Full Text Searchable PDF User Manual

TLK 38
MICROPROCESSOR-BASED
DIGITAL
ELECTRONIC CONTROLLER
OPERATING INSTRUCTIONS
Vr. 03 (ENG) - cod.: ISTR 06519
TECNOLOGIC S.p.A.
Distributed by:
GESINT S.R.L.
internet : http:\\www.
gesintsrl
.it
e-mail: info@
gesintsrl
.it
FOREWORD
:
This manual contains the information necessary for the product to
be installed correctly and also instructions for its maintenance and
use; we therefore recommend that the utmost attention is paid to
the following instructions.
Though this manual has been issued with the greatest care,
TECNOLOGIC S.p.A. will not take any responsibility deriving from
its use.
The same applies to each person or Company involved in the
issuing of this manual.
This document is the exclusive property of TECNOLOGIC S.p.A.
which forbids any reproduction and divulgation , even in part, of the
document, unless expressly authorized.
TECNOLOGIC S.p.A. reserves the right to make any formal or
functional changes at any moment and without any notice.
INDEX
INSTRUMENT ORDERING CODE
7.6
MEASUREMENT RANGE TABLE
7.5
FUNCTIONAL DATA
7.4
MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING
7.3
MECHANICAL DATA
7.2
ELECTRICAL DATA
7.1
TECHNICAL DATA
7
GUARANTEE AND REPAIRS
6.3
CLEANING
6.2
ERROR SIGNALLING
6.1
PROBLEMS , MAINTENANCE AND GUARANTEE
6
PROGRAMMABLE PARAMETERS TABLE
5
PARAMETERS CONFIGURATION BY KEY01
4.13
FUNCTION OF KEY “U”
4.12
LOOP BREAK ALARM FUNCTION
4.11
ALARMS OUTPUTS FUNCTIONS
4.10
SOFT-START FUNCTION
4.9
REACHING OF SET POINT AT CONTROLLED SPEED
AND AUTOMATIC COMMUTATION BETWEEN TWO
SET POINTS
4.8
AUTO-TUNING AND SELF-TUNING FUNCTIONS
4.7
DOUBLE ACTION PID CONTROL
4.6
SINGLE ACTION PID CONTROL
4.5
NEUTRAL ZONE ON/OFF CONTROL
4.4
ON/OFF CONTROL
4.3
OUTPUTS CONFIGURATION
4.2
MEASURING AND VISUALIZATION
4.1
FUNCTIONS
4
ELECTRICAL WIRING DIAGRAM
3.4
ELECTRICAL CONNECTIONS
3.3
MECHANICAL MOUNTING
3.2
PERMITTED USE
3.1
INFORMATION ON INSTALLATION AND USE
3
ACTIVE SET POINT SELECTION
2.5
CONTROL STATES
2.4
PARAMETER PROGRAMMING LEVELS
2.3
SELECTION OF CONTROL STATE AND PARAMETER
PROGRAMMING
2.2
FAST PROGRAMMING OF SET POINT
2.1
PROGRAMMING
2
FRONT PANEL DESCRIPTION
1.2
GENERAL DESCRIPTION
1.1
INSTRUMENT DESCRIPTION
1
1 - INSTRUMENT DESCRIPTION
1.1 - GENERAL DESCRIPTION
TLK 38 is a “single loop” digital microprocessor-based controller,
with ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual
action (direct and reverse) control and with
AUTO-TUNING FAST
function,
SELF-TUNING
function and automatic calculation of the
FUZZY OVERSHOOT CONTROL
parameter for PID control. The
PID control has a particular algorithm with
TWO DEGREES OF
FREEDOM
that optimises the instrument’s features independently
in the event of process disturbance and Set Point variations. The
process value is visualized on 4 red displays, while the output
status is indicated by 2 LED displays. The instrument is equipped
with a 3 LED programmable shift indexes. The instrument provides
for the storage of 4 Set Points and can have up to 2 outputs: relay
type or can drive solid state relays type (SSR).
Depending on the model required the input accept:
C
: Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermoresistances PT100.
E
: Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermistors PTC and NTC.
I
: normalized analogue signals 0/4..20 mA
V
: normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V
Other important available functions are: Loop-Break Alarm function,
reaching of the Set Point at controlled speed, ramp and dwell
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 1

function, Soft-Start function, protection compressor function for
neutral zone control, parameters protection on different levels.
1.2
-
FRONT PANEL DESCRIPTION
OUT1
TLK 38
1
7
2
3
4
8
5
9
10
11
6
AT
ST
-
=
+
OUT2
1 - Key P
: This is used to access the programming parameters
and to confirm selection.
2 - Key DOWN
: This is used to decrease the values to be set and
to select the parameters. If the key is held down, the user returns to
the previous programming level until he exits the programming
mode.
3 - Key UP
: This is used to increase the values to be set and to
select the parameters. If the key is held down, the user returns to
the previous programming level until he exits the programming
mode. Outside the programming mode it permits visualisation of
the output control power.
4 - Key U
: This is a key with a function programmable by par.
“USrb”. It can be set to : Activate Auto-tuning and Self-tuning
functions, swap the instrument to manual control, silence the alarm,
change the active Set Point, deactivate control (see par. 4.12) and
modify the visibility of the parameters in “ConF” menu (see par.
2.3).
5 - Led OUT1
: indicates the state of output OUT1
6 - Led OUT2
: indicates the state of output OUT2
7 - Led SET
:It indicates access to the programming mode and
parameter programming level.
8 - Led AT/ST
: indicates that the Self-tuning function is activated
(light on) or that Auto-tuning (flashing ) is in progress.
9 - Led – Shift index:
indicates that the process value is lower than
the one programmed on par. “AdE”.
10 - Led = Shift index:
indicates that the process value is within
the range [SP+AdE ... SP-AdE]
11 - Led + Shift index:
indicates that the process value is higher
than the one set on par. “AdE”.
2 - PROGRAMMING
2
.1 - FAST PROGRAMMING OF THE SET POINT
This procedure permits rapid programming of the active Set Point
and possibly the alarm thresholds (see par 2.3)
Push key “P”, then release it and the display will visualise
“SP n”
(where n is the number of the Set Point active at that moment)
alternatively to the programmed value.
To modify the value, press “UP” key to increase it or the “DOWN”
key to decrease it.
These keys change the value one digit at a time but if they are
pressed for more than one second, the value increases or
decreases rapidly and, after two seconds in the same condition, the
changing speed increases in order to allow the desired value to be
reached rapidly.
Once the desired value has been reached, by pushing key P it is
possible to exit by the fast programming mode or it is possible to
visualise the alarm thresholds (see par. 2.3).
To exit the fast Set programming it is necessary to push key P,
after the visualisation of the last Set Point, or alternatively, if no key
is pressed for approx. 15 seconds, the display will return to normal
functioning automatically.
2.2 - SELECTION OF THE CONTROL STATE AND PARAMETER
PROGRAMMING
By pushing key "P" and holding it down for approx. 2 sec. it is
possible to enter into the main selection menu.
Using the "UP" or DOWN” keys, it is then possible to roll over the
selections:
to enter into the operating parameters menu
"OPEr"
to swap the regulator to the manual control state and
therefore to program the % control value using the
“UP” and “DOWN” keys
"OPLO"
to activate the Auto-tuning or Self-tuning function
"tunE"
to swap the regulator into the automatic control state
"rEG"
to swap the regulator into the OFF state
"OFF"
to enter into the configuration parameters menu
"ConF"
Once the desired item has been selected, push key “P” to confirm.
Selecting "OPEr" and "ConF" gives the possibility of accessing
other menus containing additional parameters and more precisely :
"OPEr" -
Operating parameters Menu: this normally contains the
Set Point parameters but it can contain all the desired parameters
(see par. 2.3).
"ConF" -
Configuration parameters Menu: this contains all the
operating parameters and the functioning configuration parameters
(alarm configuration, control, input, etc.)
S E L F T U N IN G
A U T O T U N IN G
A T
S T
2 s e c .
H o ld fo r
"O F F "
"rE G "
"O P L O "
To enter the menu
“ConF”
select the option “ConF”, press the key
“P” and the display will show “0”.
At this request, enter, using keys “UP” and “DOWN”, the number
reported on the last page of this manual and push key “P”.
If an incorrect password is entered, the instrument exit from
programming mode.
If the password is correct, the display will visualise the code
identifying the first group of parameters (“
]
SP
“) and with keys “UP”
and “DOWN” it will be possible to select the desired group of
parameters.
Once the desired group of parameters has been selected, the code
identifying the first parameter of the selected group will be
visualised by pushing the “P” key.
Again using the “UP” and “DOWN” keys, it is possible to select the
desired parameter and, if the key “P” is pressed, the display will
alternatively show the parameter’s code and its programming value,
which can be modified by using the “UP” or “DOWN” keys.
Once the desired value has been programmed, push key “P” once
more: the new value will be memorised and the display will show
only the code of the selected parameter.
By using the “UP” or “DOWN” keys, it is then possible to select a
new parameter (if present) and modify it as described above.
To select another group of parameters, keep the “UP” or “DOWN”
key pressed for approx. 2 sec., afterwards the display will return to
visualise the code of the group of parameters.
Release the key and by using the “UP” and “DOWN” keys, it will be
possible to select a new group.
To exit the programming mode, no key should be pressed for
approx. 20 seconds, or keep the “UP” or “DOWN” pressed until exit
from the programming mode is obtained.
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 2

The programming and exit modes for the “OPEr” menu are the
same as those described for menu “ConF” with the difference that
to access the menù "OPEr" the Password is not required.
Longer
Hold
2 sec.
Hold for
2 sec.
Hold for
ATTENTION:
The instrument is programmed in factory with all the
parameters, to exception of the Set Point "SP1" (and 2,3,4),
programmable in the menù "ConF" to the purpose to prevent wrong
accidental programming from non experienced consumers.
2.3 - PARAMETERS PROGRAMMING LEVELS
The menu “OPEr” normally contains the parameters used to
program the Set Point; however it is possible to make all desired
parameters appear or disappear on this level, by following this
procedure:
Enter the menu “ConF” and select the parameter to be made
programmable or not programmable in the menu “OPEr”.
Once the parameter has been selected, if the LED SET is switched
off, this means that the parameter is programmable only in the
menu “ConF”, if instead the LED is on, this means that the
parameter is also programmable in the menu “OPEr”.
To modify the visibility of the parameter, push key “U” : the LED
SET will change its state indicating the parameter accessibility level
(on = menu ”OPEr” and “ConF”; off = menu “ConF” only).
The active Set Point and the alarm thresholds will only be visible on
the Set Point fast programming level (described in par. 2.1) if the
relative parameters are programmed to be visible (i.e. if they are
present in the menu “OPEr”).
The possible modification of these Sets, with the procedure
described in par. 2.1, is instead subordinate to what is programmed
in par.
“Edit”
(contained in the group “
]
PAn
“).
This parameter can be programmed as :
=SE : The active Set Point can be modified while the alarm
thresholds cannot be modified.
=AE : The active Set Point cannot be modified while the alarm
thresholds can be modified
=SAE : Both the active Set Point and the alarm thresholds can be
modified
=SAnE : Both the active Set Point and the alarm thresholds cannot
be modified
2.4 - CONTROL STATES
The controller can act in 3 different ways : automatic control
(rEG),
control off
(OFF)
and manual control
(OPLO).
The instrument is able to pass from one state to the other :
- by selecting the desired state from the main selection menu suing
the keyboard.
- By using the key “U” on the keyboard; suitably programming par.
“USrb” (“USrb” = tunE; “USrb” = OPLO; “USrb” = OFF) it is possible
to pass from “rEG” state to the state programmed on the parameter
and vice versa.
- Automatically (the instrument swaps into "rEG" state at the and of
the auto-tuning execution)
When switched on, the instrument automatically reassumes the
state it was in when it was last switched off.
AUTOMATIC CONTROL (rEG)
– Automatic control is the normal
functioning state of the controller.
During automatic control it is possible to visualize the control power
on the display by pushing key “UP”.
The range of the power values goes from H100 (100% of the output
power with reverse action) to C100 (100% of the output power with
direct action).
CONTROL OFF (OFF)
– The instrument can be swapped into the
“OFF” state, i.e. the control and the relative outputs are
deactivated.
The alarm outputs are instead working normally.
BUMPLESS MANUAL CONTROL (OPLO)
– By means of this
option it is possible to manually program the power percentage
given as output by the controller by deactivating automatic control.
When the instrument is swapped to manual control, the power
percentage is the same as the last one supplied and can be
modified using the “UP” and “DOWN” keys.
As in the case of automatic control, the programmable values
range from H100 (+100%) to C100 (-100%).
To return to automatic control, select "rEG" in the selection menu.
2.5 - ACTIVE SET POINT SELECTION
This instrument permits pre-programming of up to 4 different Set
points (
“SP1”
,
“SP2”
,
“SP3”
,
“SP4”
) and then selection of which
one must be active. The maximum number of Set points is
determined by the par.
"nSP"
located in the group of parameters “
]
SP
“.
The active Set point can be selected :
- by parameter
"SPAt"
in the group of parameters “
]
SP
“.
- by key “U” if par. "USrb" = CHSP
- Automatically between SP1 and SP2 if a time “dur.t” (see par. 4.8)
has been programmed.
Set Points “SP1”, “SP2”, “SP3”, “SP4” will be visible depending on
the maximum number of Set Points selected on par. “nSP” and they
can be programmed with a value that is between the value
programmed on par.
“SPLL”
and the one programmed on par.
“SPHL”.
Note
: in all the following examples the Set point is indicated as
"SP", however the instrument will act according to the Set point
selected as active.
3 - INFORMATION ON INSTALLATION AND USE
3.1 - PERMITTED USE
The instrument has been projected and
manufactured as a measuring and control device to
be used according to EN61010-1 for the altitudes
operation until 2000 ms.The use of the instrument
for applications not expressly permitted by the
above mentioned rule must adopt all the necessary protective
measures. The instrument CANNOT be used in dangerous
environments (flammable or explosive) without adequate
protection. The installer must ensure that EMC rules are respected,
also after the instrument installation, if necessary using proper
filters.
Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please
remember that the plant has to be equipped with additional devices
which will guarantee safety.
3.2 - MECHANICAL MOUNTING
The instrument, in case 33 x 75 mm, is designed for flush-in panel
mounting. Make a hole 29 x 71 mm and insert the instrument, fixing
it with the provided special bracket. We recommend that the gasket
is mounted in order to obtain the front protection degree as
declared. Avoid placing the instrument in environments with very
high humidity levels or dirt that may create condensation or
introduction of conductive substances into the instrument. Ensure
adequate ventilation to the instrument and avoid installation in
containers that house devices which may overheat or which may
cause the instrument to function at a higher temperature than the
one permitted and declared. Connect the instrument as far away as
possible from sources of electromagnetic disturbances such as
motors, power relays, relays, solenoid valves, etc.
3.3 - ELECTRICAL CONNECTION
Carry out the electrical wiring by connecting only one wire to each
terminal, according to the following diagram, checking that the
power supply is the same as that indicated on the instrument and
that the load current absorption is no higher than the maximum
electricity current permitted. As the instrument is built-in equipment
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 3

with permanent connection inside housing, it is not equipped with
either switches or internal devices to protect against overload of
current: the installation will include an overload protection and a
two-phase circuit-breaker, placed as near as possible to the
instrument, and located in a position that can easily be reached by
the user and marked as instrument disconnecting device which
interrupts the power supply to the equipment. It is also
recommended that the supply of all the electrical circuits connected
to the instrument must be protect properly, using devices (ex.
fuses) proportionate to the circulating currents. It is strongly
recommended that cables with proper insulation, according to the
working voltages and temperatures, be used. Furthermore, the
input cable of the probe has to be kept separate from line voltage
wiring. If the input cable of the probe is screened, it has to be
connected to the ground with only one side. Whether the
instrument is 12 V version it’s recommended to use an external
transformer TCTR, or with equivalent features, and to use only one
transformer for each instrument because there is no insulation
between supply and input. We recommend that a check should be
made that the parameters are those desired and that the
application functions correctly before connecting the outputs to the
actuators so as to avoid malfunctioning that may cause
irregularities in the plant that could cause damage to people, things
or animals.
Tecnologic S.p.A. and its legal representatives do not assume
any responsibility for any damage to people, things or animals
deriving from violation, wrong or improper use or in any case
not in compliance with the instrument’s features.
3.4 - ELECTRICAL WIRING DIAGRAM
-
+
+
-
TLK 38
INPUT
SUPPLY
0...1 V
ACTIVE
0/4..20 m A
0..50/60 mV
0/1..5 V
0/2..10 V
AC TIVE
PASSIVE
(2 wires)
4..20 m A
4..20 m A
OUT 10 V DC
M ax 20 mA
gen.
e xt.
R ELAY
1
2
3
C
SSR
SSR : 8 m A / 8 VD C
RELAYS: 8A-AC1 (3A-AC3) 250 VAC
7
OUT 1
NC
4
NO
5
6
9
8
10
PTC
N TC
I
+
Pt100
11
+
12
TC
+
-
+
-
+
NO
NC
C
+
-
OU T 2
4 - FUNCTIONS
4.1 - MEASURING AND VISUALIZATION
All the parameters referring measurements are contained in the
group
“
]
InP”.
Depending on the model required the input accept:
C
: Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermoresistances PT100.
E
: Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermistors PTC and NTC.
I
: normalized analogue signals 0/4..20 mA
V
: normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V
Depending on the model, using par.
“SEnS”,
it’s possible to select
the type of input probe, which can be :
- for thermocouples J (J), K (CrAL), S (S) or for infrared sensors
serie TECNOLOGIC IRTC1 with linearization J (Ir.J) or K (Ir.CA)
- for thermoresistances Pt100 IEC (Pt1) or thermistors PTC
KTY81-121 (Ptc) or NTC 103AT-2 (ntc)
- for normalised signals in current 0..20 mA (0.20) or 4..20 mA
(4.20)
- for normalised signals in tension 0..1 V (0.1), 0..5 V (0.5), 1..5 V
(1.5), 0..10 V (0.10) or 2..10 V (2.10).
- for normalised signals in tension 0..50 mV (0.50), 0..60 mV (0.60),
12..60 mV (12.60).
We recommend to switch on and off the instrument when these
parameters are modified, in order to obtain a correct measuring.
For the instruments with input for temperature probes (tc, rtd) it’s
possible to select, through par.
“Unit”,
the unit of measurement
(°C, °F) and, through par.
“dP”
(Pt100, PTC and NTC only)
the
desired resolution (0=1°; 1=0,1°).
Instead, with regards to the instruments with normalised analogue
input signals, it is first necessary to program the desired resolution
on par.
“dP”
(0=1; 1=0,1; 2=0,01; 3=0,001) and then, on par.
"SSC"
, the value that the instrument must visualise at the
beginning of the scale (0/4 mA, 0/12 mV, 0/1 V o 0/2 V) and, on
par.
"FSC",
the value that the instrument must visualise at the end
of the scale (20 mA, 50 mV, 60 mV, 5 V or 10 V).
The instrument allows for measuring calibration, which may be
used to recalibrate the instrument according to application needs,
by using par.
“OFSt”
and
“rot”.
Programming par. “rot”=1,000, in par. “OFSt” it is possible to set a
positive or negative offset that is simply added to the value read by
the probe before visualisation, which remains constant for all the
measurements.
If instead, it is desired that the offset set should not be constant for
all the measurements, it is possible to operate the calibration on
any two points.
In this case, in order to decide which values to program on par.
“OFSt” and “rot”, the following formulae must be applied :
“rot” = (D2-D1) / (M2-M1)
“OFSt” = D2 - (“rot” x M2)
where:
M1 =measured value 1
D1 = visualisation value when the instrument measures M1
M2 =measured value 2
D2 = visualisation value when the instrument measures M2
It then follows that the instrument will visualise :
DV = MV x “rot” + “OFSt”
where: DV = visualised value
MV= measured value
Example 1: It is desired that the instrument visualises the value
effectively measured at 20° but that, at 200°, it visualises a value
lower than 10° (190°).
Therefore : M1=20 ; D1=20 ; M2=200 ; D2=190
“rot” = (190 - 20) / (200 - 20) = 0,944
“OFSt” = 190 - (0,944 x 200) = 1,2
Example 2: It is desired that the instrument visualises 10° whilst the
value actually measured is 0°, but, at 500° it visualises a 50° higher
value (550°).
Therefore : M1=0 ; D1=10 ; M2=500 ; D2=550
“rot” = (550 - 10) / (500 - 0) = 1,08
“OFSt” = 550 - (1,08 x 500) = 10
By using par.
“FiL”
it is possible to
program time constant of the
software filter for the input value measured, in order to reduce
noise sensitivity (increasing the time of reading).
In case of measurement error, the instrument supplies the power
as programmed on par.
“OPE”.
This power will be calculated according to cycle time programmed
for the PID controller, while for the ON/OFF controllers the cycle
time is automatically considered to be equal to 20 sec. (e.g. In the
event of probe error with ON/OFF control and “OPE”=50, the
control output will be activated for 10 sec., then it will be
deactivated for 10 sec. and so on until the measurement error
remains.).
By using par.
“InE”
it is also possible to decide the conditions of
the input error, allowing the instrument to give the power
programmed on par. “OPE” as output.
The possibilities of par. “InE” are :
= Or : the condition occurs in case of over-range or probe breakage
= Ur : the condition occurs in case of under-range or probe
breakage
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 4

= OUr : the condition occurs in case of over-range or under-range
or probe breakage
Using par.
“diSP”,
located in the group
“
]
PAn”,
it is possible to set
normal visualization of the display which can be the process
variable (dEF), the control power (Pou), the active Set Point (SP.F)
the Set Point operating when there are active ramps (SP.o) or
alarm threshold AL1 or AL2 (AL1, AL2).
Again in the group
“
]
PAn”
the par.
“AdE”
is present that defines
the 3 led shift index functioning.
The lighting up of the green led = indicates that the process value
is within the range [SP+AdE ... SP-AdE], the lighting up of the led –
indicates that the process value is lower than [SP-AdE] and the
lighting up of the led + indicates that the process value is higher
than [SP+AdE].
4.2 - OUTPUTS CONFIGURATION
The instrument’s outputs can be programmed by entering the group
of parameters
“
]
Out
, where the relative parameters
“O1F”
and
“O2F”
(depending on the number of outputs available on the
instrument) are located.
The outputs can be set for the following functions :
- Main control output (1.rEG)
- Secondary control output (2.rEG)
- Alarm output normally open (ALno)
- Alarm output normally closed (ALnc)
- Alarm output normally closed with led reverse indication (ALni)
- Output deactivated (OFF)
The coupling outputs number outputs – number alarms can be
made in the group referring to the alarm to the alarm (“
]
AL1”,
“
]
AL2”).
4.3 - ON/OFF CONTROL (1.rEG)
All the parameters referring to the ON/OFF control are contained in
the group
“
]
rEG”.
This type of control can be obtained by programming par.
"Cont"
=
On.FS or = On.FA and works on the output programmed as 1.rEG,
depending on the measure, on the active Set Point
“SP”
, on the
functioning mode
"Func”
and on the hysteresis
"HSEt
".
The instrument carries out an ON/OFF control with symmetric
hysteresis if “Cont" = On.FS or with asymmetrical hysteresis if
“Cont” = On.FA.
O UT
SP
PV
off
ON
HEAt - On.FA
OUT
time
HSEt
SP
PV
HSEt
time
CooL - On.FA
ON
ON
ON
ON
ON
off
off
off
CooL - On.FS
HEAt - On.FS
ON
ON
O UT
SP
off
PV
off
ON
HSEt
time
OUT
ON
SP
PV
ON
off
off
ON
time
HSEt
HSEt
HSEt
1.rEG
1.rEG
1.rEG
1.rEG
The control works in the following way : in the case of reverse
action, or heating (“FunC”=HEAt), it deactivates the output, when
the process value reaches [SP + HSEt] in case of symmetrical
hysteresis, or [SP] in case of asymmetrical hysteresis and is then
activated again when the process value goes below value [SP -
HSEt].
Vice versa, in case of direct action or cooling ("Func”=CooL), it
deactivates the output, when the process value reaches [SP -
HSEt] in case of symmetrical hysteresis, or [SP] in case of
asymmetrical hysteresis and is activated again when the process
value goes above value [SP + HSEt].
4.4 - NEUTRAL ZONE ON/OFF CONTROL (1.rEG - 2.rEG)
All the parameters referring to Neutral Zone ON/OFF control are
contained in the group
“
]
rEG”.
This type of control can be obtained when 2 outputs are
programmed respectively as 1.rEG and 2.rEG and the par.
“Cont”
= nr .
The Neutral Zone control is used to control plants in which there is
an element which causes a positive increase (ex. Heater,
humidifier, etc.) and an element which causes a negative increase
(ex. Cooler, de-humidifier, etc).
The control functions works on the programmed outputs depending
on the measurement, on the active Set Point
“SP”
and on the
hysteresis
"HSEt
".
The control works in the following way : it deactivates the outputs
when the process value reaches the Set Point and it activates the
output 1.rEG when the process value goes below value [SP -
HSEt], or it activates the output 2.rEG when the process value goes
above [SP + HSEt].
Consequently, the element causing a positive increase has to be
connected to the output programmed as 1.rEG while the element
causing a negative increase has to be connected to the output
programmed as 2.rEG.
0N
OUT 2.rEG
(cooling)
OUT 1.rEG
(heating)
SP
PV
off
0N
off
off
off
0N
time
HSEt
HSEt
If 2.rEG output is used to control compressor is possible to use the
“Compressor Protection” function that has the meaning to avoid
compressor “short cycles”.
This function allows a control by time on the output 2.rEG
activation, independently by the temperature control request.
The protection is a “delayed after deactivation” type.
This protection permits to avoid the output activation for a time
programmable on par. “
CPdt
” (expressed in sec.); the output
activation will occurs only after the elapsing of time “CPdt”.
The time programmed on parameter “CPdt” is counted starting from
the last output deactivation.
Obviously, whether during the time delay caused by the
compressor protection function, the regulator request should stop,
the output activation foreseen after time “CPdt” would be erased.
The function is not active programming “CPdt” =OFF.
The led relative to 2.rEG output blinks during the phases of output
activation delay, caused by “Compressor Protection” function.
4.5 - SINGLE ACTION PID CONTROL (1.rEG)
All the parameters referring to PID control are contained in the
group
“
]
rEG”.
The Single Action PID control can be obtained by programming
par.
"Cont"
= Pid and works on the output 1.rEG depending on the
active Set Point
“SP”
, on the functioning mode
"Func”
and on the
instrument’s PID algorithm with two degree of freedom.
0 N
t c r 1
1 .r E G
( H E a t )
S P
P V
t c r 1
o f f
t c r 1
t c r 1
t c r 1
t c r 1
0 N
o f f
o ff
0 N
o f f
o ff
0 N
0 N
t c r 1
o f f
0 N
0 N
ti m e
O U T
In order to obtain good stability of the process variable, in the event
of fast processes, the cycle time “tcr1” has to have a low value with
a very frequent intervention of the control output.
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 5

In this case use of a solid state relay (SSR) is recommended for
driving the actuator.
The Single Action PID control algorithm foresees the setting of the
following parameters :
"Pb"
– Proportional Band
"tcr1"
– Cycle time of the output 1.rEG
"Int"
– Integral Time
"rS"
– Manual Reset (if “Int =0 only)
"dEr"
– Derivative Time
“FuOC” -
Fuzzy Overshoot Control
This last parameter allows the variable overshoots at the start up of
the process or at the changing of the Set Point to be avoided.
Please remember that a low value on this parameter reduces the
overshoot while a high value increase it.
2
1
3
S P
P V
t i m e
1: Value “FuOC” OK
2: Value “FuOC” too high
3: Value “FuOC” too low
4.6 - DOUBLE ACTION PID CONTROL (1.rEG - 2.rEG)
All the parameters referring to PID control are contained in the
group
“
]
rEG”.
The Double Action PID control is used to control plants where there
is an element which causes a positive increase (ex. Heating) and
an element which causes a negative increase (ex. Cooling).
This type of control can be obtained when 2 outputs are
programmed respectively as 1.rEG and 2.rEG and the par.
“Cont”
= Pid.
The element causing a positive increase has to be connected to the
output programmed as 1.rEG while the element causing a negative
increase has to be connected to the output programmed as 2.rEG.
The Double Action PID control works on the outputs 1.rEG and
2.rEG depending on the active Set Point
“SP”
and on the
instrument’s PID algorithm with two degrees of freedom.
In order to obtain good stability of the process variable, in case of
fast processes, the cycle times “tcr1” and “tcr2” have to have a low
value with a very frequent intervention of the control outputs.
In this case use of solid state relays (SSR) to drive the actuators is
recommended.
The Double Action PID control algorithm needs the programming of
the following parameters :
"Pb"
- Proportional Band
"tcr1"
- Cycle time of the output 1.rEG
“tcr 2”
- Cycle time of the output 2.rEG
"Int"
- Integral Time
"rS"
- Manual Reset (if “Int =0 only)
"dEr"
- Derivative Time
“FuOC” -
Fuzzy Overshoot Control
"Prat"
- Power Ratio or relation between power of the element
controlled by output 2.rEG and power of the element controlled by
output 1.rEG.
If par. “Prat” = 0, the output 2.rEG is disabled and the control
behaves exactly as a single action PID controller, through output
1.rEG.
4.7 - AUTOTUNING
AND SELFTUNING FUNCTIONS
All the parameters referring to the AUTO-TUNING and
SELF-TUNING functions are contained in the group
“
]
rEG”.
The AUTO-TUNING and SELF-TUNING functions permit the
automatic tuning of the PID controller.
The
AUTO-TUNING
function permits the calculation of thePID
parameters by means of a FAST type tuning cycle and, at the end
of this operation, the parameters are stored into the instrument’s
memory and remain constant during control.
The
SELF-TUNING
function (rule based "TUNE-IN") instead allows
control monitoring and the continuous calculation of the parameters
during control.
Both functions automatically calculate the following parameters :
"Pb"
- Proportional Band
"tcr1"
- Cycle time of the output 1rEG
"Int"
- Integral Time
"dEr"
- Derivative Time
“FuOC” -
Fuzzy Overshoot Control
and, for the Double Action PID control, also :
“tcr 2”
- Cycle time of the output 2rEG
"Prat"
- Power Ratio P 2.rEG/ P 1.rEG
To activate the AUTO-TUNING function proceed as follows :
1) Program and activate the desired Set Point.
2) Program par. "Cont" =Pid.
3) Program par. "Func" according to the process to be controlled
through output 1rEG.
4) Program an output as 2.rEG if the instrument controls a plant
with double action
5) Program par.
"Auto"
as:
- "1” – if auto-tuning is desired automatically, each time the
instrument is switched on, on the condition that the process value is
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func”
=CooL) than [SP+ |SP/2|].
- "2" – if auto-tuning is desired automatically, the next time the
instrument is switched on, on the condition that the process value is
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func”
=CooL) than [SP+ |SP/2|], and once the tuning is finished, the par.
“Auto” is automatically swapped to the OFF state
- "3" - if manual auto-tuning is desired, by selecting par. “tunE” in
the main menu or by correctly programming key “U” as “USrb” =
tunE. The Autotuning will start at the condition that the process
value is lower (with “Func” =HEAt) than [SP- |SP/5|] or higher (with
“Func” =CooL) than [SP+ |SP/5|].
- "4" - if it’s desired to activate the autotuning automatically to
every change of Set Point, or at the end of programmed Soft-Start
cycle. The Autotuning will start at the condition that the process
value is lower (with “Func” =HEAt) than [SP- |SP/5|] or higher (with
“Func” =CooL) than [SP+ |SP/5|].
6) Exit from the parameter programming.
7) Connect the instrument to the controlled plant.
8) Activate the Auto-tuning by switch off and turn on the instrument
if “Auto”=1 or 2 , or by selecting par.
“tunE”
in the main menu (or
by correctly programming key “U” ).
At this point the Auto-tuning function is activated and is indicated by
the flashing led AT/ST.
The regulator carries out several operations on the connected plant
in order to calculate the most suitable PID parameters.
If, at the Auto-tuning start, the condition for the lower or higher
process value is not found the display will show
“ErAt”
and the
instrument will be swapped to normal control conditions according
to the previously programmed parameters.
To make the error “ErAt” disappear, press key P.
The Auto-tuning cycle duration has been limited to 12 hours
maximum.
If Auto-tuning is not completed within 12 hours, the instrument will
show
"noAt"
on the display
.
In case of probe error, the instrument automatically stops the cycle
in progress.
The values calculated by Auto-tuning are automatically stored in
the instrument’s memory at the end of the correct PID parameters
tuning.
Note :
The instrument is already programmed in our factory to carry
out auto-tuning at first instrument switch on ("Auto" = 2).
To activate the SELF-TUNING function proceed as follows
1) Program and activate the desired Set Point.
2) Program par. "Cont" =Pid.
3) Program par. "Func" according to the process to be controlled
through output 1.rEG.
4) Program an output as 2.rEG if the instrument controls a
dual-action plant
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 6

5) Program par.
"SELF"
= yES
6) Exit from the parameter programming.
7) Connect the instrument to the controlled plant.
8) Activate Self-tuning selecting par.
“tunE”
in the main menu (or
by correctly programming key “U”).
When the Self-tuning function is active, the led AT/ST is
permanently lit up and all the PID parameters ("Pb", "Int", "dEr",
etc.) are no longer visualized.
Note :
It’s always preferable tuning the instrument using the
Autotuning and to activate the Selftuning after because the tuning
through Selftuning is more slow.
To stop the Auto-tuning cycle or deactivate the Self-tuning function
select one of the control types : "rEG", "OPLO" or "OFF" from the
menu “SEL”. If the instrument is switched off during Auto-tuning or
with the Self-tuning function activated, these functions will remain
activated the next time it is switched on.
4.8 - REACHING OF THE SET POINT AT CONTROLLED SPEED
AND AUTOMATIC SWITCHING BETWEEN TWO SET POINTS
(RAMPS AND DWELL TIME)
All the parameters referring to the ramps functioning are contained
in the group
“
]
rEG”.
It is possible to reach the set point in a predetermined time (in any
case longer than the time the plant would naturally need). This
could be useful in those processes (heating or chemical
treatments, etc.) where the set point has to be reached gradually, in
a predetermined time.
Once the instrument has reached the first Set Point (SP1) it is
possible to have automatic switching to the second Set Point (SP2)
after a set time, thus obtaining a simple automatic process cycle.
These functions are available for all the programmable controls
(PID single and double action, ON/OFF and Neutral Zone
ON/OFF).
The function is determined by the following parameters :
"SLor"
- Gradient of first ramp expressed in unit/minute
"SLoF"
- Gradient of second ramp expressed in unit/minute.
"dur.t"
- Dwell time of Set Point “SP1” before automatic switching
to Set Point “SP2” (expressed in hrs. and min.).
The functions are deactivated when the relative parameters are =
InF.
If is desired only one ramp (ex. to reach “SP1”) it is enough to
program on the par. "SLor" the desired value.
The ramp "SLor" it will always active at power on and when the
Active Set Point value is changed.
S P 1
[ U n it ]
P V
S P 1 V a lu e
c h a n g e
S P 1
t im e [ m in . ]
S L o r
S L o r
If it is desired an automatic cycle from the power on instead it is
necessary to program the par. "nSP" = 2, to program the two Set
Point values "SP1" and "SP2" and naturally to program the par.
"SLor", "dur.t" and "SLoF" with the desired values.
In this case at the end of the cycle all the ramps won't be more
active.
[ U n it ]
S P 1
P V
A U T O
c h a n g e
S e t
d u r . t
S P 2
t im e [ m in . ]
S L o r
S L o F
Examples with starts from values lower than SP and with
decreasing of SP.
Note:
In case of PID control, if Auto-tuning is desired whilst the
ramp function is active, this will not be carried out until the tuning
cycle has been completed. It is therefore recommended that
Auto-tuning be started avoiding activating the ramp function and,
once the tuning is finished, deactivate Auto-tuning (“Auto” = OFF),
program the desired ramp and, if it automatic tuning is desired,
enable the Self-tuning function.
4.9 - SOFT-START FUNCTION
All the parameters referring to the Soft -Start functioning are
contained in the group
“
]
rEG”.
The Soft-Start function only works through PID control and allows
the limitation of control power when the instrument is switched on,
for a programmable period of time.
This is useful when the actuator, driven by the instrument, may be
damaged excess power supplied when the application is not yet in
the normal rating. (ex. for certain heating elements).
The function depends on the following parameters :
“St.P”
- Soft-Start power
“SSt”
- Soft-Start time (expressed in hh.mm)
“HSEt”
- End Soft Start cycle threshold
If both parameters are programmed with values other than OFF,
when switched on the instrument gives an output power as
programmed on par. “St.P” for the time programmed on par. “SSt”
or when is reached the absolute value programmed at par. “HSEt”.
Practically, the instrument works in manual condition and switches
to automatic control at the elapsing of time “SSt” or when is
reached the absolute value programmed at par. “HSEt”.
To disable the Soft-Start function simply program par. “SSt” = OFF.
Whenever, a measurement errors occurs during the Soft-Start
execution, the function is interrupted and the instrument gives an
output power as programmed on par. “OPE”.
If the measurement is restored, the Soft-Start is still deactivated.
If it’s desired to activate the Autotuning with Soft-Start set par.
“Auto”=4.
The Autotuning will start automatically at the end of programmed
Soft-Start cycle at the condition that the process value is lower (with
“Func” =HEAt) than [SP- |SP/5|] or higher (with “Func” =CooL) than
[SP+ |SP/5|].
4.10 - ALARMS OUTPUTS FUNCTIONS (AL1, AL2)
The alarms (AL1, AL2) are depending on the process value and
before to set his functioning it’s necessary to establish to which
output the alarm has to correspond to.
First of all it’s necessary to configure, in the parameters group
“
]
Out”,
the parameters relative to the outputs required as alarm
(“O1F” , “O2F”) programming the parameter relative to the desired
output as follows :
= ALno
if the alarm output has to be ON when the alarm is active,
while it’s OFF when the alarm is not active
= ALnc
if the alarm output has to be ON when the alarm is not
active, while it’s OFF when the alarm is active
= ALni
if the alarm output has to be ON when the alarm is not
active, while it is OFF when the alarm is active but with reverse led
indication (led ON= alarm OFF).
Note:
In all the examples that follow is made reference to the alarm
AL1. Naturally the operation of the other alarms results analogous.
Have now access at the group
“
]
AL1”,
and program on par.
“OAL1”
, to which output the alarm signal has to be sent.
The alarm functioning is instead defined by parameters :
"AL1t "
- ALARM TYPE
"Ab1"
- ALARM CONFIGURATION
“AL1”
- ALARM THRESHOLD
“AL1L”
- LOW ALARM THRESHOLD (for band alarm) OR
MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high
alarm)
“AL1H”
- HIGH ALARM THRESHOLD (for band alarm) OR
MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high
alarm)
“HAL1” -
ALARM HYSTERESIS
“AL1d”
- ALARM ACTIVATION DELAY (in sec.)
"AL1i"
- ALARM BEHAVIOUR IN THE EVENT OF
MEASUREMENT ERROR
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 7

"AL1t" – ALARM TYPE :
the alarm output can behave in six
different ways.
LoAb
= ABSOLUTE LOW ALARM: The alarm is activated when the
process value goes below the alarm threshold set on parameter
"AL1” and will be deactivated when it goes above the value
[AL1+HAL1].
With this mode is possible to program the minimum and the
maximum set of “AL1” by “AL1L” and “AL1H” parameters.
HiAb
= ABSOLUTE HIGH ALARM: The alarm is activated when the
process value goes higher than the alarm threshold set on
parameter "AL1" and will be deactivated when it goes below the
value [AL1 - HAL1].
With this mode is possible to program the minimum and the
maximum set of “AL1” by “AL1L” and “AL1H” parameters.
LoAb
off
ON
AL1
AL1
PV
HiAb
HAL1
time
off
ON
AL1
PV
time
HAL1
off
off
ON
OUT
off
off
ON
OUT
AL1
LodE
= DEVIATION LOW ALARM: The alarm is activated when the
process value goes below the value [SP + AL1] and will be
deactivated when it goes above the value [SP + AL1 + HAL1].
With this mode is possible to program the minimum and the
maximum set of “AL1” by “AL1L” and “AL1H” parameters.
HidE
= DEVIATION HIGH ALARM: The alarm is activated when the
process value goes above the value [SP + AL1] and will be
deactivated when it goes below the value [SP + AL1 - HAL1].
With this mode is possible to program the minimum and the
maximum set of “AL1” by “AL1L” and “AL1H” parameters.
LodE
ON
off
PV
SP
-AL1
HAL1
time
off
ON
SP
AL1
PV
HidE
time
HAL1
ON
off
off
off
off
ON
OUT
AL1
OUT
AL1
LHAb
= ABSOLUTE BAND ALARM: The alarm is activated when
the process value goes under the alarm threshold set on parameter
"AL1L" or goes higher than the alarm threshold set on parameter
"AL1H" and will be deactivated when it goes below the value [AL1H
- HAL1] or when it goes above the value [AL1L + HAL1].
LHdE
= DEVIATION BAND ALARM: The alarm is activated when
the process value goes below the value [SP + AL1L] or goes above
than the value [SP + AL1H] and will be deactivated when it goes
below the value [SP + AL1H - HAL1] or when it goes above the
value [SP + AL1L + HAL1].
LHAb
ON
off
AL1H
AL1L
PV
ON
time
off
HAL1
HAL1
SP
- AL1L
AL1H
PV
time
LHdE
HAL1
HAL1
off
off
ON
ON
off
off
OUT
AL1
OUT
AL1
"
Ab1" - ALARM CONFIGURATION:
This parameter can assume a
value between 0 and 31.
The number to be set, which will correspond to the function desired,
is obtained by adding the values reported in the following
descriptions :
ALARM BEHAVIOUR AT SWITCH ON: the alarm output may
behave in two different ways, depending on the value added to par.
“Ab1”.
+0 = NORMAL BEHAVIOUR: The alarm is always activated when
there are alarm conditions.
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched
on, the instrument is in alarm condition, the alarm is not activated. It
will be activated only when the process value is in non-alarm
conditions and then back in alarm conditions.
P V
+ 1
+ 0
t i m e
A L 1
O N
O N
O N
o f f
o f f
o f f
o f f
A b 1
exemple with absolute low alarm
ALARM DELAY: the alarm output may behave in two different
ways depending on the value added to par. “Ab1”.
+0 = ALARM NOT DELAYED: The alarm is immediately activated
when the alarm condition occurs.
+2 = ALARM DELAYED: When the alarm condition occurs, delay
counting begins, as programmed on par. “AL1d” (expressed in
sec.) and the alarm will be activated only after the elapsing of that
time.
ALARM LATCH: : the alarm output may behave in two different
ways depending on the value added to par. “Ab1”.
+ 0 = ALARM NOT LATCHED: The alarm remains active in alarm
conditions only.
+ 4 = ALARM LATCHED: The alarm is active in alarm conditions
and remains active even when these conditions no longer exist,
until the correctly programmed key “U”, (“USrb”=Aac) has been
pushed.
A L 1
P V
O N
O N
t i m e
+ 0
A b 1
+ 4
o f f
o f f
o f f
exemple with absolute high alarm
ALARM AKNOWLEDGEMENT: : the alarm output may behave in
two different ways depending on the value added to par. “Ab1”.
+ 0 = ALARM NOT AKNOWLEDGED: The alarm always remains
active in alarm conditions.
+ 8 = ALARM AKNOWLEDGED: The alarm is active in alarm
conditions and can be deactivated by key “U” if properly
programmed (“USrb”=ASi), and also if alarm conditions still exist.
ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION
ALARMS ONLY): the alarm output may behave in two different
ways, depending on the value added to par. “Ab1”.
+0 = NORMAL BEHAVIOUR: The alarm is always activated when
there are alarm conditions.
+16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,
when Set Point change, the instrument is in alarm condition, the
alarm is not activated. It will be activated only when the process
value is in non-alarm conditions and then back in alarm conditions.
"AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
ERROR:
This allows one to establish how the alarm have behave
in the event of a measurement error (yES=alarm active; no=alarm
deactivated).
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 8

4.11 - LOOP BREAK ALARM FUNCTION
All the parameters referring to the Loop Break alarm function are
contained in the group
“
]
LbA”.
The Loop Break alarm is available on all the instruments, which
intervenes when, for any reason (short-circuit of a thermocouple,
thermocouple inversion, load interruption), the loop control is
interrupted.
First of all, it is necessary to establish to which output the alarm has
to correspond.
To do this it is necessary to set the parameter relative to the output
to be used
(“O1F” , “O2F”) in the group
“
]
Out”,
programming the
parameter as :
= ALno
if the alarm output has to be ON when the alarm is active
while it is OFF when the alarm is not active.
= ALnc
if the alarm output has to be ON when the alarm is not
active while it is OFF when the alarm is active.
= ALni
if the alarm output has to be ON when the alarm is not
active, while it is OFF when the alarm is active but with reverse led
indication (led ON= alarm OFF).
Enter group
“
]
LbA”
and program which output the alarm signal
has to be addressed to on par.
“OLbA”
,.
The Loop Break alarm is activated if the output power remains at
the 100% of the value for the time programmed on par.
"LbAt"
(expressed in sec.).
To avoid false alarms, the value of this parameter has to be set
considering the time the plant takes to reach the Set point when the
measured value is a long distance from it (for example at the plant
start-up).
On alarm intervention, the instrument visualizes the message
“LbA”
and behaves as in the case of a measurement error giving a
power output as programmed on par.
“OPE”
(programmable in the
group
“
]
InP”)
.
To restore normal functioning after the alarm, select the control
mode “OFF” and then re-program the automatic control (“rEG”)
after checking the correct functioning of probe and actuator.
To exclude the Loop Break alarm, set “OLbA” = OFF.
4.12 - FUNCTIONING OF KEY “U”
The function of key “U” can be set through par.
“USrb”
contained
in the group “
“
]
PAn”.
The parameter can be programmed as :
= noF
: no function
= tunE
: Pushing the key for 1 sec. at least, it is possible to
activate/deactivate Auto-tuning or Self-tuning
= OPLO
: Pushing the key for 1 sec. at least, it is possible to swap
from automatic control (rEG) to manual one (OPLO) and vice versa.
= Aac
: Pushing the key for 1 sec. at least, it is possible to
acknowledge the alarm. (see par. 4.10)
= ASi
: Pushing the key for 1 sec. at least, it is possible to
acknowledge an active alarm (see par. 4.10)
= CHSP
: Pushing the key for 1 sec. at least, it is possible to select
one of the 4 pre-programmed Set Points on rotation.
= OFF
: Pushing the key for 1 sec. at least, it is possible to swap
from automatic control (rEG) to OFF control (OFF) and vice versa.
4.13 - PARAMETERS CONFIGURATION BY “KEY01”
The instrument is equipped with a connector that allows the transfer
from and toward the instrument of the functioning parameters
through the device
TECNOLOGIC KEY01
with
5 poles
connector.
This device it’s mainly useable for the serial programming of the
instruments which need to have the same parameters configuration
or to keep a copy of the programming of an instrument and allow its
rapid retransmission.
To use the device KEY01 it’s necessary that the device or
instrument are being supplied.
To transfer the configuration of an instrument into the device
(UPLOAD)
it is necessary to proceed in the following way:
1) position both dip switch of KEY 01 in the
OFF
mode.
2) connect the device to the instrument TLK plugging the special
connector.
3) verify that the instrument or the device are supplied
4) observe the indication led on the device KEY 01: if it results
green this means that a configuration is already loaded on the
device while if it results green blinking or red blinking this means
that it has not been loaded any valid configuration on the device .
5) press the button placed on the device.
6) observe the indication led : after having pressed the button, the
led becomes red and therefore, at the end of the data transfer, it
becomes green.
7) now it is possible to disconnect the device.
To transfer the configuration loaded on the device onto an
instrument of the same family
(DOWNLOAD)
, it is necessary to
proceed in the following way:
1) position both dip switch of KEY 01 in the
ON
mode.
2) connect the device to an instrument TLK having the same
features of the one from which has been downloaded the desired
configuration, plugging the special connector.
3) verify that the instrument or the device are supplied
4) observe the indication led on the device KEY 01: it has to result
green, because if the led results green blinking or red blinking, this
means that on the device it has not been downloaded any valid
configuration and therefore it’s useless to continue.
5) if the les results green, press the button placed on the device.
6) observe the indication led : after having pressed the button, the
led becomes red and therefore, at the end of the data transfer, it
becomes green.
7) now it is possible to disconnect the device.
Instrument supplied and device not supplied
SUPPLY
Instrument supplied from the device
SUPPLY ADAPTER
12 VDC
AC SUPPLY
For additional info, please have a look at the KEY01 instruction
manual.
5 - PROGRAMMABLE PARAMETERS
Here following are described all the parameters available on the
instrument. Some of them could be not present or because they are
depending on the type of instrument or because they are
automatically disabled as unnecessary.
Group “
]
SP”
(parameters relative to the Set Point)
9999
SPLL ÷ 9999
High Set Point
SPHL
8
-1999
-1999 ÷ SPHL
Low Set Point
SPLL
7
0
SPLL ÷ SPHL
Set Point 4
SP4
6
0
SPLL ÷ SPHL
Set Point 3
SP3
5
0
SPLL ÷ SPHL
Set Point 2
SP2
4
0
SPLL ÷ SPHL
Set Point 1
SP1
3
1
1 ÷ nSP
Active Set point
SPAt
2
1
1 ÷ 4
Number of the
programmable Set
point
nSP
1
Note
Def.
Range
Description
Par.
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 9

Group “
]
InP”
(parameters relative to the measure input)
0
-100 ÷ 100
%
Output power in case of
measuring error
OPE
18
OUr
OUr / Or / Ur
“OPE” functioning in
case of measuring error
OUr = Over and
under-range
Or = Over-range only
Ur = Under-range only
InE
17
1.000
0.000 ÷ 2.000
Rotation of the
measuring straight line
rot
16
0
-1999 ÷ 9999
Measuring Offset
OFSt
15
1.0
0FF÷ 20.0
sec.
Input digital filter
FiL
14
°C
°C / °F
Temperature unit of
measurement
Unit
13
0
Pt1 / Ptc / ntc:
0 / 1
norm sig.:
0 ÷ 3
Number of decimal
figures
dP
12
100
SSC ÷ 9999
High scale limit input
with V / I signals
FSC
11
0
-1999 ÷ FSC
Low scale limit input
with V / I signals
SSC
10
J
Ptc
4.20
0.10
input C :
J / CrAL / S /
Ir.J / Ir.CA /
Pt1 / 0.50 /
0.60 / 12.60
input E :
J / CrAL / S /
Ir.J / Ir.CA /
Ptc / ntc /
0.50 / 0.60 /
12.60
input I :
0.20 / 4.20
input V :
0.1 /
0.5 / 1.5 /
0.10 / 2.10
Probe type:
J= thermocoupled J
CrAL= termocoupled K
S= thermocoupled S
Ir.J=Infrared Sen. IRS J
Ir.CA= Infrared Sen.
IRS K
Pt1= thermores. Pt100
0.50= 0..50 mV
0.60= 0..60 mV
12.60= 12..60 mV
Ptc= thermistor PTC
KTY81-121
ntc= thermistor NTC
103-AT2
0.20= 0..20 mA
4.20= 4..20 mA
0.1= 0..1 V
0.5=0..5 V
1.5= 1..5 V
0.10= 0..10 V
2.10= 2..10 V
SEnS
9
Note
Def.
Range
Description
Par.
Group“
]
Out”
(parameters relative to the outputs)
ALno
1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
Functioning of output 2:
see “O1F”
O2F
20
1.rEG
1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
Functioning of output 1:
1.rEG= Control output 1
2.rEG= Control output 2
ALno= Alarm Out
normally opened
ALnc= Alarm Out
normally closed
ALni= Alarm Out
normally closed with
reverse led func.
O1F
19
Note
Def.
Range
Description
Par.
Group “
]
AL1”
(parameters relative to alarm AL1)
LoAb
LoAb / HiAb
LHAb / LodE
HidE / LHdE
Alarm AL1 type:
LoAb= Absolute Low
HiAb= Absolute High
LHAb= Absolute Band
LodE= Deviation Low
HidE= Deviation High
LHdE= Deviation Band
AL1t
23
Out2
Out1 / Out2 /
OFF
Output where alarm
AL1 is addressed
OAL1
22
Note
Def.
Range
Description
Par.
no
no / yES
Alarm AL1 activation in
case of measuring error
AL1i
30
OFF
OFF ÷ 9999
sec.
Activation delay of
alarm AL1
AL1d
29
1
OFF ÷ 9999
Alarm AL1 hysteresis
HAL1
28
9999
AL1L ÷ 9999
High threshold band
alarm AL1 or Maximum
set alarm AL1 for high
or low alarm
AL1H
27
-1999
-1999 ÷ AL1H
Low threshold band
alarm AL1 or Minimum
set alarm AL1 for high
or low alarm
AL1L
26
0
AL1L÷ AL1H
Alarm AL1 threshold
AL1
25
0
0 ÷ 31
Alarm AL1 functioning:
+1 = not activated at
power on
+2 = delayed
+4 = latch
+8 = aknowledged
+16 = not activated at
Set change (Dev. Al.)
Ab1
24
Group “
]
AL2”
(parameters relative to alarm AL2)
no
no / yES
Alarm AL2 activation in
case of measuring error
AL2i
39
OFF
OFF ÷ 9999
sec.
Activation delay of
alarm AL2
AL2d
38
1
OFF ÷ 9999
Alarm AL2 hysteresis
HAL2
37
9999
AL2L ÷ 9999
High threshold band
alarm AL2 or Maximum
set alarm AL2 for high
or low alarm
AL2H
36
-1999
-1999 ÷ AL2H
Low threshold band
alarm AL2 or Minimum
set alarm AL2 for high
or low alarm
AL2L
35
0
AL2L÷ AL2H
Alarm AL2 threshold
AL2
34
0
0 ÷ 31
Alarm AL2 functioning:
see “Ab1”
Ab2
33
LoAb
LoAb / HiAb
LHAb / LodE
HidE / LHdE
Alarm AL2 type:
see “AL1t”
AL2t
32
OFF
Out1 / Out2 /
OFF
Output where alarm
AL2 is addressed
OAL2
31
Note
Def.
Range
Description
Par.
Group “
]
LbA”
(parameters relative to Loop Break Alarm)
OFF
OFF ÷ 9999
sec.
Time necessary to
activate alarm LbA
LbAt
41
OFF
Out1 / Out2 /
OFF
Output where alarm
LbA is addressed
OLbA
40
Note
Def.
Range
Description
Par.
Group “
]
rEG”
(parameters relative to the control)
OFF
OFF÷ 9999
sec.
Compressor Protection
time for 2.rEG
CPdt
45
1
0 ÷ 9999
Hysteresis of ON/OFF
control (or end Soft
Start cycle threshold)
HSEt
44
HEAt
HEAt / CooL
Functioning mode
output 1.rEG
Func
43
Pid
Pid / On.FA
On.FS / nr
Control type:
Pid= PID
On.FA= ON/OFF asym.
On.FS= ON/OFF sym.
nr= Neutral Zone
ON/OFF
Cont
42
Note
Def.
Range
Description
Par.
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 10

OFF
OFF/0.1÷7.59
/ InF hrs.-min.
Soft-Start time
SSt
60
0
-100 ÷ 100 %
Soft-Start power
St.P
59
InF
0.00 ÷ 99.99
/ InF
unit / min.
Gradient of second
ramp:
InF= Ramp not active
SLoF
58
InF
0.00 ÷ 99.59
/ InF
hrs.-min.
Duration time between
two ramps
InF= Time not active
dur.t
57
InF
0.00 ÷ 99.99
/ InF unit/min.
Gradient of first ramp :
InF= Ramp not active
SLor
56
0.0
-100.0÷100.0
%
Manual reset
rS
55
10.0
0.1 ÷ 130.0
sec.
Cycle time of 2.rEG
tcr2
54
1.00
0.01 ÷ 99.99
Power ratio 2.rEg /
1.rEG
Prat
53
20.0
0.1 ÷ 130.0
sec.
Cycle time of output
1.rEG
tcr1
52
0.5
0.00 ÷ 2.00
Fuzzy overshoot control
FuOc
51
50
OFF÷ 9999
sec.
Derivative time
dEr
50
200
OFF ÷ 9999
sec.
Integral time
Int
49
50
0 ÷ 9999
Proportional band
Pb
48
no
no / yES
Selftuning enable
SELF
47
2
OFF /
1 / 2 / 3 / 4
Autotuning Fast enable
OFF = Not active
1 = Start each power on
2= Start at first power
on
3= Start manually
4= Start after Soft Start
or change Set Point
Auto
46
Group “
]
PAn”
(parameters relative to the user interface)
SAE
SE / AE /
SAE / SAnE
Set Fast program.:
SE= Active Set can be
modified while the
alarm thresholds
cannot be modified
AE= Active Set cannot
be modified while the
alarm thresholds can
be modified
SAE= Active Set and
alarm thresholds can
be modified
SAnE= Active Set and
alarm thresholds
cannot be modified
Edit
64
2
OFF...9999
Shift value for the shift
index functioning
AdE
63
dEF
dEF / Pou /
SP.F / SP.o /
AL1 / AL2
Variable visualized on
the display:
dEF= Process Value
Pou= Control Power
SP.F= Active Set
SP.o = Operative Set
AL1 = AL1 threshold
AL2 = AL2 threshold
diSP
62
noF
noF / tunE /
OPLO / Aac /
ASi / CHSP /
OFF
Functioning of key “U” :
noF = No Function
tune= Start Autotuning
or Selftuning
OPLO= Manual Control
(open loop)
Aac= Reset Alarms
latch
ASi= Aknowledged
Alarms
OFF= Control OFF
USrb
61
Note
Def.
Range
Description
Par.
6 - PROBLEMS, MAINTENANCE AND GUARANTEE
6.1 - ERROR SIGNALLING
Push key “P”
Possible anomaly of
the EEPROM memory
ErEP
Check the working of
probe and actuator and
swap the instrument to
(rEG) control
Loop control
interrupted
(Loop break alarm)
LbA
Check the functioning of
probe and actuator and try
to repeat the auto-tuning.
Auto-tuning not
finished within 12
hours
noAt
Push key “P” in order to
make the error message
disappear. Once the error
has been found, try to
repeat the auto-tuning.
Auto-tuning not
possible because the
process value is too
higher or too lower
ErAt
The measured variable
is over the probe’s
limits (over-range)
oooo
The measured variable
is under the probe’s
limits (under-range)
uuuu
Verify the correct
connection between probe
and instrument and then
verify the correct
functioning of the probe
Probe interrupted
- - - -
Action
Reason
Error
In error conditions, the instrument provides an output power as
programmed on par. “OPE” and activates the desired alarms, if the
relative parameters “ALni” have been programmed = yES.
6.2 - CLEANING
We recommend cleaning of the instrument with a slightly wet cloth
using water and not abrasive cleaners or solvents which may
damage the instrument.
6.3 - GUARANTEE AND REPAIRS
The instrument is under warranty against manufacturing flaws or
faulty material, that are found within 12 months from delivery date.
The guarantee is limited to repairs or to the replacement of the
instrument. The eventual opening of the housing, the violation of
the instrument or the improper use and installation of the product
will bring about the immediate withdrawal of the warranty’s effects.
In the event of a faulty instrument, either within the period of
warranty, or further to its expiry, please contact our sales
department to obtain authorisation for sending the instrument to
our company. The faulty product must be shipped to TECNOLOGIC
with a detailed description of the faults found, without any fees or
charge for Tecnologic, except in the event of alternative
agreements.
7 - TECHNICAL DATA
7.1 - ELECTRICAL DATA
Power supply: 12 VAC/VDC, 24 VAC/VDC, 100.. 240 VAC +/- 10%
Frequency AC: 50/60 Hz
Power consumption: 4 VA approx.
Input/s: 1 input for temperature probes: tc J,K,S ; infrared sensors
TECNOLOGIC IRS J e K; RTD Pt 100 IEC; PTC KTY 81-121 (990
Ω
@ 25 °C); NTC 103AT-2 (10K
Ω
@ 25 °C) or mV signals 0...50
mV, 0...60 mV, 12 ...60 mV or normalized signals 0/4...20 mA, 0..1
V, 0/1...5 V , 0/2...10 V.
Normalized signals input impedance: 0/4..20 mA: 51
Ω
; mV and
V: 1 M
Ω
Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 250
VAC) ; or in tension to drive SSR (8mA/ 8VDC).
Auxiliary supply output: 10 VDC / 20 mA Max.
Electrical life for relay outputs: 100000 operat.
Installation category: II
Measurement category: I
Protection class against electric shock: Class II for Front panel
Insulation:
Reinforced insulation between the low voltage part
(power supply 115 / 230 V and relay outputs) and front panel;
Reinforced insulation between the low voltage section (Supply 115 /
230 V and relay outputs) and the extra low voltage section (input,
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 11

SSR outputs); Reinforced between power supply and relay; No
insulation between supply 12 V and input.
No insulation between
input and SSR outputs.
7.2 - MECHANICAL DATA
Housing: Self-extinguishing plastic, UL 94 V0
Dimensions: 33 x 75 mm, depth 64 mm
Weight: 110 g approx.
Mounting: Flush in panel in 29 x 71 mm hole
Connections: 2,5 mm
2
screw terminals block
Degree of front panel protection : IP 65 mounted in panel with
gasket
Pollution situation: 2
Operating temperature: 0 ... 50 °C
Operating humidity: 30 ... 95 RH% without condensation
Storage temperature: -10 ... +60 °C
7.3 - MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING [mm]
TLK 38
75
33
5
64
28
ST
AT
OUT2
+
=
-
OUT1
RECOMMENDED
PANEL CUTOUT
29
71
min. 15 mm
m
in.
12
m
m
TYPE 1
PANEL
+
G
ASKET
PANEL
+
G
ASKET
T
YPE 2
BRACKET
TYPE 1
BRACKETS
TYPE 2
86
74
43
31
34
MA
X
12
m
m
MA
X
29
m
m
7.4 - FUNCTIONAL FEATURES
Control: ON/OFF, ON/OFF Neutral Zone, PID single Action, PID
double action.
Measurement range: according to the used probe (see range table)
Display resolution: according to the probe used 1/0,1/0,01/0,001
Overall accuracy: +/- 0,5 % fs (tc S: +/- 1 % fs)
Sampling rate: 130 ms.
Display: 4 Digit Red h 12 mm
Compliance: ECC directive EMC 2004/108/CE (EN 61326), ECC
directive LV 2006/95/CE (EN 61010-1)
Approvals: C-UL (file n. E206847)
7.5 - MEASURING RANGE TABLE
2 ... 10 V
“SEnS” = 2.10
0 ... 10 V
“SEnS” = 0.10
1 ... 5 V
“SEnS” = 1.5
0 ... 5 V
“SEnS” = 0.5
0 ... 1 V
“SEnS” = 0.1
12 ... 60 mV
“SEnS” = 12.60
0 ... 60 mV
“SEnS” = 0.60
0 ... 50 mV
“SEnS” = 0.50
4..20 mA
“SEnS” = 4.20
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
-1999 ... 9999
0..20 mA
“SEnS” = 0.20
-50.0 ... 110.0 °C
-58.0 ... 230.0 °F
-50 ... 110 °C
-58 ... 230 °F
NTC (103-AT2)
“SEnS” = ntc
-55.0 ... 150.0 °C
-67.0 ...302.0 °F
-55 ... 150 °C
-67 ... 302 °F
PTC (KTY81-121)
“SEnS” = Ptc
-199.9 ... 850.0 °C
-199.9 ... 999.9 °F
-200 ... 850 °C
-328 ... 1562 °F
Pt100 (IEC)
“SEnS” = Pt1
- - - -
0 ... 1760 °C
32 ... 3200 °F
tc S
“SEnS” = S
- - - -
0 ... 1370 °C
32 ... 2498 °F
tc K
“SEnS” = CrAl
- - - -
0 ... 1000 °C
32 ... 1832 °F
tc J
“SEnS” = J
“dP”= 1, 2, 3
“dP” = 0
INPUT
7.6 – INSTRUMENT ORDERING CODE
TLK38 a b c d ee f
a : POWER SUPPLY
F
=
12 VAC/VDC
L
= 24 VAC/VDC
H
= 100... 240 VAC
b : INPUT
C
= thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100)
E
= thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC)
I
= normalized signals 0/4..20 mA
V
= normalized signals 0..1 V, 0/1..5 V, 0/2..10 V.
c : OUTPUT OUT1
R
= Relay
O
= VDC for SSR
d : OUTPUT OUT2
R
= Relay
O
= VDC for SSR
-
= None
ee: SPECIAL CODES
f: SPECIAL VERSIONS
TLK 38 PASSWORD = 381
TECNOLOGIC spa - TLK 38
- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 12