PDF User Manual

  1. Home
  2. Manuals
  3. Tecnoware ECO STRIP 0.50 User Manual

Tecnoware ECO STRIP 0.50 User Manual

ECO STRIP 0.70 ECO STRIP 0.90 ECO STRIP 1.1 ECO STRIP 1.3

Made by: Tecnoware
Type: User Manual
Category: UPS
Pages: 17
Size: 0.33 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

 

 

 

 
 

 

 

Uninterruptible Power Supply 

 

ECO STRIP 0.50 

ECO STRIP 0.70 

ECO STRIP 0.90 

ECO STRIP 1.1 

ECO STRIP 1.3 

 

User’s manual 


background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

1

 

User’s manual 

 

Index  

 

Safety Warnings ................................................................................ 2

 

1

 

Introduction ................................................................................. 3

 

2

 

General Characteristics ................................................................... 3

 

3

 

Receipt and site selection ................................................................ 4

 

4

 

EXTERNAL DESCRIPTION .................................................................. 5

 

4.1

 

Front Panel ............................................................................. 5

 

4.2

 

Rear Side ................................................................................ 6

 

5

 

Electrical Installation and First Start Up ............................................... 7

 

6

 

Functioning ................................................................................. 8

 

6.1

 

Normal Mode ........................................................................... 8

 

6.2

 

Battery Mode ........................................................................... 8

 

6.3

 

Low Battery and Automatic Restart ................................................. 8

 

6.4

 

Load Control ............................................................................ 8

 

6.5

 

Fault Condition ........................................................................ 9

 

7

 

Communication Interface ................................................................. 9

 

8

 

Technical Characteristics ................................................................ 10

 

9

 

Maintenance ............................................................................... 11

 

9.1

 

UPS Cleaning ......................................................................... 11

 

9.2

 

Battery ................................................................................ 11

 

9.3

 

Battery Replacement ............................................................... 11

 

9.4

 

Operator Safety ...................................................................... 12

 

10

 

Troubleshooting ........................................................................... 13

 

Conformity to the European Directives ................................................... 14

 

Product Disposal ............................................................................... 14

 

Lead Batteries ................................................................................. 14

 

 
 
 
 
 
 
 
 
 
 
 

© Copyright 2012 TECNOWARE s.r.l. All rights reserved. 
All trademarks are property of their respective owners. 
 
TECNOWARE s.r.l. 
Via Montetrini, 2E – Loc. Molino del Piano – 50065 – Pontassieve (FI) – Italy 
www.tecnoware.com 
 
Edition: May 2012 – version: 2.0 
 

No part of this manual may be reproduced, even partially, without the 
authorisation of TECNOWARE s.r.l. 

TECNOWARE s.r.l. reserves the right to change specifications at any time 
and without notice. 

 


background image

 

User’s manual 

2

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 

Safety Warnings 

 

                                                                        

 

 

Read  this  manual  carefully  and  completely  before  installing  and  using  the  TECNOWARE  ECO 
STRIP Uninterruptible Power Supply, which, from here after, will also be referred to as UPS. 

 

This manual should be kept close to the UPS and read before the UPS is installed and used. 

 

The  UPS  must  be  used  only  by  properly  trained  personnel.  To  ensure  correct  and  safe 
operations,  it  is  necessary  that  operators  and  maintenance  personnel  observe  the  general 
safety Standards as well as the specific instructions included in this manual. 

 

Risk of electric shock: do not remove the cover. The UPS contains internal parts, which are at a 
high  Voltage  and  are  potentially  dangerous,  capable  of  causing  injury  or  death  by  electric 
shock. 

 

There are no internal parts in the UPS, which are user serviceable. Any repair or maintenance 
work  must  be  performed  exclusively  by  qualified  technical  personnel  authorized  by 
TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. 

 

Warning  to  the  technical  personnel  authorized  for  Service:  since  internal  components  are 
connected to the batteries, they will remain powered, and therefore dangerous, even after the 
UPS  has  been  disconnected  from  AC  power  mains.  Before  any  repair  or  maintenance  work, 
disconnect the batteries, by removing the positive cable (red colour) from the positive pole of 
the battery.  

 

It  is  compulsory  to  ground  the  UPS  according  to  Safety  Standards. The AC mains power supply 
socket used to power the UPS must have an earth connection. 

 

In  the  event  of  AC  main  power  supply  failure  (when  the  UPS  works  in  Battery  mode),  do  not 
unplug the power supply cable to the UPS to ensure earth continuity to the connected loads. 

 

Since the AC mains power supply cable acts as a separation device, the AC mains power socket 
used to supply the UPS and/or the rear side of the UPS must be accessible to easily disconnect 
the cable in case of dangerous conditions. 

 

Risk of electric shock at the Output lines when the UPS is ON. 

 

Risk of electric shock at the Output lines while the unit is connected to the AC utility line. 

 

Do not obstruct ventilation slots or holes and do not rest any object on top of the UPS. 

 

Do not insert objects or pour liquids in the ventilation holes. 

 

Install the UPS indoors, in a protected, clean and moisture-free environment. 

 

Do not expose to the direct sun light. 

 

Do not keep liquids, flammable gases or corrosive substances near the UPS.  

                                                                        

 

 

 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

3

 

User’s manual 

 

1

 

Introduction 

ECO STRIP is an UPS (Uninterruptible Power Supply) specifically designed to protect your computer from any type 
of irregularities in the AC line (such as black-outs, under or over voltages, micro-interruptions), which often cause 
damage to your Hardware and Software. 

Under normal AC line condition, ECO STRIP filters frequently occurring electrical disturbances (such as transients, 
spikes, interferences, etc.), thus protecting all devices connected to the outlets, and recharging the batteries in 
an ideal way. In case of anomaly to the AC line, the UPS continues feeding the protected equipment.   

 

 

Read  this  manual  carefully  before  using  the  ECO  STRIP;  it  includes  important  safety 
warnings and useful advices for correct use and installation. 

This  manual  is  a  guide  that  enables  you  to  correctly  install  and  use  your  UPS.  This 
manual  includes  important  SAFETY  instructions  for  the  operator,  for  the  UPS  correct 
installation,  and  gives  useful  advice  on  the  product  and  battery  maintenance.  For  any 
type of problem, please refer to this manual before calling the customer service. 

 

ECO  STRIP  is  constantly  being  developed  and  improved:  consequently,  your  unit  may  differ  somewhat  from  the 
description contained in this manual.  

This manual includes the following models: 

 

ECO STRIP 0.50 (500 VA) 

 

ECO STRIP 0.70 (700 VA) 

 

ECO STRIP 0.90 (900 VA) 

 

ECO STRIP 1.1 (1100 VA) 

 

ECO STRIP 1.3 (1300 VA) 

 

In this manual ECO STRIP will simply be referred to as UPS. 

 
 

2

 

General Characteristics 

ECO STRIP has all the advanced features, which guarantee maximum reliability and safety:  

 

All functions are controlled by a microprocessor, giving full guarantee of high reliability. 

 

Overload protection both in normal mode and in battery mode. 

 

High performance battery charger, which extends the battery medium life ensuring an optimal recharge. 

 

Start up even if the electrical network is not available. 

 

Automatic restart after an automatic shut down due to a low battery condition once the AC utility power 
returns. 

 

Adapts automatically to 50 or 60 Hz input frequency. 

 


background image

 

User’s manual 

4

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 
 

 

Visual and acoustic signals indicating operating mode and alarm/fault conditions.  

 

High efficiency  

 

Maximum reliability  

 

Smart design and easy to use 

 
 

3

 

Receipt and site selection 

Carefully remove the UPS from its packaging, and carry out a meticulous inspection. We recommend keeping the 
original  packaging  in  a  secure  place,  in  case  you  need  to  send  the  UPS  for  maintenance  purposes.  In  case  of 
transport damage, notify the carrier and dealer immediately.  

We recommend paying attention to the below points in order to choose a correct placement for your UPS: 

 

The  UPS  is  designed  to  operate  in  a  protected  environment  (e.g.  offices).  We  therefore  recommend 
installing it in a place with very little or no humidity, dust or smoke.  

 

In  all  circumstances,  see  the  “Technical  Characteristics”  chapter  for  environmental  specifications  and 
check that the selected area meets these specifications. 

 

During normal operation the UPS discharges a minimal amount of heat. So it is necessary to leave at least 
20 cm of unobstructed space all around the UPS in order to keep it properly ventilated. 

 

Do not obstruct ventilation holes. 

 

Do not insert objects or pour liquids in the ventilation holes. 

 

Do not rest any object on top of the UPS. 

 

Do not keep liquids, flammable gases or corrosive substances near the unit.  

 

Install the UPS on a properly tiled floor. Avoid the installation on a floor that is not tiled flat. 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

5

 

User’s manual 

 

4

 

EXTERNAL DESCRIPTION 

4.1

 

Front Panel 

The panel informs the user about operating status, alarm conditions through 2 leds. 

On the panel there are (see figure 1): 

1.

 

The

 ON/OFF

 button: enables the user to turn ON/OFF the UPS. 

2.

 

The 

LINE/BATTERY

  led:  this  led  (blue  color)  is  always  on  during  the  functioning  in  Normal  Mode,  it  flashes 

one time every 4 seconds in Battery mode and it flashes one time every second in Low Battery condition.  

3.

 

The 

ALARM

 led: this led (red color) is on to indicate Alarm/Fault condition. 

 

 

 

Figure 1 – Front panel 

10 


background image

 

User’s manual 

6

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 

4.2

 

Rear Side 

 
 

 

 

Figure 2 – Rear Side 

 
 
 
 

On ECO STRIP rear side there are (see figure 2):  

4.

 

 AC Input power cable: 

Schuko type; to connect the UPS to the AC utility line. 

 

5.

 

Input circuit braker: 

electrical specification: max current 5A (6A on ECO STRIP 1.3), voltage 250 V. 

6.

 

Grounded UPS Output receptacles: 

Italian 10A/Schuko (only for ECO STRIP 1.1 and 1.3).

 

7.

 

Telephone protection (RJ11 IN/OUT connectors): 

to protect and filter a phone line or an ADSL (TNV-3 type 

connections).

 

8.

 

Computer  Interface  (USB  connector

)

it  is  the  communication  USB  port  (only  for  ECO  STRIP  0.90,  1.1  and 

1.3). 

 

 

On ECO STRIP up side there are (see figure2):  

9.

 

Grounded UPS Output receptacles: 

Italian 10A/Schuko.

 

10.

 

Grounded FILTRED Output receptacles: 

Italian 10A/Schuko.

 

 

 

The  1  ONLY  FILTERED  Output  receptacles  (#10),  protect  only  the  devices  connected 
from overvoltage and disturbances of the AC line. Please connect ONLY the NON-critical 
devices to the ONLY FILTERED Output receptacles  

In case of anomaly to the AC line (black-out), ONLY the UPS Output receptacles (#6 and 
#9)  continue  supplying  the  correct  power  to  all  connected  equipment.  Please  connect 
all the non-critical devices to the UPS Output receptacles. 

 
 
 
 
 
 
 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

7

 

User’s manual 

 

5

 

Electrical Installation and First Start Up 

We advise you to follow the steps below explained for greater safety: 

1.

 

Switch  off  all  the  devices  (Personal  Computer  or  other  electronic  devices)  that  need  to  be  supplied  by  the 
UPS. 

2.

 

Connect the UPS power cable to the AC line outlet. 

It is mandatory to ground the AC line outlet according 

to  the  Safety  Standards

.  Carefully  check  the  grounding,  make  sure  that  the  utility  power  is  available,  and 

that its range falls within the UPS specifications (refer to the “Technical Characteristics” chapter). 

3.

 

Press  the 

ON/OFF

  button  on  the  panel  for  about  2  seconds  until  the  UPS  emits  a  brief  acoustic  signal.  The 

UPS  turns  on  the  leds  the  front  panel  and  performs  a 

functioning  SELF-TEST

.  After  some  seconds  the  UPS 

starts  to  work  in 

Normal  mode

:  the 

LINE/BATTERY

  led  is  on.  Leave  the  UPS  in  Normal  mode  for  at least 4 

hours in order to completely recharge the batteries 

4.

 

Switch the UPS off (by pressing again the 

ON/OFF

 button for about 2 seconds). 

5.

 

Connect  the  devices  to  be  supplied  to  the  UPS  outputs,  by  using  only  the  included  cables.  Be  sure  all  the 
devices have the main switch in ON position. 

6.

 

Turn  on  the  UPS  again.  Check  that  it  starts  working  correctly  and  it  doesn’t  signal

 

any  sort  of  anomaly. 

Moreover be sure that all the devices connected to the UPS outputs are working correctly.  

7.

 

Simulate a black-out by removing the AC Input line. The UPS starts working in 

Battery mode

: the UPS emits 

an acoustic alarm signal every 4 seconds and simultaneously the 

LINE/BATTERY 

led flashes.  

8.

 

Be sure that all the devices connected to the UPS outputs are working correctly and the UPS doesn’t signal

 

any sort of anomaly. 

9.

 

Restore the AC Input line: after few seconds the UPS turns back in Normal mode. 

 

Before using ECO STRIP normally, leave it in Normal mode in order to charge the batteries completely as specified 
at point 3. The batteries reach the 90% of their capacity after about 4 hours of recharge. 

 

 

It is compulsory to ground/earth the UPS according to the Safety Standards. 

Risk  of  electric  shock  at  the  Output  lines  if  the  UPS  is  ON,  even  when  the  UPS  is  not 
connected to AC utility line. 

Risk  of  electric  shock  at  the  Output  lines  while  the  unit  is  connected  to  the  AC  utility 
line. 

Risk of electric shock: do not remove the cover. The UPS contains internal parts, which 
are  at  a high Voltage and are potentially dangerous, capable of causing injury or death 
by electric shock. 

There  are  no  internal  parts  in  the  UPS  that  are  user  serviceable.  Any  repair  or 
maintenance  work  must  be  performed  exclusively  by  qualified  technical  personnel 
authorized  by  TECNOWARE.  TECNOWARE  declines  any  responsibility  if  this  warning  is 
disregarded. 

Disregard for these warnings may lead to a risk of electric shock to operators. 

 
 
 
 
 
 
 


background image

 

User’s manual 

8

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 

6

 

Functioning 

6.1

 

Normal Mode 

The UPS typically works in 

Normal mode

: Input mains power is available and its amplitude is within specifications.  

In Normal mode the 

LINE/BATTERY

 led is always on. 

During Normal mode, the UPS recharges the batteries and keeps them in an optimal charging voltage.   

6.2

 

Battery Mode 

The UPS automatically runs in 

Battery mode

 if the AC Input Line voltage amplitude gets out of security limits (in 

case of a black-out or over-voltage/low-voltage): in this case, the UPS supplies the required output power by its 
internal battery and by the Inverter block. 

The UPS automatically returns in Normal mode a few seconds after the AC Input Line is recovered. 

In Battery mode the UPS emits an acoustic alarm signal every 4 seconds and simultaneously the 

LINE/BATTERY

 led 

flashes.  

6.3

 

Low Battery and Automatic Restart 

In  Battery  mode,  ECO  STRIP  indicates  the 

Low  Battery

  condition  whenever  the  battery  reaches  a  charge  level 

allowing connected devices to operate for approximately one more minute.  

During  Low  Battery  condition  the  UPS  emits  an  acoustic  alarm  signal  every  second  and  simultaneously  the 

LINE/BATTERY

 led flashes. 

If  AC  Input  does  not  come  back  on  within  few  minutes,  the  UPS 

shuts-down  automatically

  thus  preventing  the 

batteries from discharging excessively; the UPS stops supplying Output power, deactivates control panel indication 
and goes to a waiting state. Once AC Input comes back on, the UPS

 restarts automatically 

and after some seconds 

it goes back to work in Normal mode. 

After  a  complete  discharge,  the  UPS  needs  4  hours  to  recharge  completely  the  batteries.  The  UPS  recharges 
batteries automatically if it works in Normal mode. 

6.4

 

Load Control 

During the functioning in Battery Mode, if the Output load is higher than nominal value (

Overload condition

), the 

UPS  may  automatically  switch  off,  protecting  itself  from  this  anomalous  situation.  In  this  case,  the  user  must 
reduce power within the specifications by disconnecting the devices that cause the 

Overload condition

 

 

Do not connect a load greater than rated value to the UPS (see POWER specifications in 
the chapter “Technical Characteristics”), as this may damage the unit. In this case the 
warranty is void. 

 
 
 
 
 
 
 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

9

 

User’s manual 

 

6.5

 

Fault Condition 

The UPS indicates the 

Fault condition

 by lighting of the 

Alarm 

led and by emitting a continuous acoustic alarm. 

During Fault condition, the UPS doesn’t supply Output power and so all the supplied devices are switched off. 

 

7

 

Communication Interface 

The UPS (only for ECO STRIP 0.90, 1.1 and 1.3) is factory-equipped with 

USB Communication Interface

. On the 

UPS rear side there is the connector of the USB Interface. 
 

The USB signals are all isolated through photo-couplers from the dangerous voltages that are present inside 
the UPS. 
 

Connecting to the Web site 

www.tecnoware.com, 

it is possible to download, free of charge, the update UPS 

management Software 

ViewPower

, compatible with the most popular Operative Systems

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 


background image

 

User’s manual 

10

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 
 

8

 

Technical Characteristics 

UPS ECO STRIP Model

 

0.50

 

0.70 

0.90

 

1.1 

1.3 

Power 

500 VA 

(300 W) 

700 VA 

(420 W) 

900 VA 

(540 W) 

1100 VA 

(660 W) 

1100 VA 

(780 W) 

Recommended for: 

PC, Monitor, Notebook, Netbook, Modem/Router, Printer, Fax 

Configuration example: 

Personal 

Computer with 

350W PSU 

(250W real 

power)  

+ LCD Monitor 

(40W)  

Personal 

Computer with 

450W PSU 

(350W real 

power)  

+ LCD Monitor 

(40W) 

Personal 

Computer with 

550W PSU  

(450W real 

power)  

+ LCD Monitor 

(60W) 

 

Personal 

Computer with 

600W PSU  

(500W real 

power)  

+ LCD Monitor 

(60W)

 

Personal 

Computer with 

650W PSU  

(550W real 

power)  

+ LCD Monitor 

(100W)

 

Technology 

Easy Interactive 

Nominal Input Voltage

  

Single-phase 230 Vac 

Input Voltage Range

 

+15%  -23% 

Input/Output Frequency 

50/60 Hz (automatic selection) 

Input Frequency Range

 

+/- 5% 

Nominal Output Voltage

 

Single-phase 230 Vac 

Output Voltage Regulation  
(Normal mode) 

As Input 

Output Voltage Regulation 
(Battery mode) 

+/- 5% 

Output Inverter Waveform 

Modified Sinewave 

Accepted Overload 

< 130% 

Certifications 

CE 

Standards: CEI EN 62040-1: 2009 (Low Voltage Directive) –  

CEI EN 62040-2: 2006 (EMC Directive)

 

Efficiency 

92% 

Battery Type 

Lead acid, sealed, free maintenance 

Number of batteries 

Nominal Battery Voltage 

12 Vdc 

Battery Specifications 

12 Vdc – 4,5 Ah – 

6 cells 

12 Vdc – 4,5 Ah     

– 6 cells 

12 Vdc – 7,2 Ah – 

6 cells 

12 Vdc – 7,2 Ah – 

6 cells 

12 Vdc – 9 Ah –    

6 cells 

Backup Time (typical)  

10 min 

Battery Charge Time (typical) 

4 hours 

Audible Noise (at 1 meter)

 

< 40 dBA 

Cooling 

Natural 

Environmental Operative Specification

 

Temperature: 0-40 °C  - Humidity 0-95% (without condensation)  

Altitude: max 3.000 mt 

Computer Interface 

1 USB port 

UPS Management Software 

Software ViewPower,  

downloadable free of charge from 

www.tecnoware.com

 

Telephone and Modem protection 

RJ11 plugs included 

Output sockets 

2 Output UPS sockets (Italian 10A/Schuko type) + 1 Output 

Filtred sockets (Italian 10A/Schuko type)   

4 Output UPS sockets (Italian 

10A/Schuko type) + 1 Output Filtred 

sockets (Italian 10A/Schuko type)   

Dimension (W x H x D) 

20 x 9,3 x 23 cm

 

Net Weight  

2,8 Kg 

2,9 Kg 

3,8 Kg 

4,1 Kg 

4,5 Kg 

 

Technical data may change without prior notice 

 

 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

11

 

User’s manual 

 
 

9

 

Maintenance 

9.1

 

UPS Cleaning 

 

Before starting any cleaning operation, be sure that: 

1.

 

The AC Input Voltage for the UPS has been removed. 

2.

 

The UPS is OFF. 

 

Use only a cloth dampened with water to clean the unit.  

If UPS works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes.  

Before restarting the UPS be sure it is completely dry. If any liquid gets inside the UPS, do not start the unit and 
contact Technical Service immediately. 

9.2

 

Battery  

If the UPS is NOT going to be used for a long period of time, ensure that the batteries are left fully charged.  

If the UPS has not been used for more than three months, go through the “First Start Up” procedure described in 
the chapter 5 before using it again. 

Please keep in mind that the batteries must be recharged at least once a month. Take in mind that batteries are 
recharged automatically if the UPS works in Normal mode or if the UPS is off and connected to the AC Input Line.  

Battery life strongly depends on the ambient temperature. There are also other factors like the number of charge-
discharge cycles, the discharge depth, humidity and altitude. 

The  recommended  environmental  specifications  for  a  correct  use  of  batteries  are  listed  in  the  “Technical 
Specifications” section.  

9.3

 

Battery Replacement 

Battery  replacement  must  be  performed  exclusively  by  qualified  and  authorized  technical  personnel.  We  advise 
you to follow the steps below explained for greater safety: 

1.

 

Turn the UPS off and disconnect the AC Input Line for the UPS. 

2.

 

Unscrew the 4 screws on the UPS bottom side. Remove the case cover and so you can access to the battery 
location. 

3.

 

Disconnect the battery wires and gently extract the battery from the case. 

4.

 

The new battery must be exactly the same type as the original one. 

5.

 

Put inside the new battery and connect it as the original one. 

6.

 

Reassemble the case cover. 

 


background image

 

User’s manual 

12

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 
 

 

 

 

 

 

Battery  replacement  must  be  performed  exclusively  by  qualified  technical  personnel 
authorized  by  TECNOWARE.  TECNOWARE  declines  any  responsibility  if  this  warning  is 
disregarded. 

When replacing batteries, replace with the same type and number. 

CAUTION: A battery can present a risk of electrical shock and high short circuit current. 
The following precautions should be observed when working on batteries: 

a)

 

Remove watches, rings or other metal objects; 

b)

 

Use tools with insulated handles; 

c)

 

Wear rubber gloves and boots; 

d)

 

Do not lay tools or metal parts on top of batteries; 

e)

 

Disconnect  the  charging  source  prior  to  connecting  or  disconnecting  battery 
terminals; 

f)

 

Determine  if  battery  is  inadvertently  grounded.  If  inadvertently  grounded,  remove 
source from ground. 

CAUTION: Do not dispose of batteries in a fire. The batteries may explode. 

CAUTION:  Do  not  open  or  mutilate  batteries.  Released  electrolyte is harmful to the skin 
and eyes. It may be toxic. 

 

9.4

 

Operator Safety 

Whenever the UPS is not responding anymore to original characteristics, the UPS must be made non-operative and 
every usage not authorised must be avoided. After it will be necessary to refer to qualified technical personnel. 

Original safety characteristics might not be if, for example, the UPS has visible damage or irregular operation. 
 


background image

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 - 1.3 

13

 

User’s manual 

 

10

 

Troubleshooting 

Alarms  and  problems  you may encounter during operating the UPS are given in the table below. 

Apply 

the suggestions corresponding to each anomaly as described into the table.  

If  your  anomaly  is  excluded  or  the  suggested  actions  do  not  solve  your  problem,  consult  the  Technical  Service. 
Please give the following information to the Technical Service: 

 

Model and serial number of the UPS, which can be found on the nameplate on the rear of the UPS.  

 

Description of anomaly. 

 

 

Risk of electric shock: do not remove the cover. The UPS contains internal parts that are 
at  a  high  Voltage  and  are  potentially  dangerous,  capable  of  causing  injury  or  death  by 
electric shock. 

There  are  no  internal  parts  in  the  UPS  that  are  user  serviceable.  Any  repair  or 
maintenance  work  must  be  performed  exclusively  by  qualified  technical  personnel 
authorized by TECNOWARE.  

TECNOWARE declines any responsibility if this warning is disregarded. 

Warning  to  the  technical  personnel  authorized  for  service:  since  internal  components 
are  connected  to  the  batteries,  they  will  remain  powered,  and  therefore  dangerous, 
even  after  the  UPS  has  been  disconnected  from  AC  power  mains.  Before  any  repair  or 
maintenance work, disconnect the batteries, by removing the positive cable (red colour) 
from the positive pole of the battery.  

 

ANOMALY 

POSSIBLE CAUSE 

ACTION TO SOLVE 

The UPS does not 
turn on 

ON/OFF button 

Press the ON/OFF button for almost 2 seconds. 

Batteries are flat 

Recharge the batteries for at least 4 hours. 

Electronic board failure 

Refer to Technical Service. 

The UPS always 
function on 
Battery mode 

Input mains power cable 
is disconnected. 

Check the input mains power cable. 

Check the presence of the electrical mains. 

Thermal fuse breaker 

Wait few minutes and then push the thermal fuse breaker to 
active it. 

Black-out conditions / 
surge/ Over-Voltage or 
Low-Voltage 

Wait until the AC Input Line returns to normal conditions. 

Electronic board failure 

Refer to Technical Service. 

Battery Autonomy 
is too short 

Battery is not fully 
charged. 

Recharge the battery for at least 6 hours. 

Electronic board failure 

Refer to Technical Service. 

Continuing 
Acoustic signal and 
red ALARM led on 

“FAULT” condition 

Refer to Technical Service. 

 

If the described anomalies should continue despite the advised troubleshooting, or should they 

manifest in any other form, please contact: 

TECNOWARE SERVICE 

www.tecnoware.com

 


background image

 

User’s manual 

14

 

UPS ECO STRIP 0.50 – 0.70 – 0.90 – 1.1 – 1.3 

 
 

 

 

Conformity to the European Directives 

TECNOWARE  S.r.l.  confirms  that  ECO  STRIP  models  comply  with  the  requirements  set  out  in:  the  Low  Voltage  Directive 
(Safety)  2006/95/EC  and  following  amendments,  the  EMC  (Electro-Magnetic  Compatibility)  Directive  2004/108/EC  and 
following amendments. 

The following standards were applied: 

Low Voltage Directive (Safety): CEI EN 62040-1: 2009 

EMC Directive (Electro-Magnetic Compatibility): CEI EN 62040-2: 2006 

 
 
 
 

Product Disposal

 

UPS  ECO  STRIP  cannot  be  disposed  as  an  urban  waste, but must be treated as a separate waste. Any 
violation is indictable with financial sanctions as per in force regulations.  

An incorrect waste disposal or an improper use of the same or of any parts can be damaging for the 
environment and for human health.    

A  correct  waste  disposal  of  products  having  the  dustbin  symbol  marked  by  a  cross  help  to  avoid 
negative consequences to the environment and to human health.

 

 

 
 
 
 

Lead Batteries

 

ECO STRIP models contain lead acid, sealed, maintenance free batteries. 

The  batteries  cannot  be  disposed  as  an  urban  waste,  but  must  be  treated  in  conformity  with 
2006/66/CE European Directive; any violation is indictable with financial sanctions as established into 
2006/66/CE European Directive. 

 

 
 
 
 


background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TECNOWARE s.r.l. 

www.tecnoware.com