PDF User Manual

  1. Home
  2. Manuals
  3. Tecno Control TS236 User Instructions

Tecno Control TS236 User Instructions

TS237

Made by: Tecno Control
Type: User Instructions
Category: Oxygen Equipment
Pages: 4
Size: 0.19 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

 
 

 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02/26922890 - Fax 02/2133734 

http:

 

www.tecnocontrol.it

  

e-mail:

 

info@tecnocontrol.it

 

 

EN

 

 

 

IST-2236.ZO01.02/A 

File: IST-2236.ZO01.02-A_TS236-TS237 (EN).doc 

 
 

OXYGEN 

TRANSMITTER 

 
 
 

TS236 

flue gases temperature up to 300°C 

 
 

TS237 

flue gases temperature up to 600°C 

 
 
 
 
 

USER INSTRUCTIONS 

 

 


background image

IST-2236.ZO01.02/A 

User Instructions 

Page 2/4 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02/26922890 - Fax 02/2133734 

 

CONTENTS 

 

TECHNICAL CHARACTERISTICS ............................................................ 2

 

O

 ZIRCONIUM OXIDE SENSOR (TS236 Probe) ........................................................ 2

 

SERVICE ................................................................................................... 2

 

DESCRIPTION ........................................................................................... 2

 

INSTALLATION ......................................................................................... 3

 

EXTERNAL CONNECTIONS .................................................................... 3

 

UNIT USE .................................................................................................. 4

 

SERVICE INSPECTIONS .......................................................................... 4

 

O

SENSOR CALIBRATION CHECK ............................................................................. 4

 

PROBE BODY CLEANING ............................................................................................ 4

 

 

TECHNICAL CHARACTERISTICS 

 

O

 ZIRCONIUM OXIDE SENSOR (TS236 Probe) 

 

Power Supply: 

230 Vac 

 

Output: 

4÷20 mA (0-25% O

2

 

Measuring range: 

0-25% 

 

Resolution: 

0.1% 

 

Calibration: 

automatic 

 

Working Temperature: 

Probe 0 / +800°C 

 

 

TS236 - Standard Probe Body 300°C 

 

 

TS237 High Temperature Probe Body 600°C 

 

Response Timing T

90

< 10 seconds 

 

Repeatability: 

1% on signal 

 

Medium Life: 

>160.000 Hours 

 

 

SERVICE 

 

We  suggest  to  allow  service  inspections  only  to  trained  and  qualified  people, 
especially for sensors test and calibration. 

 

On  demand  TECNOCONTROL  is  able  to  offer  programmed  service  agreements  each 
six months (beginning and half season) or once a year depending on the type of boiler 
and its use. 
The  service  normally  includes  functioning  tests  of  the  unit,  test  and  calibration  of 
Oxygen sensor, replacement (when necessary) of O

2

 sensor.

 

 

Documento / Document name:

 

IST-2236.ZO01.02-A_TS236-TS237 (EN).doc

 

Oggetto / Subject :

 

TS236-TS237 (EN)

 

Rev. 

Data / Date 

Da / By 

Note 

07/05/2007 

UT/FG 

Aggiunta Intestazione Sonda TS237 

 

 

 

 

 

 

 

 

 

 


background image

IST-2236.ZO01.02/A 

User Instructions 

Page 3/4 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02/26922890 - Fax 02/2133734 

DESCRIPTION 

The transmitter is used for measuring Oxygen (O

2

) concentration into flue gases. 

TS236

 model is supplied with a standard Probe Body supporting flue gases temperature up to 300°C. 

TS237

 model is supplied with a standard Probe Body supporting flue gases temperature up to 600°C. 

Consider that this instrument has not been designed as a security control system, therefore, if used for 
the  control  of  air  as  supporter  of  combustion,  you  need  all  possible  measures  to  avoid  danger 
situations or whole plant stop in case of its fault.   

The Oxygen Transmitter is composed by aluminium housing with dimensions 210 x 110 x 120 mm with 
protection range IP55. Inside the housing there are: the power supply circuit, the oxygen concentration 
measuring  circuit  and  the  terminals  for  the  external  connections.  The  probe  is  connected  to  the 
housing by 1 meter cable.  

INSTALLATION 

The Oxygen Transmitter unit has to be installed near the boiler to analyze. The Oxygen probe has to 
be placed on the chimney pipe fitting to a distance equivalent to two diameters of the pipe fitting itself. 
The distance between the probe and the housing is bound by the 1 meter cable connection. 

 

230Vac 

TS236 Oxygen PROBE

 

 

If  the  chimney  pipe  fitting  is  too  short,  you  can  fix  the  probe  directly  on  the  chimney  to  a  distance 
equivalent to two diameters of itself from the connection to the pipe fitting.  

 

230Vac 

TS236 Oxygen PROBE

 

 

EXTERNAL CONNECTIONS 

Connections to the Oxygen Transmitter terminal are for the power supply and for the 4÷20mA Output. 

TS236 Oxygen (O

2

) Probe Power Supply 

Terminal  Connection 

Cable 

Connect to "L" 230V of TS236 Oxygen Probe 

Black 1,5 mm

2

 

Ground Terminal 

Yellow/Green1,5 mm

2

 

Connect to "N" 230V of TS236 Oxygen Probe 

Blue 1,5 mm

2

 

"-" 4÷20mA of TS236 Oxygen O

Probe  

2 x 0,75 mm

2

  

"+" 4÷20mA of TS236 Oxygen O

Probe 

Shielded 

 

 


background image

IST-2236.ZO01.02/A 

User Instructions 

Page 4/4 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02/26922890 - Fax 02/2133734 

 

Alluminium Housing 

Power Supply 

230V-50Hz -22 VA 

Output 

4÷20mA 

Fuse 1A 

-  + 

Cable L = 1 meter 

Flue gases direction

Male Screw  thread 1”½

 

Fixing dowel 

TS236 Oxygen Probe 

Probe Body max.300°C 

length 400mm 

Installed in the Chimney 

 

TS236 Probe is supplied with a standard Probe Body supporting flue gases temperature up to 300°C. 
On demand it is available another one up to 600°C (See Drawing below) 

 

1 meter Length Cable

Flue gases direction 

Fixing Dowel 

Probe Body 600°C  

Length 400mm 

Installed in the Chimney 

Flange DN40 - UNI 6091 

 

UNIT USE 

Oxygen  Transmitter  Unit,  when switched on, needs about 30÷40 seconds to stabilize. After this time, 
the  probe  (automatically  calibrated)  is  able  to  start  measuring  Oxygen  concentration  into  the  flue 
gases. 

SERVICE INSPECTIONS 

O

SENSOR CALIBRATION CHECK  

Oxygen Sensor automatically calibrates itself; to check the O

sensor calibration it is necessary: 

  Unthread the Probe Body from the chimney. 

  Verify  that  after  1-3  minutes  in  clean  air,  the  output  is  about  20mA  that  correspond  to  20,9% 

Oxygen. In case you don’t see this value turn the 

SPAN

 trimmer of the O

2

 transmitter circuit (Placed 

inside the aluminium housing) up to obtain the right value (20mA). 

Check and/or calibration for the “

ZERO

” point: 

  With a gas bottle at a know Oxygen concentration (about 2% O

2

). 

  Give gas to the sensor (TECNOCONTROL Service Department uses a particular connector). After 

1÷3 minutes, necessary to stabilize the sensor, turn the 

ZERO 

trimmer on the O

2

 transmitter circuit 

up to obtain the mA value correspondant to the used concentration bottle (example: if the certificate 
of the bottle says O

2

 at 2,0% the correspondant mA value has to be about: 

,6mA

5

 

4

 

2,0)

 x 

20

16

(

=

+

 

PROBE BODY CLEANING 

Periodically, at least once a year, unthread the Probe Body from the Chimney and check that it is clean 
and  that  the  holes  are  not  obstructed  by  combustion  residual,  if  necessary  clean  it  blowing  with 
compressed air.