PDF User Manual

  1. Home
  2. Manuals
  3. Technische Alternative ANS 21 Operation And Installation Instructions Manual

Technische Alternative ANS 21 Operation And Installation Instructions Manual

Made by: Technische Alternative
Type: Operation And Installation Instructions
Category: Control Unit
Pages: 12
Size: 0.26 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

 

ANS 21 

Version 10

-1 

EN 

 
 
 
 

Simple solar control unit 

 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
Operation 
Installation instructions 

 

 

 

EN

 


background image

 

Table of contents 

 
 

Safety requirements ................................................................................................................. 3

 

Maintenance ............................................................................................................................ 3

 

Solar thermal system ............................................................................................................... 4

 

Tank load from boiler ............................................................................................................... 4

 

Selection of the program and sensor type ................................................................................ 5

 

Master – slave – function ......................................................................................................... 6

 

Sensor installation .................................................................................................................... 7

 

Installing the device ................................................................................................................. 8

 

Electrical connection ................................................................................................................ 8

 

Tips on troubleshooting ............................................................................................................ 9

 

Technical data ........................................................................................................................ 10

 

 

 

 


background image

 

3

Safety requirements: 

All installation and wiring work on the controller must only be carried 
out in a zero-volts state. 

The opening, connection and commissioning of the device may only 
be carried out by competent personnel. In so doing, all local security 
requirements must be adhered to.

 

 
The device corresponds to the latest state of the art and fulfils all necessary safety 
conditions. It may only be used or deployed in accordance with the technical data and the 
safety conditions and rules listed below. When using the device, the legal and safety 
regulations apposite to the particular use are also to be observed. 
 

 The device must only be installed in a dry interior room. 

 It must be possible to isolate the controller from the mains using an all-pole isolating 

device (plug/socket or double pole isolator). 

 Before starting installation or wiring work, the controller must be completely isolated from 

the mains voltage and protected against being switched back on. Never interchange the 
safety extra-low voltage connections (sensor connections) with the 230V connections. 
Destructive and life-threatening voltages at the device and the connected sensors may 
occur. 

 Solar thermal systems can become very hot. Consequently there is a risk of burns. Take 

care when fitting temperature sensors! 

 For safety reasons, the system should only be left in manual mode when testing. In this 

operating mode, no maximum temperatures or sensor functions are monitored. 

 Safe operation is no longer possible if the controller or connected equipment exhibits 

visual damage, no longer functions or has been stored for a lengthy period of time under 
unsuitable conditions. If this is the case, place the controller and equipment out of service 
and secure against unintentional use. 

 

Maintenance: 

If used properly, the system does not require maintenance. 
As the components relevant to accuracy are not subjected to loads if used properly, long-

term deviation is very low. The unit thus cannot be adjusted.  

The construction characteristics of the unit must not be changed for repairs. Spare parts 

must correspond to the original parts and be used as intended. 

 


background image

KS

BS

pump

BS

pump

KS

Solar thermal system 

function switch in position 

S+ (solar) 

 

 
 
 
 
 
 
 
 
 
 
The pump runs when sensor

 

KS

 has a temperature of 

diff 

higher than sensor

 BS  

and 

BS

 

has not exceeded the threshold 

max

.  

Pump = KS > (BS + diff) & BS < max

 

 
Collector excess temperature:

 if the collector temperature climbs above 130°C, the pump 

is switched off and only released again, if the temperature falls below 110°C. 
During the excess temperature shutoff, the two top LEDs of the collector display flash. 

 

Tank load from boiler

 function switch on position 

L+ (feed pump)

 

 
 
 
 
 
 
 
 
The pump runs when 

sensor KS

 is greater than the threshold 

max

 (here used as "min") and 

sensor KS

 is greater than 

BS

 by the difference 

diff

.

   

Pump = KS > max & KS > (BS + diff)

 

 

The difference function:

 

The output only switches the pump when the temperature of the collector or the boiler is 
greater than the temperature of the boiler by the set difference 

diff

 

The thermostat function:

 

Solar S: If the 

tank temperature

 exceeds the set 

maximum threshold

, the pump is 

switched off regardless of the temperature of the collector (protection from calcification). 

 

Feed pump L

: If the 

boiler temperature

 falls below the minimum threshold, the pump is 

switched off (protection from sooting).  

 
 

 


background image

 

5

Selection of the program and sensor type:

 

  The selection of the program and the sensor type has to be made before installation. 

The controller does not operate or operates incorrectly, if the incorrect sensor type is 
set.

 

 
 

ALWAYS PULL THE MAINS PLUG BEFORE OPENING THE CASING!

 

 

 

S+K

 

S+P

 

L+K

 

L+P

 

ANS 21

 

 

  The selection occurs by means of a slide switch on the right border of the board. There is 
no access possible to the slide switch from outside. 
Four positions are available: 

 

  1) 

L+P

  Feed pump requirement by PT1000 sensors  

  2) 

L+K

  Feed pump requirement by KTY sensors  

  3) 

S+P

  Solar power system with PT1000 sensors  

  4) 

S+K

  Solar power system with KTY sensors 

     
     

Manual / automatic switchover: 

On the front side of the control is a sliding switch with the functions AUS (=OFF), AUT (= 
automatic, normal setting) and HAND (=ON, endurance run). 

 

 


background image

TK2

TK1

p - master

p - slave

KS - master

BS - master

BS - slave

TK2

TK1

p - master

v - slave

KS - master

BS- slave

BS - master

Master – slave – function: 

Two ANS 21 controllers, can be connected via the data link. Consequently it is possible to 
charge two tanks, of which one tank is prioritised for charging by the "master".  
Both sensors are connected to the master. 
Only the tank sensor BS is connected to the slave controller that is subordinate to the master. 
The slave receives the collector temperature from the master. 
There are two operating modes for this master-slave operation: 
 
 
 
 
 
 
 
 
 
 
 
 

 

2-pump mode:

 as can be seen in the schematic diagram, a pump is connected to both 

master and slave. The master pump has absolute priority, hence the slave pump can 
only be switched on if the master pump is switched off (dependent on the starting 
conditions). 2-pump mode is activated if the terminals of the collector sensor at the 
slave remain disconnected (= interruption). 
 

 
 
 
 
 
 
 
 
 
 
 

 
 

 

Pump-valve mode:

 the common pump is connected to the master controller, the slave 

controls the valve. As soon as the starting condition is no longer fulfilled at the master, 
the slave receives the command to switch on the pump and switches the valve to "its" 
consumer TK2. Pump-valve mode is activated if the terminals of the collector sensor 
at the slave are bridged with a jumper (= short circuit). 

 

 


background image

 

7

Sensor installation:

 

The sensors must be properly arranged and installed for the system to function correctly.  

  Collector sensor (red or grey cable with connection box):

 Either insert the sensor in a 

pipe directly soldered or riveted to the absorber and extending out of the collector casing 
or screw the sensor onto a T piece on the end of the supply line’s collecting tube using an 
immersion sleeve. No water may be allowed to enter the immersion sleeve (danger of 
freezing). 

 

 Storage sensor:

 The sensor should be used with an immersion sleeve just above the 

outlet for the exchanger’s return line if heat exchangers with ribbed tubes are used and 
with a T piece on the outlet of the exchanger’s feed line if integrated non-ribbed tubes are 
used. It should not be installed below the respective register or heat exchanger in any 
case.

 

  Boiler sensor (boiler supply line):

 This sensor is either screwed into the boiler using an 

immersion sleeve or at a short distance from the boiler on the supply line.

 

 Pool sensor (swimming pool):

  Install directly at the outlet from the pool on the suction 

line as an attached sensor (see attached sensor). Installation using an immersion sleeve is 
not recommended due to the possibility of condensation within the sleeve.

 

 Attached sensor:

 Attach to the line using pipe or hose clamps. Make sure the material 

used is proper (corrosion, temperature resistance, etc.). Then, the sensor has to be well 
insulated so that the pipe temperature is measured exactly and the ambient temperature 
does not influence the measurement.

 

All of the sensor cables with a cross-section of 0.75mm

2

 can be extended up to 30m. 

Beyond 30m they can be extended by use of a suitably larger cross section. The sensor and 
the extension can be connected as follows: cut the heat-shrinkable sleeve provided down to 
4 cm and put it over a wire; twist the naked ends of the wires, and put the heat-shrinkable 
sleeve over the naked end; heat it carefully (such as with a cigarette lighter) until the sleeve 
has wrapped itself around the connection. 

 
 
 

 


background image

Installing the device 

WARNING!

 ALWAYS PULL THE MAINS PLUG BEFORE OPENING THE CASING!

 

 

 

Unscrew the four screws on the edges of the case and screw on the basin through the two 

holes on the bottom side using the fastening screws provided. 

 
 

Electrical connection 

Only a trained electrician may provide the electrical connection in compliance with local 

guidelines. The sensor lines must not be laid in the same cable channel as the supply 
voltage. In a commonly used cable channel, appropriate shielding has to be provided. 

 

Caution: 

Only work on the inside of the control system when it is dead. The connections 

are to be put according to the marking of the clamps. 

 

Note:

 To provide protection from lightening, the system has to be grounded in accordance 

with the regulations. Sensor failures due to storms and static electricity are usually the result 
of improper grounding or overvoltage protection on the collector sensor. 

 

 

Pin configuration: 

 

 

When using the master-slave function, the data link must be connected in-phase to both units 
(data to data, ground to ground).

 

S+K

S+P

L+K

L+P

ANS 21

 

230V~

KS

BS

 

Fuse 3.15 A

 

Data link 

Ground

 

Dat

a

 

 


background image

 

9

Tips on troubleshooting:

 

 

When the control system does not function properly on automatic mode, the function 

switch and the sensors should be checked. 

Version display: 

as the controller is connected, the version is temporarily displayed using 

the right tank LEDs (binary code - reading from the top down). 

A short-circuit or an interruption

 of a sensor are displayed directly on the control system. If 

a short-circuit occurs, the lowest LED of the collector or tank icon blinks. In case of an 
interruption, the top LED of the icon blinks. 

Collector excess temperature:

 if the collector temperature climbs above 130°C, the pump 

is switched off and only released again, if the temperature falls below 110°C. 
During the excess temperature shutoff, the two top LED's of the collector display flash. 

Master-slave mode

: the control circuit continues to function at least partly, if an error occurs 

at a sensor: 

  if the master tank sensor fails, the master pump is deactivated, however it can activate 

the slave at any time, depending on the operating mode. 

  if the slave tank sensor fails, the master operates in stand-alone mode (master-slave 

mode is deactivated) 

  if the master collector sensor fails, the system shuts down completely (LEDs continue 

to display the error) 

 

In addition, the sensors can be measured by means of an ohmmeter. 

 

Temp.

 

[°C] 

0  10 20 25 30 40 50 60 70 80 90 100

R (Pt1000)

 [

]  1000 1039 1078 1097 1117 1155 1194 1232 1271 1309 1347 1385

R (KTY)

 [

1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182 3392

 
If the system is not in operation although supply voltage is connected, the 3.15A quick-

blowing fuse that protects the control system and the output should be checked and 
exchanged if necessary. 

 

 


background image

10 

Technical data: 

  Temp.difference:      adjustable from 2-12°C (hysteresis = 3K) 

 

  Overheating 

temp./ 

Min.threshold: adjustable from 40-100°C (hysteresis = 3K) 

 

 

Accuracy:  

 

 

 

 

 

 

 

tip. +-2% 

  Output:         230V~/ 

max. 

200VA 

 

 

Power draw:   

 

 

 

 

 

 

max. 2 W 

  Supply 

cable:       3x 

1mm² H05VV-F conforming to EN 60730-1 

 
 

Dimensions in mm: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
We reserve the right to make technical changes. 

             

 

© 

2012 

 
 

 


background image

 

 


background image

 

 

Guarantee conditions 
 

Note: 

The following guarantee conditions do not in any way limit the legal right to a 

guarantee, rather expand your rights as a consumer. 
 

1.  The company Technische Alternative elektronische Steuerungsgerätegesellschaft m. b. H. 

provides a two-year guarantee from the date of purchase by the end consumer for all the 
devices and parts which it sells. Defects must be reported immediately upon detection and 
within the guarantee period. Technical support knows the correct solution for nearly all 
problems. In this respect, contacting us immediately will help to avoid unnecessary expense or 
effort in troubleshooting.  

 

2.  The guarantee includes the free of charge repair (but not the cost of on site fault-finding, 

removal, refitting and shipping) of operational and material defects which impair operation. In 
the event that a repair is not, for reasons of cost, worthwhile according to the assessment of 
Technische Alternative, the goods will be replaced.  

 

3.  Not included is damage resulting from the effects of overvoltage or abnormal ambient 

conditions. Likewise, no guarantee liability can be accepted if the device defect is due to: 
transport damage for which we are not responsible, incorrect installation and assembly, 
incorrect use, non-observance of operating and installation instructions or incorrect 
maintenance.  
 

4.  The guarantee claim will expire if repairs or actions are carried out by persons who are not 

authorised to do so or have not been so authorised by us or if our devices are operated with 
spare, supplementary or accessory parts which are not considered to be original parts. 

 

5.  The defective parts must be sent to our factory with an enclosed copy of the proof of pur-

chase and a precise description of the defect. Processing is accelerated if an RMA number is 
applied for via our home page 

www.ta.co.at

. A prior clarification of the defect with our technical 

support is necessary. 

 

6.  Services provided under guarantee result neither in an extension of the guarantee period nor 

in a resetting of the guarantee period. The guarantee period for fitted parts ends with the 
guarantee period of the whole device.  

 

7.  Extended or other claims, especially those for compensation for damage other than to the 

device itself are, insofar as a liability is not legally required, excluded. 
 

 
 
 
 

Technische Alternative 

elektronische Steuerungsgerätegesellschaft m. b. H.  
A-3872 Amaliendorf Langestraße 124 
Tel +43 (0)2862 53635                     Fax +43 (0)2862 53635 7
E-Mail: 

mail@ta.co.at

                      --- 

www.ta.co.at

  ---                                 © 2012