Techno-Matic A/S 
Granlidevej 22, Hornum 
DK-9600 Aars 
Denmark 

Tel: +45 96987711 

Fax: +45 98661822 

tm@techno-matic.dk

www.techno-matic.dk

 

 

START

STOP

Mode: Running

>Temperature        65.0 C
 O2                  8.0%
 Setting

o

 

 
 
 
 

TM3006 Technical Manual 

Revision: 

7.95rev.3 

 
 
 
 
 

TABLE OF CONTENTS 

 
Table of Contents .............................................................................................................................................. 1

 

Important notes .................................................................................................................................................. 2

 

1

 

Transient Protection.............................................................................................................................. 2

 

2

 

Power Current Connections ................................................................................................................. 2

 

3

 

Sensor Connections..............................................................................................................................2

 

4

 

The Print ............................................................................................................................................... 3

 

5

 

Connecting the TM3006 ....................................................................................................................... 4

 

 

 


background image

TM3006 TECHNICAL MANUAL 

© Techno-Matic A/S 

Side 2

 

Important notes 

This documentation has been made solely to serve as an aid to the stoker producer to describe his 
product.  Techno-Matic  A/S  does  not  issue  any  warranty  that  this  documentation  fulfils  or  satisfies 
the  national  or  international  demands  for  documenting  the  product  since  this  is  the  duty  of  the 
individual  stoker  producer.  However,  Techno-Matic  A/S  will  be  thankful  for  any  comment  or  advice 
that may help to improve this manual. 
 
Please  note:  You  must  always  turn  off  the  power  supply  before  actually  touching  anything  in  the 
system  in  order  to  avoid  dangerous  situations.  Only  persons  with  permission  from  the  stoker 
producer  and  with  an  authorization  in  accordance  with  the  national  legislation  must  carry  out  any 
interventions/repairs in the installations. 

1  TRANSIENT PROTECTION 

In  order  to  secure  the  controller  against  interference,  relays  and  solenoid  valves  should  be  transient 
protected. (DC relays and solenoid valves with diodes and AC relays and solenoid valves with RC filter). 

2  POWER CURRENT CONNECTIONS 

IMPORTANT:  
Always prefuse the system with maximum 10A prefuses.  
Always make sure not to exceed the maximum limit of the total load on the outputs.  
Unused cable glands must be filled out and all cable glands must be tighten with an open ring wrench.  
The main supply cords must not exceed 1,5 mm2  
Supply 

 

 

Terminal Main supply  N 

L3 
L2 
L1 

Supply for system 

230VAC  (L1)  or  400VAC.  Remember  ALWAYS 
to connect N. 
Maximum prefuse 10A 

Power Current Output 

 

Maximum total load on all outputs 2000W 

Terminal Stoker           N 

                                    W 

Connecting the Stoker Motor 

230VAC (U) Maximum load 550W 
Or 
400VAC. Maximum load 3*550W 

Terminal Blower       N 

Connecting the Blower Motor 

230VAC. Maximum load 550W 

Terminal                      N 
Ignition /Motor 2          U            

Connecting the Ignition Unit/ 
Motor 2 

230VAC. Maximum load 550W 

3  SENSOR CONNECTIONS 

Digital Inputs 

 

 

Terminals 1 & 11 

Function input 

On/off switch 

Terminals 2 & 12 

Function input 

On/off switch 

Terminals 3 & 13 

Function input 

On/off switch 

Terminals 4 & 14 

Hot boiler Thermostat 

 

Analogue Inputs 

 

 

Terminals 5 & 15 

Boiler Temperature Sensor 

NTC thermistor (12kOhm at 25 

°

C) 

Terminals 6 & 16 

Stoker Tube Temperature Sensor 

NTC thermistor (12kOhm at 25 

°

C) 

Terminals 7 & 17 

Photo Sensor  
Exhaust Gas Temperature Sensor  

Danfoss LDS 
PT1000 (6 mW) 

Terminals 8 & 18 

Oxygen Sensor 

Lambda probe 

Supply 

oxygen 

sensor 

 

 

Terminals 9 & 19 

Oxygen Sensor Heating Element 

12VAC  for  Heating  Element

.  Please  Note:  During 

the heating of the oxygen sensor, the supply for the 
computer will be gone for about 3 minutes!

 

Photo Sensor 

 

 

Terminals K & A 

Photo Sensor Transmitter 

K = 0V. DC.   A = 5 V. DC. 

Alarm Output 

 

 

Terminals k1 & k2 

Alarm Output 

Potential free output: Max. 1A. 
Max. 30 V. DC. 

 


background image

TM3006 TECHNICAL MANUAL 

© Techno-Matic A/S 

Side 3

 

4  THE PRINT 

 

 
Besides the terminals at the bottom of the print there are the following components/sockets: 
 

F1 

Fuse 63mA 

Fuse on primary side of transformer 

JP1  10-pol socket 

Program Updating Connection 

JP2  10-pol socket 

RS232 Connection 

JP3  4-pol socket 

Optional connector (Not in use) 

JP4  4-pol socket 

Optional connector (Not in use) 

J12  8-pol socket 

Keyboard (foil) 

K1 

Relay 

Hot Boiler Relay 

K2 

Relay 

Hot Boiler Relay 

K3 

Relay 

Alarm relay 

SR1  Solid State Relay 

Stoker 

SR2  Solid State Relay 

Stoker 

SR3  Solid State Relay 

Blower 

SR4  Solid State Relay 

Ignition/Motor 2 

TR 

230V/12V 

Transformer 

U3 

16-pol socket 

Display 

 
 
 
 
 
 
 
 
 
 
 
 

 


background image

TM3006 TECHNICAL MANUAL 

© Techno-Matic A/S 

Side 4

 

5  CONNECTING THE TM3006 BY 400 VAC 

 

6  CONNECTING THE TM3006 BY 230 VAC 

 

C62 

C62 

C62