1

User Guide 

 

 

 

 

 

TP3016M Series  

Switching Mode DC Power Supply  

 
 
 

 

 


background image

 

2

 

Introduction  

 

 

I. Quick Start  

 

1.1 Front Panel Description

   

1.2 Pre-Checking  

 

1.3 Quick Start

    

1.4 Output Checking

 

 

 

II. Specifications

 

 

2.1 Major Specification  

 

2.2 Supplementary Characteristic

 

 

III. Operation

 

3.1 Keypad 

 

3.2 Front Panel 

 

3.3 Voltage Setting

  

3.4 Current Setting

 

3.5 Output Switch

 

 

3.6 Data Saving Operation 

 

 


background image

 

3

3.7 Recall Saving Operation

 

3.8 USB Power Charging

 

 

IV. Calibration 

4.1Voltage Calibration 

 

4.2 Current Calibration 

 

 

 


background image

 

4

Introduction   

                                                              

 
Thank you for selecting the TP3016M Switching DC Power Supply, please read this user guide before 
the operation. 

 

 

Safety 

 
This manual contains important safety and operation instructions for correct use of power supply. 
Read through the manual and pay attention to the markings and labels of this unit to be connected.  
 
Do not install the substituted spare parts or operate the modification without permission, please 
send the unit back for A/S to our authorized dealers or factory for guaranty of the stability of the unit.      
 
Pay special attention to the information of WANRINGS or CAUTIONS to avoid the damage to power 
supply or connected equipment and human injured.   
 
Please contact the trained technicians for repair service.  

 
Safety Marks  
 

WARNING:  

 


background image

 

5

Failure to observe this warning may cause injury to persons and damage to power supply or 
connected equipment.  
 
CAUTION: 

 

Failure to observe this warning may result in damage to equipment and improper functioning of 
power supply. 

 

  

Grounding

 

 

   

High Voltage

  

   

Attention on the Warning or Caution

 

 

Specification Compliance 

TP3016M Switch mode DC Power Supply is compliance with the specification described in this manual.   
 
The content or specification of this manual is subject to change, without prior notice.  
 

Product Features

 

 


background image

 

6

TP3016M is the single output switch mode DC power supply with max. 30V output voltage, 1.6A 
output current and max. output power as 50W.  
 
TP3016M is integrating the AC/DC and DC/DC 2nd level voltage regulator technology, the AC/DC 
input is adapting the worldwide voltage range. The DC/DC is using the synchronous buck mode, which 
with the high efficiency and high speed dynamic response performance.  
 
TP3016M can be set the voltage and current through the keypad of front panel and save the setting 
groups for further performance.  
 
TP3016M also has the 4 digit voltage and current meter, as well as the fantastic handheld size. The 
TP3016M is perfect for solving a variety of loading conditions and applications.  
Please find the following main features of TP3016M:   

 

 

Handheld design  

●  

Without noise of fan  

  

4 digits LCD display  

●  

Output short circuit protection 

●  

High speed dynamic response 

 

Once power cut-off, automatically protect under power off status  

● 

The output has the automatic recognition of USB charging port 

 

Can be calibrated via software operation  

 


background image

 

7

 

  

 

I. Quick Start  

This chapter describes the basic check points on TP3016M for making sure the proper operation, as 
well as the functions of TP3016M.  
 

1.1

 

Front Panel Description 

 
1 – Current Setting Indicator  
2 – Voltage Setting Indicator 
3 – Measured Value Display  
4 – Keypad  
5 – USB Charging Ports  
6 – DC Output Terminals  

 


background image

 

8

     

 

 


background image

 

9

 
1.2 Pre-Checking 

Before the operation, please check the accessories are fully included, if any missing, please contact 
the local distributor.  
 

 Power Cord – 1PC (Compliance with the standard voltage of the region) 

 User Guide – 1PC 

 

Connect with power and switch on TP3016M, the unit start the self-system checking, the LCD displays 
0.5s, date of manufacturing, production lot, model number version number in turn.  

 

 

1.3 Quick Start  

OUT Button 

Press and light 

OUT

 button, the power supply is under output status and read the measuring value of 

voltage or current in the display. Press again OUT button to exit output function.  

 

 

 


background image

 

10

UP Arrow Key + DOWN Arrow Key 

Press 

UP

 arrow key to activate the LCD backlit 

Press 

DOWN

 arrow key to exit the LCD backlit  

 

LEFT Arrow Key + RIGHT Arrow Key 

Press LEFT arrow key to decrease the contrast of LCD 

Press 

RIGHT

 arrow key to increase the contrast of LCD 

 

V/A Key 

Press the 

V/A

 key to activate voltage measurement and read the voltage value from display.  

Push the 

V/A

 key again to switch current measurement and read the current value from the display 

USB Button 

Push and light the 

USB

 button and adjust voltage to 5.2V and the current as 3A to enter USB 

 


background image

 

11

power charging mode; then, push and light the 

OUT

 button, the TP3016M is working as 

power charger.  

 

Push the USB button again and USB button lights out to exit USB power charging mode.  

 

SET Button

 + 

V/A Button

 + Direction Arrow Keys 

 

Push  the 

SET

  button, by  pressing  the direction arrow  keys  to  adjust the voltage  value  setting,  Push 

the 

V/A

  button  to  switch  the  current  value  setting  mode,  by  pressing  the  direction  arrow  keys  to 

measured current value.  

 

1.4 Output Checking 

 

1.41 The output voltage regulation mode check 

This is for checking the functions of power supply under non-load voltage stability.  
 
1)

 

Switch on the product, the power is off and the indicators of CC & CV are light off.  

 


background image

 

12

2)

 

Push and light the 

OUT

 button, the indicator of CV is light on at LCD display.  

3)

 

Setting the voltage of power supply  
Push the 

V/A 

 button and shift to voltage display mode, adjust various voltage values then, check 

the voltage value displayed at LCD is approaching the settled voltage value and within the 
tolerance, current value is showed as 0A.   

4)

 

Make sure the voltage can be adjusted from 0.5V to max. 30V.  

 

1.42 The output constant current mode check 

This is for checking the functions of power supply under constant current mode.  
 
1)

 

Switch on the product, the power is off and the indicators of CC & CV are light off. 

2)

 

Adjust voltage value as 30V. 

3)

 

Connect the resistance (3Ω/50W) between output terminals.  

4)

 

Push and light the 

OUT 

button, the indicator of CC is also light.   

5)

 

Setting the current of power supply  
Push 

V/A

 button and shift to current display mode, adjust various current values, then,  check the 

current value displayed at LCD is approaching the settled current value and within the tolerance.  

6)

 

Make sure the current can be adjusted from 0A to the max. value.  

 

1.43 The output short circuit protection check 

This is for checking the function of short circuit protection of output.  
 

 


background image

 

13

 
1)

 

Switch on the product, the power is off and the indicators of CC & CV are light off. 

2)

 

Adjust voltage value is over 5V and current value is over 1A. 

3)

 

Push and light the 

OUT 

button. 

4)

 

Connect the output terminals by wire for short circuit, the light of 

OUT 

button is off and output 

off.  

 

1.44 The USB charging function check 

This is for checking USB charging function.  
 
1)

 

Switch on the product, the power is off and the indicators of CC & CV are light off. 

2)

 

Push and light the 

USB

 button. Adjust the voltage as 5.1V and current as 2.0A.  

3)

 

Push and light 

OUT

 button. 

4)

 

Make sure the power supply under CV mode, the CV indicator is light in LCD.

 

5)

 

Setting the current value and make sure the current value can be adjusted from 0A to the max. 
value of measuring range. Do not adjust voltage.  

 

II. Specification 
 

2.1 Major Specification 

 

 


background image

 

14

Input Voltage 

110AC~  60Hz 

Input Current 

1A 

Output Rating 

Voltage range 

0.5V~30V 

Current range 

0~3.75A 

   Line Regulation 

±

of output + offset 

Voltage 

CV

0.01%+3mV 

Current 

CC

0.01%+3mA 

   Load Regulation 

±

of output + offset 

Voltage 

CV

0.02%+3mV 

Current 

CC

0.02%+3mA 

Measurement Accuracy  

Voltage 

10mV 

Current 

1mA 

Measured  Value  Accuracy 
@  25

 

±

of output + offset 

Voltage 

0.05%+5mV 

Current 

0.05%+5mA 

Measurement Speed  

Voltage 

100ms/ones 

Current 

100ms/ones 

Setting  Value  Accuracy  @  
25

 

±

of output + offset 

Voltage 

0.05%+5mV 

 

Current 

0.05%+5mV 

Ripple and Noise 
20HZ-20MHZ 

Voltage 

10mVrms/100mVp-p 

Current 

10mVrms/100mVp-p 

Temperature  Coefficient 
@ 0~40

 

±%of output + offset    

Voltage 

0.05% 

Current 

0.1% 

Dimensions 

185x88x38 mm 

Weight (Net ) 

370g 

 


background image

 

15

2.2 Supplementary Characteristic 

 

Build-in EEPROM  
Recommended Calibration Time

1 Time/Year 

AC Input Power: 110VAC, 60 Hz

 

 
Operating Temperature: 0 to 40 

 

Storage Temperature:  -20 to 70 

 

 
 

III. Operation  

 

Check the rating label of the power supply and ensure that it complies with the AC mains voltage that 
is to be used.  
 
Connect the power supply to the AC minas using the provided power cord.  
 

3.1 Keypad Description 

OUT

   

 

 

 

 

Output check 

 

V/A 

   

 

 

 

 

Voltage & Current Shift

 

USB 

   

 

 

 

 

5V Cell Phone Charging

 

 


background image

 

16

SET/ENTER 

  

 

 

 

Voltage & Current Setting/Enter

 

 

STORE/RECALL

              

 

Data Saving/Recall 

 

UP

 

DOWN

      

LEFT

  

RIGHT

  

Direction Arrow Keys 

 

 

3.2 Front Panel 

After power on, the panel operation mode is the default setting of power supply and all the 
functional buttons can be operated.  

 

 

3.3 Voltage Setting 

The voltage setting range is from 0.50V to 30V; follow the setting steps as below: 

  

1.

 

Switch on the power supply 

2.

 

Push the 

OUT 

button to stop the output setting and light off 

OUT

 button  

3.

 

Push and light the 

SET/ENTER

 button, the max. value position is flickering of voltage setting area 

4.

 

Push the 

LEFT

 or 

RIGHT

 arrow keys to move the cursors 

5.

 

Push the 

UP

 or 

DOWN

 arrow keys to change the settings 

6.

 

Push 

SET/ENTER

 button and light off this button to exit voltage setting mode 

 

 

                                                     

UP

                            

ENTER

 

OUT 

 

SET

 

 

 0 0.0 0 

V ------------- >

3 0.0 0 

V --------------->  OK 

 

 
 

 


background image

 

17

Remark:  
 
I.

 

It is possible to set voltage values once the outputs are valid. However, for protection of the 
load, it is recommended to stop output before voltage setting.  
 

II.

 

Due to the total power limit, current settings might be decreased automatically once 
voltage setting increasing.  

 
 

3.4 Current Setting 

The current setting range is from 0.000A to 1.66A, follow the setting steps as below: 

  

 

1.

 

Switch on the power supply 

2.

 

Push the 

OUT 

button to stop the output setting and light off 

OUT

 button  

3.

 

Push and light the 

SET/ENTER

 button, the max. value position is flickering of voltage setting area.  

4.

 

Push the 

V/A

 button, the max. value position of current setting is flickering and current setting is 

activated 

5.

 

Push the 

LEFT

 or 

RIGHT

 arrow keys to move the cursors 

6.

 

Push the 

UP

 or 

DOWN

 arrow keys to change the settings 

7.

 

Push 

SET/ENTER

 button and light off this button to exit current setting mode 

 

           

                                                  

 


background image

 

18

UP

                         

ENTER 

 

OUT

 

SET

 

V/A

 

0. 000 

A ---------> 

2.000 

A ------------ > OK   

 
Remark: 
I.   

It is possible to set current values once the outputs are valid. However, for protection of the 
load, it is recommended to stop output before current setting.  

3.5 Output Switch 

 

 

Under the panel operating mode, by pushing 

OUT

 button to shift output status. Once 

OUT

 button 

lighted, the measured values displayed at LCD; push 

OUT

 button again to exit output mode.  

 

3.6 Data Saving Operation  
 

1.

 

Under the voltage setting or current setting mode, push the 

STORE

 button to save the  values of 

voltage or currents into memory of power supply for future recall purpose. (as below steps)  

2.

 

Refer 3.3 or 3.4 for voltage or current setting mode.  

3.

 

Push 

STORE

 button to enter data saving mode, the min. value position is flickering and displayed

 

STORE

 icon in LCD.  

4.

 

Move 

UP

 or 

DOWN

 arrow keys to select storage group serial number. 

5.

 

Click 

ENTER

 button to confirm data saving, click 

STORE

 button to exit data saving mode. 

 


background image

 

19

 
 

                                       

UP

              

SET

 

 

STORE

 

 

1

 

2

 

ENTER

 -----> OK   

 

 
 
3.7 Recall Saving Operation 

 

Under the panel operating mode, push the 

RECALL

 button for getting the saved data from memory; 

follow the setting steps as below:  
 
1.

 

Switch on the power supply 

2.

 

Push 

RECALL

 button to enter data recall mode, the min. value position is flickering and displayed

 

RECALL

 icon in LCD.  

3.

 

Move 

UP

 or 

DOWN

 arrow keys to recall the stored group serial number, the default values from 

voltage or current setting mode displayed in LCD.  

4.

 

Click 

ENTER

 button to confirm data recall, click 

STORE

 button to exit data recall mode. 

 

 

                                

UP

     

 

RECALL

 

 

2

 

ENTER

 --------> OK 

 

 


background image

 

20

3.8 USB Power Charging  

 

Push the 

USB

 button and light the green indicator, the default setting is voltage @ 5.1V and current 

@ 2.0A, the LCD will display 5.1V, current value also can be as 0A. Connect the mobile phone via USB 
cable for power charging.  
 
The USB ports are suitable for both android mobile phone and l Iphone, with automatic check 
function, the product can set the proper charging current automatically.  
 
1.

 

Push and light the 

OUT

 button to activate output mode.  

2.

 

Push the 

USB

 button and 

USB

 indicator is off to exit USB charging mode.    

 

USB

  

 

OUT

  

 OK 

 

 


background image

 

21

IV Calibration  

 
Follow the below chart, connect the 5 digit displayed volt meter, current meter, resistance 
(10Ω/100W) into the output terminals, calibration follow the steps start from point of zero voltage -  
voltage coefficient – current zero – current coefficient.  

 

Hold the 

SET 

button to switch on power supply till “

REF

” displayed in LCD to enter calibration mode.  

 
 

 

 


background image

 

22

4.1 Voltage Calibration 

At the power supply displayed 

2.000A

 & 

05.00V

 in setting area of LCD and 

**.**V

 displayed in main 

part of LCD.  Connect the output terminal with an external reference voltage meter and shift to CV 
mode. Hold the 

LEFT

 or 

RIGHT

 arrow keys to move the cursors to left or right and push the 

UP

 or 

DOWN

 arrow keys to adjust the values same as readings of external reference voltage meter, then 

click 

ENTER

 button to finish the voltage bias calibration. 

 

 
At the power supply displayed 

2.000A

 & 

30.00V

 in setting area of LCD, hold the 

LEFT

 or 

RIGHT

 arrow 

keys to move the cursors to left or  right and push the 

UP

 or 

DOWN

 arrow keys to adjust the values 

same as readings of external reference voltage meter, then click 

ENTER

 button to finish the voltage 

gain calibration. 
 

 

4.2 Current Calibration  

Push the 

V/A

 button and power supply displayed 

0.500A

 & 

20.00V

 in setting area of LCD and 

*.***A

 

displayed in the main part of LCD. Connect the output terminals with the external reference current 
meter and the load (6Ω/100W), shift to CC mode. Hold the 

LEFT

 or 

RIGHT

 arrow keys to move the 

cursors to left or right and push the 

UP

 or 

DOWN

 arrow keys to adjust the values same as readings of 

the external reference current meter, then click 

ENTER

 button to finish the current bias calibration.  

 


background image

 

23

At the power supply displayed 

3.000A

 & 

20.00V

 in the setting area of LCD, hold the 

LEFT

 or 

RIGHT

 

arrow keys to move the cursors to left or  right and push the 

UP

 or 

DOWN

 arrow keys to adjust the 

values same as readings of external reference voltage meter, then click 

ENTER

 button to finish the 

current gain calibration.  
 
Push

 OUT

 button to exit and restart the power supply to complete the calibration function.