Full Text Searchable PDF User Manual

www.ta.co.at
Manual Version 1.08.1
English
C.M.I.
Control and Monitoring Interface
Software Version 1.30.2
Quick Guide:
Mounting and connection
Commissioning


Table of contents
Manual version 1.08.1 EN
1. Delivery scope ............................................................................................................. 4
2. Mounting and connection ............................................................................................ 4
2.1. Connections ..................................................................................................................... 4
2.2. Making the connections .................................................................................................. 5
3. IP-Address .................................................................................................................. 5
3.1 Network with DHCP server (standard) ............................................................................ 5
3.2. Network without DHCP server ........................................................................................ 5
3.3. Fixed IP address ............................................................................................................... 5
4. Access via browser ..................................................................................................... 5
4.1. Access via LAN or port forwarding ................................................................................. 5
4.2. Access via C.M.I. web portal https://cmi.ta.co.at ......................................................... 6
5. Resetting and loading of factory settings .................................................................... 9
UVR1611 compatibility information
In order to be able to access the full range of functions, the controller must have at least
operating system version A3.25.

4
1. Delivery scope
The delivery scope of the device includes the following parts:
1 pc. Control and Monitoring Interface C.M.I.
1 pc. SD card
1 pc. 4-pole plug for the CAN bus
1 pc. 3-pole plug for the DL bus
1 pc. Brief guide
1 pc. 12V power unit (only with model: 01/CMI-NT)
2. Mounting and connection
The C.M.I. can be assembled either with 2 screws on an even surface or with the enclosed
rapid mounting to a TS35 DIN rail according to the EN 50022 Standard.
Dimensions:
2.1. Connections
Connections are labelled and must not be confused.
The following Figure also shows termination on the left (CAN bus).
Power consumption: typically 1.5 W
Reset button on the
rear side
Rapid mounting to a TS35
SD Card

5
2.2. Making the connections
Connections must be made in the following sequence
1.
Connection LAN cable
2.
Connection CAN bus or DL bus cable
3.
Optional: power supply with power unit
(positive pole on the internal conductor, earth outside)
The
POWER
LED now has to be
green permanently
.
3. IP-Address
Access requires an IP address.
3.1 Network with DHCP server (standard)
The network settings are determined
automatically
.
3.2. Network without DHCP server
Direct C.M.I. connection
–
Windows PC
DHCP must be activated on the PC.PC and C.M.I. automatically gets an IP address this way.
This process can take more than 1 minute.
3.3. Fixed IP address
1.
Create a
Text file
called
fix_ip.txt
with the required IP address and UTF-8 encoding in
the root directory of the SD card. The content of this file must be only an IP address
(example: 192.168.0.10) and "Enter".
2.
Insert
the SD card in the C.M.I.
3.
During the next start,
the C.M.I. adopts this IP address and deletes the txt file on the
SD card.
The network settings must then be configured locally (C.M.I. menu Settings/Ethernet).
The
LAN
LED now has to
flash green or be green permanently
.
4. Access via browser
4.1. Access via LAN or port forwarding
1.
Browser
start
2.
Entry in the address field
of the browser:
cmi
(factory setting, only under Windows) or
IP address
Entry "cmi“
Entry IP address (example)
The language in this window depends on the language setting in the PC operating system.

6
3.
Authentication
: Entry user name and password
The
factory-set
predefined
user name is
admin
, the
password also
admin
.
Confirmation with "
OK
".
The language in this win-
dow depends on the lan-
guage setting in the PC
operating system.
4.
Now the
menu
of the C.M.I. appears already.
The additional operation is described in the online help
(
help.ta.co.at
).
4.2. Access via C.M.I. web portal
https://cmi.ta.co.at
If you want access via
Internet
, then
the C.M.I can be connected via “„
C.M.I. web portal
“. The
C.M.I. web portal is a server that was set up by Technische Alternative.
1.
Select the address
https://cmi.ta.co.at
and click
“
Log in
” and “
Registration
“.

7
2.
Completing
the registration form and accepting the terms of use
3.
After completing registration, an e-mail with an activation link will be sent to the e-mail
address used for registration. This process can take up to 30 minutes.
4.
After clicking the link, the
start page
of the web portal is displayed already.
5.
Adding
the C.M.I. in the Web portal
Selection of the tab “
C.M.I.s
“
6.
Selection “
Add C.M.I.
“

8
7.
Entry of C.M.I. data
On the rear of the device is the
serial number
on the rating plate and the
key
on the
key label. The key must be entered
without spaces
.
Caution
All warranty and guarantee claims become void if the rating plate or key label
is removed!
The "
Designation
“ helps with the selection of several individual C.M.I.s and is visible in
the list of individual C.M.I.s. If service by the
super user
(e.g. Technische Alternative)
is to be allowed at
all times
, the appropriate field will be checked.

9
8.
After u
pdating the page, the C.M.I. appears in the list “
My C.M.I.s
“.
Clicking on the serial number takes you to the C.M.I. menu.
The additional operation is described in the online help (
help.ta.co.at
).
5. Resetting and loading of factory settings
Briefly
pressing the reset key on the rear of the C.M.I. restarts the C.M.I. (reset).
The C.M.I. can also be restarted (reset) by unplugging the CAN bus connection and plugging
it back in.
If the reset button is pressed and released while the red LEDs are still illuminated, resets the
C.M.I. to factory settings.
Caution:
Pressing the reset button until the red LEDs stop being illuminated starts a firmware
update with the C.M.I. operation system saved to the SD card. Up to boot sector 1.04, the
current firmware in the "UPDATE" folder of the SD card must be called "
CMI.BIN
". From boot
sector 1.05 onwards, it must be called "
FIRMWARE.cmi
". You can identify whether the boot
sector is 1.05 or above by 4 red LEDs, which begin to glow faintly when the device is started.
We reserve the right to make technical changes.
©
2018

EU Declaration of conformity
Document- Nr. / Date:
TA17021 / 02/02/2017
Company / Manufacturer: Technische Alternative RT GmbH
Address:
A- 3872 Amaliendorf, Langestraße 124
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Product name:
C.M.I.
Product brand:
Technische Alternative RT GmbH
Product description:
Control and Monitoring Interface
The object of the declaration described above is in conformity with Directives:
2014/35/EU
Low voltage standard
2014/30/EU
Electromagnetic compatibility
2011/65/EU
RoHS Restriction of the use of certain hazardous substances
Employed standards:
EN 60730-1: 2011
Automatic electrical controls for household and similar use
–
Part 1: General requirements
EN 61000-6-3: 2007
+A1: 2011
+ AC2012
Electromagnetic compatibility (EMC) - Part 6-3: Generic standards -
Emission standard for residential, commercial and light-industrial
environments
EN 61000-6-2: 2005
+ AC2005
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards -
Immunity for industrial environments
EN 50581: 2012
Technical documentation for the assessment of electrical and electron-
ic
products with respect to the restriction of hazardous substances
Position of CE - label:
On packaging, manual and type label
Issuer:
Technische Alternative RT GmbH
A- 3872 Amaliendorf, Langestraße 124
This declaration is submitted by
Dipl.-Ing. Andreas Schneider, General manager,
02/02/2017
This declaration certifies the agreement with the named standards, contains however no warranty of
characteristics.
The security advices of included product documents are to be considered.


Guarantee conditions
Note:
The following guarantee conditions do not in any way limit the legal right to a guaran-
tee; rather expand your rights as a consumer.
1.
The company Technische Alternative RT GmbH provides a two-year guarantee from the date
of purchase by the end consumer for all the devices and parts which it sells. Defects must be
reported immediately upon detection and within the guarantee period. Technical support
knows the correct solution for nearly all problems. In this respect, contacting us immediately
will help to avoid unnecessary expense or effort in troubleshooting.
2.
The guarantee includes the free of charge repair (but not the cost of on site fault-finding, re-
moval, refitting and shipping) of operational and material defects which impair operation. In
the event that a repair is not, for reasons of cost, worthwhile according to the assessment of
Technische Alternative, the goods will be replaced.
3.
Not included is damage resulting from the effects of overvoltage or abnormal ambient condi-
tions. Likewise, no guarantee liability can be accepted if the device defect is due to: transport
damage for which we are not responsible, incorrect installation and assembly, incorrect use,
non-observance of operating and installation instructions or incorrect maintenance.
4.
The guarantee claim will expire if repairs or actions are carried out by persons who are not au-
thorised to do so or have not been so authorised by us or if our devices are operated with
spare, supplementary or accessory parts which are not considered to be original parts.
5.
The defective parts must be sent to our factory with an enclosed copy of the proof of pur-
chase and a precise description of the defect. Processing is accelerated if an RMA number is
applied for via our home page
www.ta.co.at
. A prior clarification of the defect with our tech-
nical support is necessary.
6.
Services provided under guarantee result neither in an extension of the guarantee period nor in
a resetting of the guarantee period. The guarantee period for fitted parts ends with the guaran-
tee period of the whole device.
7.
Extended or other claims, especially those for compensation for damage other than to the de-
vice itself are, insofar as a liability is not legally required, excluded.
Legal notice
These assembly and operating instructions are protected by copyright.
Use outside the copyright requires the consent of the company Technische Alternative RT GmbH.
This applies in particular to reproductions, translations and electronic media.
Technische Alternative RT GmbH
A-3872 Amaliendorf Langestraße 124
Tel ++43 (0)2862 53635 Fax ++43 (0)2862 53635 7
E-Mail:
mail@ta.co.at
---
www.ta.co.at
--- © 2018