Full Text Searchable PDF User Manual

1 of 12
© 2010
D 313 - 11/10
tekmarNet
®
2 Wiring Center 313
D 313
11/10
Zoning
Replaces: 10/09
Installation & Operation Manual
Benefi ts
Simple, convenient wiring location
Compact enclosure for flexible installation
Reduce equipment cycling through the use of
tekmarNet
®
2 Thermostats
•
•
•
The tekmarNet
®
2 (tN2) Wiring Center 313 is designed to
operate up to four zone valves in a hydronic heating system.
It can be mounted in the mechanical room or near a remote
zone manifold, providing a convenient location to wire both
thermostats and zone valves while only requiring two wires
to be run back to the mechanical room. When combined
with tekmarNet
®
2 Thermostats, all devices communicate
to provide a synchronized end switch that reduces cycling
of equipment.
Features
Four 24 V (ac) powered zone outputs
For use with tekmarNet
®
2 Thermostats
Supports two-stage tekmarNet
®
2 Thermostats
tN4 expansion terminals
Isolated end switch
External diagnostic LEDs
CSA C US Certified for use in USA and Canada
•
•
•
•
•
•
•
Introduction
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 10 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
tN2 Wiring Center 313
Four Zone Valves
For use with
tN2 thermostats only
tN2
Made in Canada
tektra 1034-01
Note
Not for use with tekmarNet
®
4 Thermostats
•

© 2010
D 313 - 11/10
2 of 12
Table of Contents
Getting Started
Caution
Installation ......................................................................2
Preparation .................................................................2
Physical Dimensions ..................................................3
Installation Location ...................................................3
Rough-In Wiring .........................................................3
Sizing the Transformer ...............................................4
Control Wiring ............................................................4
Testing the Control Wiring ..........................................6
Applications ....................................................................7
User Interface ............................................................... 10
LEDs ........................................................................ 10
Sequence of Operation ................................................ 10
tekmarNet
®
System .................................................. 10
Relay Outputs ........................................................... 10
Energy Saving Features ........................................... 11
Troubleshooting ............................................................ 11
Frequently Asked Questions .................................... 11
Technical Data .............................................................. 12
Limited Warranty and Product Return Procedure ........ 12
Congratulations on the purchase of your new tekmarNet
®
Wiring Center!
This manual covers the complete installation, programming and sequence of operation for this control. You will also find
instruction on testing, commissioning, and troubleshooting the control and system that it operates.
Improper installation and operation of this control could
result in damage to the equipment and possibly even
personal injury or death. It is your responsibility to ensure
that this control is safely installed according to all applicable
codes and standards. This electronic control is not intended
for use as a primary limit control. Other controls that are
intended and certified as safety limits must be placed into
the control circuit. Do not attempt to service the control.
Refer to qualified personnel for servicing. There are no
user serviceable parts. Attempting to do so voids warranty
and could result in damage to the equipment and possibly
even personal injury or death.
Installation
The installer must ensure that this control and its wiring are
isolated and/or shielded from strong sources of electromagnetic
noise. Conversely, this Class B digital apparatus complies
with Part 15 of the FCC Rules and meets all requirements of
the Canadian Interference-Causing Equipment Regulations.
However, if this control does cause harmful interference
to radio or television reception, which is determined by
turning the control off and on, the user is encouraged to try
to correct the interference by re-orientating or relocating
the receiving antenna, relocating the receiver with respect
to this control, and/or connecting the control to a different
circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes
les exigences du Règlement sur le matériel brouilleur du
Canada.
Radio Frequency Interference
Preparation
Tools Required
---------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------
tekmar or jeweller screwdriver
Phillips head screwdriver
•
•
Needle-nose pliers
Wire stripper
•
•
Materials Required
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
(2) #10 x 1” wood screws
(2) wire nuts
18 AWG LVT solid wire (low voltage connections)
•
•
•
14 AWG solid wire (line voltage connections)
tekmar 009 (24 V (ac) transformer)
Cable or conduit connectors
•
•
•
Power Required
--------------------------------------------------------------------------------------
--------------------------------------------------------------------------------------
120 V (ac), 1-phase, 15 A service from circuit breaker
panel
•
Power disconnect (optional)
•

3 of 12
© 2010
D 313 - 11/10
Installation Location
When choosing the location for the control, consider the
following:
Keep dry. Avoid potential leakage onto the control.
RH 90% to 122°F (50°C) in a non-condensing
environment.
Do not expose to operating temperatures beyond 32-
122°F (0-50°C).
Provide adequate ventilation.
Keep away from equipment, appliances or other sources
of electrical interference.
•
•
•
•
•
Locate the control near zone valves if possible.
Provide easy access for wiring and viewing the
control.
Mount approximately 5 ft. (1.5 m) off the finished floor.
Install to wall using #10 x 1” wood screws. Wall anchors
are recommended when mounting to sheet rock, wall-
board or masonry.
•
•
•
•
Rough-In Wiring
Line Voltage Wiring
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
In most cases, the control can be mounted directly to a wall
without the need for any line voltage connections.
As an option, the control may be mounted to a 4” x 4”
electrical junction box so that the high voltage electrical
connections for the transformer are safely contained.
For ease of service, the circuit breaker or power disconnect
should be located in reasonably close proximity to the
equipment.
All line voltage wire connections are recommended to
be pulled inside a flexible or solid conduit. Always follow
proper wiring practices, building and electrical codes for
your jurisdiction.
Each cable must be pulled to the electrical junction box. It
is recommended to label each cable for easy identification.
All line voltage wires should be stripped to a length of 1/2”
(13 mm).
Pull a three conductor 14 AWG cable for the following
equipment:
Circuit Breaker or Power Disconnect (if applicable)
•
Physical Dimensions
5-1/2”
(140 mm)
5-1/2”
(140 mm)
1-1/8” (30 mm)
7/8”
(22 mm)
CL
Front View
1/2” Knock-out (x 4)
Ø 1/8” (3 mm)
7/8” x 1/2” (23 mm x 12 mm)
Knock-out (x 4)
1/2” x 5/8”
(12 mm x 16 mm)
Knock-out (x 4)
2-1/4”
(57 mm)
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 10 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
tN2 Wiring Center 313
Four Zone Valves
tN4
CX
Expansion
Vlv
C
Zone 1
Vlv
C
Zone 2
Vlv
C
Zone 3
Vlv
C
Zone 4
XC
Input P
ow
er
R
For use with
tN2 thermostats only
Mee
ts Class B: ICES & FCC P
ar
t 1
5
H8003A
End Switch
tN2
Use at leas
t 1
67°F (7
5°C) conduct
ors
Made in Canada
tektra 1034-01
Side View
Back View

© 2010
D 313 - 11/10
4 of 12
The control requires an external transformer. A tekmar
Transformer 009 (or 009K which includes a 4”x 4” electrical
box) can supply up to 40 VA, and includes an in-line fuse
to protect the transformer and control.
In order to correctly size the external transformer, all loads
connected to the control must be taken into account.
When adding up the loads, consider the following:
tekmarNet
®
2 Thermostats draw approximately 2 VA each.
Each zone valve must be sized for peak load. This can be
obtained by multiplying the peak current draw (in Amps)
by 24 V (ac).
•
•
The total power capacity of the power supply should be
larger than the total load of all the devices connected
to the control. This total load must not exceed 100 VA.
Multiple tekmar Transformer 009’s can be wired together
to increase total VA capacity.
The following chart is provided to simplify transformer
sizing:
Zone
1
2
3
4
Thermostat Load
Zone Valve Load
Control
Load (VA)
Total Zone Load
+
+
+
+
3
Transformer
must exceed:
VA
Sizing the Transformer
Control Wiring
Line Voltage Wiring
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
Wire the Ground
Connect the power supply ground to the electrical box
as shown in Figure 1.
Wire the Neutral (N)
Connect the 115 V (ac) neutral (N) wire to the 115 V
(ac) side of the transformer. Use a wire nut or approved
connector. See Figure 1.
Wire the Power (L)
Connect the 115 V (ac) line voltage (L) wire to the 115 V
(ac) side of the transformer. Use a wire nut or approved
connector. See Figure 1.
•
•
•
CAUTION: TURN ALL POWER OFF BEFORE PERFORMING ANY WIRING.
Each cable must be pulled from the equipment to the
control’s plastic enclosure. All low voltage wiring connections
enter the enclosure through conduit knockouts on the
sides, or through the square knockouts on the rear. It is
recommended to label each cable for easy identification.
All low voltage wires are to be stripped to a length of 3/8”
(9 mm) to ensure proper connection to the control.
Pull two conductor 18 AWG LVT cable, up to 500 feet
(150 m) for the following equipment:
tekmarNet
®
2 Thermostats
tekmarNet
®
2 House Control (if applicable)
•
•
24 V (ac) Power
Zone Valves
Boiler T-T (If using End Switch)
Pull three conductor 18 AWG LVT cable for the following
equipment:
tekmarNet
®
4 Accessories (User Switch, Timer)
•
•
•
•
Low Voltage Wiring
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
Power Source
(L, N, Ground)
Figure 1 - Connect
Line Voltage Wires

5 of 12
© 2010
D 313 - 11/10
External Power Supply
It is strongly recommended that a transformer with an in-line
fuse be used in order to protect the transformer from high
currents. The tekmar Transformer 009 includes a fuse.
Connect the 24 V (ac) leads from the transformer to the C
and R terminals marked “Input Power” on the 313.
tN2 Thermostats
The 313 is designed to operate with tekmarNet
®
2 Thermostats.
They provide the heating and cooling control for each zone,
and communicate with any other tekmarNet
®
device on
the system.
Connect the tN2 terminals from each thermostat to the
corresponding tN2 terminals for each zone on the 313.
Zone Valves
Wire the zone valves to the C and Vlv terminals on the 313.
End switches on zone valves are not required when
using the 313.
•
•
•
•
Low Voltage Wiring
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
The enclosure may be mounted directly to a wall or to
an electrical junction box.
Ensure that the high voltage wires are neatly tucked
inside the electrical junction box.
Using 2 of the 4 holes in the back of the enclosure, securely
fasten it to the electrical junction box with 2 #10 screws as
shown in Figure 2.
•
•
•
Install The Enclosure
---------------------------------------------------------------------------------
---------------------------------------------------------------------------------
Figure 2
tN4 Expansion Terminals
The 313 uses the Expansion tN4 and C terminals to communicate
with additional Wiring Centers, House Controls, and other
tekmarNet
®
devices.
Connect the tN4 and C Expansion terminals on the 313
to the corresponding tN4 and C Expansion terminals of
the additional external device.
Wiring the End Switch
The 313 can operate a single on-off boiler or provide a
demand to a tekmar control.
Connect the X X End Switch terminals on the 313 to the
T-T (or R-W) terminals on the boiler.
If required, use the X X End Switch terminals to switch
24 V (ac) to power a demand on a tekmar outdoor reset
control.
•
•
•

© 2010
D 313 - 11/10
6 of 12
Two Stage tN2 Thermostats
A two stage thermostat is automatically detected when
connected to Zone 1 or Zone 3. If there is no tN2 thermostat
connected to Zone 2 or Zone 4, these outputs will automatically
operate the heating equipment for 2nd stage heat.
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
tN2 Wiring Center 313
Four Zone Valves
tN4
CX
Expansion
Vlv
C
Zone 1
Vlv
C
Zone 2
Vlv
C
Zone 3
Vlv
C
Zone 4
Vlv
XC
Input P
ow
er
R
H8003B
End Switch
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 3 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
For use with
tN2 thermostats only
Mee
ts Class B: ICES & FCC P
ar
t 1
5
tN2
Use at leas
t 1
67°F (7
5°C) conduct
ors
Made in Canada
tektra 1034-01
Zone Valves
tekmarNet
®
2 Two-Stage Thermostats
Testing the Control Wiring
Testing the Power
-----------------------------
-----------------------------
If the control Power light does not turn on, check the Input
Power wiring terminals using an electrical multimeter. The
voltage should measure between 21.6 to 26.4 V (ac). If the
voltage is below this range, measure the line voltage side
of the transformer. The voltage should measure between
103.5 to 126.5 V (ac).
Testing the Thermostats
----------------------
----------------------
If the thermostat display turns on, this indicates that the
thermostat is operating correctly and there are no electrical
issues. In the event that the display is off, or the display is
cycling on and off, follow this procedure.
1. Remove the tN2 wires from the thermostat.
2. Use an electrical meter to measure DC voltage between
the tN2 terminals.
If the DC voltage is 0 V (dc) for 20 seconds, then there is
an open or short circuit in the tN2 wires. If the DC voltage
is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5
seconds, this indicates the wiring is correct.
3. Connect the thermostat to the tN2 wires from a zone
on a House Control, Wiring Center, or Zone Manager.
4. If the thermostat display is off, or is cycling on and off,
move the thermostat to the next available zone on the
House Control, Wiring Center, or Zone Manager.
If the thermostat display remains permanently on, there
may be a fault with the previously tried zone on the House
Control, Wiring Center, or Zone Manager.
If the thermostat display continues to be off, or is cycling
on and off, there may be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales representative
for assistance.
Testing the Zone Output
----------------------
----------------------
Turn up the thermostat connected to Zone 1 until it calls
for heat showing the H1 on the display. Using an electrical
meter, measure the voltage between the zone valve and
the common (C) terminals. The voltage should measure
between 21.6 V (ac) and 26.4 V (ac). Repeat for Zones 2,
3, and 4.
Two-Stage Thermostat Wiring
------------------------------------------------------------------------
------------------------------------------------------------------------
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
Two-Stage Terminal Designation
Zone 1
Zone 3
Stage 1
Stage 2
Stage 1 Stage 2

7 of 12
© 2010
D 313 - 11/10
Applications
R
C
L
N
Expansion
tN4
C
tN4
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
tN2 Wiring Center 313
Four Zone Valves
tN4
CX
Expansion
Vlv
C
Zone 1
Vlv
C
Zone 2
Vlv
C
Zone 3
Vlv
C
Zone 4
XC
Input P
ow
er
R
H8003B
End Switch
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 3 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
For use with
tN2 thermostats only
Mee
ts Class B: ICES & FCC P
ar
t 1
5
tN2
Use at leas
t 1
67°F (7
5°C) conduct
ors
Made in Canada
tektra 1034-01
Description:
tN2 Wiring Center 313, four tekmarNet
®
2 Thermostats, and four zone valves wired into a tekmar tN2 House
Control 400 which controls the boiler, primary pump and DHW pump.
tekmarNet
®
4 Expansion to House Control
A313-1
313
070
400
tekmarNet
®
2 Thermostats
24 V (ac)
Transformer 009
Zone Valves (Z1 to Z4)
External
tekmarNet
®
4
Expansion to
House Control
Z1
Z2
Z3
Z4
tekmarNet
®
2
Thermostats
tekmarNet
®
2
Thermostats

© 2010
D 313 - 11/10
8 of 12
Description:
tN2 Wiring Center 313, four tekmarNet
®
2 Thermostats, and four zone valves wired into a powered boiler
demand input on a device such as a tekmar Boiler Control 260 which controls the primary pump and DHW pump.
R
C
L
N
Demand
Boiler
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
tN2 Wiring Center 313
Four Zone Valves
tN4
CX
Expansion
Vlv
C
Zone 1
Vlv
C
Zone 2
Vlv
C
Zone 3
Vlv
C
Zone 4
XC
Input P
ow
er
R
H8003B
End Switch
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 3 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
For use with
tN2 thermostats only
Mee
ts Class B: ICES & FCC P
ar
t 1
5
tN2
Use at leas
t 1
67°F (7
5°C) conduct
ors
Made in Canada
tektra 1034-01
260
313
070
End Switch (X-X) To Powered Boiler Demand
A313-2
24 V (ac)
Transformer 009
Zone Valves (Z1 to Z4)
tekmarNet
®
2 Thermostats
Powered Boiler Demand
(ie. Input into tekmar
House Control)
tekmarNet
®
2 Thermostats
Z1
Z2
Z3
Z4

9 of 12
© 2010
D 313 - 11/10
Description:
tN2 Wiring Center 313, four tekmarNet
®
2 Thermostats, and four zone valves wired into the T-T terminals on
the boiler to give an enable. The primary pump is controlled externally.
R
C
L
N
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Zone 1
Zone 2
Zone 3
Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
tN2 Wiring Center 313
Four Zone Valves
tN4
CX
Expansion
Vlv
C
Zone 1
Vlv
C
Zone 2
Vlv
C
Zone 3
Vlv
C
Zone 4
XC
Input P
ow
er
R
H8003B
End Switch
Input Power: 24 V (ac) ±10% 60 Hz
100 VA Max, Class 2
Control Load: 3 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
4 A (96 VA) max total
For use with
tN2 thermostats only
Mee
ts Class B: ICES & FCC P
ar
t 1
5
tN2
Use at leas
t 1
67°F (7
5°C) conduct
ors
Made in Canada
tektra 1034-01
T
T
313
End Switch (X-X) To Boiler Enable (T-T)
A313-3
24 V (ac)
Transformer 009
Zone Valves (Z1 to Z4)
tekmarNet
®
2 Thermostats
End Switch (X-X)
to boiler enable (T-T)
Z1
Z2
Z3
Z4
tekmarNet
®
2 Thermostats

© 2010
D 313 - 11/10
10 of 12
Sequence of Operation
tekmarNet
®
System
Section A
tekmarNet
®
is a family of products that use communication
to operate the HVAC system in a comfortable and efficient
manner. The Wiring Center is a zoning component in
a tekmarNet
®
system and requires tekmarNet
®
2 (tN2)
Thermostats to be directly connected to it.
The tekmarNet
®
4 (tN4) Expansion terminals can link the
Wiring Center with other tekmarNet
®
components:
House Controls 400, 401, 402, 403 - Provides boiler and
DHW control
•
Wiring Centers 313, 314, 315, 316 - Add additional zones
tN4 Thermostats - Add thermostats
tN4 Timer 033 - Adds 4 programmable schedules
tN4 User Switch 479 - Provides a system override for
vacations and holidays
tN4 Setpoint Control 161, 162 - Control hot tubs, pools
and more
•
•
•
•
•
Relay Outputs
Section B
Synchronized End Switch Operation
----------
----------
tekmarNet
®
2 thermostats provide the Wiring Center with
a synchronized end switch feature. This ‘synchronizes’
the start times of the zones and reduces short cycling of
equipment connected to the wiring center’s end switch.
The net effect is increased system efficiency and reduced
wear on equipment.
The End Switch relay (‘XX’) closes and the end switch
LED turns on. The switch remains closed as long as any
zone is calling for heat. This can provide a boiler demand
to a tekmar reset control, or provide a boiler enable to a
boiler’s TT terminals.
If the Wiring Center is connected to a tN4 bus, all
communication messages will pass through the 313’s
tN4 expansion connection. tN4 messages are required
in order to create a boiler demand on a device such as
a tekmar House Control 400.
24 V (ac) Zone Relay Operation
----------------
----------------
When a thermostat calls for heat, it sends a message to
the Wiring Center and the corresponding zone LED turns
on. Power is then supplied to the appropriate zone output
as indicated by the LED.
•
ZONE 1
The zone 1 thermostat is calling for heat
and the 24 V (ac) output is energized.
ZONE 2
The zone 2 thermostat is calling for heat
and the 24 V (ac) output is energized.
ZONE 3
The zone 3 thermostat is calling for heat
and the 24 V (ac) output is energized.
ZONE 4
The zone 4 thermostat is calling for heat
and the 24 V (ac) output is energized.
POWER
24 V (ac) is being applied to the Wiring
Center to provide it with power.
END SWITCH
At least one of the zone thermostats are
calling for heat and the end switch relay
output is closed.
LEDs
User Interface
Power
Zone 1
Zone 2
Zone 3
Zone 4
End Switch
Wiring Center 313
Zone LED Flashing
----------------------------
----------------------------
The zone has an open or short circuit and communication
to the thermostat on the zone has been interrupted. Check
the wiring between the thermostat and the Wiring Center
for open or short circuits. If the thermostat was intentionally
removed, power the Wiring Center off for 10 seconds.

11 of 12
© 2010
D 313 - 11/10
Network Schedules
----------------------------
----------------------------
Adding a schedule to a tekmarNet
®
system is both easy
and valuable. A Timer 033 provides scheduling with up to
4 events per day for every tekmarNet
®
Thermostat. Turning
down the room temperatures when they are unoccupied
reduces boiler on-time and energy consumption which
helps save money and the environment.
One-Touch Economy
--------------------------
--------------------------
A User Switch 479 allows for one-touch overrides of the
system. For example, if leaving the building for vacation,
simply press the “Away” button and all the thermostats
will immediately operate at a lower temperature, instead
of having to walk around the building lowering the heating
temperature setting and raising the cooling temperature
setting on each thermostat.
Energy Saving Features
Section C
Zone Synchronization
-------------------------
-------------------------
Another feature of the Wiring Center is Zone Synchronization.
In typical zoned systems, the thermostats operate on a
stand-alone basis. This means that a zone turns on and off
as required without any regard for other zones. The net effect
is random operation of the zones causing short cycling of
the heat source. tekmarNet
®
thermostats communicate to
ensure that their cycles are synchronized. Energy is saved
by ensuring zones requiring heat operate on the same cycle,
therefore reducing short cycling of the boiler.
Symptom
Look For...
Corrective Action
Power LED is off Power to control
Use electrical meter to measure 24 V (ac) voltage on input power R and C
terminals.
No central
heating
Zone LEDs
If there are no green Zone LEDs, there are no thermostats calling for heat.
System in AWAY
During AWAY, the thermostats operate at a lower temperature. Locate a ‘User
Switch’ and set to Normal to resume heating.
Single zone over
heating
LED shows zone on
Thermostats have a differential of +/- 1.5°F (0.8°C) of the temperature setting.
Due to the display rounding numbers up, heating can appear on when the
temperature is 2°F (1.1°C) above the setting. This is normal operation.
LED shows zone off
Ensure zone valve terminals measure 0 V (ac). Measuring 0 V (ac) indicates
mechanical zone valve may have failed in open position. Measuring 24 V (ac)
indicates control relay may have failed.
Single zone under
heating
LED shows zone on
Ensure zone valve terminals measure 24 V (ac). Measuring 24 V (ac) indicates
mechanical zone valve may have failed in closed position. Measuring 0 V (ac)
indicates control relay may have failed.
LED shows zone off
Check the thermostat to see if it is calling for heat (H1 displayed on the screen).
Zone LED flashing
The zone has an open or short circuit and communication to the thermostat on
the zone has been interrupted. Check the wiring between the thermostat and
the Wiring Center for open or short circuits. If the thermostat was intentionally
removed, power the Wiring Center off for 10 seconds.
Frequently Asked Questions
Troubleshooting

Product design, software and literature are Copyright © 2010 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
12 of 12
All specifications are subject to change without notice.
Printed in Canada. D 313 - 11/10.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Offi ce: 5100 Silver Star Road,
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
Limited Warranty
The liability of tekmar under this warranty is lim-
ited. The Purchaser, by taking receipt of any tekmar product (“Prod-
uct”), acknowledges the terms of the Limited Warranty in effect at
the time of such Product sale and acknowledges that it has read
and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold
hereunder is a manufacturer’s pass-through warranty which the
Purchaser is authorized to pass through to its customers. Under
the Limited Warranty, each tekmar Product is warranted against
defects in workmanship and materials if the Product is installed and
used in compliance with tekmar’s instructions, ordinary wear and
tear excepted. The pass-through warranty period is for a period of
twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the docu-
mented date of installation if installed within twenty-four (24) months
from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at
tekmar’s sole discretion: the cost of parts and labor provided by tekmar
to repair defects in materials and/or workmanship of the defective prod-
uct; or to the exchange of the defective product for a warranty replace-
ment product; or to the granting of credit limited to the original cost of the
defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any
way, tekmar is not responsible, in contract, tort or strict product liabil-
ity, for any other losses, costs, expenses, inconveniences, or damages,
whether direct, indirect, special, secondary, incidental or consequential,
arising from ownership or use of the product, or from defects in work-
manship or materials, including any liability for fundamental breach of
contract.
The pass-through Limited Warranty applies only to those defective Prod-
ucts returned to tekmar during the warranty period. This Limited War-
ranty does not cover the cost of the parts or labor to remove or transport
the defective Product, or to reinstall the repaired or replacement Product,
all such costs and expenses being subject to Purchaser’s agreement and
warranty with its customers.
Any representations or warranties about the Products made by Purchaser
to its customers which are different from or in excess of the tekmar Lim-
ited Warranty are the Purchaser’s sole responsibility and obligation. Pur-
chaser shall indemnify and hold tekmar harmless from and against any
and all claims, liabilities and damages of any kind or nature which arise
out of or are related to any such representations or warranties by Pur-
chaser to its customers.
The pass-through Limited Warranty does not apply if the returned Prod-
uct has been damaged by negligence by persons other than tekmar,
accident, fire, Act of God, abuse or misuse; or has been damaged by
modifications, alterations or attachments made subsequent to purchase
which have not been authorized by tekmar; or if the Product was not
installed in compliance with tekmar’s instructions and/or the local codes
and ordinances; or if due to defective installation of the Product; or if the
Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA-
TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT
EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUC-
TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY
THE GOVERNING LAW.
Product Warranty Return Procedure
All Products that are believed to
have defects in workmanship or materials must be returned, together
with a written description of the defect, to the tekmar Representative
assigned to the territory in which such Product is located. If tekmar
receives an inquiry from someone other than a tekmar Representative,
including an inquiry from Purchaser (if not a tekmar Representative) or
Purchaser’s customers, regarding a potential warranty claim, tekmar’s
sole obligation shall be to provide the address and other contact informa-
tion regarding the appropriate Representative.
Technical Data
tN2 Wiring Center 313
Four Zone Valves
Literature
D313, Q313
Control
Microprocessor control. This is not a safety (limit) control.
Packaged weight
1.4 lbs (640 g)
Dimensions
5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm)
Enclosure
NEMA 1 rated, Blue PC+ABS plastic
Approvals
CSA C US, meets class B: ICES & FCC Part 15
Ambient conditions
Indoor use only, 32 to 122°F (0 to 50°C), RH 90% Non-condensing
Power supply
24 V (ac) ±10% 60 Hz, 3 VA min, 100 VA max, Class 2
Zone valve load
24 V (ac) 2 A, maximum combined current (zones 1 to 4): 4 A
End switch relay
24 V (ac) 2 A
Warranty
Limited 3 Year
Limited Warranty and Product Return Procedure