1

2

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR1

COI

L

CR1

COI

L

CR6

COI

L

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

#8

TS1

B

R

B

R

W

W

B

R

B

R

W

W

X3

X1

120V

T2

F6

XF

TB1 FOR REMOTE TEMPERATURE CONTROL (IF USED).

FLOW SWITCH

PL2 "FLOW"

1

GROUND

  POOL

GROUND

ENCLOSURE

TERMINAL

HEATER GROUND

SEE INSTRUCTION MANUAL FOR COMPONENT

THREE PHASE

480V – 45kW

3.

W

W

R

B

R

B

IDENTIFICATION.

4.

ALL WIRING TO BE 105°C INSULATED, MINIMUM.
CONTROL CIRCUIT WIRING; 14 AWG.
POWER CIRCUIT WIRING; AS NOTED.

B = BLACK

R = RED

LEGEND;

5.

W = WHITE

#8

HEATING ELEMENTS

TB1

2

TS2

PL3 "ELEMENT"

MODEL PHS

F5

F5

B

R

B

R

W

W

3J45E

RS1

1

2

C

B

A

#2  

BRASS

#1  

COPPER

#3  

ALUMINUM

#8

#8

#8

#8

#8

CR1

CO

IL

CR1

CO

IL

CR6

COI

L

F1

F1

F1

F1

F1

F1

#8

#8

#8

#8

#8

#8

#8

TS1

B

R

B

R

W

W

X3

X1

120V

T2

F6

XF

15

 


background image

 

LIMITED WARRANTY

 

 

The company extends this limited warranty to the original purchaser of a Coates Electric Pool Heater. 

 

Coates warrants the electrical components* and wiring (excluding enclosure, enclosure parts, knobs and accessories) in this 
new Pool Heater to be free from defects in materials and workmanship for one (1) year from the provable date of purchase, 
or eighteen (18) months from date of factory shipment, whichever occurs first.  Coates further warrants the stainless steel 
water containment vessel to be free from defects in materials and workmanship for two (2) years from the provable date of 
purchase or thirty (30) months from the factory shipment, whichever occurs first.  Enclosure, enclosure parts, knobs and 
accessories have no warranty whatsoever. 

 

*Exception: Factory installed heating elements are warranted for ninety 90 days from the date of heater installation, or 
eighteen (18) months from date of factory shipment, whichever occurs first. 

 

COATES will repair or replace at its option, defective component parts as explained above, during the warranty period 
provided such parts are returned to the factory, freight prepaid.  Factory authorization MUST BE OBTAINED under this 
warranty before returning such defective parts. 

 

Limited Warranty Does Not Cover 

 

1. 

New products purchased outside the United States of America and Canada. 

2. 

Uncrating, unpacking, set-up, installation and / or startup of this unit. 

3. 

Adjustments to controls normally operated by consumer, purchaser or installer. 

4. 

This limited warranty does not extend to any defect, malfunction or failure caused by, or resulting from improper 
service, maintenance or repair, abuse, neglect, accident, 

corrosion caused by improper water chemistry or by 

equipment that use salt to create a sanitizer

, lack of water, or any other cause beyond the control of Coates 

Heater Company, Inc. or to any product where the nameplate shall have been removed, altered, replaced, defaced or 
rendered illegible. 

5. 

This limited warranty is void if the Spa Heater is used in a salt water system or under any extreme or unusual 

 

corrosive condition for which stainless steel metals would not be recommended. 

6. 

This limited warranty does not extend to the repair or replacement of defective components except at COATES or a 

 

service facility authorized by COATES 

 

IMPLIED WARRANTIES, WHEN APPLICABLE, SHALL COMMENCE UPON THE SAME DATE AS THE EXPRESS 
WARRANTY PROVIDED ABOVE, AND SHALL, EXCEPT FOR WARRANTIES OF TITLE, EXTEND ONLY FOR 
THE DURATION OF THE EXPRESS WARRANTY.  SOME STATES DO NOT ALLOW LIMITATIONS ON HOW 
LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.  THE ONLY 
REMEDY PROVIDED TO YOU UNDER AN APPLICABLE IMPLIED WARRANTY AND THE EXPRESS 
WARRANTY SHALL BE THE REMEDY PROVIDED UNDER THE EXPRESS WARRANTY, SUBJECT TO THE 
TERMS AND CONDITIONS CONTAINED THEREIN. 

 

COATES SHALL NOT BE LIABLE FOR INCIDENTAL AND CONSEQUENTIAL LOSSES AND DAMAGES, UNDER 
THE EXPRESS WARRANTY, ANY APPLICABLE IMPLIED WARRANTY, OR CLAIMS FOR NEGLIGENCE, 
EXCEPT TO THE EXTENT THAT THIS LIMITATION IS FOUND TO BE UNENFORCEABLE UNDER APPLICABLE 
STATE LAW. 

 

SOME STATES DO NOT ALLOW THE EXCLUSION OF LIMITATION OF INCIDENTAL OR CONSEQUENTIAL 
DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. 

 

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS 
WHICH VARY FROM STATE TO STATE. 

 

 

HEATER COMPANY, INC. 

 

P.O. Box 1750 

Kent, WA 98035 

P/N 

90007001             

 

 

 

2/06