1 of 12
A Watts Water Technologies Company
Multi-Staging
Introduction
The Boiler Control 284 can communicate with a Building Automation System (BAS) using either BACnet
®
IP or Modbus
®
.
This manual provides information about boiler plant & system parameters that can be accessed by building automation or
management systems that use BACnet
®
IP or Modbus
®
communication. The 284 can be configured to provide monitoring
access or read / write access with optional target temperature control from the connected BAS.
BACnet
®
IP
Modbus
®
Table of Contents
284 Configuration ......................................................... 2
Lock / Unlock Switch ................................................ 2
Application Mode Setting ......................................... 2
BAS Type Setting ..................................................... 2
BACnet Protocol Implementation Conformance
Statement (PICS) ......................................................... 3
BACnet
®
Connection ..................................................... 3
BACnet
®
Settings in the 284 BAS Menu ....................... 4
BACnet
®
Analog Parameters ........................................ 6
BACnet
®
Binary Parameters ......................................... 7
Modbus
®
Specification .................................................. 8
Modbus
®
Settings in the 284 BAS Menu ...................... 9
Modbus
®
Parameters .................................................. 10
Modbus
®
Troubleshooting ........................................... 11
Error Codes ................................................................ 12

© 2014
284_B - 08/14
2 of 12
A Watts Water Technologies Company
284 Confi guration
Ensure the 284 has the correct Application Mode & BAS Type settings before connecting to the BAS. To view menu
selections in the 284, press & hold the Home button for 3 seconds.
BAS Type Setting
Select the type of BAS connection in the BAS Menu of the 284.
284 BAS Type
BAS Operation
BACnet
®
IP
The 284 communicates with the BAS using the BACnet
®
Internet Protocol (IP) protocol.
Modbus
®
The 284 communicates with the BAS using the Modbus
®
protocol.
Lock / Unlock Switch
The 284 has an ‘Advanced’ access level that allows full access to all settings. To change from
the Installer or User access to the Advanced access level, the
switch to the left side of the
display on the front of the control must first be set to the unlock position. The access level can be
changed in the toolbox menu.
View Menu
(default display)
Press
& hold
Navigate
available
menus
Setup
Source 1
Source 2
Source 3
Source 4
Monitor
Monitor 1
Monitor 2
Monitor 3
Monitor 4
Schedule
Time
BAS
Toolbox
Enter
selected
menu
Change
item
setting
Navigate
available
items
Press
once
Press
twice
Application Mode Setting
The Application Mode of the 284 determines what options are available to the BAS.
284 Application Mode
BAS Operation
RSET
Outdoor Temperature Reset
BAS Monitor Mode (BAS Monitor Setting set to ON)
Remote monitoring & adjustment of select settings of the 284.
Refer to the BACnet
®
& Modbus
®
Parameter Tables in this brochure for a listing of
available read / write parameters.
SETP
Setpoint
DDHW
Dedicated Domestic Hot Water
EMS
Energy Management System
BAS
Building Automation System
BAS Temperature Mode
Provides Setpoint Temperature and Setpoint Call commands to the 284.
Provides Primary Pump(s) and DHW Pump request commands to the 284.
Remote monitoring & adjustment of select settings of the 284.
Refer to the BACnet
®
& Modbus
®
Parameter Tables in this brochure for a listing of
available read / write parameters.

© 2014
284_B - 08/14
3 of 12
A Watts Water Technologies Company
Vendor Name:
tekmar Control Systems Ltd.
Vendor ID:
585
Product Name:
Boiler Control 284
Product Model Number:
284
Application Software Version: J1220x
Firmware Revision: TBD
BACnet Protocol Revision: 10
Product Description:
The 284 is a control that operates up to four boilers to provide heating for multiple loads. The control uses Proportional
Integral Derivative (PID) logic to accurately maintain target temperature and offers advanced features including
communication capability with a Building Automation System (BAS).
Supported BIBBs (Annex K)
Name
DS-RP-B
Data Sharing-ReadProperty-B
DS-RPM-B
Data Sharing-ReadPropertyMultiple-B
DS-WP-B
Data Sharing-WriteProperty-B
DM-DDB-B
Device Management-Dynamic Device Binding-B
DM-DOB-B
Device Management-Dynamic Object Binding-B
DM-DCC-B
Device Management-Device Communication Control-B
*
DeviceCommunicationControl password is tekmar.
Data Link Layer
Supported
BACnet
®
IP (Annex J)
Yes
Character Set
Supported
ANSI X3.4
Yes
Device Address Binding
Supported
Static Device Address Binding
No
BACnet Standardized Device Profile (Annex L)
BACnet
®
Application Specific Controller (B-ASC)
Standard Object Types Supported
Creatable
Deletable
Analog Input
No
No
Analog Value
No
No
Binary Input
No
No
Binary Output
No
No
Binary Value
No
No
Segmentation Capability
Supported
Window Size
Able to transmit segmented messages
No
Able to receive segmented messages
No
Network Security Options
Non-secure Device
BACnet
®
Protocol Implementation Conformance Statement (PICS)
BACnet
®
Connection
RJ45
Boiler
Control 284
BACnet
®
Network
Switch
Use a top or back knock-out to bring a CAT-5E or CAT-6 wire into
the wiring chamber. Connect the 284 to the BACnet
®
network switch
using the RJ45 port on the top edge of the control board.
Cable length must not exceed 150 ft. (45.7 m) for CAT-5E or
300 ft. (91.4 m) for CAT-6.
If the cable was manually made, check continuity across each
of the wires.
•
•

© 2014
284_B - 08/14
4 of 12
A Watts Water Technologies Company
Item Field
Range
Description
OFF or ON
Default: OFF
Access: ADV
BAS MONITOR
Selects whether or not BAS monitoring is available.
Note:
This item is only available when APP MODE is set to either RSET, SETP,
DDHW or EMS.
BACn, MODB
Default: BACn
Access: ADV
BAS TYPE
Selects the communication protocol used with the BAS network. Modbus
®
communicates over RS485 and BACnet
®
is over IP.
0 to 4, 0 to 99, 0 to
99, 0 to 99
Default: 0, 0, 0, 0
Access: ADV
BACNET DEVICE ID
Sets the unique address within the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note:
This item is only available when BAS TYPE is set to BACn.
0x1 to 0xFFFF
Default: 0xBAC0
(47808)
Access: ADV
BACNET PORT
Sets the User Datagram Port (UDP) port on the BACnet
®
network.
Note:
This item is only available when BAS TYPE is set to BACn.
OFF or ON
Default: ON
Access: ADV
BACNET DHCP
Selects whether or not the Dynamic Host Configuration Protocol (DHCP) is used
to automatically assign the IP address on the BACnet
®
network. If ON is selected,
the address is displayed in the source output fields.
Note:
This item is only available when BAS TYPE is set to BACn.
0 to 255, 0 to 255, 0
to 255, 1 to 254
Default:
192,168,0,200
Access: ADV
BACNET IP ADDRESS
Sets the IP address on the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note:
This item is only available when BAS TYPE is set to BACn and BACn DHCP
is set to OFF.
0 to 255, 0 to 255, 0
to 255, 1 to 254
Default: 192,168,0,1
Access:
ADV
BACNET GATEWAY
Sets the Gateway address on the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note:
This item is only available when BAS TYPE is set to BACn and BACn DHCP
is set to OFF.
0 to 255, 0 to 255, 0
to 255, 0 to 255
Default:
255,255,255,0
Access: ADV
BACNET SUBNET
Sets the subnet address on the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note:
This item is only available when BAS TYPE is set to BACn and BACn DHCP
is set to OFF.
OFF, 30 to 65535
Default: OFF
Access: ADV
BACNET BBMD TIME
Sets the Bacnet
®
Broadcast Management Device (BBMD) time-to-live used
for foreign device registration.
Note:
This item is only available when BAS TYPE is set to BACn.
BACnet
®
Settings in the 284 BAS Menu

© 2014
284_B - 08/14
5 of 12
A Watts Water Technologies Company
Item Field
Range
Description
0 to 255, 0 to 255, 0
to 255, 0 to 255
Default:
127,127,127,127
Access: Adv
BACNET BBMD IP
Sets the BBMD IP address on the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note:
This item is only available when BAS TYPE is set to BACn and BBMD TIME
is not set to OFF.
0x1 to 0xFFFF
Default: 0xBAC0
(47808)
Access: Adv
BACNET BBMD PORT
Sets the BBMD UDP port on the BACnet
®
network.
Note:
This item is only available when BAS TYPE is set to BACn and BBMD TIME
is not set to OFF.
BACnet
®
Settings in the 284 BAS Menu

© 2014
284_B - 08/14
6 of 12
A Watts Water Technologies Company
Object
ID
Name
Description
Data
Type
Read /
Write
Units
Range / Value
Analog Input Objects
0
Boil TARG
Boiler Target Temperature
AI
R
°F (64)
-22 to 266°F
1
Boil MIN
Minimum Boiler Target Temperature
AI
R
°F (64)
60 to 180°F
2
Boil MAX
Maximum Boiler Target Temperature AI
R
°F (64)
90 to 225°F
3
Boil SUP
Boiler Supply Temperature
AI
R
°F (64)
-22 to 266°F
4
Boil RET
Boiler Return Temperature
AI
R
°F (64)
-22 to 266°F
5
OUTDOOR
Outdoor Air Temperature
AI
R
°F (64)
-76 to 149°F
6
DHW
DHW Tank Temperature
AI
R
°F (64)
-22 to 266°F
7
VENT
Vent Temperature
AI
R
°F (64)
-22 to 266°F
8
Boil INLET
Boiler Inlet Temperature
AI
R
°F (64)
-40 to 500°F
9
FLOW RATE
Flow Rate
AI
R
GPM (89)
0 to 65535 gpm
10
ENERGY
Energy Usage
AI
R
Therms (21) 0 to 65535 Therms
11
PRESSURE
System Pressure
AI
R
PSI (56)
0 to 65535 psi
12
PRIM P1 RT
Primary Pump 1 Running Time
AI
R
Hours (71)
0 to 65535 Hours
13
PRIM P2 RT
Primary Pump 2 Running Time
AI
R
Hours (71)
0 to 65535 Hours
14
DHW P RT
DHW Pump Running Time
AI
R
Hours (71)
0 to 65535 Hours
15
ERROR
Current Error
AI
R
N/A (95)
See Error List
16, 22,
28, 34
Boil (n) TYPE Boiler (n) Type
AI
R
N/A (95)
0 = MOD, 1 = 1STG,
2 = 2STG, 3 = EMS
17, 23,
29, 35
Boil (n) OUT
Boiler (n) Outlet Temperature
AI
R
°F (64)
-22 to 266°F
18, 24,
30, 36
Boil (n) MOD
Boiler (n) Modulating Output
AI
R
% (98)
0 to 100%
19, 25,
31, 37
BURNER (n)
Boiler (n) Running Time
AI
R
Hours (71)
0 to 65535 Hours
20, 26,
32, 38
CYCLES (n)
Boiler (n) Cycles
AI
R
N/A (95)
0 to 65535
21, 27,
33, 39
PUMP (n) RT
Boiler (n) Pump Running Time
AI
R
Hours (71)
0 to 65535 Hours
Analog Value Objects
0
SETPOINT
BAS Setpoint Temperature
AV
R/W
°F (64)
60 to 225°F
1
ROOM Occ
Room Occupied Temperature
AV
R/W
°F (64)
35 to 100°F
2
ROOM UnOcc Room UnOccupied Temperature
AV
R/W
°F (64)
35 to 100°F
3
OUT DSGN
Outdoor Design Temperature
AV
R/W
°F (64)
-60 to 45°F
4
TERMINAL
Terminal Unit Type
AV
R/W
N/A (95)
0 = HRF1, 1 = HRF2,
2 = CONV, 3 = COIL,
4 = RAD, 5 = BASE
5
OUTDOOR
BAS Outdoor Air Temperature
AV
R/W
°F (64)
-85 to 149°F
(-85°F = invalid temp. / no
BAS sensor)
BACnet
®
Analog Parameters
Analog Input Object = AI
Analog Value Object = AV
Read = R
Read / Write = R / W
(n) represents the specific Boiler number, including 1, 2, 3 and 4.

© 2014
284_B - 08/14
7 of 12
A Watts Water Technologies Company
Object ID Name
Description
Data Type Read / Write Units
Range / Value
Binary Input Objects
0
PRIM P1
Primary Pump 1 Status
BI
R
N/A
0 = Off, 1 = On
1
PRIM P2
Primary Pump 2 Status
BI
R
N/A
0 = Off, 1 = On
2
DHW PUMP
DHW Pump Status
BI
R
N/A
0 = Off, 1 = On
3
SETBACK
Setback Status
BI
R
N/A
0 = Off, 1 = On
4
AUX RLY
Auxiliary Relay Status
BI
R
N/A
0 = Off, 1 = On
5
ALERT RLY
Alert Relay Status
BI
R
N/A
0 = Off, 1 = On
6
HEAT CALL
Heat Call Status
BI
R
N/A
0 = Off, 1 = On
7
DHW CALL
DHW Call Status
BI
R
N/A
0 = Off, 1 = On
8
SETP CALL
Setpoint Call Status
BI
R
N/A
0 = Off, 1 = On
9
FLOW PROOF
Flow Proof Call Status
BI
R
N/A
0 = Off, 1 = On
10
CA PROOF
C.A. Proof Call Status
BI
R
N/A
0 = Off, 1 = On
11, 13,
15, 17
CONDENSE (n)
Boiler (n) Condensing
BI
R
N/A
0 = No, 1 = Yes
12, 14,
16, 18
B(n) PUMP
Boiler (n) Pump Status
BI
R
N/A
0 = Off, 1 = On
Binary Output Objects
0
DHW PUMP
BAS DHW Pump Request
BO
R/W
N/A
0 = Off, 1 = On
Binary Value Objects
0
BAS SETP CALL
BAS Setpoint Call
BV
R/W
N/A
0 = Off, 1 = On
1
BAS PRIM PMP REQ
BAS Primary Pump Request
BV
R/W
N/A
0 = Off, 1 = On
2, 3,
4, 5
ENABLE B(n)
Enable / Disable Boiler (n)
BV
R/W
N/A
0 = Enable,
1 = Disable
Refer to the 284_D Installation & Operational Manual for additional information.
Troubleshooting
If there is no communication, check the following:
Check the ethernet cable. Cable length must not exceed 150 ft. (45.7 m) for CAT-5E or 300 ft. (91.4 m) for CAT-6.
If the cable was manually made, check continuity across each of the wires.
If there is intermittent communication, check the following:
Check the ethernet cable. Cable length must not exceed 150 ft. (45.7 m) for CAT-5E or 300 ft. (91.4 m) for CAT-6.
•
•
•
BACnet
®
Binary Parameters
Binary Input Object = BI
Binary Output Object = BO
Binary Value Object = BV
Read = R
Write = W
(n) represents the specific Boiler number, including 1, 2, 3 and 4.

© 2014
284_B - 08/14
8 of 12
A Watts Water Technologies Company
Communication Protocol
Modbus
®
over RS485
Physical Layer
RS485 two-wire plus signal ground
Baud Rate
2400, 9600, 19200, 57600, 115000 (default: 19200 bps)
Recommended Cable
18 AWG shielded, twisted pair (STP)
Transmission Mode
RTU or ASCII (default: RTU)
Maximum Cable Length
11500 bps: 580 ft (177 m)
57600 bps: 1,158 ft (353 m)
19200, 9600, 2400 bps: 3,280 ft (1,000 m)
3,280 ft (1,000 m) for all baud rates if 120 Ohm terminating resistors used
Start Bit
1 bit
Data Length
8 bits for RTU mode
7 bits for ASCII mode
Parity
None (2 stop bits)
Even (1 stop bit)
Odd (1 stop bit)
(default: Even)
Addressing
1 to 247
(default: 1)
Modbus
®
Specifi cation
Modbus
®
Connection
B A G
Master
284
40
41
42
Gnd
+
RS 485
B
A
(+) (-)
Use a top or back knock-out to bring a shielded twisted pair wire from the nearest
Modbus
®
RS485 connection point into the wiring chamber. Wire the A, B & G
conductors from the Modbus
®
point to the 284 A, B & Gnd terminals.
Gnd should not be connected to the ground screws in the 284.
•

© 2014
284_B - 08/14
9 of 12
A Watts Water Technologies Company
Item Field
Range
Description
OFF or ON
Default: OFF
Access: ADV
BAS MONITOR
Selects whether or not BAS monitoring is available.
This item is only available when APP MODE is set to either RSET, SETP, DDHW
or EMS.
NONE, BACn, MODB
Default: BACn
Access: ADV
BAS TYPE
Selects the communication protocol used with the BAS network. Modbus
®
communicates over RS485 and BACnet
®
is over IP.
1 to 247
Default: 1
Access: ADV
MODBUS ADDRESS
Sets the unique address within the Modbus
®
network.
This item is only available when BAS TYPE is set to MODB.
RTU or ASCI
Default: RTU
Access: ADV
MODBUS DATA
Selects whether the Modbus
®
data communication type is RTU or ASCII (ASCI).
This item is only available when BAS TYPE is set to MODB.
2400, 9600, 19K2,
57K6, 115K
Default: 19K2
Access: ADV
MODBUS BAUD RATE
Selects the communication speed. In order to ensure reliable communications, the
baud rate on the control must be same as the Modbus
®
network.
This item is only available when BAS TYPE is set to MODB.
NONE, EVEN, ODD
Default: EVEN
Access: ADV
MODBUS PARITY
Selects the parity used for the Modbus
®
communication.
This item is only available when BAS TYPE is set to MODB.
Modbus
®
Settings in the 284 BAS Menu

© 2014
284_B - 08/14
10 of 12
A Watts Water Technologies Company
Register
Parameter Name
Read /Write
Units
Type
Format Range
System Status Registers
1
Boiler Target Temperature
R
°F
Input
S16
-22 to 266°F
2
Boiler Minimum
R
°F
Input
S16
60 to 180°F
3
Boiler Maximum
R
°F
Input
S16
90 to 225°F
4
Boiler Supply Temperature
R
°F
Input
S16
-22 to 266°F
5
Boiler Return Temperature
R
°F
Input
S16
-22 to 266°F
6
Outdoor Air Temperature
R
°F
Input
S16
-76 to 149°F
7
DHW Temperature
R
°F
Input
S16
-22 to 266°F
8
Vent Temperature
R
°F
Input
S16
-40 to 500°F
9
Boiler Inlet Temperature
R
°F
Input
S16
-22 to 266°F
10
Flow
R
10*GPM
Input
U16
0 to 65535 gpm
11
Energy
R
Therms
Input
U16
0 to 65535 Therms
12
System Pressure
R
10*PSI
Input
U16
0 to 65535 psi
13
Primary Pump 1 Relay Status
R
Enum
Input
U16
0=Off, 1=On
14
Primary Pump 2 Relay Status
R
Enum
Input
U16
0=Off, 1=On
15
DHW Pump Relay Status
R
Enum
Input
U16
0=Off, 1=On
16
Primary Pump 1 Runtime
R
Hours
Input
U16
0 to 65535 Hours
17
Primary Pump 2 Runtime
R
Hours
Input
U16
0 to 65535 Hours
18
DHW Pump Runtime
R
Hours
Input
U16
0 to 65535 Hours
19
Setback Status
R
Enum
Input
U16
0 = Occ, 1 = UnOcc
20
Auxiliary Relay Status
R
Enum
Input
U16
0 = Off, 1 = On
21
Alert Relay Status
R
Enum
Input
U16
0 = Off, 1 = On
22
Heat Call Status
R
Enum
Input
U16
0 = Off, 1 = On
23
DHW Call Status
R
Enum
Input
U16
0 = Off, 1 = On
24
Setpoint Call Status
R
Enum
Input
U16
0 = Off, 1 = On
25
Flow Proof Call Status
R
Enum
Input
U16
0 = Off, 1 = On
26
C.A. Proof Call Status
R
Enum
Input
U16
0 = Off, 1 = On
27
Error Code
R
Enum
Input
U16
See Error Code List
System Parameter Registers
1
Setpoint Call Request
R/W
Enum
Holding
U16
0 = Off, 1 = On
2
Setpoint Target Request
R/W
°F
Holding
U16
60 to 225°F
3
Primary Pump Request
R/W
Enum
Holding
U16
0 = Off, 1 = On
4
IDHW Pump Request
R/W
Enum
Holding
U16
0 = Off, 1 = On
5
Room Occupied
R/W
°F
Holding
S16
35 to 100°F
6
Room UnOccupied
R/W
°F
Holding
S16
35 to 100°F
7
Outdoor Design Temperature
R/W
°F
Holding
S16
-60 to 45°F
8
Terminal Unit Type
R/W
Enum
Holding
U16
0 = HRF1, 1 = HRF2,
2 = CONV, 3 = COIL,
4 = RAD, 5 = BASE
9
Outdoor Temperature
R/W
°F
Holding
S16
-85 to 149°F
(-85°F = invalid
temp. / no BAS
sensor)
Modbus
®
Parameters
Read = R
Read / Write = R / W
(n) represents the specific Boiler number, including 1, 2, 3 and 4.

© 2014
284_B - 08/14
11 of 12
A Watts Water Technologies Company
Register
Parameter Name
Read /Write
Units
Type
Format
Range
Boiler Status Registers
10,11,12,13
Boiler (n) Enable/Disable
R/W
Enum
Holding
U16
0 = Enable, 1 = Disable
28,36,44,52
Boiler (n) Type
R
Enum
Input
U16
0 = MOD, 1 = 1STG,
2 = 2STG, 3 = EMS
29,37,45,53
Boiler (n) Condensing
R
Enum
Input
U16
0 = No, 1 = Yes
30,38,46,54
Boiler (n) Outlet
Temperature
R
°F
Input
S16
-22 to 266°F
31,39,47,55
Boiler (n) Modulation Rate
R
%
Input
U16
0 to 100%
32,40,48,56
Boiler (n) Runtime
R
Hours
Input
U16
0 to 65535 Hours
33,41,49,57
Boiler (n) Cycles
R
Num
Input
U16
0 to 65535
34,42,50,58
Boiler (n) Pump Status
R
Enum
Input
U16
0 = Off, 1 = On
35,43,51,59
Boiler (n) Pump Runtime
R
Hours
Input
U16
0 to 65535
Product Information
60
Product Model
R
Num
Input
U16
284
61
Firmware Revision
R
Num
Input
U16
SVN revision
62
Application Version
R
Num
Input
U16
J number letter
(A=1, B=2,...)
Modbus
®
Parameters
Modbus
®
Troubleshooting
If there is no communication, check the following:
Check that the polarity on the Modbus
®
A & B terminals
is correct.
Check that Modbus
®
GND terminal is securely
connected.
Check that the Baud Rate on both devices are the
same.
•
•
•
If the communication is intermittent, check the
following:
Check that the communication cable is of the twisted
pair type.
Reliable communication depends on the cable length &
Baud rate used. Long cable length may require a lower
Baud Rate.
•
•
Read = R
Read / Write = R / W
(n) represents the specific Boiler number, including 1, 2, 3 and 4.

Product design, software and literature are Copyright ©2014 by
tekmar Control Systems Ltd.,
A Watts Water Technologies Company
12 of 12
All specifications are subject to change without notice.
Printed in Canada. 284_B - 08/14.
tekmar Control Systems Ltd.,
A Watts Water Technologies Company
. Head Offi ce: 5100 Silver Star Road,
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com
Code
Description
0
No Error
1
EEPROM Error
2
Boiler Supply Sensor Error
3
Boiler Return Sensor Error
4
DHW Sensor Error
5
Outdoor Sensor Error
6
Vent Sensor Error
7
Boiler 1 Outlet Sensor Error
8
Boiler 2 Outlet Sensor Error
9
Boiler 3 Outlet Sensor Error
10
Boiler 4 Outlet Sensor Error
11
Boiler 1 Maximum Outlet Temperature Warning
12
Boiler 2 Maximum Outlet Temperature Warning
13
Boiler 3 Maximum Outlet Temperature Warning
14
Boiler 4 Maximum Outlet Temperature Warning
15
Boiler Inlet Sensor
Code
Description
16
Flow Proof Error
17
C.A. Proof Error
18
Vent Maximum Temperature Warning
19
No Heat Warning
20
tN4 Duplicate Master
21
tN4 Schedule Master
22
tN4 Schedule Member
23
tN4 Device Lost (Bus b)
24
tN4 Device Lost (Bus 1)
25
tN4 Device Lost (Bus 2)
26
tN4 Device Lost (Bus 3)
27
tN4 Device Error (Bus b)
28
tN4 Device Error (Bus 1)
29
tN4 Device Error (Bus 2)
30
tN4 Device Error (Bus 3)
Error Codes