TD-1/11-102

 

 

 

TFD 1430 

4 Wire Optical Smoke Detector 
 

TFD 1450 

4 Wire Optical Smoke + Heat Detector 

 

Installation and User Manual 

Publish Date: 15/4/2011

 

 

IMPORTANT WARNINGS 

GENERAL 

Before  using  the  device  read  this  manual  carefully.  Keep  it 
just in case of necessity. 

Abide  all  the  rules  and  precautions  stated  in  the  manual. 
Follow all the instructions one by one. 

Keep the devices away from water and moisture. 

CONDITIONS 

Do not energise the device above or below the given limits 
of extreme hot or cold conditions. 

 

Temperature: 

Between 0

°

C and +55

°

 

Relative Moisture: 

%95 at +40

°

 

Air flow limit: 

Below 600 meters/min 

SERVICE 

Do  not  try  to  fix  the  device  on  your  own,  Removal  of  cover 
may end up with electricity shock. 

In case of any defect or malfunction, contact with your dealer 
or with authorized service. All the technical interventions has 
to be done by technicians of service company. 

MALFUNCTIONS FOR TECHNICAL SERVICE 

In  case  of  any  malfunction  or  below  conditions  contact  with 
your authorized service. 

  When Mains cable or the plug is harmed, 

  Contact of device with a fluid, 

  Exposure of rain and water, 

  Fell down of device or harmed outer cover, 

  Serious performance fall on the device, 

  Depending  on  the  instructions  stated  in  manual,  if  your 

device  not  working  properly,  further  usage  or  possible 
wrong  usage  may  cause  other  malfunctions  .  Contact 
with your authorized service in such terms. 

 

SPARE PART 

If  the  repair  will  be  done  by  spare  parts,  to  avoid  fire, 
electricity  shock  or  any  other  hazardous  conditions,  Make 
sure  your  service  is  using  original  parts  or  parts  compatible 
with your equipment. 

SAFETY CHECK 

To  make  sure  if  your  device  working  properly  and  in  safe 
conditions or not demand service from your dealer to check 
devicefunctionality. 

INSTALLATION AND CONNECTION 

1.  Remove  the  head  of  the  detector  attached  to  base  by 

turning it counter clock wise until you reach the short line 
on the base(1),then pull it off(2). 

   

 

2.  Use  at  least  2  opposite  ones  from  4  of  the  screw  holes   

on the base to fasten it.  

 
 
 
 
 
 
 
 
 
 
3.  Do  the  wiring  according  to  schematic shown  below.  The 

order  of  cables  do  not  make any  difference.  There is no 
(+/-).   

 

4.  Place  the  detector  head  back.  Make  sure  the  short  line 

on head fits with long one on the base.  

5.  Energise  the  detector.  If  there  is  no  alarm  condition  the 

LED on detector flashes once every 10 secs  to show it is 
working at that moment. . 

 

TEST 

 


background image

TD-1/11-102

 

This  test  process  captures  both  heat  and  smoke  sensor 
inside.To make a correct test, you need stable air flow at 
70°C or visible smoke flow. (TFD 1450 only).  

 

Visible smoke flow is enough for testing TFD1430. 

1.  If  your  panel  has  the  test  function  ability.  Start  the  test 

function. 

2.  Start  the  hot  air  flow  and  control  the  temperature 

continuosly. 

3.  Let the air flow directly to the top of detector head which 

covers thermistor. Detector will switch to alarm mode 30 
seconds at most. 

4.  Reset detector from the panel. 

5.  For smoke test, allow smoke from a cotton wick or a test 

smoke  aerosol  to  enter  the  detector-sensing  chamber 
for  at  least  10  seconds.When  sufficient  smoke  enters 
the chamber, the detector will start the alarm. 

6.  After  the  alarm  is  active  remove  the    source.  Check  if 

the  red  LED  on  detector  is  active.  Then  reset  the 
detector from panel. 

7.  If the detector is not responding in 30secs and not going 

in alarm mode,you must send it to service . 

8.  After the test is complete, system can be activated. 
 

IMPORTANT NOTES ABOUT DETECTOR USAGE 

 

Multisensor Works as combination of both heat and 

smoke  detector.  At  least  one  of  them  going  alarm 
mode is enough for it to warn (TFD1450 only). 

 

To  make  sure  both  heat  and  smoke  is  working, 

complete all steps on the test. 

 

The  recommended  minimum  requirement  for  the 

detector  maintenance  consists  of  an  annual 
cleaning  of dust  from  the detector  head by  using  a 
vacuum  cleaner  cleaning  program  should  be 
agreed 

to 

the 

individual 

environment 

in 

conformance with EN 54-7:2000 and EN 54-5:2000 
standard 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

PROPERTIES 

Model 

Alarm 

conditions 

2 / 4 

wire 

Power 

Supply 

Contact 

ratings 

Operating 

temperature 

(°C) 

Startup time 

(max ,seconds) 

Dimensions 

(mm) 

Body material 

TFD 1430 NC 

54°C 

And/or 

Visible smoke 

9 - 15 

VDC 

15mA 

NC 

30V 50mA 

max. 

-10 ~ 50 

60 

Ø110, h50 

Cream color UL 94 

Fireproof  ABS 

plastic 

TFD 1450 NC 

54°C 

 

MANUFACTURER 

 

WARNING ! 

 DO NOT TRY TO REMOVE THE DETECTOR FROM 

THE PLASTIC COVER. THIS ASSEMBLY IS SEALED 

FOR YOUR SAFETY. USERS MUST AVOID 

INTERVENTION. OPENING THE DETECTOR HEAD 

WILL REMOVE WARRANTY. 