Full Text Searchable PDF User Manual

Telca air conditioner unit
TAC-12D-10
Service manual
Document No.: TELCA0.010.0205
Edition No.: V1.0
TELCA SCIENCE&TECHNOLOGY CO., LTD.

Service manual: TAC-12D-10
1/9
Contents:
1. General
2. Technical data
3. Assembly
4. Electrical connection
5. Commencing operation and control behavior
6. Maintenance
1.
General
The cooling circuit is designed in the form of a maintenance-free, hermetically sealed
system. The cooling unit is filled with the required quantity of refrigerant at the factory,
checked for leaks, and subjected to a functional test run. The installed maintenance-free
fans are mounted on ball bearings, protected against moisture and dust, and fitted with a
temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling
unit is thus largely maintenance-free. All that may be required from time to time is to
clean the components of the external air circuit using a vacuum cleaner or compressed
air if they become visibly dirty.
Maintenance interval:
12 months
. Depending on the level of contamination in the
ambient air, the maintenance interval may be reduced to suit the air pollution intensity.
2.
Technical data
Model No.
TAC-12D-10
Dimensions WxHxD
420 x 1000 x 180 mm
Cooling output @L35/L35
1200 W
Heating output
1000 W
Rated voltage Volt/Hz
220VAC, 50/60Hz
Rated current
3.3 A (Cooling)
4.5 A (Heating)
Temperature range
-40°C ~ +55°C
Power consumption
720 W (Cooling)
1000 W (Heating)
Air circuit (External)
570 m
3
/h
Air circuit (Internal)
450 m
3
/h
Noise
62dB
Refrigerant
R134a
Protection category
IP55
Weight
34Kg
Special voltages available on request.

Service manual: TAC-12D-10
2/9
3.
Assembly
Mechanical design, electrical connection and possible repair works must only be carried
out by qualified personnel. Only use original spare parts!
3.1 Assembly instructions
Prior to mounting, ensure that
●
The site of cabinet and hence the arrangement of air conditioner unit, is selected
in such a way as to ensure good ventilation;
●
The location is free from excessive dirt and moisture;
●
The mains connection ratings, as stated on the name plate of the unit, are
available;
●
The ambient temperature does not exceed +55°C;
●
The packaging shows no signs of damage. Traces of oil on damaged packaging
are an indication of refrigerant loss and leakage in the unit system. Any damage
to the packaging may be the cause of subsequent malfunctions;
●
After successful test and wire binding, the wire inlet of the equipment should be
hermetically sealed. Condensation will occur and cooling effect will reduce if the
cabinet is leaky;
●
The distance of equipment from all obstacles around should not be less than
200mm;
●
Air inlet and outlet are not obstructed on the inside of the cabinet;
●
Air conditioner unit should only be fitted horizontally in the specified position.
Max. deviation from true horizontal:2º;
●
To avoid an increase in condensation, the unit should be switch off immediately
when the equipment door is opened;
●
Gaskets should be bonded to the fixing frame for the unit in door or wall of the
cabinet.

Service manual: TAC-12D-10
3/9
3.2 Assembly
Uplift air conditioner unit into front door of the cabinet, position it on the fixing frame
bonded with gaskets, and rivet it with M4 nuts. Care must be taken to ensure that the
internal air outlet of the unit is contraposed to that of the cabinet(see figure 3.1)
Fig.3.1

Service manual: TAC-12D-10
4/9
4.
Electrical connection
After verifying that the connection voltage and frequency match the nominal values
specified on the rating plate, insert one end of power supply cable with the plug into the
socket established in the unit, please notice the direction of the connector, avoid put
wrong, and tighten the screws of the plug to secure the connection. For detail connection
details, please view figure 4.1 and figure 4.2.
L
K6
CN4
CN3
K4
N
External Fan
Compressor
Blue
Black
Red
Black
Brown
Blue
R
S
C
F1
Fuse
TAC_CTL V1.1
Heater
K5
220V/60Hz
Brown (L)
Blue (N)
Yellow/Green
1
5
3
Internal Fan
2 uF
Black
Brown
Blue
Fig.4.1

Service manual: TAC-12D-10
5/9
Fig. 4.2 D-SUB 9PIN female
5.
Commencing operation and control behavior
Following the completion of mounting and a waiting period of approximately 30 minutes
(to allow oil to collect in the compressor in order to ensure lubrication and cooling)
electrical connection can be made.
The cooling unit operates automatically, i.e. after electrical connection, the internal fan
will run continuously to circulate the air inside the enclosure. This results in a uniform
temperature distribution in the cabinet. The compressor and heater (optional) are
controlled by a microcontroller.
●
Compressor and external fan control
If the temperature of internal air inlet exceeds P0 (35°C), the external fan and
compressor will be switched on.
Contrarily, if the temperature of internal air inlet is lower than P0-P1 (35-6=29°C), the
external fan and compressor will be switched off.
Important:
In order to avoid cyclic operation, switch-on of compressor is delayed by
about 3 minutes since last switch-off, please don’t take this as a failure!
●
Heater control (optional)
If the temperature of internal air inlet is lower than P2 (5°C), the heater will be switched
on.
Contrarily, if the temperature of internal air inlet exceeds P2+P3 (5+10=15°C), the heater
will be switched off.

Service manual: TAC-12D-10
6/9
●
Parameters setting
Fig.5.1 Display terminal (optional)
The display terminal consists of a LED display which indicates the inside temperature.
Press ▲ or ▼ button to display the evaporator temperature, the LED display will flash.
Parameter setting range
Parameters
Default Value
Setting Range
Note
P0
35 °C
25~40
Cooling temperature
P1
6 °C
3~15
Cooling temperature difference
P2
5 °C
0~15
Heating temperature
P3
10 °C
3~15
Heating temperature difference
P4
45 °C
40~60
High temperature alarm
P5
0 °C
-9~10
Low temperature alarm
P6
0 °C
-9~10
Evaporator freezing alarm
P7
15 min
1~60
Cooling cycle time when
sensors defective
P8
1
1~10
Machine address
Keys introduction
EXT
Press the
EXT
button once to setting the parameter P2, press ▲ or ▼ button
to modify the setting value, press
EXT
button to exit, otherwise exit
automatically after 5 seconds delay.
SET
Press the
SET
button once to setting the parameter P0, press ▲ or ▼ button
to modify the setting value, press
SET
button to exit, otherwise exit
automatically after 5 seconds delay;
Press the
SET
button for more than 3 seconds to enter the parameters setting
menu, press ▲ or ▼ to select the parameter to modify, press
SET
button
once to enter the appropriate parameter setting state, press ▲ or ▼ to modify
the setting value, after being adjusted, press the
EXT
button to exit, otherwise
exit automatically after 5 seconds delay.
▲ Up button
▼ Down button

Service manual: TAC-12D-10
7/9
●
LED status indication
The
WORK
LED light at the left side of the screen is used as working indicator lights,
flashing is to indicate the delay of cooling; if the LED is always on, it indicates it is on the
state of cooling or heating;
The
SET
LED light at the left side of the screen is used as setting indicator lights, if the
LED is always on, it indicates it is on the state of setting.
●
Door limit switch
If a door limit switch is used and the cabinet door is open (contact is closed when door is
open), the cooling unit (external fan and compressor) will switch off after approx 5 s,
thereby avoiding an increase in condensation while the door is open. To avoid cyclic
operation, switch on of compressor and external fan is delayed by about 3 minutes after
the door has been closed.
●
Alarm output
The air conditioner is permanently controlled by the microcontroller. Faults which can
occur are registered and will be passed on the LED display panel, also the dry contact
alarm.
Alarm code and system message
Alarm code
System message
E1
Internal temperature exceeds P4
E2
Internal temperature below P5
E3
Evaporator freezing
E4
High/low 220VAC power supply
E5
Condenser high pressure
E6
Internal temperature sensor failure
E7
Evaporator temperature sensor failure
E8
Door open
The dry contact alarm is triggered if any of the above alarm is detected.
The dry contact alarm functions as follows:
Storage conditions: Open contact
Operation:
Closed contact
Alarm:
Open contact
The maximum load of dry contact is:
Resistive load 3A@250VAC or 3A@30VDC

Service manual: TAC-12D-10
8/9
●
Self-test
To enter the self-test function, press the
SET
button and ▲ button for 5 seconds and
release.
Self test steps:
1 - LED scanning
3 seconds
2 - Internal Fan
-- seconds (running all the time)
3 - Heating
30 seconds
(Heater)
4 - Cooling
60 seconds
(Compressor and external fan)
5 - External fan
10 seconds
When the self test is completed, controller will automatically exit. During self-testing, you
can press the
EXT
button to exit.
6.
Maintenance
6.1 Trouble Shooting
The air conditioners are designed for trouble free life as long as the inlet filter is
maintained in a clean condition. To aid in service definition the service personnel can
initially identify probable cause by referring to the following trouble shooting chart.
Problem
Potential Cause
Solution
No Power
Check power source and
electrical connections
Fuse Blown on Control Board
Replace with 3.15A slow blow
fuse
Unit not running
Faulty Control components
Replace control board
Filter clogged
Clean or replace filter
Blocked evaporator or
condenser coil
Clean coil
Evaporator or condenser fan
not operating
Replace motor, capacitor or
entire assembly
Unit not cooling
sufficiently
Loss of refrigerant or oil leaks
Return to Telca or locate and
repair leak
Insufficient heat load or unit
oversized for application
Contact Telca
Ice on evaporator coil
Failed evaporator fan
Replace evaporator fan motor
or assembly
Condensate draining
continuously
Enclosure not properly
sealed
Check and seal all openings
Defective fan motor or wheel Replace fan sub assembly.
Excessive vibration
Compressor loose
Tighten mounting bolts

Service manual: TAC-12D-10
9/9
6.2 Evaporator and Condenser Coil Cleaning
Periodically the coils should be cleaned. No fixed period for cleaning can be provided
due to the varying environments in which the air conditioner may be installed.
However once the coils become visibly coated with dust it is recommended that they
be cleaned with a brush or compressed air. Both sides of the coils should be
inspected regularly. (at least once every 12 months.)
Caution:
Prior to any maintenance work, the air conditioner must be switched free
from potential on the supply side.
If in doubt, Contact
IT Enclosure Systems
for
assistance. Always have the Model #,
Serial # date available before you
call.