PDF User Manual

  1. Home
  2. Manuals
  3. Tekmar 313 Installation & Operation Manual

Tekmar 313 Installation & Operation Manual

Made by: Tekmar
Type: Installation & Operation Manual
Category: Control Systems
Pages: 12
Size: 1.14 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

1 of 12

© 2010  

D 313  -  11/10

tekmarNet

®

2 Wiring Center 313

D 313

11/10

Zoning

Replaces: 10/09

Installation & Operation Manual

Benefi ts

Simple, convenient wiring location
Compact enclosure for flexible installation
Reduce equipment cycling through the use of 
tekmarNet

®

2 Thermostats



The tekmarNet

®

2 (tN2) Wiring Center 313 is designed to 

operate up to four zone valves in a hydronic heating system. 
It can be mounted in the mechanical room or near a remote 
zone manifold, providing a convenient location to wire both 
thermostats and zone valves while only requiring two wires 
to be run back to the mechanical room. When combined 
with tekmarNet

®

2 Thermostats, all devices communicate 

to provide a synchronized end switch that reduces cycling 
of equipment.

Features

Four 24 V (ac) powered zone outputs
For use with tekmarNet

®

2 Thermostats

Supports two-stage tekmarNet

®

2 Thermostats

tN4 expansion terminals
Isolated end switch
External diagnostic LEDs
CSA C US Certified for use in USA and Canada







Introduction

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 10 VA
End Switch:  24 V (ac) 2 A
Zone Output:  2 A (48 VA) per zone
 

4 A (96 VA) max total

 

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

tN2 Wiring Center 313

Four Zone Valves

For use with 

tN2 thermostats only

tN2

Made in Canada

tektra 1034-01

Note

Not for use with tekmarNet

®

4 Thermostats


background image

© 2010

D 313 - 11/10

2 of 12

 Table of Contents 

 Getting Started 

  

 Caution 

   

Installation ......................................................................2

Preparation .................................................................2
Physical Dimensions ..................................................3
Installation Location ...................................................3
Rough-In Wiring .........................................................3
Sizing the Transformer ...............................................4
Control Wiring ............................................................4
Testing the Control Wiring ..........................................6

Applications ....................................................................7

User Interface ............................................................... 10

LEDs ........................................................................ 10

Sequence of Operation ................................................ 10

tekmarNet

®

 System .................................................. 10

Relay Outputs ........................................................... 10
Energy Saving Features ........................................... 11

Troubleshooting ............................................................ 11

Frequently Asked Questions .................................... 11

Technical Data .............................................................. 12

Limited Warranty and Product Return Procedure ........ 12

Congratulations on the purchase of your new tekmarNet

® 

Wiring Center!

This manual covers the complete installation, programming and sequence of operation for this control. You will also find 
instruction on testing, commissioning, and troubleshooting the control and system that it operates. 

Improper installation and operation of this control could 
result in damage to the equipment and possibly even 
personal injury or death. It is your responsibility to ensure 
that this control is safely installed according to all applicable 
codes and standards. This electronic control is not intended 
for use as a primary limit control. Other controls that are 
intended and certified as safety limits must be placed into 

the control circuit. Do not attempt to service the control. 
Refer to qualified personnel for servicing. There are no 
user serviceable parts. Attempting to do so voids warranty 
and could result in damage to the equipment and possibly 
even personal injury or death.

Installation

The installer must ensure that this control and its wiring are 
isolated and/or shielded from strong sources of electromagnetic 
noise. Conversely, this Class B digital apparatus complies 
with Part 15 of the FCC Rules and meets all requirements of 
the Canadian Interference-Causing Equipment Regulations. 
However, if this control does cause harmful interference 
to radio or television reception, which is determined by 
turning the control off and on, the user is encouraged to try 

to correct the interference by re-orientating or relocating 
the receiving antenna, relocating the receiver with respect 
to this control, and/or connecting the control to a different 
circuit from that to which the receiver is connected.

Cet appareil numérique de la classe B respecte toutes 
les exigences du Règlement sur le matériel brouilleur du 
Canada.

 Radio Frequency Interference 

Preparation

Tools Required

 ---------------------------------------------------------------------------------------

 ---------------------------------------------------------------------------------------

tekmar or jeweller screwdriver
Phillips head screwdriver


Needle-nose pliers
Wire stripper


Materials Required

 -----------------------------------------------------------------------------------

 -----------------------------------------------------------------------------------

(2) #10 x 1” wood screws
(2) wire nuts
18 AWG LVT solid wire (low voltage connections)



14 AWG solid wire (line voltage connections)
tekmar 009 (24 V (ac) transformer)
Cable or conduit connectors



Power Required

 --------------------------------------------------------------------------------------

 --------------------------------------------------------------------------------------

120 V (ac), 1-phase, 15 A service from circuit breaker 
panel

Power disconnect (optional)


background image

3 of 12

© 2010  

D 313 - 11/10

Installation Location

When choosing the location for the control, consider the 
following:
Keep dry. Avoid potential leakage onto the control.
RH   90% to 122°F (50°C) in a non-condensing 
environment.
Do not expose to operating temperatures beyond 32-
122°F (0-50°C).
Provide adequate ventilation.
Keep away from equipment, appliances or other sources 
of electrical interference.


Locate the control near zone valves if possible.
Provide easy access for wiring and viewing the 
control.
Mount approximately 5 ft. (1.5 m) off the finished floor.
Install to wall using #10 x 1” wood screws. Wall anchors 
are recommended when mounting to sheet rock, wall-
board or masonry.



Rough-In Wiring

Line Voltage Wiring

-----------------------------------------------------------------------------------

-----------------------------------------------------------------------------------

In most cases, the control can be mounted directly to a wall 
without the need for any line voltage connections.

As an option, the control may be mounted to a 4” x 4” 
electrical junction box so that the high voltage electrical 
connections for the transformer are safely contained.

For ease of service, the circuit breaker or power disconnect 
should be located in reasonably close proximity to the 
equipment.

All line voltage wire connections are recommended to 
be pulled inside a flexible or solid conduit. Always follow 
proper wiring practices, building and electrical codes for 
your jurisdiction. 

Each cable must be pulled to the electrical junction box. It 
is recommended to label each cable for easy identification. 
All line voltage wires should be stripped to a length of 1/2” 
(13 mm).

Pull a three conductor 14 AWG cable for the following 
equipment:

Circuit Breaker or Power Disconnect (if applicable)

Physical Dimensions

5-1/2”

(140 mm)

5-1/2”

(140 mm)

1-1/8” (30 mm)

7/8”

(22 mm)

CL

Front View

1/2” Knock-out (x 4)

Ø 1/8” (3 mm)

7/8” x 1/2” (23 mm x 12 mm)

Knock-out (x 4)

1/2” x 5/8”

(12 mm x 16 mm)

Knock-out (x 4)

2-1/4”

(57 mm)

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 10 VA
End Switch:  24 V (ac) 2 A
Zone Output:  2 A (48 VA) per zone
 

4 A (96 VA) max total

 

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

tN2 Wiring Center 313

Four Zone Valves

tN4

CX

Expansion

Vlv

C

Zone 1

Vlv

C

Zone 2

Vlv

C

Zone 3

Vlv

C

Zone 4

XC

Input P

ow

er

R

For use with 

tN2 thermostats only

Mee

ts Class B: ICES & FCC P

ar

t 1

5

H8003A

End Switch

tN2

Use at leas

t 1

67°F (7

5°C) conduct

ors

Made in Canada

tektra 1034-01

Side View

Back View


background image

© 2010

D 313 - 11/10

4 of 12

The control requires an external transformer. A tekmar 
Transformer 009 (or 009K which includes a 4”x 4” electrical 
box) can supply up to 40 VA, and includes an in-line fuse 
to protect the transformer and control.
In order to correctly size the external transformer, all loads 
connected to the control must be taken into account. 
When adding up the loads, consider the following:

tekmarNet

®

2 Thermostats draw approximately 2 VA each.

Each zone valve must be sized for peak load. This can be 
obtained by multiplying the peak current draw (in Amps) 
by 24 V (ac).


The total power capacity of the power supply should be 
larger than the total load of all the devices connected 
to the control. This total load must not exceed 100 VA. 
Multiple tekmar Transformer 009’s can be wired together 
to increase total VA capacity. 

The following chart is provided to simplify transformer 
sizing:

Zone

1

2

3

4

Thermostat Load

Zone Valve Load

Control 

Load (VA)

Total Zone Load

+

 

+

+

+

3

Transformer 

must exceed:

VA

Sizing the Transformer

Control Wiring

Line Voltage Wiring

-----------------------------------------------------------------------------------

-----------------------------------------------------------------------------------

Wire the Ground

Connect the power supply ground to the electrical box 
as shown in Figure 1.

Wire the Neutral (N)

Connect the 115 V (ac) neutral (N) wire to the 115 V 
(ac) side of the transformer. Use a wire nut or approved 
connector. See Figure 1.

Wire the Power (L)

Connect the 115 V (ac) line voltage (L) wire to the 115 V 
(ac) side of the transformer. Use a wire nut or approved 
connector. See Figure 1.

CAUTION: TURN ALL POWER OFF BEFORE PERFORMING ANY WIRING.

Each cable must be pulled from the equipment to the 
control’s plastic enclosure. All low voltage wiring connections 
enter the enclosure through conduit knockouts on the 
sides, or through the square knockouts on the rear. It is 
recommended to label each cable for easy identification. 
All low voltage wires are to be stripped to a length of 3/8” 
(9 mm) to ensure proper connection to the control.

Pull two conductor 18 AWG LVT cable, up to 500 feet 
(150 m) for the following equipment:

tekmarNet

®

2 Thermostats

tekmarNet

®

2 House Control (if applicable)


24 V (ac) Power
Zone Valves
Boiler T-T (If using End Switch)

Pull three conductor 18 AWG LVT cable for the following 
equipment:

tekmarNet

®

4 Accessories (User Switch, Timer)



Low Voltage Wiring

 -----------------------------------------------------------------------------------

 -----------------------------------------------------------------------------------

Power Source 

(L, N, Ground)

Figure 1 - Connect 
Line Voltage Wires


background image

5 of 12

© 2010  

D 313 - 11/10

External Power Supply

It is strongly recommended that a transformer with an in-line 
fuse be used in order to protect the transformer from high 
currents. The tekmar Transformer 009 includes a fuse.

Connect the 24 V (ac) leads from the transformer to the C 
and R terminals marked “Input Power” on the 313.

tN2 Thermostats

The 313 is designed to operate with tekmarNet

®

2 Thermostats. 

They provide the heating and cooling control for each zone, 
and communicate with any other tekmarNet

®

 device on 

the system.

Connect the tN2 terminals from each thermostat to the 
corresponding tN2 terminals for each zone on the 313.

Zone Valves

Wire the zone valves to the C and Vlv terminals on the 313.
End switches on zone valves are not required when 
using the 313.


Low Voltage Wiring

 -----------------------------------------------------------------------------------

 -----------------------------------------------------------------------------------

The enclosure may be mounted directly to a wall or to 
an electrical junction box.
Ensure that the high voltage wires are neatly tucked 
inside the electrical junction box.
Using 2 of the 4 holes in the back of the enclosure, securely 
fasten it to the electrical junction box with 2 #10 screws as 
shown in Figure 2.

Install The Enclosure

 ---------------------------------------------------------------------------------

 ---------------------------------------------------------------------------------

Figure 2

tN4 Expansion Terminals

The 313 uses the Expansion tN4 and C terminals to communicate 
with additional Wiring Centers, House Controls, and other 
tekmarNet

®

 devices.

Connect the tN4 and C Expansion terminals on the 313 
to the corresponding tN4 and C Expansion terminals of 
the additional external device.

Wiring the End Switch

The 313 can operate a single on-off boiler or provide a 
demand to a tekmar control.

Connect the X X End Switch terminals on the 313 to the 
T-T (or R-W) terminals on the boiler.
If required, use the X X End Switch terminals to switch 
24 V (ac) to power a demand on a tekmar outdoor reset 
control.


background image

© 2010

D 313 - 11/10

6 of 12

Two Stage tN2 Thermostats

A two stage thermostat is automatically detected when 
connected to Zone 1 or Zone 3. If there is no tN2 thermostat 
connected to Zone 2 or Zone 4, these outputs will automatically 
operate the heating equipment for 2nd stage heat.

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

tN2 Wiring Center 313

Four Zone Valves

tN4

CX

Expansion

Vlv

C

Zone 1

Vlv

C

Zone 2

Vlv

C

Zone 3

Vlv

C

Zone 4

Vlv

XC

Input P

ow

er

R

H8003B

End Switch

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 3 VA
End Switch:  24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
 

4 A (96 VA) max total

 

For use with 

tN2 thermostats only

Mee

ts Class B: ICES & FCC P

ar

t 1

5

tN2

Use at leas

t 1

67°F (7

5°C) conduct

ors

Made in Canada

tektra 1034-01

Zone Valves

tekmarNet

®

2 Two-Stage Thermostats

Testing the Control Wiring

Testing the Power 

 

-----------------------------

 

-----------------------------

If the control Power light does not turn on, check the Input 
Power wiring terminals using an electrical multimeter. The 
voltage should measure between 21.6 to 26.4 V (ac). If the 
voltage is below this range, measure the line voltage side 
of the transformer. The voltage should measure between 
103.5 to 126.5 V (ac).

Testing the Thermostats 

 ----------------------

 ----------------------

If the thermostat display turns on, this indicates that the 
thermostat is operating correctly and there are no electrical 
issues. In the event that the display is off, or the display is 
cycling on and off, follow this procedure.

1.  Remove the tN2 wires from the thermostat.
2.  Use an electrical meter to measure DC voltage between 

the tN2 terminals.

If the DC voltage is 0 V (dc) for 20 seconds, then there is 
an open or short circuit in the tN2 wires. If the DC voltage 
is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5 
seconds, this indicates the wiring is correct.

3.  Connect the thermostat to the tN2 wires from a zone 

on a House Control, Wiring Center, or Zone Manager.

4.  If the thermostat display is off, or is cycling on and off, 

move the thermostat to the next available zone on the 
House Control, Wiring Center, or Zone Manager.

If the thermostat display remains permanently on, there 
may be a fault with the previously tried zone on the House 
Control, Wiring Center, or Zone Manager.

If the thermostat display continues to be off, or is cycling 
on and off, there may be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales representative 
for assistance.

Testing the Zone Output 

 ----------------------

 ----------------------

Turn up the thermostat connected to Zone 1 until it calls 
for heat showing the H1 on the display. Using an electrical 
meter, measure the voltage between the zone valve and 
the common (C) terminals. The voltage should measure 
between 21.6 V (ac) and 26.4 V (ac). Repeat for Zones 2, 
3, and 4.

Two-Stage Thermostat Wiring

 ------------------------------------------------------------------------

 ------------------------------------------------------------------------

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

Two-Stage Terminal Designation

Zone 1

Zone 3

Stage 1

Stage 2

Stage 1 Stage 2


background image

7 of 12

© 2010  

D 313 - 11/10

Applications

R

C

L

N

Expansion

tN4

C

tN4

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

tN2 Wiring Center 313

Four Zone Valves

tN4

CX

Expansion

Vlv

C

Zone 1

Vlv

C

Zone 2

Vlv

C

Zone 3

Vlv

C

Zone 4

XC

Input P

ow

er

R

H8003B

End Switch

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 3 VA
End Switch:  24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
 

4 A (96 VA) max total

 

For use with 

tN2 thermostats only

Mee

ts Class B: ICES & FCC P

ar

t 1

5

tN2

Use at leas

t 1

67°F (7

5°C) conduct

ors

Made in Canada

tektra 1034-01

Description:

 tN2 Wiring Center 313, four tekmarNet

®

2 Thermostats, and four zone valves wired into a tekmar tN2 House 

Control 400 which controls the boiler, primary pump and DHW pump.

tekmarNet

®

4 Expansion to House Control

A313-1

313

070

400

tekmarNet

®

2 Thermostats

24 V (ac)

Transformer 009

Zone Valves (Z1 to Z4)

External 

tekmarNet

®

4

Expansion to

House Control

Z1

Z2

Z3

Z4

tekmarNet

®

Thermostats

tekmarNet

®

Thermostats


background image

© 2010

D 313 - 11/10

8 of 12

Description: 

tN2 Wiring Center 313, four tekmarNet

®

2 Thermostats, and four zone valves wired into a powered boiler 

demand input on a device such as a tekmar Boiler Control 260 which controls the primary pump and DHW pump.

R

C

L

N

Demand

Boiler

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

tN2 Wiring Center 313

Four Zone Valves

tN4

CX

Expansion

Vlv

C

Zone 1

Vlv

C

Zone 2

Vlv

C

Zone 3

Vlv

C

Zone 4

XC

Input P

ow

er

R

H8003B

End Switch

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 3 VA
End Switch:  24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
 

4 A (96 VA) max total

 

For use with 

tN2 thermostats only

Mee

ts Class B: ICES & FCC P

ar

t 1

5

tN2

Use at leas

t 1

67°F (7

5°C) conduct

ors

Made in Canada

tektra 1034-01

260

313

070

End Switch (X-X) To Powered Boiler Demand

A313-2

24 V (ac)

Transformer 009

Zone Valves (Z1 to Z4)

tekmarNet

®

2 Thermostats

Powered Boiler Demand 

(ie. Input into tekmar 

House Control)

tekmarNet

®

2 Thermostats

Z1

Z2

Z3

Z4


background image

9 of 12

© 2010  

D 313 - 11/10

Description: 

tN2 Wiring Center 313, four tekmarNet

®

2 Thermostats, and four zone valves wired into the T-T terminals on 

the boiler to give an enable. The primary pump is controlled externally.

R

C

L

N

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Zone 1

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

tN2 Wiring Center 313

Four Zone Valves

tN4

CX

Expansion

Vlv

C

Zone 1

Vlv

C

Zone 2

Vlv

C

Zone 3

Vlv

C

Zone 4

XC

Input P

ow

er

R

H8003B

End Switch

Input Power:  24 V (ac) ±10% 60 Hz

 

100 VA Max, Class 2                      

Control Load: 3 VA
End Switch:  24 V (ac) 2 A
Zone Output: 2 A (48 VA) per zone
 

4 A (96 VA) max total

 

For use with 

tN2 thermostats only

Mee

ts Class B: ICES & FCC P

ar

t 1

5

tN2

Use at leas

t 1

67°F (7

5°C) conduct

ors

Made in Canada

tektra 1034-01

T

T

313

End Switch (X-X) To Boiler Enable (T-T)

A313-3

24 V (ac)

Transformer 009

Zone Valves (Z1 to Z4)

tekmarNet

®

2 Thermostats

End Switch (X-X)

to boiler enable (T-T) 

Z1

Z2

Z3

Z4

tekmarNet

®

2 Thermostats


background image

© 2010

D 313 - 11/10

10 of 12

Sequence of Operation

 tekmarNet

®

 System 

Section A

tekmarNet

®

 is a family of products that use communication 

to operate the HVAC system in a comfortable and efficient 
manner. The Wiring Center is a zoning component in 
a tekmarNet

®

 system and requires tekmarNet

®

2 (tN2) 

Thermostats to be directly connected to it.

The tekmarNet

®

4 (tN4) Expansion terminals can link the 

Wiring Center with other tekmarNet

®

 components:

House Controls 400, 401, 402, 403 - Provides boiler and 
DHW control

Wiring Centers 313, 314, 315, 316 - Add additional zones
tN4 Thermostats - Add thermostats
tN4 Timer 033 - Adds 4 programmable schedules
tN4 User Switch 479 - Provides a system override for 
vacations and holidays
tN4 Setpoint Control 161, 162 - Control hot tubs, pools 
and more




Relay Outputs

Section B

Synchronized End Switch Operation

 ----------

 ----------

tekmarNet

®

2 thermostats provide the Wiring Center with 

a synchronized end switch feature. This ‘synchronizes’ 
the start times of the zones and reduces short cycling of 
equipment connected to the wiring center’s end switch. 
The net effect is increased system efficiency and reduced 
wear on equipment. 

The End Switch relay (‘XX’) closes and the end switch 
LED turns on.  The switch remains closed as long as any 
zone is calling for heat. This can provide a boiler demand 
to a tekmar reset control, or provide a boiler enable to a 
boiler’s TT terminals. 

If the Wiring Center is connected to a tN4 bus, all 
communication messages will pass through the 313’s 
tN4 expansion connection. tN4 messages are required 
in order to create a boiler demand on a device such as 
a tekmar House Control 400.

24 V (ac) Zone Relay Operation

 ----------------

 ----------------

When a thermostat calls for heat, it sends a message to 
the Wiring Center and the corresponding zone LED turns 
on. Power is then supplied to the appropriate zone output 
as indicated by the LED.

ZONE 1

The zone 1 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 2

The zone 2 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 3

The zone 3 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 4

The zone 4 thermostat is calling for heat 
and the 24 V (ac) output is energized.

POWER

24 V (ac) is being applied to the Wiring 
Center to provide it with power.

END SWITCH

At least one of the zone thermostats are 
calling for heat and the end switch relay 
output is closed. 

LEDs

User Interface

Power

Zone 1

Zone 2

Zone 3

Zone 4

End Switch

Wiring Center 313

Zone LED Flashing

 ----------------------------

 ----------------------------

The zone has an open or short circuit and communication 
to the thermostat on the zone has been interrupted. Check 
the wiring between the thermostat and the Wiring Center 
for open or short circuits. If the thermostat was intentionally 
removed, power the Wiring Center off for 10 seconds.


background image

11 of 12

© 2010  

D 313 - 11/10

Network Schedules

----------------------------

----------------------------

Adding a schedule to a tekmarNet

®

 system is both easy 

and valuable. A Timer 033 provides scheduling with up to 
4 events per day for every tekmarNet

®

 Thermostat. Turning 

down the room temperatures when they are unoccupied 
reduces boiler on-time and energy consumption which 
helps save money and the environment.

One-Touch Economy

 --------------------------

 --------------------------

A User Switch 479 allows for one-touch overrides of the 
system.  For example, if leaving the building for vacation, 
simply press the “Away” button and all the thermostats 
will immediately operate at a lower temperature, instead 
of having to walk around the building lowering the heating 
temperature setting and raising the cooling temperature 
setting on each thermostat.

 Energy Saving Features 

Section C

Zone Synchronization

 -------------------------

 -------------------------

Another feature of the Wiring Center is Zone Synchronization. 
In typical zoned systems, the thermostats operate on a 
stand-alone basis. This means that a zone turns on and off 
as required without any regard for other zones. The net effect 
is random operation of the zones causing short cycling of 
the heat source. tekmarNet

®

 thermostats communicate to 

ensure that their cycles are synchronized. Energy is saved 
by ensuring zones requiring heat operate on the same cycle, 
therefore reducing short cycling of the boiler.

Symptom

Look For...

Corrective Action

Power LED is off Power to control

Use electrical meter to measure 24 V (ac) voltage on input power R and C 
terminals.

No central 
heating

Zone LEDs

If there are no green Zone LEDs, there are no thermostats calling for heat.

System in AWAY

During AWAY, the thermostats operate at a lower temperature. Locate a ‘User 
Switch’ and set to Normal to resume heating.

Single zone over 
heating

LED shows zone on

Thermostats have a differential of +/- 1.5°F (0.8°C) of the temperature setting. 
Due to the display rounding numbers up, heating can appear on when the 
temperature is 2°F (1.1°C) above the setting. This is normal operation.

LED shows zone off

Ensure zone valve terminals measure 0 V (ac). Measuring 0 V (ac) indicates 
mechanical zone valve may have failed in open position. Measuring 24 V (ac) 
indicates control relay may have failed.

Single zone under 
heating

LED shows zone on

Ensure zone valve terminals measure 24 V (ac). Measuring 24 V (ac) indicates 
mechanical zone valve may have failed in closed position. Measuring 0 V (ac) 
indicates control relay may have failed.

LED shows zone off

Check the thermostat to see if it is calling for heat (H1 displayed on the screen). 

Zone LED flashing

The zone has an open or short circuit and communication to the thermostat on 
the zone has been interrupted. Check the wiring between the thermostat and 
the Wiring Center for open or short circuits. If the thermostat was intentionally 
removed, power the Wiring Center off for 10 seconds.

 Frequently Asked Questions 

Troubleshooting


background image

Product design, software and literature are Copyright © 2010 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

12 of 12

All specifications are subject to change without notice.

Printed in Canada. D 313 - 11/10.

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. 

Head Offi ce: 5100 Silver Star Road, 

Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650  Web Site: www.tekmarcontrols.com

Limited Warranty 

The liability of tekmar under this warranty is lim-

ited. The Purchaser, by taking receipt of any tekmar product (“Prod-
uct”), acknowledges the terms of the Limited Warranty in effect at 
the time of such Product sale and acknowledges that it has read 
and understands same.

The tekmar Limited Warranty to the Purchaser on the Products sold 
hereunder is a manufacturer’s pass-through warranty which the 
Purchaser is authorized to pass through to its customers. Under 
the Limited Warranty, each tekmar Product is warranted against 
defects in workmanship and materials if the Product is installed and 
used in compliance with tekmar’s instructions, ordinary wear and 
tear excepted. The pass-through warranty period is for a period of 
twenty-four (24) months from the production date if the Product is 
not installed during that period, or twelve (12) months from the docu-
mented date of installation if installed within twenty-four (24) months 
from the production date.

The liability of tekmar under the Limited Warranty shall be limited to, at 
tekmar’s sole discretion: the cost of parts and labor provided by tekmar 
to repair defects in materials and/or workmanship of the defective prod-
uct; or to the exchange of the defective product for a warranty replace-
ment product; or to the granting of credit limited to the original cost of the 
defective product, and such repair, exchange or credit shall be the sole 
remedy available from tekmar, and, without limiting the foregoing in any 
way,  tekmar  is  not  responsible,  in  contract,  tort  or  strict  product  liabil-
ity, for any other losses, costs, expenses, inconveniences, or damages, 
whether direct, indirect, special, secondary, incidental or consequential, 
arising from ownership or use of the product, or from defects in work-
manship or materials, including any liability for fundamental breach of 
contract.

The pass-through Limited Warranty applies only to those defective Prod-
ucts  returned  to  tekmar  during  the  warranty  period.  This  Limited  War-
ranty does not cover the cost of the parts or labor to remove or transport 
the defective Product, or to reinstall the repaired or replacement Product, 
all such costs and expenses being subject to Purchaser’s agreement and 
warranty with its customers.

Any representations or warranties about the Products made by Purchaser 
to its customers which are different from or in excess of the tekmar Lim-
ited Warranty are the Purchaser’s sole responsibility and obligation. Pur-
chaser shall indemnify and hold tekmar harmless from and against any 
and all claims, liabilities and damages of any kind or nature which arise 
out of or are related to any such representations or warranties by Pur-
chaser to its customers.

The pass-through Limited Warranty does not apply if the returned Prod-
uct has been damaged by negligence by persons other than tekmar, 
accident, fire, Act of God, abuse or misuse; or has been damaged by 
modifications, alterations or attachments made subsequent to purchase 
which have not been authorized by tekmar; or if the Product was not 
installed in compliance with tekmar’s instructions and/or the local codes 
and ordinances; or if due to defective installation of the Product; or if the 
Product was not used in compliance with tekmar’s instructions.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS 
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO 
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, 
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR 
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE 
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS 
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA-
TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY 
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY 
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT 
EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUC-
TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY 
THE GOVERNING LAW. 

Product Warranty Return Procedure

 All Products that are believed to 

have defects in workmanship or materials must be returned, together 
with a written description of the defect, to the tekmar Representative 
assigned to the territory in which such Product is located. If tekmar 
receives an inquiry from someone other than a tekmar Representative, 
including an inquiry from Purchaser (if not a tekmar Representative) or 
Purchaser’s customers, regarding a potential warranty claim, tekmar’s 
sole obligation shall be to provide the address and other contact informa-
tion regarding the appropriate Representative.

Technical Data

tN2 Wiring Center 313

 

Four Zone Valves

 

Literature

D313, Q313

Control

Microprocessor control. This is not a safety (limit) control.

Packaged weight

1.4 lbs (640 g)

Dimensions

5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm)

Enclosure

NEMA 1 rated, Blue PC+ABS plastic

Approvals

CSA C US, meets class B: ICES & FCC Part 15

Ambient conditions

Indoor use only, 32 to 122°F (0 to 50°C), RH   90% Non-condensing

Power supply

24 V (ac) ±10% 60 Hz, 3 VA min, 100 VA max, Class 2

Zone valve load

24 V (ac) 2 A, maximum combined current (zones 1 to 4): 4 A 

End switch relay

24 V (ac) 2 A

Warranty

Limited 3 Year

 Limited Warranty and Product Return Procedure