PDF User Manual

  1. Home
  2. Manuals
  3. Technologic TLK 43 Operating Instructions Manual

Technologic TLK 43 Operating Instructions Manual

Made by: Technologic
Type: Operating Instructions
Category: Controller
Pages: 21
Size: 0.81 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 1

 

 

MICROPROCESSOR-BASED 

DIGITAL  

ELECTRONIC CONTROLLER

 

 

 

 

 

OPERATING INSTRUCTIONS

 

Vr. 02 (ENG) - cod.: ISTR 6267

 

 

TECNOLOGIC S.p.A.

 

 

VIA INDIPENDENZA 56

 

27029 VIGEVANO (PV) ITALY

 

TEL.:  +39 0381 69871 

FAX: +39 0381 698730

 

internet : http:\\www.tecnologic.it

 

e-mail: info@tecnologic.it 

 
 

FOREWORD

This manual contains the information necessary for the product to 
be installed correctly and also instructions for its maintenance and 
use; we therefore recommend that the utmost attention is paid to the 
following instructions.  
Though this manual has been issued with the greatest care, 
TECNOLOGIC S.p.A. will not take any responsibility deriving from 
its use.  
The same applies to each person or Company involved in the 
issuing of this manual.  
This document is the exclusive property of TECNOLOGIC S.p.A. 
which forbids any reproduction and divulgation , even in part, of the 
document, unless expressly authorized.  
TECNOLOGIC S.p.A. reserves the right to make any formal or 
functional changes at any moment and without  any notice. 

 

 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 2

 

INDEX 

1

 

INSTRUMENT DESCRIPTION

 

1.1 GENERAL 

DESCRIPTION 

1.2 

FRONT PANEL DESCRIPTION 

2

 

PROGRAMMING

 

2.1 

FAST PROGRAMMING OF THE SET POINT  

2.2  SELECTION OF CONTROL STATE AND PARAMETERS 

PROGRAMMING 

2.3 

PARAMETER PROGRAMMING LEVELS 

2.4 CONTROL 

STATES 

2.5 

ACTIVE SET POINT SELECTION 

3

 

INFORMATION ON INSTALLATION AND USE

 

3.1 PERMITTED 

USE 

3.2 MECHANICAL 

MOUNTING 

3.3 ELECTRICAL 

CONNECTIONS 

3.4 

ELECTRICAL WIRING DIAGRAM 

4

 

FUNCTIONS

 

4.1 

MEASURING AND VISUALIZATION 

4.2 OUTPUT 

CONFIGURATION 

4.3 ON/OFF 

CONTROL 

4.4 

NEUTRAL ZONE ON/OFF CONTROL 

4.5 

SINGLE ACTION PID CONTROL 

4.6 

DOUBLE ACTION PID CONTROL 

4.7  PID CONTROL FOR MOTORIZED ACTUATORS WITH 

TIME POSITIONING 

4.8 

AUTO-TUNING AND SELF-TUNING FUNCTIONS 

4.9 

CONTROL POWER LIMITATION 

4.10  LIMITATION OF THE CONTROL POWER VARIATION 

SPEED (MAXIMUM RATE OF RISE) 

4.11  SPLIT RANGE FUNCTION 
4.12  REACHING OF SET POINT AT CONTROLLED SPEED 

AND AUTOMATIC COMMUTATION BETWEEN TWO 
SET POINTS 

4.13 SOFT-START 

FUNCTION 

4.14 ALARM 

FUNCTIONS 

4.14.1  ALARM OUTPUT CONFIGURATION 
4.14.2 ALARM HYSTERESIS 

4.15  HEATER BREAK ALARM FUNCTION 
4.16  LOOP BREAK ALARM FUNCTION 
4.17  FUNCTION OF KEY “U” 
4.18 DIGITAL 

INPUT 

4.19  RS 485 SERIAL INTERFACE 
4.20  PARAMETERS CONFIGURATION BY KEY01 

5

 

PROGRAMMABLE PARAMETERS

 

5.1 PARAMETERS 

TABLE 

5.2 PARAMETERS 

DESCRIPTION 

6

 

PROBLEMS , MAINTENANCE AND GUARANTEE

 

6.1 ERROR 

WARNINGS 

6.2 CLEANING 
6.3 

GUARANTEE AND REPAIRS 

7

 

TECHNICAL DATA

 

7.1 ELECTRICAL 

DATA 

7.2 MECHANICAL 

DATA 

7.3  MECHANICAL DIMENSIONS, PANEL CUT-OUT AND 

MOUNTING 

7.4 FUNCTIONAL 

DATA 

7.5 

MEASURING RANGE TABLE 

7.6 

INSTRUMENT ORDERING CODES 

 

1 - INSTRUMENT DESCRIPTION 

 
1.1 – GENERAL DESCRIPTION

 

TLK 43  is a “single loop” digital microprocessor-based controller, 
with  ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual 
action (direct and reverse) control, PID for motorized actuators with 
time positioning control.  
The instrument is equipped with 

AUTO-TUNING FAST

 function, 

SELF-TUNING

 function and automatic calculation of the 

FUZZY 

OVERSHOOT CONTROL

 parameter for PID control. 

The PID control has a particular algorithm with 

TWO DEGREES OF 

FREEDOM 

that optimises the instrument’s features independently 

of the event of process disturbances and Set Point variations. 

Furthermore, the instrument allows for RS485 serial communication 
using MODBUS-RTU communication protocol and a transmission 
speed up to 38.400 baud.

 

The process value is visualized on 4 red displays, the Set value is 
visualized on 4 green displays while the outputs status is indicated 
by 4 leds.  
The instrument provides for the storage of 4 Set Points and can 
have up to 4 outputs : relay type or can drive solid state relays type 
(SSR), or it is also possible to have up to 2 analogue outputs.  
The input is programmable and accepts temperature probes 
(Thermocouples J,K,S,B,C,E,L,N,R,T; Thermo-resistances PT100, 
Thermistors PTC and NTC; Infrared sensors mod. TECNOLOGIC 
IRS) and normalized analogue signals (0/4..20 mA, 0/1..5 V, 0/2..10 
V, 0..50/60 mV, 12..60 mV).  
The instrument can be equipped with an input for the current 
transformer, working as a  Heater Break Alarm function and with a 
programmable digital input as an alternative to output OUT4. 
Other important available functions are: Loop-Break Alarm function, 
control power limitation, limitation of the variation speed of the 
control power, split-range, reaching of the Set Point at controlled 
speed, ramp and dwell function, Soft-Start function, parameters 
protection on different levels.

 

 

1.2 - 

 

FRONT PANEL DESCRIPTION

 

 

1 - Key P

 : This is used to access the programming parameters and 

to confirm selection. 

2 - Key DOWN

 : This is used to decrease the values to be set and 

to select the parameters. If the key is held down, the user returns to 
the previous programming level until he exits the programming 
mode. Outside the programming mode it permits visualisation of the 
current measured by the TAHB input, on the SV display.   

3 - Key UP

 : This is used to increase the values to be set and to 

select the parameters. If the key is held down, the user returns to 
the previous programming level until he exits the programming 
mode. Outside the programming mode it permits visualisation of the 
output control power, on the SV display.  

4 - Key U

 : This is a key with a function programmable by par. 

“USrb”. It can be set to : Activate Auto-tuning and Self-tuning 
functions, swap the instrument to manual control, silence the alarm, 
change the active Set Point, deactivate control.  

5 - Led OUT1 

: indicates the state of output OUT1 

 

6 - Led OUT2 

: indicates the state of output OUT2 

7 - Led OUT3 

: indicates the state of output OUT3 

8 - Led OUT4 

: indicates the state of output OUT4 

9 - Led SET 

: when flashing, it indicates access to the programming 

mode.  

10 - Led AT/ST 

:  indicates that the Self-tuning function is activated 

(light on) or that Auto-tuning (flashing ) is in progress.

 

11 – Display PV : 

normally indicates the process value 

12 - Display SV : 

normally indicates the active Set value, however it 

can be programmed, using par. “diSP”, to visualize other values. 
 

2 -  PROGRAMMING 

 

2.1 – FAST PROGRAMMING OF THE SET POINT 

This procedure permits rapid programming of the active Set Point 
and possibly the alarm thresholds (see par 2.3) 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 3

 

Push key “P”, then release it and the display will visualise 

“SP n”

 

(where n is the number of the Set Point active at that moment) 
alternatively to the programmed value. 
To modify the value, press “UP” key to increase it or the “DOWN” 
key to decrease it.

 

These keys change the value one digit at a time but if they are 
pressed for more than one second, the value increases or 
decreases rapidly and, after two seconds in the same condition, the 
changing speed increases in order to allow the desired value to be 
reached rapidly. 
Once the desired value has been reached, by pushing key P it is 
possible to exit by the fast programming mode or it is possible to 
visualise the alarm thresholds (see par. 2.3). 
To exit the fast Set programming it is necessary to push key P, after 
the visualisation of the last Set Point, or alternatively, if no key is 
pressed for approx. 15 seconds, the display will return to normal 
functioning automatically. 
 

2.2 - SELECTION OF THE CONTROL STATE AND PARAMETERS 
PROGRAMMING

 

By pushing key "P" and holding it down for approx. 2 sec. it is 
possible to enter into the main selection menu. 
Using the "UP" or DOWN” keys, it is then possible to roll over the 
selections: 

"OPEr"

   to enter into the operating parameters menu 

"ConF"

   to enter into the configuration parameters menu 

"OFF"

 

 to swap the regulator into the OFF state 

"rEG"

 

 to swap the regulator into the automatic control state 

"tunE"

 

 to activate the  Auto-tuning or Self-tuning function  

"OPLO"

   to swap the regulator to the manual control state 

and therefore to program the % control value using 
the “UP” and “DOWN” keys 

Once the desired item has been selected, push key “P” to confirm. 
Selecting "OPEr" and "ConF" gives the possibility of accessing other 
menus containing additional parameters and more precisely : 

"OPEr" –

 Operating parameters Menu: this normally contains the 

Set Point parameters but it can contain all the desired parameters 
(see par. 2.3). 

"ConF" –

 Configuration parameters Menu: this contains all the 

operating parameters and the functioning configuration parameters 
(alarm configuration, control, input, etc.) 
To enter the menu 

“OPEr”

, select the option “OPEr” and press the 

key “P”. 
The display will now show the code identifying the first group of 
parameters (“ 

]

SP 

“) and by pressing the “UP” and “DOWN” keys it 

will be possible to select the group of parameters to be modified. 
Once the desired group of parameters has been selected, the first 
group will be visualised on the PV display while the code identifying 
the first parameter will be visualised on the SV display, by pushing 
the “P” key. 
Again, by using the “UP” and “DOWN” keys, it is possible to select 
the desired parameter and, if the key “P” is pressed, the display PV 
will  show the parameter’s code while the display SV will show its 
programming value, which can be modified by using the “UP” or 
“DOWN” keys. 
Once the desired value has been programmed, push key “P” once 
more: the new value will be memorised and the displays will show 
again the code of the selected parameter and the group. 
By using the “UP” or “DOWN” keys, it is then possible to select a 
new parameter (if present) and modify it as described above. 
To select another group of parameters, keep the “UP” or “DOWN” 
key pressed for approx. 2 sec., afterwards the display SV will return 
to visualise the code of the group of parameters. 
Release the key and by using the “UP” and “DOWN” keys, it will be 
possible to select a new group (if present). 
To exit the programming mode, no key should be pressed for 
approx. 20 seconds, or keep the “UP” or “DOWN” pressed until exit 
from the programming mode is obtained. 
To enter the menu  

"ConF"

 a PASSWORD is required. 

At this request, enter, using keys “UP” and “DOWN”, the number 
reported on the last page of this manual and push key “P”. 

If an incorrect password is entered, the instrument returns to the 
previous control state. 
If the password is correct, the display SV will visualise the code 
identifying the first group of parameters (“ 

]

SP 

“) and with keys “UP” 

and “DOWN” it will be possible to select the desired group of 
parameters 
The programming and exit modes for the “ConF” menu are the 
same as those described for menu “OPEr”. 

 

 

 
2.3 – PARAMETERS PROGRAMMING LEVELS

 

The menu “OPEr” normally contains the parameters used to 
program the Set Point; however it is possible to make all desired 
parameters appear or disappear on this level, by following this 
procedure: 
Enter the menu “ConF” and select the parameter to be made 
programmable or not programmable in the menu “OPEr”. 
Once the parameter has been selected, if the LED SET is switched 
off, this means that the parameter is programmable only in the 
menu “ConF”, if instead the LED is on, this means that the 
parameter is also programmable in the menu “OPEr”. 
To modify the visibility of the parameter, push key “U” : the LED SET 
will change its state indicating the parameter accessibility level (on = 
menu ”OPEr” and “ConF”; off = menu “ConF” only). 
The active Set Point and the alarm thresholds will only be visible on 
the Set Point fast programming level (described in par. 2.1) if the 
relative parameters are programmed to be visible (i.e. if they are 
present in the menu  “OPEr”). 
The possible modification of these Sets, with the procedure 
described in par. 2.1, is instead subordinate to what is programmed 
in par. 

“Edit”

 (contained in the group “ 

]

PAn 

“). 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 4

 

This parameter can be programmed as : 
=SE : The active Set Point can be modified while the alarm 
thresholds cannot be modified. 
=AE : The active Set Point cannot be modified while the alarm 
thresholds can be modified 
=SAE : Both the active Set Point and the alarm thresholds can be 
modified 
=SAnE : Both the active Set Point and the alarm thresholds cannot 
be modified 
 

2.4 – CONTROL STATE

 

The controller can act in 3 different ways : automatic control

 (rEG),

  

control off 

(OFF)

 and manual control

 (OPLO). 

The instrument is able to pass from one state to the other : 
- by selecting the desired state from the main selection menu suing 
the keyboard. 
- By using the key “U” on the keyboard; suitably programming par. 
“USrb” (“USrb” = tunE; “USrb” = OPLO; “USrb” = OFF) it is possible 
to pass from “rEG” state to the state programmed on the parameter 
and vice versa. 
- Automatically (the instrument swaps into "rEG" state at the and of 
the auto-tuning execution) 
When switched on, the instrument automatically reassumes the 
state it was in when it was last switched off. 

AUTOMATIC CONTROL (rEG)

 – Automatic control is the normal 

functioning state of the controller. 
During automatic control, on the SV display, it is possible to 
visualize the control power on the display by pushing key “UP”. 
The range of the power values goes from H100 (100% of the output 
power with reverse action) to C100 (100% of the output power with 
direct action). 

CONTROL OFF (OFF)

 – The instrument can be swapped into the 

“OFF” state, i.e. the control and the relative outputs are deactivated. 
The alarm outputs are instead working normally. 

BUMPLESS MANUAL CONTROL (OPLO)

 – By means of this 

option it is possible to manually program the power percentage 
given as output by the controller by deactivating automatic control. 
When the instrument is swapped to manual control, the power 
percentage, visualised on the SV display, is the same as the last 
one supplied and can be modified using the “UP” and “DOWN” 
keys. 
In case of ON/OFF control, 0% corresponds to the deactivated 
output while any value different from 0 corresponds to the activated 
output. 
As in the case of visualization, the programmable values range from 
H100 (100% output power with reverse action) to C100 (100% 
output power with direct action). 
In case of motorized actuators with time positioning, the manual 
control of the output is obtainable in the following way : 
- By pushing the UP key, the opening of the actuator is driven   
- By pushing DOWN key, the closing of the actuator is driven 
For all time during which the manual control is active, “3 Pt” or 
“OPEn” is visible on the lower display if the UP key is pressed or 
“CLOS” if the DOWN key is pressed. 
To return to automatic control, select "rEG" in the selection menu. 
 

2.5 – ACTIVE SET POINT SELECTION 

This instrument permits pre-programming of up to 4 different Set 
points (

“SP1”

“SP2”

“SP3”

“SP4”

) and then selection of which 

one must be active. The maximum number of Set points is 
determined by the par. 

"nSP"

 located in the group of parameters “ 

]

SP 

“.  

The active Set point can be selected : 
- by parameter 

"SPAt"

 in the group of parameters “ 

]

SP 

“. 

- by key “U” if  par. "USrb" = CHSP 
- by digital input if  par. “diF” = CHSP or = SP1.2 or =HECo) 
- Automatically between SP1 and SP2 if a time “dur.t” (see par. 
4.12) has been programmed. 
Set Points “SP1”, “SP2”, “SP3”, “SP4” will be visible depending on 
the maximum number of Set Points selected on par. “nSP” and they 
can be programmed with a value that is between the value 

programmed on par.  

“SPLL”

 and the one programmed on par. 

“SPHL”.

  

Note

 : in all the following examples the Set point is indicated as 

"SP", however the instrument will act according to the Set point 
selected as active. 

 

3 - INFORMATION ON INSTALLATION AND USE 

 

 

3.1 - PERMITTED USE 

The instrument has been projected and 
manufactured as a measuring and control 
device to be used according to EN61010-1 for 
the altitudes operation until 2000 ms.

 

The use of the instrument for applications not expressly permitted 
by the above mentioned rule must adopt all the necessary protective 
measures. 
The instrument CANNOT be used in dangerous environments 
(flammable or explosive) without adequate protection. 
The installer must ensure that EMC rules are respected, also after 
the instrument installation, if necessary using proper filters.

 

Whenever a failure or a malfunction of the device may cause 
dangerous situations for persons, thing or animals, please 
remember that the plant has to be equipped with additional devices 
which will guarantee safety. 

 
3.2 – MECHANICAL MOUNTING 

The instrument, in DIN case 48 x 48 mm, is designed for flush-in 
panel mounting.  
Make a hole 45 x 45 mm and insert the instrument, fixing it with the 
provided special bracket. 
We recommend that the gasket is mounted in order to obtain the 
front protection degree as declared. Avoid placing the instrument in 
environments with very high humidity levels or dirt that may create 
condensation or introduction of conductive substances into the 
instrument. 
Ensure adequate ventilation to the instrument and avoid installation 
in containers that house devices which may overheat or which may 
cause the instrument to function at a higher temperature than the 
one permitted and declared.   
Connect the instrument as far away as possible from sources of 
electromagnetic disturbances such as motors, power relays, relays, 
solenoid valves, etc.  
The instrument can be removed from its housing from the front side 
: it is recommended that the instrument be disconnected from  the 
power supply when it is necessary to carry out this operation. 
 

3.3 - ELECTRICAL CONNECTION 

Carry out the electrical wiring by connecting only one wire to each 
terminal, according to the following diagram, checking that the 
power supply is the same as that indicated on the instrument and 
that the load current absorption is no higher than the maximum 
electricity current permitted.  
As the instrument is built-in equipment with permanent connection 
inside housing, it is not equipped with either switches or internal 
devices to protect against overload of current: the installation will 
include a two-phase circuit-breaker, placed as near as possible to 
the instrument, and located in a position that can easily be reached 
by the user and marked as instrument disconnecting device which 
interrupts the power supply to the equipment. 
It is also recommended that all the electrical circuits connected to 
the instrument must be protect properly, using devices (ex. fuses) 
proportionate to the circulating currents.  
It is strongly recommended that cables with proper insulation, 
according to the working voltages and  temperatures, be used.  
Furthermore, the input cable of the probe has to be kept separate 
from line voltage wiring. If the input cable of the probe is screened, it 
has to be connected to the ground with only one side.  
We recommend that a check should be made that the parameters 
are those desired and that the application functions correctly before 
connecting the outputs to the actuators so as to avoid 
malfunctioning that may cause irregularities in the plant that could 
cause damage to people, things or animals. 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 5

 

 
Tecnologic S.p.A. and its legal representatives do not assume 
any responsibility for any damage to people, things or animals 
deriving from violation, wrong or improper use or in any case 
not in compliance with the instrument’s features. 
 
3.4 - ELECTRICAL WIRING DIAGRAM 

 
 
 
 

4 - FUNCTIONS

 

 

4.1 – MEASURING AND VISUALIZATION 

All the parameters referring measurements are contained in the 
group 

]

InP”. 

By using par. 

“HCFG”,

 it is possible to select the input signal type 

which may come: from a thermocouple (tc), a thermo-resistance or 
a thermistor (rtd), from a transducer with normalised analogue 
signal in current (I) or tension (UoLt) or also from a signal coming 
from the communication serial line of the instrument (SEr).  
Once the signal type has been selected, it is necessary to set the 
type of input probe on par. 

“SEnS”,

 which can be : 

- for thermocouples J (J), K (CrAL), S (S), B (b), C (C), E (E), L (L), 
N (n), R (r), T (t) or for infrared sensors serie TECNOLOGIC IRS – A 
range - with linearization J (Ir.J) or K (Ir.CA) 
- for thermoresistances Pt100 IEC (Pt1) or thermistors PTC KTY81-
121 (Ptc) or NTC 103AT-2 (ntc) 
- for normalised signals in current 0..20 mA (0.20) or 4..20 mA 
(4.20) 
- for normalised signals in tension 0..50 mV (0.50), 0..60 mV (0.60), 
12..60 mV (12.60), 0..5 V (0.5), 1..5 V (1.5), 0..10 V (0.10) or 2..10 V 
(2.10). 
We recommend that the instrument be switched on and off 
whenever these parameters are modified, in order to obtain a 
correct measurement. 
For the instruments with input for temperature probes (tc, rtd) it is 
possible to select the unit of measurement  (°C, °F) through par. 

“Unit”,

 and the desired resolution (0=1°; 1=0,1°) through par. 

“dP”

Instead, with regards to the instruments with normalised analogue 
input signals, it is first necessary to program the desired resolution 
on par. 

“dP”

  (0=1; 1=0,1; 2=0,01; 3=0,001) and then, on par. 

"SSC"

, the value that the instrument must visualise at the beginning 

of the scale (0/4 mA, 0/12 mV, 0/1 V o 0/2 V) and, on par. 

"FSC", 

the value that the instrument must visualise at the end of the scale 
(20 mA, 50 mV, 60 mV, 5 V or 10 V). 
In the case of infrared sensors (TECNOLOGIC IRS-"A" range), by 
programming the sensor as "Ir.J" or "Ir.CA", the par.  "

rEFL

" is also 

present and it allows the correction of possible measuring errors 
caused by the environment lighting and by the reflectivity of the 
material. This parameter should be programmed with a high value if 
the material to be measured is particularly bright / reflective and 
must be reduced if the surface is particularly dark / not reflective, 

keeping in mind however that for most materials, the recommended 
value is within 1.00 and 0.80.   
The instrument allows for measuring calibration, which may be used 
to recalibrate the instrument according to application needs, by 
using par. 

“OFSt”

 and 

“rot”.

 

Programming par. “rot”=1,000, in par. “OFSt” it is possible to set a 
positive or negative offset that is simply added to the value read by 
the probe before visualisation, which remains constant for all the 
measurements. 
If instead, it is desired that the offset set should not be constant for 
all the measurements, it is possible to operate the calibration on  
any two points.  
In this case, in order to decide which values to program on par. 
“OFSt” and “rot”, the following formulae must be applied : 

“rot” = (D2-D1) / (M2-M1) “OFSt” = D2 - (“rot” x M2)

 

where: 
M1 =measured value 1 
D1 = visualisation value when the instrument measures M1 
M2 =measured value 2 
D2 = visualisation value when the instrument measures M2 
It then follows that the instrument will visualise : 

DV = MV x “rot” + “OFSt”

 

where:  DV = visualised value  

MV= measured value 

Example 1: It is desired that the instrument visualises the value 
effectively measured at 20° but that, at 200°, it visualises a value 
lower than 10° (190°).     
Therefore :  M1=20 ;  D1=20 ;  M2=200 ;  D2=190 
“rot” = (190 - 20) / (200 - 20) = 0,944 
“OFSt” = 190 - (0,944 x 200) = 1,2

 

Example 2: It is desired that the instrument visualises 10° whilst the 
value actually measured is 0°, but, at 500° it visualises a 50° higher 
value (550°). 
Therefore :  M1=0 ;  D1=10 ;  M2=500 ;  D2=550 
“rot” = (550 - 10) / (500 - 0) = 1,08 
“OFSt” = 550 - (1,08 x 500) = 10

 

By using par.

 “FiL” 

it is possible to

 

program time constant of the  

software filter for the input value measured, in order to reduce noise 
sensitivity (increasing the time of reading). 
In case of measurement error, the instrument supplies the power as 
programmed on par.  

“OPE”. 

This power will be calculated according to cycle time programmed 
for the PID controller, while for the ON/OFF controllers the cycle

 

time is automatically considered to be equal to 20 sec. (e.g. In the 
event of probe error with ON/OFF control and “OPE”=50, the control 
output will be activated for 10 sec., then it will be deactivated for 10 
sec. and so on until the measurement error remains.). 
By using par. 

“InE”

 it is also possible to decide the conditions of the 

input error, allowing the instrument to give the power  programmed 
on par. “OPE” as output. 
The possibilities of par. “InE” are : 
= Or : the condition occurs in case of over-range or probe breakage 
= Ur : the condition occurs in case of under-range or probe 
breakage 
= Our : the condition occurs in case of over-range or under-range or 
probe breakage 
Using par. 

“diSP”, 

located in the group 

]

PAn”, 

it is possible to set 

normal visualization of the SV display which can be the active Set 
Point (SP.F), the control power (Pou), the Set Point operating when 
there are active ramps (SP.o) or alarm threshold AL1, 2 or 3 (AL1, 
AL2 or AL3).

 

 
4.2 - OUTPUT CONFIGURATION 

The instrument’s outputs can be programmed by entering the group 
of parameters 

]

O1”, “

]

O2”, “

]

O3”, “

]

O4”

, where different 

parameters (depending on the type of outputs –digital or analogue- 
available on the instrument) are located.

 

Note:

 In the following examples, the number of outputs is 

generically indicated  with 

n

 

- DIGITAL OUTPUTS relay or SSR type : 

Within the selected group only the par. 

“OnF” 

will be present

This parameter can be set for the following functions : 
= 1.rEG : Main control output 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 6

 

= 2.rEG : Secondary control output 
= ALno : Alarm output normally open 
= ALnc : Alarm output normally closed 
= OFF : Output deactivated  
The coupling [outputs number – alarms number] can be effectuated 
in the group relative to the alarm (“

]

AL1”,”

]

AL2” or “

]

AL3”). 

- ANALOGICAL OUTPUTS 0/4..20 mA or 0/2..10 V (only OUT1,2):

 

The parameter 

“Aorn”

 will present within the group, with which it is 

possible to set the beginning of the scale used for the output. 
This parameter will therefore be set at: 
= 0 : if one intends to use the beginning of the scale as equal to 0 (0 
mA if the output is 0/4...20 mA, or 0 V if the output is  0/2...10 V) 
= no_0 : if one intends to use the beginning of the scale other than 0  
(4 mA if the output is 0/4...20 mA, or 2 V if the output is 0/2...10 V)

 

The parameter 

“AonF”

 will be present by which it is possible to 

configure the function of the analogical output as: 
= 1.rEG : Primary control output  
= 2.rEG : Secondary control output 
= r.inP : measurement retransmission output 
= r.Err : error retransmission output [SP-PV] 
= r.SP : Active Set Point retransmission output 
= r.SEr : output led by serial communication line of the instrument 
= OFF : deactivated output 
In the case that analogical output is configured as 1.rEG or 2.rEG 
the output signal  will be proportional to the control power calculated 
by the instrument starting from 0% (output signal corresponding to 
the set beginning of the scale) up to 100% (output signal 
corresponds to the maximum that can be supplied by the type of 
output available). 
The analogical control outputs can only be used for PID single 
action or dual action controls. 
If the set control mode was the ON/OFF type, the analogical output 
could only take on the control states 0 % or 100 %. 
In the case that the analogical output function should be configured 
for the retransmission of the signal, it is therefore necessary to 
programme another two parameters which set the minimum and 
maximum reference values. 
Therefore, in these cases, set the parameter 

"AonL"

 with the value 

that the instrument must provide the minimum value (0/4 mA or 0/2 
V) in output and the value to which the instrument must provide the 
maximum value (20 mA o 10 V) to the parameter

 "AonH"

 in output. 

 

4.3 – ON/OFF CONTROL (1rEG) 

All the parameters referring to the ON/OFF control are contained in 
the group 

]

rEG”. 

This type of control can be obtained by programming par.

"Cont"

 = 

On.FS or = On.FA  and works on the output programmed as 

1.rEG,

 

depending on the measure, on the active Set Point 

“SP”

, on the 

functioning mode 

"Func” 

and on the hysteresis 

"HSEt

". 

The instrument carries out an ON/OFF control with symmetric 
hysteresis if “Cont" = On.FS or with asymmetrical hysteresis if 
“Cont” = On.Fa. 
The control works in the following way : in the case of reverse 
action, or heating (“FunC”=HEAt), it deactivates the output, when 
the process value reaches [SP + HSEt] in case of symmetrical 
hysteresis, or [SP] in case of asymmetrical hysteresis and is then 
activated again when the process value goes below value [SP - 
HSEt]. Vice versa, in case of direct action or cooling ("Func”=CooL), 
it deactivates the output, when the process value reaches [SP - 
HSEt] in case of symmetrical hysteresis, or [SP] in case of 
asymmetrical hysteresis  and is activated again when the process 
value goes above value [SP + HSEt]. 

 

4.4 – NEUTRAL ZONE ON/OFF CONTROL (1rEG - 2rEG)

 

All the parameters referring to Neutral Zone ON/OFF control are 
contained in the group 

]

rEG”. 

This type of control can be obtained when 2 outputs are 
programmed respectively as 1rEG and 2rEG and the par. 

“Cont”

 = 

nr . 
The Neutral Zone control is used to control plants in which there is 
an element which causes a positive increase (ex. Heater, humidifier, 
etc.) and an element which causes a negative increase (ex. Cooler, 
de-humidifier, etc). 
The control functions works on the programmed outputs depending 
on the measurement, on the active Set Point 

“SP” 

and on the 

hysteresis 

"HSEt

". 

The control works in the following way : it deactivates the outputs 
when the process value reaches the Set Point and it activates the 
output 1rEG when the process value goes below value [SP - HSEt], 
or it activates the output 2rEG when the process value goes above 
[SP + HSEt].  
Consequently, the element causing a positive increase has to be 
connected to the output programmed as 1rEG while the element 
causing a negative increase has to be connected to the output 
programmed as 2rEG. 

 

 
4.5 – SINGLE ACTION PID CONTROL (1rEG) 

All the parameters referring to PID control are contained in the 
group 

]

rEG”. 

The Single Action PID control can be obtained by programming 
par.

"Cont"

 = Pid  and works on the output 1rEG depending on the 

active Set Point 

“SP”

, on the functioning mode 

"Func” 

and on the 

instrument’s PID algorithm with two degree of freedom. 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 7

 

 

In order to obtain good stability of the process variable, in the event 
of fast processes and with control by digital output, the cycle time 
“tcr1” has to have a low value with a very frequent intervention of the 
control output. 
In this case use of a solid state relay (SSR) is recommended for 
driving the actuator. 
The Single Action PID control algorithm foresees the setting of the 
following parameters : 

"Pb"

 – Proportional Band 

"tcr1"

 – Cycle time of the output 1rEG (digital output only) 

"Int"

 – Integral Time 

"rS"

 – Manual Reset (if “Int =0 only) 

"dEr"

 – Derivative Time 

“FuOC” - 

Fuzzy Overshoot Control 

This last parameter allows the variable overshoots at the start up of 
the process or at the changing of the Set Point to be avoided. 
Please remember that a low value on this parameter reduces the 
overshoot while a high value increase it. 

 

1: Value “FuOC” OK 
2: Value “FuOC” too high 
3: Value “FuOC” too low 
 

4.5 - DOUBLE ACTION PID CONTROLLER (1rEG - 2rEG) 

All the parameters referred to PID control are contained into the 
group 

]

rEG”. 

The Double Action PID control is used to control plants where there 
is an element which causes a positive increment (ex. Heating) and 
an element which causes a negative increment (ex. Cooling). 
This type of control is obtainable when 2 outputs are programmed 
respectively as 1rEG and 2rEG and the par. 

“Cont”

 = Pid. 

The element causing a positive increase has to be connected to the 
output programmed as 1rEG while the element causing a negative 
increase has to be connected to the output programmed as 2rEG. 
The Double Action PID control works on the outputs 1rEG and 2rEG 
depending on the active Set Point 

“SP” 

and on the instrument’s PID 

algorithm with two degree of freedom. 
In order to obtain a good stability of the process variable, in case of 
fast processes and  with control by digital outputs, the cycle times 
“tcr1” and “tcr2” have to have a low value with a very frequent 
intervention of the control outputs. 
In this case it’s recommended to use solid state relays (SSR) to 
drive the actuators. 
The Double Action PID control algorithm needs the programming of 
the following parameters : 

"Pb"

 – Proportional Band  

"tcr1"

 – Cycle time of the output 1rEG 

“tcr 2”

 – Cycle time of the output 2rEG 

"Int"

 – Integral Time 

"rS"

 – Manual Reset (if “Int =0 only) 

"dEr"

 – Derivative Time 

“FuOC” - 

Fuzzy Overshoot Control

 

"Prat"

 - Power Ratio or relation between power of the element 

controlled by output 2rEG and power of the element controlled by 
output 1rEG. 
 

4.7 - PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME 
POSITIONING (1rEG - 2rEG) 

All the parameters concerning the PID control for motorised 
actuators are contained in the group 

]

rEG”. 

This type of control is used to control installations that have a 
motorised actuator with digital opening and closing controls that 
remain at the point they have reached if no command is received 
and which are started up when 2 outputs are configured as 1rEG 
and 2rEG respectively and the parameter 

“Cont”

 = 3 Pt is set. 

The opening command for actuation will be supplied by the output 
configured as 1rEG while the closing command will be supplied by 
the output configured as 2rEG. 
The PID type control for motorised actuators therefore acts on the 
outputs 1rEG and 2rEG depending on the active Set point 

“SP” 

and 

the result of the PID control algorithm with two degrees of liberty for 
the instrument. 
The control system used does not foresee a retroaction for finding 
the current position of the actuator. 
If the actuator is not fitted  with safety stop contacts that interrupt the 
actuator at the end of its run it is necessary to equip the installation 
with these contacts (SQo, SQc) as shown in the diagram 

 

The PID control algorithm for motorised actuators with time 
positioning foresees the setting of the following parameters: 

“Pb”

 - Proportional band 

“Int”

 - Integral time 

“rS”

 - manual reset  (only if “Int =0) 

“dEr”

 - Derivative time 

“FuOC” - 

Fuzzy Overshoot Control 

“tcor”

 -  time of actuator run. 

This is the time, expressed in seconds that is needed for the 
actuator to pass from the “completely open” position to “completely 
closed” position. 

“SHrI”

 - Minimum control value.  

It is the value that the control must have reached  (in %) before it 
has an effect on the output. It is needed to prevent the control from 
intervening too frequently. 

“PoSI”

 - Switch on position.  

This is the position that the actuator must reach when the 
instrument is switched on. It can have the following values : 
nO = the actuator remains where it is, 
oPEn = the actuator goes to the “completely open” position, 
cLoS =  the actuator goes to the “completely closed” position. 
If the options "OPEn" or "CloS" are programmed, when it is turned 
on the device with activate the output 1rEG (if "oPEn") or 2rEG (if 
"cLoS") for the time set on parameter "tcor" after which control 
begins. 
In the event of an error in measurement, the outputs are activated 
so that the valve moves to the position fixed by the parameter 
“PoSI”. 
 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 8

 

4.8 – AUTO-TUNING

 

AND SELF-TUNING FUNCTIONS 

All the parameters referring to the AUTO-TUNING and SELF-
TUNING functions are contained in the group 

]

rEG”. 

The AUTO-TUNING and SELF-TUNING functions permit the 
automatic tuning of the PID controller. 
The 

AUTO-TUNING

 function permits the calculation of the PID 

parameters by means of a FAST type tuning cycle and, at the end of 
this operation, the parameters are stored into the instrument’s 
memory and remain constant during control. 
The 

SELF-TUNING

 function (rule based "TUNE-IN") instead allows 

control monitoring and the continuous calculation of the parameters 
during control. 
Both functions automatically calculate the following parameters : 

"Pb"

 – Proportional Band 

"tcr1"

 – Cycle time of the output 1rEG 

"Int"

 – Integral Time 

"dEr"

 – Derivative Time 

“FuOC” - 

Fuzzy Overshoot Control

 

and, for the Double Action PID control, also : 

“tcr 2”

 – Cycle time of the output 2rEG 

"Prat"

 - Ratio P 2rEG/ P 1rEG 

To activate the AUTO-TUNING function proceed as follows : 
1) Program and activate the desired Set Point. 
2) Program par. "Cont" =Pid or =3 Pt if the instrument drives a 
motorized actuator with time positioning. 
3) Program par. "Func" according to the process to be controlled 
through output 1rEG. 
4) Program an output as 2rEG if the instrument controls a plant with 
double action or a motorized actuator with time positioning.  
5) Program par. 

"Auto"

 as: 

- "1” – if auto-tuning is desired automatically, each time the 
instrument is switched on, on the condition that the process value is 
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” 
=CooL) than [SP+ |SP/2|]. 
- "2" – if auto-tuning is desired automatically, the next time the 
instrument is switched on, on the condition that the process value is 
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” 
=CooL) than [SP+ |SP/2|], and once the tuning is finished, the par. 
“Auto” is automatically swapped to the OFF state  
- "3"  - if manual auto-tuning is desired, by selecting  par. “tunE” in 
the main menu or by correctly programming key “U” as “USrb” = 
tunE. In this case the auto-tuning starts without any control on the 
process value condition. It is recommended to use this option, 
starting the auto-tuning when the process value is as far as possible 
from the Set Point because, in order to feature the Auto-tuning 
FAST with its best performances , it is preferable to respect this 
condition. 
- "4"  - if it’s desired to activate the autotuning automatically at the 
end of programmed Soft-Start cycle. The Autotuning will start at the 
condition that the process value is lower (with “Func” =HEAt) than 
[SP- |SP/2|] or higher (with “Func” =CooL) than [SP+ |SP/2|]. 
6) Exit from the parameter programming. 
7) Connect the instrument to the controlled plant. 
8) Activate the Auto-tuning by selecting par. 

“tunE”

 in the main 

menu (or by correctly programming key “U” ). 
At this point the Auto-tuning function is activated and is indicated by 
the flashing led AT/ST. 
The regulator carries out several operations on the connected plant  
in order to calculate the most suitable PID parameters.   
If “Auto” = 1 or “Auto” = 2, and if, at the Auto-tuning start, the 
condition for the lower process value is not found (with “Func” 
=HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than [SP+ 
|SP/2|], the display will show 

“ErAt”

 and the instrument will be 

swapped to normal control conditions according to the previously 
programmed parameters. 
To make the error “ErAt” disappear, swap the instrument to the OFF 
control (OFF) and then turn it to automatic control (rEG). 
The Auto-tuning cycle duration has been limited to 12 hours 
maximum. 
If Auto-tuning is not completed within 12 hours, the instrument will 
show 

"noAt" 

on the display

.

  

In case of probe error, the instrument automatically stops the cycle 
in progress. 
The values calculated by Auto-tuning are automatically stored in the 
instrument’s memory at the end of the correct PID parameters 
tuning.  

Note :

 The instrument is already programmed in our factory to carry 

out auto-tuning at every instrument switch on ("Auto" = 1). 
To activate the SELF-TUNING function proceed as follows 
1) Program and activate the desired Set Point. 
2) Program par. "Cont" =Pid. 
3) Program par. "Func" according to the process to be controlled 
through output 1rEG. 
4) Program an output as 2rEG if the instrument controls a dual-
action plant  
5) Program par. 

"SELF"

 = yES 

6) Exit from the parameter programming. 
7) Connect the instrument to the controlled plant. 
8) Activate Self-tuning selecting par. 

“tunE”

 in the main menu (or 

by correctly programming key “U”). 
When the Self-tuning function is active, the led AT/ST is 
permanently lit up and all the PID parameters ("Pb", "Int", "dEr", 
etc.) are no longer visualized. 
 
To stop the Auto-tuning cycle or deactivate the Self-tuning function 
select one of the control types : "rEG", "OPLO" or "OFF" from the 
menu “SEL”. If the instrument is switched off during Auto-tuning or 
with the Self-tuning function activated, these functions will remain 
activated the next time it is switched on. 
 

4.9 - CONTROL POWER LIMITATION 

 

Using this function, it is possible to limit the output control power 
(separately for both control outputs) within a minimum limit and a 
maximum limit . 
It is only possible to use these limits if the PID control is single or 
dual action and it may be useful to overcome some mechanical 
problems of the actuators such as valves that do not open until the 
output has reached at least 20% and/or are already completely 
closed when the power has reached 80%. 
The PID control of the instrument normally works producing power 
between  0 and 100 % in the case of single-action PID and –100 (C) 
and 100 (H) % in the case of dual-action PID. 
The function is therefore deactivated by setting “ro1.L” =0 “ro2.L” = 
0 and “ro1.H” =100, “ro2.H” = 100. 
By setting different values the power is lowered to within the limits 
set in order to use the actuator’s dynamics to the maximum. 
The parameters that can be set for this function, contained in the 

]

rEG” 

block are: 

“ro1.L”

 - minimum power in output from 1rEG (H) 

“ro1.H”

 - maximum power in output from 1rEG (H) 

“ro2.L”

 - minimum power in output from 2rEG (C) 

“ro2.H”

 - maximum power in output from 2rEG (C) 

The limitation is not active under the “OPLO” manual control mode. 
 

4.10 - LIMITATION OF THE CONTROL POWER VARIATION 
SPEED 

This function makes it possible to limit the variation speed of the 
control power in output (separately for both control outputs). 
It is only possible to use this function if the PID control is single or 
dual action and can be useful for overcoming some problems with 
the actuators that may need a slow progressive variation in power. 
The parameters that can be set for this function, contained in the 
block 

]

rEG”, 

are: 

“OPS1”

 - variation speed of the output power from 1rEG (H) 

expressed  in [% / sec]. 

“OPS2”

 - variation speed of the output power from 2rEG (C) 

expressed in [% / sec]. 
The limitation function is deactivated by setting the parameters = 
InF and if “OPLO” is not active in manual control mode. 
 

4.11 - SPLIT RANGE FUNCTION

 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 9

 

The use of this function is only possible if the PID control is dual 
function and can be used to delay or bring forward the intervention 
of the actuators commanded by the instrument. 
Using this function it is therefore possible to optimise the 
intervention of the two actuators in such a way that their actions do 
not overlap or so that they overlap so that they obtain the mix of the 
two actions of the actuators. 
Basically, this means setting two power offsets (one for direct action 
and one for reverse action) that set the beginning of the intervention 
of the actuator commanded by the output. 
The parameters that can be set for this function contained in the 
block 

]

rEG”,

 are: 

“thr1”

 : Power threshold at which output 1rEG begins to operate. 

“thr2”

 : Power threshold at which output 2rEG begins to operate. 

Basically, if one wishes to bring forward the reverse action (1rEG) 
and delay the direct action (2rEG) it is necessary to set positive 
values on parameter “thr1” and negative values on parameter “thr2”. 
In this way, the area within which the two outputs are not activated 
at the same time is increased. 

 

Vice versa if one wishes to extend the reverse action (1rEG) and 
bring forward the direct action (2rEG) it is necessary to set negative 
values on parameter “thr1” and positive values on parameter “thr2”. 
In this way, the area within which the two outputs are activated at 
the same time is increased. 

 

The split range function is deactivated by setting the respective 
parameters =0.

 

 

note

 : In order to simplify the explanation of the example graphs a  

dual action control that is only proportional (and therefore with “dEr”  
and “Int” = OFF)  with “Prat” = 1.0 and “rS” = 0.0 was considered. 
 

4.12 - REACHING OF THE SET POINT AT CONTROLLED SPEED 
AND AUTOMATIC SWITCHING BETWEEN TWO SET POINTS 
(RISE RAMP, FALL RAMP AND DWELL TIME)

 

All the parameters referring to the ramps functioning are contained 
in the group 

]

rEG”.

 

It is possible to reach the set point in a predetermined time (in any 
case longer than the time the plant would naturally need). This could 
be useful in those processes (heating or chemical treatments, etc.) 
where the set point has to be reached gradually, in a predetermined 
time. 
Once the instrument has reached the first Set Point (SP1) it is 
possible to have automatic switching to the second Set Point (SP2) 
after a set time, thus obtaining a simple automatic thermic cycle. 
These functions are available for all the programmable controls (PID 
single and double action, ON/OFF and Neutral Zone ON/OFF). 
The function is determined by the following parameters :  

"SLor"

 - Gradient of rise ramp  (Process value < Set point) 

expressed in unit/minute  

"SLoF"

 - Gradient of fall ramp (Process value > Set point) 

expressed in unit/minute. 

"dur.t"

 – Dwell time of Set Point SP1 before automatic switching to 

Set Point 2 SP2 (expressed in hrs. and min.). 
The functions are deactivated when the relative parameters are = 
InF. 
When the Set Point value is changed or at switch on, the instrument 
automatically determines which of the two values “SLor” or “SLoF” it 
has to use.  

Note:

 In case of PID control, if Auto-tuning is desired whilst the 

ramp function is active, this will not be carried out until the tuning 
cycle has been completed. 
It is therefore recommended that Auto-tuning be started avoiding 
activating the ramp function and, once the tuning is finished, 
deactivate Auto-tuning  (“Auto” = OFF), program the desired ramps 
and, if it automatic tuning is desired, enable the Self-tuning function. 

 

Examples with starts from values lower than SP and with decreasing 
of SP. 
 

4.13 - SOFT-START FUNCTION

 

All the parameters referring to the Soft -Start functioning are 
contained in the group 

]

rEG”.

 

The Soft-Start function only works through PID control and allows 
the limitation of control power when the instrument is switched on, 
for a programmable period of time. 
This is useful when the actuator, driven by the instrument, may be 
damaged excess power supplied when the application is not yet in 
the normal rating. (ex. for certain heating elements).  
The function depends on the following parameters : 

 “St.P”

 – Soft-Start power 

“Sst”

 – Soft-Start time (expressed in hh.mm) 

The possible function modes are the following : 

1) 

If both parameters are programmed with values other than OFF, 

when switched on the instrument gives an output power as 
programmed on par. “St.P” for the time programmed on par. “SSt”. 
Practically, the instrument works in manual condition and switches 
to automatic control at the elapsing of time “SSt”. 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 10

 

It is advisable not to program a power “St.P” that is too high as the 
function is not deactivated when the automatic control power is 
found to be lower than the programmed one. 

2)

 If par. “St.P” = OFF and a value is set on par. “SSt” , at the switch 

on, the power calculated by the PID controller is divided by the time 
“SSt”, in order to calculate a ramp. The output power starts from 0 
and is progressively increased, depending on the calculated ramp, 
until the “SSt” time is reached or until the power overcomes the 
power calculated by the PID controller. 
To disable the Soft-Start function simply program par. “Sst” = OFF 
Whenever, a measurement errors occurs during the Soft-Start 
execution, the function is interrupted and the instrument gives an 
output power as programmed on par. “OPE”. 
If the measurement is restored, the Soft-Start is still deactivated. 
If it’s desired to activate the Autotuning with Soft-Start set par. 
“Auto”=4.  
The Autotuning will start automatically at the end of programmed 
Soft-Start cycle at the condition that the process value is lower (with 
“Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than 
[SP+ |SP/2|]. 
 

4.14 – ALARM FUNCTION (AL1, AL2, AL3)

 

 

4.14.1 – ALARM OUTPUT CONFIGURATION

 

The alarms depend on the process value (AL1, AL2, AL3) and 
before setting them to work, it is necessary to know which output the 
alarm has to correspond to. 
First of all it is necessary to configure in the groups of parameters  

]

O ”,

 the parameters relative to the outputs required as alarm 

(“O1F” , “O2F” ,“O3F” ,“O4F”),

 

 programming the parameter relating 

to the desired output as follows : 

= ALno

 if the alarm output has to be ON when the alarm is active, 

while it is OFF when the alarm is not active 

= ALnc

 if the alarm output has to be ON when the alarm is not 

active, while it is OFF when the alarm is active  

Note:

 In the following examples the alarm’s number is generally 

indicated as 

 n

 

Access the group 

]

ALn”,

 relating to the alarm to be set and 

program which output the alarm signal must be sent to on par. 

“OALn”

The alarm functioning is instead defined by parameters : 

"ALnt "

 – ALARM TYPE 

"Abn"

 – ALARM CONFIGURATION 

“ALn”

 – ALARM THRESHOLD  

“ALnL”

 – LOW ALARM THRESHOLD (for band alarm) OR 

MINIMUM SET OF ALn ALARM THRESHOLD (for low or high 
alarm) 

“ALnH”

 - HIGH ALARM THRESHOLD (for band alarm) OR 

MAXIMUM SET OF ALn ALARM THRESHOLD (for low or high 
alarm) 

“HALn” - 

ALARM HYSTERESIS 

“ALnd”

 – ALARM ACTIVATION DELAY (in sec.) 

"ALni"

 – ALARM BEHAVIOUR IN THE EVENT OF 

MEASUREMENT ERROR 
 

"ALnt" – ALARM TYPE :

  the alarm output can behave in six 

different ways.

 

LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the 
process value goes below the alarm threshold set on parameter 
"ALn”. With this mode is possible to program the minimum and the 
maximum set  of  “ALn” by “ALnL” and “ALnH” parameters.

 

 

HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the 
process value goes higher than the alarm threshold  set on 
parameter "ALn". With this mode is possible to program the 
minimum and the maximum set  of  “ALn” by “ALnL” and “ALnH” 
parameters. 

 

LHAb = ABSOLUTE BAND ALARM: The alarm is activated when 
the process value goes under the alarm threshold set on parameter 
"ALnL" or goes higher than the alarm threshold set on parameter 
"ALnH". 

 

LodE = DEVIATION LOW ALARM: The alarm is activated when the 
process value goes below the value [SP + ALn]. With this mode is 
possible to program the minimum and the maximum set  of  “ALn” 
by “ALnL” and “ALnH” parameters. 

 

HidE = DEVIATION HIGH ALARM: The alarm is activated when the 
process value goes above the value [SP + ALn]. With this mode is 
possible to program the minimum and the maximum set  of  “ALn” 
by “ALnL” and “ALnH” parameters. 

 

LHdE = DEVIATION BAND ALARM: The alarm is activated when 
the process value goes below the value [SP + ALnL] or goes above 
than the value [SP + ALnH] 

 

 
"

Abn" - ALARM CONFIGURATION:

 This parameter can assume a 

value between 0 and 15. 
The number to be set, which will correspond to the function desired, 
is obtained by adding the values reported in the following 
descriptions : 
ALARM BEHAVIOUR AT SWITCH ON: the alarm output may 
behave in two different ways, depending on the value added to par. 
“Abn”. 
+0 = NORMAL BEHAVIOUR: The alarm is always activated when 
there are alarm conditions. 
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched 
on, the instrument is in alarm condition, the alarm is not activated. It 
will be activated only when the process value is in non-alarm 
conditions  and then back in alarm conditions. 

 

ALARM DELAY:  the alarm output may behave in two different ways 
depending on the value added to par. “Abn”. 
+0 = ALARM NOT DELAYED: The alarm is immediately activated 
when the alarm condition occurs. 
+2 = ALARM DELAYED: When the alarm condition occurs, delay 
counting begins, as programmed on par. “ALnd” (expressed in sec.) 
and the alarm will be activated only after the elapsing of that time. 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 11

 

ALARM LATCH: :  the alarm output may behave in two different 
ways depending on the value added to par. “Abn”. 
+ 0 = ALARM NOT LATCHED: The alarm remains active in alarm 
conditions only. 
+ 4 = ALARM LATCHED: The alarm is active in alarm conditions 
and remains active even when these conditions no longer exist, until  
the correctly programmed key “U”, (“USrb”=Aac) has been pushed. 

 

ALARM AKNOWLEDGEMENT: :  the alarm output may behave in 
two different ways depending on the value added to par. “Abn”. 
+ 0 = ALARM NOT AKNOWLEDGED: The alarm always remains 
active in alarm conditions. 
+ 8 = ALARM AKNOWLEDGED: The alarm is active in alarm 
conditions and can be deactivated by key “U” if properly 
programmed (“USrb”=ASi), and also if alarm conditions still exist. 
 

"ALni" - ALARM ACTIVATION IN CASE OF MEASUREMENT 
ERROR:

 This allows one to establish how the alarm have behave in 

the event of a measurement error (yES=alarm active; no=alarm 
deactivated). 
 

4.14.2 - ALARMS HYSTERESIS

 

The alarm function depend s on alarm hysteresis  (par. "HALn"), 
which works in asymmetric way. 
In the event of low alarm, the alarm will be activated when the 
process value goes below the alarm threshold value and will be 
deactivated when it goes above the alarm threshold + "HALn" ; in 
case of high alarm, the alarm will be activated when the process 
value goes above the alarm threshold value and will be deactivated 
when it goes below the alarm threshold  - "HALn". 

 

For the band alarms, the example of the low alarm is applicable to 
the low threshold ("ALnL") while the example of the high alarm is 
applicable to the high threshold ("ALnH"). 

 
4.15 - HEATER BREAK ALARM FUNCTION (HB) 

All the parameters referring to the Heater Break alarm function are 
contained in the group 

]

Hb”.

 

The Heater Break alarm function (Breakage of the heating element) 
is only available when the instrument is equipped with the input 
(TAHB) to measure the current and if use a digital output to control 
the load. 
This input accepts signals coming from current transformers (TA) 
with max. output 50 mA.  
The first operation to be carried out in order to obtain a correct 
current measurement, is to set the current that the instrument has to 
measure at the end of scale of the input TA (50 mA) on par. 

“IFS”

It is necessary to establish to which output the alarm has to 
correspond.   
To do this it is necessary to set the parameter relative to the output 
to be used

 

(“O1F” , “O2F” ,“O3F” ,“O4F”) in the groups 

]

O ”, 

programming the parameter as : 

= ALno

 if the alarm output has to be active when the alarm is active 

while it is deactivated when the alarm is not active. 

= ALnc

 if the alarm output has to be active when the alarm is not 

active while it is deactivated when the alarm is active.  
Enter group 

]

Hb”

 and program which output the alarm signal has to 

address on parameter 

“OHb

.  

The functioning mode of the alarm is instead defined on par. 

“HbF”

 

which can be set in the following way : 
= 1 : The alarm is active when, with output 1rEG active, the current 
measured by the input TAHB is lower than the value programmed 
on par. 

"IHbL"

 . 

= 2 : The alarm is active when, with output 1rEG not active, the 
current measured by the input TAHB is higher than the value 
programmed on par. 

"IHbH"

 . 

= 3 : The alarm is active when, with output 1rEG active, the current 
measured by the input TAHB is lower than the value programmed 
on par. 

"IHbL"

 or with output 1rEG not active, the current measured 

by the input TAHB is higher than the value programmed on par. 

"IHbH"

= 4 : The alarm is active when the current measured by the input 
TAHB is lower than the value programmed on par. 

"IHbL" 

or the 

measured current is higher than the value programmed on par. 

"IHbH"

, independently by the state of the output 1rEG.    

On par. “IHbL” the value of the current normally absorbed by the 
load when output 1rEG is active has to be set, while on par. “IHbH” 
the current normally absorbed by the load when output 1rEG is not 
active. 
The programming of these parameters has to be carried out while 
also considering the fluctuations of the net voltage to avoid 
undesired alarms. 
With regards to the hysteresis of the HB alarm, this is automatically 
calculated by the instrument as 1% of the programmed thresholds. 
During functioning it is possible to visualize the current measured by 
the input TAHB when output 1rEG is activated, by pushing the 
“DOWN” key and the current measured when output 1rEG is 
deactivated, by pushing the “DOWN” and “U” keys at the same time. 
To exclude the Heater Break alarm it is enough to set “OHb” = OFF.

 

Note :

 The HB current measurement is valid if the output 1rEG is 

activated (or deactivated) for 264 ms. at least.  
This means that, if the cycle time (“tcr1”) is = 1 sec, the HB alarm is 
able to intervene only when the output power is higher than 26,4%. 

 

 
4.16 - LOOP BREAK ALARM FUNCTION

 

All the parameters referring to the Loop Break alarm function are 
contained in the group 

]

LbA”.

 

The Loop Break alarm is available on all the instruments, which 
intervenes when, for any reason (short-circuit of a thermocouple, 
thermocouple inversion, load interruption), the loop control is 
interrupted. 
First of all, it is necessary to establish to which output the alarm has 
to correspond.   
To do this it is necessary to set the parameter relative to the output 
to be used

 

(“O1F” , “O2F” ,“O3F” ,“O4F”) in the groups 

]

O ”, 

programming the parameter as : 

= ALno

 if the alarm output has to be ON when the alarm is active 

while it is OFF when the alarm is not active. 

= ALnc

 if the alarm output has to be ON when the alarm is not 

active while it is OFF when the alarm is active.  
Enter group  

]

LbA”

 and program which output the alarm signal has 

to be addressed to on par. 

“OLbA”

.  

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 12

 

The Loop Break alarm is activated if the output power remains at 
the 100% of the value for the time programmed on par. 

"LbAt"

 

(expressed in sec.). 
To avoid false alarms, the value of this parameter has to be set 
considering the time the plant takes to reach the Set point when the 
measured value is a long distance from it (for example at the plant 
start-up).  
On alarm intervention, the instrument visualizes the message 

“LbA”

 and behaves as in the case of a measurement error giving a 

power output as programmed on par.  

“OPE”

 (programmable in the 

group 

]

InP”)

To restore normal functioning after the alarm, select the control 
mode “OFF” and then re-program the automatic control (“rEG”) after 
checking the correct functioning of probe and drive. 
To exclude the Loop Break alarm, set “OLbA” = OFF. 
 

4.17 - FUNCTIONING OF KEY “U”

 

The function of key “U” can be set through par. 

“USrb”

 contained in 

the group “

]

PAn”. 

The parameter can be programmed as : 

= noF

 : no function 

= tunE

 : Pushing the key for 1 sec. at least, it is possible to 

activate/deactivate Auto-tuning or Self-tuning 

= OPLO

 : Pushing the key for 1 sec. at least, it is possible to swap 

from automatic control (rEG) to manual one (OPLO) and vice versa. 

= Aac

 : Pushing the key for 1 sec. at least, it is possible to 

acknowledge the alarm. (see par. 4.14.1) 

= ASi 

: Pushing the key for 1 sec. at least, it is possible to 

acknowledge an active alarm (see par. 4.14.1) 
 

= CHSP

 : Pushing the key for 1 sec. at least, it is possible to select 

one of the 4 pre-programmed Set Points on rotation.  

= OFF

 : Pushing the key for 1 sec. at least, it is possible to swap 

from automatic control (rEG) to OFF control (OFF) and vice versa. 
 

4.18 – DIGITAL INPUT 

The instrument can also be equipped (in alternative to OUT4) with a 
digital input whose function can be set by the parameter 

"diF"

 

contained in the group 

]

InP”. 

The parameter can be programmed as: 

= noF

 : the input does not carry out any function 

= AaC

 : By closing the contact connected to the digital input, it is 

possible to reset a memorised alarm (see par. 4.14.1) 

= ASi: 

By closing the contact connected to the digital input, it is 

possible to silence an active alarm (see par. 4.14.1) 

=

 

HoLd

: By closing the contact connected to the digital input the 

measurement taken at that moment is blocked (N.B.: not the 
reading on the display, therefore the indication may stabilise itself 
with a delay that is proportional to the measuring filter). With the 
hold function turned on, the instrument carries out control according 
to the memorised measurement. By opening the contact, the 
instrument starts normal measurement acquisition once more. 

= OFF

 : When the instrument is in “rEG” status, by closing the 

contact connected to the digital input, the instrument is placed in 
OFF status. By reopening the contact, the instrument returns to the 
automatic control status “rEG”. 

= CHSP

 : by closing and reopening the contact connected to the 

digital input, it is possible to select one of the 4 memorised set 
points in rotation.  

= SP1.2 

: By closing the contact connected to the digital input, the 

set point SP2 is selected as being active while opening the contact 
selects the set point SP1 as active. The function can only be 
activated using “nSP” = 2 , also, when it is activated, it disables the 
selection of the active set by the parameter “SPAt” and by the key 
U. 

= HE.Co 

: by closing the contact connected to the digital input it is 

possible to select as active the set point SP2 in “CooL” mode. 
Reopening the contact is select as active the set point SP1 in 
“HEAt” mode. This function is possible only when “nSP” = 2. 
 

4.19 - RS 485 SERIAL INTERFACE 

The instrument can be equipped with a RS 485 serial 
communication interface, by means of which it is possible to 
connect the regulator with a net to which other instruments 
(regulators of PLC) are connected, all depending typically on a 
personal computer used as plant supervisor. Using a personal 
computer it is possible to acquire all the function information and to 
program all the instrument’s configuration parameters. The software 
protocol adopted for TLK43 is a MODBUS RTU type, widely used in 
several PLC and supervision programs available on the market (TLK 
protocol manual is available on request). 
The interface circuit allows the connection of up to 32 instruments 
on the same line. 
To maintain the line in rest conditions  a 120 Ohm resistance (Rt) 
must be connected to the end of the line. 
The instrument is equipped with two terminals called A and B which 
have to be connected with all the namesake terminals of the net. 
For the wiring operation they must be interlaced with a double cable 
(telephonic type) and all the GND terminals must be connected to 
the ground. Nevertheless, particularly when the net results very long 
or noised and being present potential differences between the GND 
terminals, it is advisable to adopt a screened cable wired as in the 
drawing. 

 

If the instrument is equipped with a serial interface, the parameters 
to be programmed are the following, all present in the parameters 
group   

]

SEr”

 : 

"Add"

 : Address of the station. Set a different number for each 

station, from 1 to 255. 

"baud"

 : Transmission speed (baud-rate), programmable from 1200 

to 38400 baud. All the stations have to have the same transmission 
speed. 

"PACS"

 : Programming access. If programmed as "LoCL" this 

means that the instrument is only programmable from the keyboard, 
if programmed as "LorE" it is programmable both from the 
keyboards and serial line.  
If an attempt is made to enter the programming from the keyboard 
whilst a communication through the serial port is in progress the 
instrument will visualise 

"buSy"

 to indicate the busy state. 

 

4.20 - PARAMETERS CONFIGURATION BY “KEY01” 

The instrument is equipped with a connector that allows the transfer 
from and toward the instrument of the functioning parameters 
through the device 

TECNOLOGIC KEY01

 with 

3 poles

 connector. 

This device it’s mainly useable for the serial programming of the 
instruments which need to have the same parameters configuration 
or to keep a copy of the programming of an instrument and allow its 
rapid retransmission. 
To use the device KEY01 it’s necessary that both device and 
instrument are being supplied. 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 13

 

 

P.A.:

 For the instruments equipped with RS485 serial 

communication, it’s indispensable that the parameter “PACS” is 
programmed = LorE. 
 
To transfer the configuration of an instrument into the device 

(UPLOAD)

 it is necessary to proceed in the following way:   

1) position both dip switch of KEY 01 in the 

OFF

 mode.   

2) connect the device to the instrument TLK plugging the special 
connector.   
3) verify that the instrument and the device are supplied  
4) observe the indication led on the device KEY 01: if it results 
green this means that a configuration is already loaded on the 
device while if it results green blinking or red blinking this means 
that it has not been loaded any valid configuration on the device .   
5) press the button placed on the device.   
6) observe the indication led : after having pressed the button, the 
led becomes red and therefore, at the end of the data transfer, it 
becomes green.   
7) now it is possible to disconnect the device. 
 
To transfer the configuration loaded on the device onto an 
instrument of the same family 

(DOWNLOAD)

, it is necessary to 

proceed in the following way:   
1) position both dip switch of KEY 01 in the 

ON 

mode.   

2) connect the device to an instrument TLK having the same 
features of the one from which has been downloaded the desired 
configuration,   plugging the special connector.   
3) verify that the instrument and the device are supplied  
4) observe the indication led on the device KEY 01: it has to result 
green, because if the led results green blinking or red blinking, this 
means that on the device it has not been downloaded any valid 
configuration and therefore it’s useless to continue. 
5) if the les results green, press the button placed on the device.   
6) observe the indication led : after having pressed the button, the 
led becomes red and therefore, at the end of the data transfer, it 
becomes green.   
7) now it is possible to disconnect the device. 
 
For additional info, please have a look at the KEY01 instruction 
manual. 
 
 

5 - PROGRAMMABLE PARAMETERS

 

 
Here following are described all the parameters available on the 
instrument. Some of them could be not present or because they are 
depending on the type of instrument or because they are 
automatically disabled as unnecessary. 

 
5.1 - PARAMETERS TABLE

 

 

Group “SP” 

(parameters relative to the Set Point) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

1

 

nSP

 

Number of 
programmable Set 
point

 

 1 ÷ 4

 

1

 

 

2

 

SPAt

 

Active Set point 

 

1 ÷ nSP

 

1

 

 

SP1

  Set Point 1

 

SPLL ÷ SPHL

 

0

 

 

4

SP2

  Set Point 2

 

SPLL ÷ SPHL

0

 

 

5

SP3

  Set Point 3

 

SPLL ÷ SPHL

0

 

 

6

SP4

  Set Point 4

 

SPLL ÷ SPHL

0

 

 

7

 

SPLL

Low Set Point 

 

-1999 ÷ SPHL -1999

 

8

 

SPHL

High Set Point 

 

SPLL ÷ 9999

9999

   

Group “InP” 

(parameters relative to the measure input) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

9

HCFG

Input type 

tc / rtd / I / 

UoLt / SEr 

tc  

10

SEnS

Probe type 

tc : 

J/ CrAL/ S/ b/ 

E/ L/ n/ r/ t/ C/

Ir.J / Ir.CA 

rtd : 

Pt1 / Ptc / ntc

I : 

0.20 / 4.20 

UoLt :

 

 

0.50 / 0.60 / 
12.60 / 0.5 / 

1.5 / 0.10 / 

2.10  

J  

11

rEFL

Reflection coefficient 
for IRS sensors 

0.10 ÷ 1.00 

1.00   

12

SSC

  Low scale limit in case 

of input with V / I 
signals  

-1999 ÷ FSC

 

13

FSC

  High scale limit in case 

of input with V / I 
signals  

SSC ÷ 9999 

 

14

dP 

  Number of decimal 

figures 

tc/rtd :

 

 

0 / 1 

UoLt / I / SEr: 

0 ÷ 3 

0  

15

Unit

  Temperature unit of 

measurement 

tc/rtd :  

°C / °F 

°C  

16

FiL

  Input digital filter  

0FF÷ 20.0 

sec. 

0.2  

17

OFSt

Measuring Offset 

-1999 ÷ 9999

 

18

 rot 

Rotation of the 
measuring straight line 

0.000 ÷ 2.000 1.000  

19

InE

  “OPE” functioning in 

case of measuring error 

Our / Or / Ur 

OUr   

20

OPE 

Output power in case of 
measuring error 

-100 ÷ 100 

0  

21

dIF

  Digital input function 

noF / AaC / 

ASi / HoLd / 

OFF / CHSP / 
SP1.2 /HE.Co

noF  

Group “O1” 

(parameters relative to output 1) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

22

O1F

  Functioning of output 1 

if digital type  

1.rEG / 2.rEG 

ALno / ALnc 

OFF  

1.rEG  

23

Aor1

Beginning of output 1 
scale if analogical type 

0 / no_0 

 

24

Ao1F

Functioning of output 1 
if analogue type 

1.rEG / 2.rEG 

r.inP / r.Err 

r.SP / r.SEr  

OFF 

1.rEG  

25

Ao1L

Minimum reference for 
analogical output 1 for 
signal retransmission 

-1999 ÷ Ao1H

 

26

Ao1H

Maximum reference for 
analogical output 1 for 
signal retransmission 

Ao1L ÷ 9999

 

Group “O2” 

(parameters relative to output 2) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 14

 

27 

O2F

  Functioning of output 2 

if digital type  

1.rEG / 2.rEG 

ALno / ALnc 

OFF  

OFF  

28 

Aor2

  Beginning of output 2 

scale if analogical type 

0 / no_0 

 

29 

Ao2F

  Functioning of output 2 

if analogue type 

1.rEG / 2.rEG 

r.inP / r.Err 

r.SP / r.SEr  

OFF 

OFF  

30 

Ao2L

  Minimum reference for 

analogical output 2 for 
signal retransmission 

-1999 ÷ Ao2H 

 

31 

Ao2H

  Maximum reference for 

analogical output 2 for 
signal retransmission 

Ao2L ÷ 9999 

 

Group “O3” 

(parameters relative to output 3) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

32 

O3F

  Functioning of output 3  1.rEG / 2.rEG 

ALno / ALnc 

OFF  

OFF  

Group “O4” 

(parameters relative to output 4) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

33 

O4F

  Functioning of output 4  1.rEG / 2.rEG 

ALno / ALnc 

OFF  

OFF  

Group “AL1”

 (parameters relative to alarm AL1) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

34 

OAL1

  Output where alarm 

AL1 is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

Out2  

35 

AL1t

  Alarm AL1 type 

LoAb / HiAb 

LHAb / LodE 

HidE / LHdE 

LoAb  

36 

Ab1

  Alarm AL1 functioning 

0 ÷ 15 

 

37 

AL1

  Alarm AL1 threshold 

 AL1L÷ AL1H 

 

38 

AL1L

  Low threshold band 

alarm AL1 or Minimum 
set alarm AL1 for high 
or low alarm 

-1999 ÷ AL1H  -1999  

39 

AL1H

  High threshold band 

alarm AL1 or Maximum 
set alarm AL1 for high 
or low alarm 

AL1L ÷ 9999  9999   

40 

HAL1

  Alarm AL1 hysteresis 

OFF ÷ 9999 

 

41 

AL1d

  Activation delay of 

alarm AL1 

OFF ÷ 9999  

sec. 

OFF  

42 

AL1i

  Alarm AL1 activation in 

case of measuring error 

no / yES 

no 

 

Group “AL2”

 (parameters relative to alarm AL2) 

Par. Description  Range 

Def. 

Note 

43

  OAL2 

Output where alarm 
AL2 is addressed

 

Out1 / Out2 
Out3 / Out4 

OFF

 

OFF

   

44

  AL2t 

Alarm AL2 type

 

LoAb / HiAb 

LHAb / LodE 

HidE / LHdE

 

LoAb

   

45

  Ab2 

Alarm AL2 functioning

 

0 ÷ 15

 

0

 

 

46

  AL2 

Alarm AL2 threshold

 

 AL2L÷ AL2H

 

0

 

 

47

  AL2L 

Low threshold band 
alarm AL2 or Minimum 
set alarm AL2 for high 
or low alarm

 

-1999 ÷ AL2H

 

-1999

 

48

  AL2H 

High threshold band 
alarm AL2 or Maximum 
set alarm AL2 for high 
or low alarm

 

AL2L ÷ 9999

 

9999

   

49

  HAL2 

Alarm AL2 hysteresis

 

OFF ÷ 9999

 

1

 

 

50

  AL2d 

Activation delay of 
alarm AL2

 

OFF ÷ 9999  

sec.

 

OFF

   

51

AL2i

Alarm AL2 activation in 
case of measuring error

 

no / yES

 

no

 

 

Group “AL3”

 (parameters relative to alarm AL3) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

52

OAL3

Output where alarm 
AL3 is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

OFF  

53

AL3t

Alarm AL3 type 

LoAb / HiAb 

LHAb / LodE 

HidE / LHdE 

LoAb  

54

Ab3

  Alarm AL3 functioning 

0 ÷ 15 

 

55

AL3

  Alarm AL3 threshold 

AL3L÷ AL3H

 

56

AL3L

Low threshold band 
alarm AL3 or Minimum 
set alarm AL3 for high 
or low alarm 

-1999 ÷ AL3H -1999  

57

AL3H

High threshold band 
alarm AL3 or Maximum 
set alarm AL3 for high 
or low alarm 

AL3L ÷ 9999

9999   

58

HAL3

Alarm AL3 hysteresis 

OFF ÷ 9999 

 

59

AL3d

Activation delay of 
alarm AL3 

OFF ÷ 9999 

sec. 

OFF  

60

AL3i

Alarm AL3 activation in 
case of measuring error 

no / yES 

no 

 

Group “LbA” 

(parameters relative to Loop Break Alarm) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

61

OLbA

Output where alarm 
LbA is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

OFF  

62

LbAt

Time necessary to 
activate alarm LbA  

OFF ÷ 9999 

sec. 

OFF  

Group “Hb” 

(parameters relative to Heater  Break Alarm) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

63

OHb

  Output where alarm HB 

is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

OFF  

64

IFS

  High scale limit for input 

TA HB 

0.0 ÷ 100.0 

100.0  

65

HbF

  Alarm HB function 

1 / 2 / 3 / 4 

 

66

IHbL

Low alarm HB threshold 
(with Out 1rEG ON) 

0.0 ÷ IFS 

0.0   

67

IHbH

High alarm HB 
threshold (with Out 
1rEG OFF) 

IHbL ÷ IFS 

100.0  

Group “rEG” 

(parameters relative to control) 

Par.

 

Description

 

Range

 

Def.

 

Note

68 

Cont

Control type 

Pid / On.FA 

On.FS / nr  

3 Pt 

Pid  

69 

Func

Functioning mode 
output 1rEg 

HEAt / CooL  HEAt   

70 

HSEt

Hysteresis of ON/OFF 
control 

0 ÷ 9999 

 

71 

Auto 

Autotuning Fast enable 

OFF /  

1 / 2 / 3 / 4 

1  

72 

SELF

Selftuning enable 

no / yES 

no 

 

73 

Pb

  Proportional band 

0 ÷ 9999 

50 

 

74 

Int

  Integral time 

OFF ÷ 9999 

sec. 

200  

75 

dEr

  Derivative time 

OFF÷ 9999 

sec. 

50  

76 

FuOc

Fuzzy overshoot control  0.00 ÷ 2.00 

0,5 

 

77 

tcr1

  Cycle time of output 

1rEg 

0.1 ÷ 130.0 

sec. 

20,0  

78 

Prat

  Power ratio  2rEg / 1rEg  0.01 ÷ 99.99 

1.00   

79 

tcr2

  Cycle time of  2rEg  

0.1 ÷ 130.0 

sec. 

10.0  

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 15

 

80 

rS

  Manual reset 

-100.0÷100.0 

0.0  

81 

  tcor  

Time for motorised 
actuator run 

4 ÷ 1000 sec. 

 

82 

SHrI

  Minimum value for 

motorised actuator 
control 

0.0 ÷ 10.0 % 

0.0 

 

83 

PoSI

  Switch on position for 

motorised actuator 

no /  

cLoS / oPEn 

no  

84 

SLor

  Gradient of rise ramp 

0.00 ÷ 99.99  

/ InF 

unit/min. 

InF  

85 

dur.t

  Duration time 

0.00 ÷ 99.59  

/ InF 

 hrs.-min. 

InF  

 

86 

SLoF

  Gradient of fall ramp 

0.00 ÷ 99.99  

/ InF  

unit / min. 

InF  

87 

ro1.L

  Minimum power in 

output from 1rEG 

0 ÷ ro1.H 

0  

88 

ro1.H

  Maximum power from 

output from 1rEG 

ro1.L ÷ 100 

100  

89 

ro2.L

  Minimum power in 

output from 2rEG 

0 ÷ ro2.H 

0  

90 

ro2.H

  Maximum power from 

output from 2rEG 

ro2.L ÷ 100 

100  

91 

OPS1

  Power variation speed 

in output from 1rEG 

1 ÷ 50 / InF 

% / sec. 

InF  

92 

OPS2

  Power variation speed 

in output from 2rEG 

1 ÷ 50 / InF 

% / sec. 

InF  

93 

thr1

  Split Range Power 

threshold  of output 
1rEG 

-100 ÷ 100 % 

 

94 

thr2

  Split Range Power 

threshold  of output 
2rEG 

-100 ÷ 100 % 

 

95 

St.P

  Soft-Start power 

OFF /  

-100 ÷ 100 % 

OFF  

96 

SSt

  Soft-Start time 

OFF /  

0.1÷7.59  

/ InF  

hrs.-min. 

OFF  

Group “PAn”

 (parameters relative to the user interface) 

Par.

 

Description

 

Range

 

Def.

 

Note

97 

USrb

  Functioning of key “U” 

noF / tunE / 

OPLO / Aac / 

ASi / CHSP / 

OFF 

noF  

98 

diSP

  Variable visualized on 

the SV display  

OFF / Pou / 

SP.F / SP.o / 

AL1 / AL2 / 

AL3 

SP.F  

99 

Edit

  Fast programming of  

active Set Point and 
alarms  

SE / AE / 

SAE / SAnE 

SAE  

Group “SEr”

 (parameters relative to the serial communication) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

100 

Add

  Station address in case 

of serial communication 

0 … 255 

 

101 

baud

  Transmission speed 

(Baud rate)  

1200 / 2400 / 

9600 / 19.2 / 

38.4 

9600  

102 

PACS

  Access at the 

programming through 
serial port 

LoCL / LorE 

LorE   

 
5.2 - PARAMETERS DESCRIPTION 
 
GROUP “ 

]

SP”  (PARAMETERS RELATIVE TO THE SET POINT): 

These allow the setting of the control Sets and the Sets 
function modes. 
nSP

 – NUMBER OF PROGRAMMABLE SET POINTS: This allows 

definition of the number of Set Points which will be programmed and 
stored (from 1 to 4). 

SPAt

 – ACTIVE SET POINT : If more than one Set Point is stored, 

this allows selection of the active Set Point.  

SP1 - 

SET POINT 1: Value of the Set Point n. 1  

SP2 - 

SET POINT 2: Value of the Set Point n. 2 (it appears if “nSP” 

>2 only) 

SP3 - 

SET POINT 3: Value of the Set Point n. 3 (it appears if “nSP” 

>3 only)  

SP4 - 

SET POINT 4: Value of the Set Point n. 4 (it appears if “nSP” 

=4 only)  

SPLL

 – LOW SET POINT: Lower value programmable as Set Point 

SPHL 

– HIGH SET POINT : Higher value programmable as Set 

Point 

 
GROUP “ 

]

InP” (PARAMETERS RELATIVE TO THE INPUTS):

 

These permit the definition of visualization modes of the 
variable measured by the probe. 
HCFG

 – INPUT TYPE : This permits selection of the input type : 

thermocouples (tc), thermo-resistances or thermistors  (rtd), 
normalized signals in current (I),  in voltage (UoLt) or a 
measurement coming from the serial line (SEr). 

SEnS

 – PROBE TYPE: Depending on what is programmed on par. 

“HCFG” this permits  the type of probe to be selected : 
- for thermocouples (“HCFG”=tc): J (J), K (CrAL), S (S), B (b), C (C), 
E (E), L (L), N (n), R (r), T (t), or for TECNOLOGIC infrared sensors 
IRS series range A with linearization J (Ir.J) or K (Ir.CA) 
- thermoresistances/thermistors (“HCFG”=rtd): Pt100 IEC (Pt1) or 
thermistors PTC KTY81-121 (Ptc) or NTC 103AT-2 (ntc) 
- normalized signals in current (“HCFG”=I): 0..20 mA (0.20) or 4..20 
mA (4.20) 
- normalized signals in voltage (“HCFG”=UoLt): 0..50 mV (0.50), 
0..60 mV (0.60), 12..60 mV (12.60), 0..5 V (0.5), 1..5 V (1.5), 0..10 V 
(0.10) or 2..10 V (2.10). 

rEFL

 - REFLECTION COEFFICIENT FOR IRS SENSORS: this can 

be used only when “SEnS” = Ir.J or Ir.CA and allows any measuring 
errors caused by the environment’s lighting and the reflexivity of the 
material to be corrected. Set this parameter to a high value when 
the material to be measured is particularly light/reflective and reduce 
it when the surface is especially dark/non-reflective , keeping in 
mind however that for most materials,  the recommended value is 
between 1.00 and  0.80. 

SSC

 – LOW SCALE LIMIT IN EVENT OF INPUT WITH V/I 

SIGNALS  : This is the value the instrument has to visualise when  
the minimum value that can be measured on the scale (0/4 mA, 
0/12 mV, 0/1 V or 0/2 V) is present at the output. 

FSC

 – HIGH SCALE LIMIT IN EVENT OF INPUT WITH V/I 

SIGNALS  : This is the value the instrument has to visualise when 
the maximum value that can be measured on the scale (20 mA, 50 
mV, 60 mV, 5 V or 10 V) is present at the input. 

dP

 – NUMBER OF DECIMAL FIGURES: This allows determination 

of the measuring resolution as 1 (0), 0.1 (1), 0.01 (2), 0.001 (3). In 
the case of temperature probes the allowed resolutions are 1° (0) 
and  0.1° (1). 

Unit

 – TEMPERTURE UNIT OF MEASUREMENT : When the 

temperature is measured by temperature probes, this parameter 
permits definition if the visualisation is expressed as degree 
Centigrade (°C) or Fahrenheit (°F). 

Filt

 – INPUT DIGITAL FILTER : This permits  programming of the 

constant of time of the software filter referring to the measured input 
value (in sec.) in order to reduce noise sensitivity (increasing the 
time of reading). 

OFSt

 – MEASURING OFFSET: Positive or negative Offset which is 

added to the value measured by the probe. 

rot

 – ROTATION OF THE MEASURING STRAIGHT LINE: In this 

way the offset programmed on par. “OFSt” is not constant for all 
measurements. By programming “rot”=1.000, the value “OFSt” is 
simply added to the value read by the probe before visualisation and 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 16

 

it remains constant for all the measurements. If instead one does 
not want the programmed offset to be constant for all the 
measurements, it is possible to carry out calibration on two desired 
values. 
 In this case, to define the values to be programmed on par. “OFSt” 
and “rot”, it is necessary to enforce the following formulae : 

“rot” = (D2-D1) / (M2-M1)  

“OFSt” = D2 - (“rot” x M2)

 

where: M1 =measured value  1; D1 = visualisation value when the 
instrument measures M1 
M2 =measured value. 2; D2 = visualisation value when the 
instrument measures M2 
It then follows that the instrument will visualise : 

DV = MV x “rot” + 

“OFSt” 

where:  DV = visualised value; MV= measured value 

InE – 

“OPE” FUNCTIONING IN CASE OF MEASUREMENT 

ERROR: This defines the error conditions of the input allowing the 
instrument to give the power programmed on par. “OPE” as output. 
The possibilities are : 
= Or : the condition occurs in case of over-range or probe breakage 
= Ur : the condition occurs in case of under-range or probe 
breakage 
= Our : the condition occurs in case of over-range or under-range or 
probe breakage 

OPE

 – OUTPUT POWER IN CASE OF MEASUREMENT ERROR: 

This permits setting of the power that the instrument has to give as 
output in case of measurement error.  For the ON/OFF regulators 
the power is calculated considering a cycle time equal to 20 sec. 

 

dIF

 - DIGITAL INPUT FUNCTION: this allows the digital input 

function to be defined as: 
= noF : the input does not carry out any function 
= Aac : By closing the contact connected to the digital input it is 
possible to reset a memorised alarm  
= ASi

 

:By closing the contact connected to the digital input it is 

possible to silence an active alarm  
= HoLd : By closing the contact connected to the digital input the 
measurement taken at that moment is blocked (N.B.: not the 
reading on the display, therefore the indication may stabilise itself 
with a delay that is proportional to the measuring filter). With the 
hold function turned on, the instrument carries out control according 
to the memorised measurement. By opening the contact, the 
instrument starts normal measurement acquisition once more. 
= OFF : When the instrument is in “rEG” status, by closing the 
contact connected to the digital input, the instrument is placed in 
OFF status. . 
= CHSP : by closing and reopening the contact connected to the 
digital input, it is possible to select one of the 4 memorised set 
points in rotation.  
= SP1.2

 

: By closing the contact connected to the digital input, the 

set point SP2 is selected while opening the contact selects the set 
point SP1 . The function can only be activated using “nSP” = 2 , . 
= HE.Co

 

: Closing the contact connected to the digital input it is 

possible to select as active the set point SP2 in “CooL” mode. 
Reopening the contact is select as active the set point SP1 in 
“HEAt” mode. This function is possible only when “nSP” = 2. 
 

GROUP “ 

]

 O1” (PARAMETERS RELATIVE TO OUTPUT OUT1):

 

They permit to program the output OUT1 functioning.

 

O1F

 – FUNCTIONING OF OUTPUT OUT 1 DIGITAL TYPE: This 

defines the functioning of output OUT 1 as: control output 1 (1.rEG), 
control output 2 (2.rEG), alarm output as normally open (ALno), 
output alarm normally closed (ALnc), output not used (OFF). 

Aor1

 - BEGINNING OF OUTPUT SCALE 1 ANALOGICAL TYPE: 

This allows the beginning of the analogical output OUT1 to be set. 
This parameter will therefore be set with: "0" if one intends to use 
the beginning of the scale as being equal to 0 (0 mA, or 0 V) or 
"no_0" if one intends to use the beginning of the scale as being 
other than 0  (4 mA, or 2 V). 

Ao1F

 - ANALOGICAL OUTPUT OUT1 FUNCTION: This determines 

the function of the OUT 1 output as: control output 1 (1.rEG), control 
output 2 (2.rEG), measurement retransmission output (r.inP), error 
retransmission output [SP-PV] (r.Err), Active Set Point 

retransmission output (r.SP), output guided by the instrument’s 
serial communications line (rSEr), output not used (OFF). 

Ao1L - 

MINIMUM REFERENCE FOR ANALOGICAL OUTPUT OUT 

1 FOR SIGNAL RETRANSMISSION: in the event that the analogical 
output function is configured for the retransmission of the signal, set 
this parameter with the value to which the instrument must supply 
the minimum value in output (0/4 mA or 0/2 V) 

Ao1H - 

MAXIMUM

 

REFERENCE FOR ANALOGICAL OUTPUT 

OUT 1 FOR SIGNAL RETRANSMISSION: in the event that the 
analogical output function is configured for the retransmission of the 
signal, set this parameter with the value to which the instrument 
must supply the maximum value in output (20 mA or 10 V). 

 
GROUP “ 

]

 O2” (PARAMETERS RELATIVE TO OUTPUT OUT2):

 

They permit to program the output OUT2 functioning.

 

O2F

 - FUNCTIONING OF OUTPUT OUT 2 DIGITAL TYPE: Equal to 

“O1F” but referred to output OUT2. 

Aor2

 - BEGINNING OF ANALOGICAL OUTPUT SCALE OUT 2 : 

Equal to “Aor1” but referred to output OUT2. 

Ao2F

 - ANALOGICAL OUTPUT OUT2 FUNCTION: Equal to “Ao1F” 

but referred to output OUT2. 

Ao2L - 

MINIMUM REFERENCE FOR ANALOGICAL OUTPUT OUT 

2 FOR SIGNAL RETRANSMISSION: Equal to “Ao1L” but referred to 
output OUT2.  

Ao2H - 

MAXIMUM REFERENCE FOR ANALOGICAL OUTPUT 

OUT 2 FOR SIGNAL RETRANSMISSION: Equal to “Ao1H” but 
referred to output OUT2.  

 
GROUP “ 

]

 O3” (PARAMETERS RELATIVE TO OUTPUT OUT3):

 

They permit to program the output OUT3 functioning.

 

O3F

 – FUNCTIONING OF OUTPUT OUT 3 DIGITAL TYPE: Equal 

to “O1F” but referred to OUT3. 
 

GROUP “ 

]

 O4” (PARAMETERS RELATIVE TO OUTPUT OUT4):

 

They permit to program the output OUT4 functioning.

 

O4F

 – FUNCTIONING OF OUTPUT OUT 4 DIGITAL TYPE: Equal 

to “O1F” but referred to OUT4. 
 

GROUP  “ 

]

AL1” (PARAMETERS RELATIVE TO ALARM AL1):

 

These permit setting of the process alarm AL1 function. 
OAL1

 – OUTPUT WHERE ALARM AL1 IS ADDRESSED: It defines 

to which output the alarm AL1 has to be addressed. 

AL1t

 – ALARM AL1 TYPE: permits the choice of behaviour for 

alarm A1, by 6 different selections:   
= LoAb – ABSOLUTE LOW ALARM : The alarm is activated when 
the process value goes below the alarm threshold set on parameter 
"AL1". 
= HiAb - ABSOLUTE HIGH ALARM: The alarm is activated when 
the process value goes above the alarm threshold set on parameter 
"AL1". 
= LHAb - ABSOLUTE BAND ALARM: The alarm is activated when 
the process value goes below the alarm threshold set on parameter 
"AL1L" or goes higher than alarm set on parameter "AL1H". 
= LodE – DEVIATION LOW ALARM: The alarm is activated when 
the process value goes below the value [SP + AL1] 
= HidE – DEVIATION HIGH ALARM: The alarm is activated when 
the process value goes above the value [SP + AL1] 
= LHdE – DEVIATION BAND ALARM: The alarm is activated when 
the process value goes below the value [SP + AL1L] or goes above 
the value [SP + AL1H] 

Ab1

 – ALARM AL1 FUNCTION: This permits definition of alarm AL1 

functions, by entering a number between 0 and 15. The number to 
be programmed, that corresponds to the desired function, is 
obtained adding the values reported in the following description : 
ALARM BEHAVIOUR AT SWITCH ON: 
+0 = NORMAL BEHAVIOUR: The alarm is always activated when 
there are alarm conditions. 
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, at switch on, 
the instrument is in alarm condition, the alarm is not activated. It will 
be activated only when the process value goes beyond and then 
returns to alarm conditions. 
ALARM DELAY:  

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 17

 

+0 = ALARM NOT DELAYED: The alarm is immediately activated 
when the alarm condition occurs. 
+2 = ALARM DELAYED: When the alarm condition occurs, delay 
counting starts as programmed on par. “ALnd” (expressed in sec.) 
and the alarm will be activated only after this time has elapsed. 
ALARM LATCH: :  
+ 0 = ALARM NOT LATCHED: The alarm remains active in alarm 
conditions only. 
+ 4 = ALARM LATCHED: The alarm is active in alarm conditions 
and remains active even if these conditions no longer exist, until the 
correctly programmed key “U” (“USrb”=Aac) has been pushed 
ALARM AKNOWLEDGEMENT: :  
+ 0 = ALARM NOT AKNOWLEDGED: The alarm remains always 
active in alarm conditions. 
+ 8 = ALARM AKNOWLEDGED: The alarm is active in alarm 
conditions and can be deactivated through key “U” if properly 
programmed (“USrb”=ASi), also if alarm conditions still exist. 

AL1

 – ALARM AL1 THRESHOLD : Alarm AL1 threshold for low and 

high alarms. 

AL1L

 – LOW ALARM AL1 : Alarm AL1 low threshold when the 

alarm is a band type or minimum set of AL1 alarm threshold when 
the alarm is low or high type. 

AL1H

 – HIGH ALARM AL1: Alarm AL1 high threshold when the 

alarm is a band type or maximum set of AL1 alarm threshold when 
the alarm is low or high type. 

HAL1 - 

ALARM AL1 HYSTERESIS: Asymmetrical semi-band 

relative to alarm AL1 threshold which defines the deactivation value 
of alarm AL1. 

AL1d

 – ACTIVATION DELAY OF ALARM AL1: This permits 

definition of  alarm delay activation AL1 when the delay function on 
par. “Ab1” is activated. 

AL1i

 – ALARM AL1 ACTIVATION IN CASE OF MEASUREMENT 

ERROR: This permits a definition of measurement error conditions, 
i.e whether the alarm has to be active ("yES") or not ("no"). 
 

GROUP “ 

]

AL2” (PARAMETERS RELATIVE TO ALARM AL2): 

These permit the setting of the process alarm AL2 functions. 
OAL2

 - OUTPUT WHERE ALARM AL2 IS ADDRESSED: this 

defines on which output the alarm AL2 has to be addressed. 

AL2t

 - ALARM AL2 TYPE: Similar to “AL1t” but referring to alarm 

AL2. 

Ab2

 - ALARM AL2 FUNCTIONING: Similar to “Ab1t” but referring to 

alarm AL2

AL2

 - ALARM AL2 THRESHOLD : Similar to “AL1” but referring to 

alarm AL2

AL2L

 - LOW ALARM AL2 : Similar to “AL1L” but referring to alarm 

AL2

AL2H

 - HIGH ALARM AL2 : Similar to “AL1H” but referring to alarm 

AL2. 

HAL2 - 

ALARM AL2 HYSTERESIS: Similar to “HAL1” but referring 

to alarm AL2. 

AL2d

 - ACTIVATION DELAY OF ALARM AL2: Similar to “AL1d” but 

referring to alarm AL2. 

AL2i

 - ALARM AL2 ACTIVATION IN CASE OF MEASUREMENT 

ERROR: Similar to “AL1i” but referring to alarm AL2. 
 

GROUP “ 

]

AL3” (PARAMETERS RELATIVE TO ALARM AL3): 

These permit the setting of the process alarm AL3. 
OAL3

 - OUTPUT WHERE ALARM AL3 IS ADDRESSED: It defines 

on which output the alarm AL3 has to be addressed. 

AL3t

 - ALARM AL3 TYPE: Similar to “AL1t” but referring to alarm 

AL3. 

Ab3

 - ALARM AL3 FUNCTIONING: Similar to “Ab1t” but referring to 

alarm AL3

AL3

- ALARM AL3 THRESHOLD : Similar to “AL1” but referring to 

alarm AL3

AL3L

 - LOW ALARM AL3 : Similar to “AL1L” but referring to alarm 

AL3

AL3H

 - HIGH ALARM AL3 : Similar to “AL1H” but referring to alarm 

AL3. 

HAL3 - 

ALARM AL3 HYSTERESIS: Similar to “HAL1” but referring 

to alarm AL3. 

AL3d

 - ACTIVATION DELAY OF ALARM AL3: Similar to “AL1d” but 

referring to alarm AL3. 

AL3i

 - ALARM AL3 ACTIVATION IN CASE OF MEASUREMENT 

ERROR: Similar to “AL1i” but referring to alarm AL3. 
 

GROUP “LbA” (PARAMETERS RELATIVE TO THE LOOP 
BREAK ALARM): this contains the parameters relative to the 
Loop Break alarm (control loop interruption), which intervenes 
when, for any reason (short-circuit of a thermocouple, load 
interruption, etc) the control loop is interrupted.  
OLbA

 – OUTPUT WHERE THE LOOP BREAK ALARM IS 

ADDRESSED: This defines to which output the LOOP BREAK alarm 
has to be addressed.  

LbAt

 – TIME NECESSARY TO ACTIVATE THE LOOP BREAK 

ALARM :  Delay time to the intervention of the Loop Break alarm. 
The alarm intervenes when the output power remains at 100% for 
the time programmed on this parameter (in sec.) 
 

GROUP  “ 

]

Hb” (PARAMETERS RELATIVE TO THE HEATER  

BREAK ALARM): this contains the parameters relative to the 
Heater  Break alarm (heating element breakage). 
This function is present only when the instrument is equipped 
with the input (TAHB) to measure the current absorbed by the 
load. This input accepts signals coming from current 
transformers (TA) with max. output 50 mA. 
OHb

 – OUTPUT WHERE HEATER BREAK ALARM IS 

ADDRESSED: this defines to which output the HEATER BREAK 
alarm has to be addressed.  

IFS

 – HIGH SCALE LIMIT FOR INPUT TA HB: Value that the 

instrument has to visualise when as input TA HB It is present a 
value of 50 mA. 

HbF

 – ALARM HB FUNCTION: It defines the functioning of the 

Heater Break alarm as: 
= 1 : The alarm is active when, with output 1rEG active, the current 
measured by the input TAHB is lower than the value programmed 
on par. "IHbL" . 
= 2 : The alarm is active when, with output 1rEG not active, the 
current measured by the input TAHB is higher than the value 
programmed on par. "IHbH" . 
= 3 : The alarm is active when, with output 1rEG active, the current 
measured by the input TAHB is lower than the value programmed 
on par. "IHbL" or with output 1rEG not active, the current measured 
by the input TAHB is higher than the value programmed on par. 
"IHbH".   
= 4 : The alarm is active when the current measured by the input 
TAHB is lower than the value programmed on par. "IHbL"

 

or the 

measured current is higher than the value programmed on par. 
"IHbH", independently by the state of the output 1rEG.    

IHbL

 – LOW ALARM HB THRESHOLD: Enter the value of the 

current normally absorbed by the load driven by the output 1reG, 
when this is active. 

IHbH

 – HIGH ALARM HB THRESHOLD: Enter the value of the 

current normally absorbed by the load driven by the output 1reG, 
when this is not active.

 

 

GROUP “ 

]

rEG” (PARAMETERS RELATIVE TO THE CONTROL): 

this contains the parameters relative to control functions. 
Cont 

– CONTROL TYPE: This permits selection of one of the 

possible control modes offered by the instrument : PID (Pid), PID for 
for motorised actuators (3Pt), ON/OFF with asymmetrical hysteresis 
(On.FA),  ON/OFF with symmetrical hysteresis (On.FS), Neutral 
Zone ON/OFF (nr).

 

Func –

 FUNCTIONING MODE OUTPUT 1rEG:

 

this permits one to 

decide whether the control output 1rEG has to carry out a reverse 
action, as for example a Heating process ("HEAt") or a direct action, 
as for example a Cooling process ("CooL"). 

HSEt

 – ON/OFF CONTROL HYSTERESIS: Semi-band relative to 

the Set Point which defines the activation and deactivation values of 
the control output/s in case of  ON/OFF control (On.FA, On.FS, nr). 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 18

 

Auto

 – AUTO-TUNING FAST ENABLE : this parameter allows one  

to decide how Auto-tuning has to be carried out. The possible 
selections are : 
= 1 – if auto-tuning is desired automatically, each time the 
instrument is switched on, on the condition that the process value is 
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” 
=CooL) than [SP+ |SP/2|]. 
= 2 – if auto-tuning is desired automatically, the next time the 
instrument is switched on, on the condition that the process value is 
lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” 
=CooL) than [SP+ |SP/2|], and once the tuning is finished, the par. 
“Auto” is automatically swapped to the OFF state  
= 3  - if manual auto-tuning is desired, by selecting  par. “tunE” in 
the main menu or by correctly programming key “U” as “USrb” = 
tunE. In this case the auto-tuning starts without any control on the 
process value condition. It is recommended to use this option, 
starting the auto-tuning when the process value is as far as possible 
from the Set Point because, in order to feature the Auto-tuning 
FAST with its best performances , it is preferable to respect this 
condition. 
= 4  - if it’s desired to activate the autotuning automatically at the 
end of programmed Soft-Start cycle. The Autotuning will start at the 
condition that the process value is lower (with “Func” =HEAt) than 
[SP- |SP/2|] or higher (with “Func” =CooL) than [SP+ |SP/2|]. 
= OFF - Autotuning disabled. 
When it’s occurring an Autotuning cycle, led AT blinks. 

SELF

 – SELF-TUNING ENABLE: Parameter used to enable (yES) 

or disable (no) the Self-tuning function. Once the function has been 
enabled, the Self-tuning has to be started by selecting item “tunE”, 
in the main menu, or through key U properly programmed (“USrb” = 
tunE).When the Self-tuning function is active, led AT is permanently 
lit, and all the PID parameters ("Pb", "Int", "dEr", ecc.) are no longer 
visualised. 

Pb

 – PROPORTIONAL BAND: Width of the band around the Set 

Point within which the proportional control is performed. 

Int

 – INTEGRAL TIME: Integral time to be programmed in the PID 

algorithm, expressed in sec.  

dEr

 – DERIVATIVE TIME: : Derivative time to be programmed in the 

PID algorithm, expressed in sec.  

FuOc 

- FUZZY OVERSHOOT CONTROL: Parameter that permits 

the elimination of the variable over-shoots at the start up of the 
process or at the changing of the Set Point. A low value of this 
parameter reduces the overshoot while a high value increase it.  
 

tcr1

 – CYCLE TIME OF OUTPUT 1rEG : Cycle time of output 1rEG 

with PID control mode, expressed in sec.. 

Prat

 – POWER RATIO 2rEG / 1rEG : Parameter where it is possible 

to program the power ratio between the element controlled by output 
2rEG (ex.Cooling) and the element controlled by output 1rEG (ex. 
Heating) in case of PID double action control. 

tcr2

 - CYCLE TIME OF OUTPUT 2rEG : Cycle time of output 2rEG 

with PID double action control mode, expressed in sec.. 

rS

 -  MANUAL RESET: Power Offset added to the power increase of 

the proportional term, in order to eliminate the error when it is not 
present the integral value. This parameter is only visualised when  
“Int” =0. 

Specific parameters for PID control for motorised actuators 
with opening and closing controls that remain at the point they 
have reached if no command is given. If the actuator has no 
stop contacts that interrupt the action at the end of its run, it is 
necessary to equip the installation with these contacts. 
tcor - TIME OF MOTORISED ACTUATOR RUN

:  the time, 

expressed in seconds that it takes the actuator to pass from the 
“completely open” position to the “completely closed” position must 
be set on this parameter". 

SHrI

 - MINIMUM VALUE OF MOTORISED ACTUATOR CONTROL: 

this is the value that the control must have reached (in %) before it 
has an effect on the output. 

PoSi

 - POSITIONING OF THE MOTORISED ACTUATOR SWITCH 

ON : this allows to decide whether, when the instrument is switched 
on, the actuator must remain where it is ("no"), whether is must be 
taken to the maximum opening position ("oPEn") or the maximum 
closing position ("cLoS"). 

Parameters relative to the ramps, allowing the Set Point to be 
reached in a predetermined time.  
Furthermore, once the first Set (SP1) has been reached, it is 
possible to have automatic switching to the second Set (SP2) 
after a programmable time, thus obtaining a simple thermal 
cycle (functions available for all the control types)   
SLor

 – GRADIENT OF RISE RAMP:  Gradient of rise ramp to be 

carried out when the process value is lower than the active Set 
Point, expressed in unit/minute. 
Programming the parameter = InF the ramp is not active. 

dur.t - 

DWELL TIME: Dwell time of the Set Point SP1 before the 

automatic switching to SP2 (expressed in hrs. and min.) 
Using this parameter,

 

once the first Set (SP1) has been reached, it 

is possible to have automatic switching to the second Set (SP2) 
after a programmable time, thus obtaining a simple thermal cycle. 
Programming the parameter = InF the function is not active. 

SLoF

 - GRADIENT OF FALL RAMP:  Gradient of fall ramp to be 

carried out when the process value is higher than the active Set 
Point, expressed in unit/minute. 
Programming the parameter = InF the ramp is not active.

 

Parameters for the power limitation and output power variation 
speed functions, functions that can only be activated using 
single or dual action PID controls. 
ro1.L

 - MINIMUM OUTPUT POWER 1rEG: on this parameter set 

the value that one desires for the output 1rEG when the internal 
control decides that the power must be  0 %. 

ro1.H

 - MAXIMUM OUTPUT POWER 1rEG: on this parameter set 

the value that one desires for the output 1rEG when the internal 
control decides that the power must be100 %. 

ro2.L

 - MINIMUM OUTPUT POWER 2rEG: on this parameter set 

the value that one desires for the output 2rEG when the internal 
control decides that the power must be  0 %. 

ro2.H

 - MAXIMUM OUTPUT POWER 2rEG: on this parameter set 

the value that one desires for the output 2rEG when the internal 
control decides that the power must be100 %. 

OPS1

 - POWER VARIATION SPEED IN OUTPUT 1rEG: this sets 

the power variation speed for the control power in output 1rEG 
(expressed in % / sec). 

OPS2

 - POWER VARIATION SPEED IN OUTPUT  2rEG: this sets 

the power variation speed for the control power in output  2rEG 
(expressed in % / sec).

 

Parameters for the function of the SPLIT RANGE that can only 
be activated using the dual action PID control and can be used 
to delay or bring forward the intervention of the two actuators 
commanded by the instrument. Using this function, it is 
possible to optimise the intervention of the two actuators in 
such a way that their actions do not overlay or so that that they 
overlap so that the mix of the actuators’ two action is obtained .

 

thr1 - 

 POWER THRESHOLD AT WHICH THE OUTPUT 1rEG 

BEGINS TO OPERATE: set this parameter with the power value at 
which the output 1rEG begins to operate, keeping in mind the fact 
that the positive values bring forward the action while negative 
values delay it. 

thr2 - 

 POWER THRESHOLD AT WHICH THE OUTPUT 2rEG 

BEGINS TO OPERATE: set this parameter with the power value at 
which the output 2rEG begins to operate, keeping in mind the fact 
that negative values bring forward the action and the positive values 
delay it

 

Parameters relative to the Soft-Start function, which allows 
limitation of control power, when the instrument is switched 
on, for a predetermined time. This function is only available for 
PID control. 
St.P

 - SOFT START POWER: If parameter “SSt” is programmed 

with a value other than OFF, this is the power given as output at the 
instrument switch on, for the time “SSt”.  
Practically speaking, the instrument works in manual condition and 
switches to automatic control at the elapsing of time “SSt”. 
If instead par. “St.P” = OFF and a value is set  on par. “SSt” at 
switch on, the power calculated by the PID controller is divided by 
the time “SSt”, in order to calculate a ramp. The output power starts 
from 0 and is progressively increased, according to the calculated 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 19

 

ramp, until the time “SSt” is reached or until the power overcomes 
the power calculated by the PID controller. 

SSt

 - SOFT START TIME (for PID control only): Duration time in 

hours and min. of the Soft-Start described on pa. “St.P”.  
To disable the Soft-Start function set par. “SSt” = OFF. 

 
GROUP  “ 

]

PAn” (PARAMETERS RELATIVE TO THE USER 

INTERFACE) : This contains the parameters relative to the key 
U and display functions.

 

Usrb -

 KEY U FUNCTION : Decides which function is associated to 

key U. The possible selections are : 
= noF : no function 
= tunE : Pushing the key for 1 sec. at least, it is possible to 
activate/deactivate the Auto-tuning or the Self-tuning 
= OPLO : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the manual one (OPLO) and vice 
versa. 
= Aac : Pushing the key for 1 sec. at least, it is possible to 
acknowledge the alarm.  
= ASi : Pushing the key for 1 sec. at least, it is possible to 
acknowledge an active alarm  
 = CHSP : Pushing the key for 1 sec. at least, it is possible to select 
one of the 4 pre-programmed Set Points on rotation.  
= OFF : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the OFF control (OFF) and vice 
versa. 

diSP - 

VARIABLE VISUALISED ON THE DISPLAY SV:

 

 Parameter 

trough which it’s possible to decide what is visualised on the display 
SV : the active Set Point (= SP.F), the Set Point active when there 
are ramps (= SP.o), the control power (= Pou),  the alarm thresholds 
AL1, 2 or 3 (= AL1, AL2 or AL3) or it can be switched off (OFF). 

Edit 

- FAST PROGRAMMING OF ACTIVE SET POINT AND 

ALARMS: This decides which are the Sets that can be programmed 
by the fast procedure. The parameter can be programmed as : 
=SE: The active Set Point can be modified while the alarm 
thresholds cannot be modified 
=AE :The active Set Point cannot be modified while the alarm 
thresholds can be modified 
=SAE: If the active Set Point or the alarm thresholds can be 
modified 
=SAnE: If the active Set Point or the alarm thresholds cannot be 
modified 
 

GROUP “ 

]

SEr”

 

(PARAMETERS RELATIVE TO THE SERIAL 

COMMUNICATION):

 

If the instrument is equipped with RS485 

serial communication these parameters allow device 
configuration for communication. 
Add

 – STATION ADDRESS IN CASE OF SERIAL 

COMMUNICATION : This is used to set the instrument address in 
the communication net. Programme a different number for each 
station, from 1 to 255. 

baud

 – TRANSMISSION SPEED (BAUD RATE): Set the data 

transmission speed of the network to which the instrument is 
connected. The possible selections are 1200, 2400, 9600, 19.2 
(19200), 38.4 (38400). 
All stations must  have the same transmission speed. 

PACS

 ACCESS TO PROGRAMMING THROUGH SERIAL PORT : 

Programming access. If programmed as "LoCL" this means that the 
instrument can only be programmed from the keyboard, if 
programmed as "LorE" it can be programmed from both the 
keyboards and serial line. 
 
 
 
 
 
 
 
 
 
 
 

 

6 - PROBLEMS, MAINTENANCE AND GUARANTEE

 

 
 6.1 - ERROR SIGNALLING 

In error conditions, the instrument provides an output power as 
programmed on par “OPE” and activates the desired alarms, if the 
relative parameters “ALni” have been programmed = yES.

 

 
6.2 - CLEANING 

We recommend  cleaning of the instrument with a slightly wet cloth 
using water and not abrasive cleaners or solvents which may 
damage the instrument. 

 
6.3 - GUARANTEE AND REPAIRS

 

The instrument is under warranty against manufacturing flaws or 
faulty material, that are found within 12 months from delivery date.  
The guarantee is limited to repairs or to the replacement of the 
instrument.  
The eventual opening of the housing, the violation of the instrument 
or the improper use and installation of the product will bring about 
the immediate withdrawal of the warranty’s effects.  
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales 
department to obtain  authorisation for sending the instrument to our 
company.  
The faulty product must be shipped to TECNOLOGIC with a detailed 
description of the faults found, without any fees or charge for 
Tecnologic, except in the event of alternative agreements. 
 

7 - TECHNICAL DATA

 

 

7.1 – ELECTRICAL DATA

 

Power supply: 24 VAC/VDC, 100... 240 VAC +/- 10%  
Frequency AC: 50/60 Hz 
Power consumption: 10 VA approx. 
Input/s: 1 input for temperature probes: tc J,K,S ; RTD Pt 100 IEC; 
PTC KTY 81-121  (990

 Ω

 @ 25 °C); NTC 103AT-2 (10K

 @ 25 °C)  

or mV  signals 0...50 mV, 0...60 mV, 12 ...60 mV or normalized 
signals 0/4...20 mA, 0/1...5 V , 0/2...10 V.  
1 input for current transformer (50 mA max.) 

Error

 

Reason

 

Action 

 

- - - -

 

Probe interrupted 

uuuu

 

The measured variable 
is under the probe’s 
limits (under-range) 

oooo

 

The measured variable 
is over  the probe’s 
limits   (over-range) 

Verify the correct 
connection between 
probe and 
instrument and then 
verify the correct 
functioning of the 
probe 

ErAt

 

Auto-tuning not possible 
because the process 
value is higher (with 
“Func” =HEAt) than [SP- 
|SP/2|] or lower (with 
“Func” =CooL) than 
[SP+ |SP/2|] 

Swap the instrument 
to OFF control (OFF) 
and then to 
automatic control 
(rEG) in order to 
make the error 
message disappear. 
Once the error has 
been found, try to 
repeat  the auto-
tuning. 

noAt

 

Auto-tuning not finished 
within 12 hours 

Check the 
functioning of probe  
and actuator and try 
to repeat the auto-
tuning. 

LbA

 

Loop control interrupted 
(Loop break alarm) 

Check the working of 
probe  and actuator 
and swap the 
instrument to (rEG) 
control  

ErEP

 

Possible anomaly of the 
EEPROM memory 

Push key “P” 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 20

 

1 digital input for free voltage contact 
Impedance normalized signals input:  0/4..20 mA: 51 

;   

mV and V: 1 M

 

Output/s: Up to 4 digital outputs. Relay SPST-NO (OUT1:5 A-AC1, 2 
A-AC3 / 250 VAC; OUT2-3-4:3 A-AC1, 1 A-AC3 / 250 VAC) ; or in 
tension to drive SSR (7mA/ 14VDC).  
Up to 2 analogue outputs: 0/4 ..20 mA o 0/2 ..10 V. 
The output OUT1 for SSR can be 20mA/14VDC if the 12 VDC 
auxiliary supply output is not used. 
Auxiliary supply output: 12 VDC / 20 mA Max. 
Electrical life for relay outputs: 100000 operat. 
Installation category:  II 
Measurement category:  I 
Protection class against electric shock:  Class II  for Front panel 
Insulation:

 

Reinforced insulation between the low voltage section 

(supply and relay outputs) and the front panel; Reinforced insulation 
between the low voltage section (supply and relay outputs) and the 
extra low voltage section (inputs, analogue outputs, SSR outputs); 
analogue and SSR outputs optoisolated respect to the input. 50 V 
insulation between RS485 and extra low voltage section.

 

 

7.2 – MECHANICAL DATA

 

Housing: Self-extinguishing plastic, UL 94 V0 
Dimensions: 48 x 48 mm DIN, depth 98 mm 
Weight: 190 g approx. 
Mounting: Flush in panel in 45 x 45  mm hole 
Connections:  2 x 1 mm

2

 screw terminals block 

Degree of front panel protection : IP 54 mounted in panel with 
gasket 
Pollution situation: 2 
Operating temperature:  0 ... 50 °C 
Operating humidity: 30 ... 95 RH% without condensation 
Storage temperature: -10 ... +60 °C 
 

7.3 – MECHANICAL DIMENSIONS, PANEL CUT-OUT AND 
MOUNTING [mm]

 

 

 

 

 
7.4 – FUNCTIONAL FEATURES 

Control: ON/OFF, single and double action PID, PID

 

for motorized 

actuators with time positioning 
Measurement range: according to the used probe (see range table) 
Display resolution: according to the probe used  1/0,1/0,01/0,001 
Overall accuracy: +/- 0,15 % fs  
Max. cold junction compensation drift (in tc) : 0,04 °C/°C with 
operating temperature 0 ... 50 °C after warm-up of 20 min. 
Sampling rate: 130 ms. 
Serial Interface : RS485 insulated 
Communication protocol: MODBUS RTU (JBUS) 
Baud rate: Programmable from 1200 ... 38400 baud 
Display: Display: 4 digit, 1 Red (PV) and 1 green (SV), h 7 mm 
Compliance: ECC directive EMC 89/336 (EN 61326), ECC directive 
LV 73/23 and 93/68 (EN 61010-1) 
 

7.5

 – 

MEASURING RANGE TABLE 

INPUT 

“dP” = 0 

“dP”= 1, 2, 3 

tc J  

“HCFG” = tc 

“SEnS” = J

 

-160 ... 1000 °C 

- 256 ... 1832 °F

 

-160.0 ... 999.9 °C 

-199.9 ... 999.9 °F

 

tc K  

“HCFG” = tc 

“SEnS” = CrAl

 

-270 ... 1370 °C 

- 454 ... 2498 °F

 

-199.9 ... 999.9 °C 

-199.9 ... 999.9 °F

 

tc S  

“HCFG” = tc 

“SEnS” = S

 

-50 ... 1760 °C 

-58 ... 3200 °F

 

-50.0 ... 999.9 °C 

-58.0 ... 999.9 °F

 

tc B 

“HCFG” = tc 

“SEnS” = b

 

72 ... 1820 °C 

162 ... 3308 °F

 

72.0 ... 999.9 °C 

162.0 ... 999.9 °F

 

tc E 

“HCFG” = tc 

“SEnS” = E

 

-150 ... 750 °C 

-252 ... 1382 °F

 

-150.0 ... 999.9 °C 

-199.9 ... 999.9 °F

 

tc L 

“HCFG” = tc 

“SEnS” = L

 

-150 ... 900 °C 

-252 ... 1652 °F

 

-150.0 ... 900.0 °C 

-199.9 ... 999.9 °F

 

tc N 

“HCFG” = tc 

“SEnS” = n

 

-270 ... 1300 °C 

-454 ... 2372 °F

 

-199.9 ... 999.9 °C 

-199.9 ... 999.9 °F

 

tc R 

“HCFG” = tc 

“SEnS” = r

 

-50 ... 1760 °C 

-58 ... 3200 °F

 

-50.0 ... 999.9 °C 

-58.0 ... 999.9 °F

 

tc T 

“HCFG” = tc 

“SEnS” = t

 

-270 ... 400 °C 

-454 ... 752 °F

 

-199.9 ... 400.0 °C 

-199.9 ... 752.0 °F

 

tc C 

“HCFG” = tc 

“SEnS” = C

 

0 ... 2320 °C 

32 ... 4208 °F

 

0.0 ... 999.9 °C 

32.0 ... 999.9 °F

 

TECNOLOGIC IRS 

range “A” 

“HCFG” = tc 

“SEnS”= Ir.J - Ir.CA

 

-46 ... 785 °C 

-50 ... 1445 °F

 

-46.0 ... 785.0 °C 

-50.8 ... 999.9 °F

 

Pt100 (IEC) 

“HCFG” = rtd 
“SEnS” = Pt1

 

-200 ... 850 °C 

-328 ... 1562 °F

 

-199.9 ... 850.0 °C 

-199.9 ... 999.9 °F

 

 


background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 21

 

PTC (KTY81-121) 

“HCFG” = rtd 
“SEnS” = Ptc

 

-55 ... 150 °C 

-67 ... 302 °F

 

-55.0 ... 150.0 °C 

-67.0 ...302.0 °F

 

NTC (103-AT2) 

“HCFG” = rtd 
“SEnS” = ntc

 

-50 ... 110 °C 

-58 ... 230 °F

 

-50.0 ... 110.0 °C 

-58.0 ... 230.0 °F

 

0..20 mA 

“HCFG” = I 

“SEnS” = 0.20

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99 
-1.999 ... 9.999

 

 

4..20 mA 

“HCFG” = I 

“SEnS” = 4.20

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

0 ... 50 mV  

“HCFG” = UoLt 

“SEnS” = 0.50

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

0 ... 60 mV 

“HCFG” = UoLt 

“SEnS” = 0.60

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

12 ... 60 mV 

“HCFG” = UoLt 
“SEnS” = 12.60

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

0 ... 5 V 

“HCFG” = UoLt 

“SEnS” = 0.5

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

1 ... 5 V 

“HCFG” = UoLt 

“SEnS” = 1.5

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

0 ... 10 V 

“HCFG” = UoLt 

“SEnS” = 0.10

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

2 ... 10 V 

“HCFG” = UoLt 

“SEnS” = 2.10

 

 

-1999 ... 9999

 

-199.9 ... 999.9  
-19.99 ... 99.99  
-1.999 ... 9.999

 

 
7.6 – INSTRUMENT ORDERING CODE

 

 
TLK 43  a b c d e f g h ii

 

 
a : POWER SUPPLY

 

= 24 VAC/VDC 

= 100 ... 240 VAC 

 
b : OUTPUT OUT1

 

= Relay 

= Voltage VDC for SSR 

= Analogue 0/4 ..20 mA 

= Analogue 0/2 .. 10 V 

 
c : OUTPUT OUT2

 

= Relay 

= Voltage VDC for SSR 

= Analogue 0/4 ..20 mA 

= Analogue 0/2 .. 10 V 

-

 = None 

 

d : OUTPUT OUT3

 

= Relay 

= Voltage VDC for SSR

 

-

 = None

 

 
e : OUTPUT OUT4

 

= Relay 

= Voltage VDC for SSR 

-

 = None

 

 
f : COMMUNICATION INTERFACE

 

= RS 485 Serial interface 

= RS 485 Serial Interface + digital input 

= No interface 

 
g : CURRENT TRANSFORMER INPUT 
-

 = Not present 

H

 = Present 

 
h : OPTIONAL PROBES

 

-

 = None

 

 
ii : SPECIAL CODES 
 
Note : 

 

- The output OUT4 must be the same type as OUT3. 
- The digital input can only be present as an alternative to the output 
OUT4. 
 
 
 

TLK 43 PASSWORD = 381