Directions for installation and maintenance 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 
 
 

 

 
 

 
 

 


background image

 

2

contents 

1.

 

Introduction  ………………….…………………………….……..………….

p3

   

 

 

 

 

2.

 

Caution …………………………………………………….………………….…..

p3

   

 

3.

 

Delivery control  …………………………………………........................

p4

   

 

 

 

 

 

 

 

 

 

4.

 

Technical description  ……………………….…………………………..

p4

 

Technical characteristics   
Outside 
Inside 
BP-100HS-A explored view 
Wire control operation 

General diagram of the refrigerating circuit 
Safety and control systems 
Electric diagram 

 

5.

 

Installation  ……………………….………………………………….......

p14

 

Rules of installation 
Hydraulic connections 
Electric connections 
Procedure of use 

 

6.

 

Water flow and refrigerating circuit pressure........................

p18

 

 

7.

 

Defrosting ……………………………………………………………………

p19

 

   

 

8.

 

Environment problem  ………………………………………............

p19

 

 

9.

 

Error messages and what to do  ………………………………..…

p20

 

 
 

 
 
 

 
 
 
 
 

 


background image

 

3

 

1- 

Introduction 

 

We thank you for having chosen our Heat pump. 
 
This installation and maintenance notice contains the necessary 
information to its installation (delivery control, the installation, the 
connections) and to its repair. It is a complementary document to the 
user’s manual which describes its instructions for use. 
We invite you to read it first.

 

 
 

2- 

Caution

 

 

This document is an integral part of the product and it must stays in 
the technical room. 
 
This Heat pump is exclusively for heating swimming pools. 
Any other use not in conformity and random will be considered as 
dangerous and unsuitable. 
 
The assembly, the electric connection and the start up must be 
carried out by specialized and professional person. 
 
When connect to socket (power supply), please make sure that live 
wire, neutral wire, earth wire is right. 
 
It is essential to maintain the temperature in the swimming pool lower 
than the recommended value by the swimming pool’s manufacturer. 
 
Please make sure that minimum water flow speed is 5m

³

/h. 

 
In a concern to a constant improvement, our products can be modified 
without notice; the present pictures in this note or the characteristics 
which are described are not contractual. 

 

 

 


background image

 

4

3- Delivery’s control   

At the delivery time, check the condition of packing; in case of 
damages, have reservation about them to the carrier, before 48 hours 
and by registered letter with acknowledged receipt. 

Before any manipulation, check the complete state of the machine. 

 
 

4

Technical description

 

 

 

Characteristics: 

MODEL 

BP-100HS-A 

Power supply 

230V~, 50Hz 

Heating consumption power * (kW) 

2.05 

Heating restored power *(kW) 

10.5 

Heating nominal intensity *(A) 

9.5 

Cooling absorptive power * (kW) 

Cooling restored power *(kW) 

Cooling nominal intensity *(A) 

Air flow (m

3

/H) 

2400 

Noise level (d(B)A) 

<53 

Refrigerant gas 

R410a 

Rate of average filling of gas (g) 

1100 

Net weight of the unit (kg) 

61 

Overall sizes L x W x H (cm) 

100 x 30 x 57 

* Possible variations of value according to climatic conditions 

 

 


background image

 

5

Outside:   
 

 

 
 
 
Inside:   

(Front sheet cover and panel removed) 

 

 

 
 

 

 

 
 

 
 

 
 

 
 

 
 

 

Fan protection grid   

Front panel 

Top cover 

Control panel 

Refrigerant pressure manometer 

Fast connection for water outlet 

Fast connection for water intlet 

Wire connection for power supply 

Evaporator 

10  Fan 
11  Compressor 
12  High and low pressure interruptor 
13  Titanium heat exchanger 
14  Temperature sensor of swimming pool water 
15  Four way valve 
16  Ambient temperature sensor 
17  Defrost sensor 
18  Water flow switch 

 


background image

 

6

 

 


background image

 

7

Wire control operation

 

The function of the LED display and control: 

 

 

Set the operation parameter: 

When the unit powered up but not running, press "

 

  " or "

 

  " to enter operation parameter 

interface. (parameter from 0-F, see Operation Parameter Table). 

 Press "

SET

" to enter current parameter setting, press "

 

  " or "

 

  "to set data for 

parameter, press "

SET

" again exit the current parameter setting. 

 No press in 8s, it will exit the setting interface. 

 

If the heat pump is running, press "

 

  " or "

 

  " to enter operation parameter check 

interface, But can’t change parameters

 (Except the parameter 0, 1, 2 for water temperature 

setting in different modes).

 

 If the heat pump is running, the LED display shows current water temperature; 

If the heat pump is turnoff, the LED display shows current time. 

NO 

Meaning 

Range 

Change 

Factory setting 

Cooling setting water temperature 

15~45°C 

YES 

27 

Heating setting water temperature 

15~45°C 

YES 

27 

Auto mode setting water temperature  15~45°C 

YES 

27 

Turnround of defrosting Under heat 
mode 

30 ~ 90 min 

YES 

40 (40 min) 

Defrosting start temperature 

-30 ~ 0°C 

YES 

-5°C 

Defrost exit temperature 

2 ~ 30°C 

YES 

15°C 

Time of exit defrost Under heat mode  0 ~ 12 min 

YES 

6 min 

Low ambient temperature protection    -20~10°C 

YES 

-7°C 

Compressor protection 
Exhaust temperature 

95 ~ 110°C 

YES 

95°C 

Automatic restart 

0/1 

YES 

Mode (heat/coo & heat) 

0/1 

NO 

Water pump mode 

0/1 

YES 

Water temperature difference to 
restart 

1 ~ 10°C 

YES 

Water temperature 

-9 ~ 99°C 

Measured value 

Compressor Exhaust temperature 

-9 ~ 125°C 

Measured value 

Copper temperature 

-9 ~ 99°C 

Measured value 

Ambient temperature 

-9 ~ 99°C 

Measured value 

 


background image

 

8

 

Choose the operation mode: 

 Press “ 

  ” to power on unit. Under running, the LED displays the water temperature and 

current mode. 

 Press “ 

MODE

 ” to choose mode(mode can be changed under running) 

◎ 

Press "

 

  " or "

 

  " to enter operation parameter check interface, Select the current mode 

water temperature setting parameters, press

 "

SET

button to enter, press " 

  " or " 

  " set 

required tempreature. 

 Stop for 3-4 minutes, reverse of cycle and restart in a new mode. 

 

 


background image

 

9

Check current temperature: 

Under running, press    "

 

  " or "

 

  "    to check the current status of the unit. You can check 

water/ambient/compressor/copper temperature.

 

 

 

 
 

Setting the time

 

press “

CLOCK

” botton to set the time. The time displayed blinks, press “

CLOCK

” botton again 

and then use the arrow "

 

  " and "

 

  " to change the hour setting. To change the minutes, 

press “

CLOCK

” botton again. Once the correct time is set. press “

CLOCK

” botton again the end. 

The display returns to normal after 8 seconds. 

 

Timer switch ON and Timer switch OFF: 

Once the time has been set correctly, this function allows a machine start time and a machine stop 
time to be programmedduring the day. 

 

Press “

TIMER ON

” botton the time displayed and “ON” to blink, press “

TIMER ON

” botton again 

Change the hour using the "

 

  " and "

 

  " keys. Press “

TIMER ON

” botton again to change 

the minutes using the "

 

  " and "

 

  " keys. Press “

TIMER ON

” botton again the end. 

 
Press “

TIMER OFF

” botton the time displayed and “OFF” to blink, press “

TIMER OFF

” botton 

again Change the hour using the "

 

  " and "

 

  " keys. Press “

TIMER OFF

” botton again to 

change the minutes using the "

 

  " and "

 

  " keys. Press “

TIMER OFF

” botton again the end. 

 
The time setting is from 0 to 24 hours to recycle. 
 
When the setting time for on and off is the same,the setting time is not available. 

 

When the setting timer, Press “

CLOCK

” to deactivate TIMER. 

 
 

Coercive Defrosting (Only on heating mode): 

1.  Press

 “ 

MODE

 ” 

10 seconds when the unit is running, the unit will go into coercive defrosting 

function. 

2.

 

When it arrives in defrosting exit criteria, defrosting is stopped.

 

3.

 

After exiting the defrosting, the unit will stop 30 seconds, then it will heat water again.

 

 

Key lock: 

Press "

SET

" and "

 

  " 5 seconds to set keylock. 

Press "

SET

" and "

 

  " 5 seconds again to release keylock. 

 
 
 
 

 


background image

 

10

General diagram of the refrigerating circuit

 

 
The heat pump is reversible allowing the swimming-pool’s heating or 
cooling: 
 
Swimming-pool water’s heating mode: 
 

The cold and liquid refrigerant fluid absorbs the heat contained in the air through the evaporator 
(gilled radiator), in which it is vaporizing; it is then put up in pressure and in temperature by the 
compressor which sends it in the condenser (exchanger) where it loses its heat (in giving it to the 
water of swimming pool) and comes back in liquid state; it loses its pressure and still cools in the 
expansion capillaries before turning back to the evaporator for a new cycle. 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Hot water

 

Cold water

 

Hot air

 

Cold air

 

Compressor 

Single 
way 
valve 

Condenser 
(exchanger) 

4 way valve 

Pressure and gas 
intake 

Evaporator 

(gilled 

radiator) 

Expansion 

capillary 

 


background image

 

11

 
Swimming-pool water’s cooling mode: 

 

The  4  way  valve  reverses  the  circulation  of  the  refrigerant  fluid;  the  fluid  vaporizes  in  the 
exchanger  (evaporator)  in  getting  the  heat  of  the  water,  goes  through  in  the  compressor  which 
reheats it and through in the gilled radiator (which becomes condenser) where it comes back to 
liquid state. 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Cold water

 

Heat water

 

Cold air

 

Hot air

 

Compressor 

Evaporator 
(exchanger) 

4 way 
valve 

Evaporator 

(gilled 

radiator) 

Pressure and gas 
intake 

Single 
way 
valve 

Expansion 

capillary 

 


background image

 

12

Safety and control systems

 

 

The heat pump is fitted out: 

 
Temperature control: 

 

A  temperature  sensor  of  the  evaporator,  starting  the 
defrosting operation. 

 

An ambient temperature sensor ensuring the cut of the heat 
pump  when  the  temperature  of  the  external  air  goes  down 
under -7°C (factory settings). 

The normal cycle restarts when the 

outside temperature goes up to

 -5C (factory settings). 

 

A temperature sensor placed on the exchanger, ensuring the cut of 
the  heat  pump  when  the  temperature  of  the  water  reaches  the 
required  temperature.  The  normal  cycle  restarts  when  the 
temperature in the exchanger goes down to a temperature lower of 
2°C (factory settings) than this required

 
 
With 4 safety systems: 
 

 

A water flow detector placed at the exit of the exchanger 

 

A high pressure gas circuit breaker, a low pressure gas circuit 
breaker   

 

An outlet compressor temperature sensor   

 

 
If a defect occurs on one of these systems (defective system, off-line 
or abnormal measured value) a message of defect appears on the 
display screen; see the paragraph “Error codes and what to do” of this 
note. 

Caution: the removal or the shunt of one of the control or safety 
systems involves the cancellation of the guarantee. 
 
 
 
 
 
 
 
 
 

 


background image

 

13

Electric diagram 

 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 


background image

 

14

 

5- Installation 

 

Rules of installation:

 

 

 

Electric and hydraulic connections must be carried out according to standards 

in effect (NF C 15 100, CE I 364). 

 

 
The machine must be installed outside.   
 
The machine must be posed on its ant vibratory studs, set and lying flat and on a 
massive base (concrete slab); this base must have a sufficient height to prevent any 
entry of water by the bottom of the machine. Height must be adjusted to fit the 
connector collecting the condensates.   
 
The obstacles such as wall and vegetation must be separated from the machine as 
indicated on the diagram below. 
 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 

 

 

    Exhausting   

 

 

 

                  Blowing 

 

 

 

          side     

 

 

 

 

  side 

 
 
 

 

Do not to install the Heat pump in a confined place (the fan would recycle its air and 
the Heat pump would be down performance). 
 
The fan should not blow towards the windows or crossing point.   
 
Safety  distance  between  the  swimming  pool  and  the  foot  bath:  the  fitter  must 
imperatively refer to the standard C15-100 section 702; the machine should not be 
installed in volume 1 surrounding the swimming pool but at least in volume 2 so at a 
distance of 3 m minimum of the swimming pool and foot bath. 
 
Other precautions of installation: 
 
- Do not to install the machine near a way with circulation of car in order to avoid 
mud projections.   
- Avoid directing blowing against dominant winds.   
- If the machine is intended to be used in winter, put it in a place protected from the 
falls of snow.   
-  The  machine  must  be  able  to  be  supervised  in  order  that  children  do  not  play 
around 
 

 

2,5 m mini 

0,5 m mini 

0,

mi

ni

 

   

0,5 m mini 

 


background image

 

Swimming-Pool 

 

Technical room 

Chemical treatment 

Blowing 

By-pass 

Heat Pump 

Drain of the 
condensates: insert 
the plastic elbow in 
the hole of 
evacuation of the 
bottom and connect 
the pipe

 

if need.   

Hydraulic connections:    

 

                                    To 

respect imperatively   

Connection is carried out with a by-pass located on 
the circuit of filtration, upstream appliances of the 
chemical treatment of water. 

Connect intake/outlet water PVC pipes DN50 to the 
openings of the machine in following the inlet / outlet 
indications (grease the worms before screwing) 

 

Filter 

1

5

 

 


background image

16 

 

Electric connections: 

 

  CAUTION: before connecting the machine, make sure that the feeder is 
disconnected to the electrical network. 

The electric installation must be carried out by an experienced electrician and the 
supply must come from a severing equipment and differential protection; the whole 
must be carried out according to standards' in force in the country where the 
material is installed. 

  Characteristics of the electric supply: 
- 230 V +/- 10%, single-phase current, 50 Hz 
- Mode of neutral TT and TN.S; the circuit of heat pump must be connected to an 
earth circuit.   

 

 

 

 

 

 

 

 

 

Characteristic minimum of the protection:  
- Protection must be of 16 A, by circuit breaker or fuse; it must protect the Heat 
pump exclusively; the circuit breaker must be specified with curve D, the fuse must 
be specified Am. 
- Differential protection : 30 mA (the length of cable between the connector block of 
the heat pump and the protection of should not exceed 12 m). 

 
Control : 
 

The heat pump is fitted out with a water flow detector which function is to apply 

the signal to the electronic card when the water flow is sufficient. 
 

We  recommend  when  it  is  possible  to  control  the  heat  pump  to  the  filtration 

pump (by contacting relay non supplied to insert in the feeding circuit of the heat 
pump). 
 
 

The remmonded water flow speed is 5m

³

/h. 

 
 
Removed control panel: 
 

An extension cord allows the removal of the panel in inserting it in a standard 

electric box into the technical local; the option is supplied with a cover allowing to 
seal the aperture let by the removal of the control panel. 
 
 
 
 
 

 
 
 
 
 

 


background image

16 

Procedure of use 

 

 
 
 

Action 

External 

Appliance 

or Button of heat 

pump 

Display 

Heat pump   

answer 

Put the heat pump 
under tension 

Engage the circuit   
breaker of the heat   
pump 

 

 

Display current water   
temperature 

Put in circulation   
the swimming   
pool water into   
the pipes 

Engage the circuit   
breaker of pump of   
filtration 

 

 

 

Chose the operation 
mode 

Press the button 

MODE 

 

Stop for 3-4 minutes,   
reverse of cycle and   
restart in a new mode 

Set the water 
temperature   
into the   
swimming pool 

,   

adjustable from   

15°C to 40°C 

 

 

The heat pump heats   
or cools until the   
required temperature 
(P7/

P8

Start 

Press the button 

 

 

 

Start between 1-   
4 minutes in the   
previous operation mode   
(heating/cooling/auto) 

Stop   

 

Press the button 

 

 

 

Immediate stop   
and wait 

Switch off 

Use the circuit   
breaker of pump   
of filtration,   
and heat pump 

 

 

Complete stop 

17 

 


background image

16 

6- Water Flow and refrigerating circuit pressure 

 

 
After putting into service, do the settings of pressure of the refrigerant circuit 

for having an optimal operating of the heat pump, following:   

 
 
Stage 1: 
Before starting the Heat Pump, ambient   
temperature around 20°C, refrigerant meter 
shows pressure from 14 to 16kg/cm². 
 
 
 
Stage 2: 
Close completely the by pass valve and open   
large inlet and outlet valves of the Heat   
Pump; in these conditions the totality of the   
water flow goes by the Heat Pump. 
Put into service the Heat Pump in heating mode, wait for the indicated 

pressure being stabilized; the correct setting of the pressure is from 21 to 35 
kg/cm²; 

In most of cases (pump of filtration given a flow until 20m

³

/h) you do not have 

to open the by pass valve. 

If the stabilized pressure is under 21kg/cm², the progressive opening of the by 

pass valve will allow rising this pressure. 

 
The adjustment of the by pass valve done, you have in principle no reason to 

modify it during the season. See the paragraph “Environment problem” too. 

 
 

 

 
 
 
 
 

18 

 


background image

16 

7- Defrosting 

 
The defrosting is necessary only in heating mode. 
Sequences of the defrosting: 
 
1- Start 
The defrosting is engaged if the following conditions are at the same time 

fulfilled: 

- the defrosting sensor temperature goes down to 15°C 
- the compressor runs without stopping for 40 minutes 
- the defrosting sensor temperature goes down to -7°C 
2- The compressor and the fan stop 
3- After 25 seconds, the 4 way valve shifts 
4- After 5 seconds, the compressor starts alone and the accumulated freeze on 

the gills becomes melting, what is generally with a steam cloud   

5- Stop: 
The defrosting stops if one of the following conditions is fulfilled: 
- the detected temperature by the defrost sensor goes up to 15°C. 
- the compressor had run totally 6 minutes 
6- The compressor stops   
7- The fan start 
8- After 5 seconds the 4 way valve shifts 
9- After 25 seconds the compressor start for restarting in heating mode. 
 

8 – Environment problem 

 

Under certain external conditions the heat exchanges between the refrigerant and 
the water on one hand and between the fluid and the air on the other hand are 
insufficient; the consequence is that the refrigerating circuit runs up in pressure 
and the compressor consumes more electricity. 

 

The temperature sensors compressor outlet and the magnetic circuit breaker 

on the compressor power supply protect the compressor from these extreme 
conditions; the error messages 

EE 06 occur. 

The condition causing this situation is as follows: 

In heating mode: 
- insufficient water flow:   

close the by-pass valve for increasing the refrigerant exchange 

à

 water 

In cooling mode: 
- too important water flow: open the by pass valve for decreasing    the water flow 
and so the exchange water 

à

 refrigerant 

- insufficient air flow: be sure that the real net of condenser are not blocked. 

 

Note: these error codes are likely to occur if temperature of swimming pool water is 
high and the ambient air is hot. 

19 

 


background image

16 

9 – Error codes and what to do: 

This table explains the error codes caused by a defective 

regulating component or by a security operation. 

Screen and state 
of the heat pump 

Component 

Possible 

Intervention 

Second reason if 

the 

intervention is 

without effect 

PP 01 
Compressor and fan 
stopped 

Water temperature 
sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, 
change it or replace the electronic card 

PP 02 
Compressor and fan 
stopped

 

compressor 

exhust 
temperature 
sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, 
change it or replace the electronic card 

PP 03 
The heat pump 
continues running 

Defrost sensor 

The defrosting is 
incomplete and the 
automatism decides 
to stop the heat pump 

Increase lightly the water flow going into 
the heat pump; the effect is to increase 
the temperature of the refrigerant in the 
evaporator. 

PP 05 

The heat pump 
continues running 

Ambient air 
temperature 
sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, 
change it or replace the electronic card 

PP 07 
 

First anti-frost 

protection active 

Low temperatures for 

water and air 

No action required 

PP 07 
 

Second anti-frost 

protection active 

Low temperatures for 

water and air 

No action required 

EE 01 

Compressor and fan 
stopped 

High pressure,   
Low pressure 
protection 

Insufficient water 
flow 

Check the water flow 

Pressure switch out 
of order 

Replace the pressure switch Have 

Too much refrigerant 
gas present 

the heat pump checked by a 
refrigeration technician 

EE 02 

Compressor and fan 
stopped

 

 
Low pressure 

protection 

Not enough 
refrigerant gas 

Have the heat pump checked by a 
refrigeration technician 

Leak in the cooling 
conduits 

Have the heat pump checked by a 
refrigeration technician 

EE 03 

Compressor and fan 
stopped

 

Flow switch 

Flow switch 
disconnected, non 
supplied or defective 

Check the connections, the wires, 
change it or replace the electronic card 

EE 04 
The unit cannot be 
started 

Emergency switch 

Emergency switch 
disconnected 

Check the connections and the wires 

EE 05 

Compressor and fan 
stopped

 

Low ambient 

temperature 

protection 

Ambient temperature 

is too low or 

protection 

temperature setting 

set too low 

Check and repair. 

EE 06 
Compressor and fan 
stopped 

compressor 

exhaust 
temperature 
sensor 

Compressor exhaust 

temperature 
detected up to 95°C 
more than 3 times in 
1HR 

Environment problem 
Refrigerant leakage 
Capillary is half blocked 

EE 07 
The unit cannot be 
started 

Phase protection 

Connection 

disconnected or 
wrong phase wiring 

Check the connections 
Put phases in order 

EE 08 

The wire control 
can't operated

 

Wire control 
Communication 
error 

Signal cable of wire 
Control is loose 

Check the connection of signal cable 

 

20