VRT600 SERIES

  INSTRUCTION MANUAL 

 


background image

VRT600 SERIES

 

 

 

 

 

 

First of all we wish to thank you for choosing to use a 

TECSYSTEM

 product and recommend you read this instruction 

manual carefully: You will understand the use of the equipment and therefore be able to take advantage of all its 
functions. 

 

ATTENTION! THIS MANUAL IS VALID AND COMPLETE FOR THE VRT600 AND VRT600 U VERSIONS. 

 
 

 

 

 

PAGE 

1)   SAFETY REQUIREMENTS 

………………………………….. 3 

2)   ACCESSORIES 

………………………………….. 4 

3)   TECHNICAL SPECIFICATIONS 

………………………………….. 5 

4)   FRONT PANEL 

………………………………….. 7 

5)   INSTALLATION 

………………………………….. 8 

6)   ELECTRICAL CONNECTIONS 

………………………………….. 9 

 

VRT600 BACK 

………………………………….. — 

 

VRT600 U BACK 

………………………………….. 10 

 

POWER SUPPLY 

………………………………….. 11 

 

OPERATION 

………………………………….. — 

 

HOW TO CHECK THE ALARM STATUS 

………………………………….. — 

 

HOW TO RESET A MOTOR IN ALARM 

………………………………….. — 

 

OPERATION WITH BAR 400 OR 600  

………………………………….. — 

7)   PROGRAMMING 

………………………………….. 12 

8)  WARRANTY REGULATIONS 

………………………………….. 13 

9)  TROUBLESHOOTING 

………………………………….. — 

10)  EQUIPMENT DISPOSAL 

………………………………….. — 

11)  USEFUL CONTACTS 

………………………………….. 14 

CONTENTS 

 

 INTRODUCTION 

 

 


background image

3

VRT600 SERIES

 

 

 

 

 

 
 

 

               ATTENTION:  

 

Read the manual carefully before starting to use the control unit. Keep the instructions for future reference. 
 
  
                Do not open the device, touching any internal components can cause electric shock. Contact with 110-240 Volts 
AC can be fatal. To reduce the risk of electric shock, do not dismantle the back of the device for any reason. Moreover its 
opening would void the warranty. B

efore connecting the device to the power supply, make sure that all the 

connections are correct.

 Always disconnect the unit from the supply before any cabling modification. 

                 Any intervention on the equipment must be entrusted to a qualified repair engineer

         Failure to comply with these instructions can cause damages, fires or electric shock, and possible serious injuries! 

 

POWER SUPPLY

 

 

The VRT600 series can be supplied by 230Vac 50/60Hz o a 12Vac –Vcc, depending on the model purchased. 
Before using it, make sure the power cable is not damaged, kinked or pinched. Do not tamper with the power cable. Never 
disconnect the unit by pulling the cable, avoid touching the pins. Do not carry out any connecting/disconnecting with wet 
hands. To disconnect the device, do not use objects such as levers. Immediately disconnect the device if you smell burning 
or see any smoke: contact technical service.  

 

LIQUIDS

 

Do not expose the equipment to splashes or drops, do not position it in places with humidity exceeding 90% and never touch 
with wet or humid hands during storms. If any liquid penetrates the control unit, disconnect it immediately and contact 
technical service. 

 
CLEANING 

Disconnect the power cable before cleaning the control unit, use a dry cloth to dust it, without any solvent or detergents, and 
compressed air. 

 
OBJECTS 

Never insert any objects into the cracks of the control unit. If this happens, disconnect the control unit and  
contact an engineer. 

 
USE RESERVED TO QUALIFIED PERSONNEL 

The purchased goods are a sophisticated electronic device that is totally unsuitable to be used by non-qualified personnel. 
Any intervention must be carried out by a specialist engineer. 

 
ACCESSORIES 

The use of non-original accessories or spare parts might damage the unit and endanger users' safety.  In the event of faults, 
contact technical service. 

 
LOCATION 

Install the control unit indoors, in a place protected from water splashes and sun rays. Do not place near heat sources 
exceeding the parameters stated in this manual. Position on a stable surface, far from any possible vibrations. Position the 
unit as far as possible from any intense magnetic fields. 

 
REPAIRS 

Do not open the control unit. For any fault, always use qualified personnel. The opening of the control unit and/or the removal 
of the series identifying label entails the automatic forfeiture of the warranty. The Warranty seal is applied to all devices, any 
attempt to open the unit would break the seal and cause the consequent automatic forfeiture of the warranty. 

 
 

TECHNICAL INFORMATION  

 

Mail: ufficiotecnico@tecsystem.it — tel: 02/4581861

 

SAFETY REQUIREMENTS 

 


background image

VRT600 SERIES

 

 

 

 

 

 

The following objects are present inside the box: 

Control unit 

 
 
 
 
 
 
 
 
 

Instruction manual CD 

 
 
 
 
 
 

 

2 blocks for panel mounting 

 
 
 
 

1 ENABLE and relay contact terminal 5 poles pitch 

5 Code: 2PL0371 

 
 

 

1

 

1 supply terminal 3 poles pitch 5 
Code: 2PL0367(*) 

 
 
 

 

2

 

Motor line terminal 6 poles pitch 5 
Code: 2PL0372 (*) 

 
 
 
 
 
                                                                                                                                                                 1MN0030 REV.  

* The above terminals are optional according to the configuration purchased. 

ATTENTION: 

always install the device using the terminals included in the pack. The use of terminals other 

than those included with the control unit might cause malfunctions. 

 ACCESSORIES 

 

 


background image

5

VRT600 SERIES

 

 
 
 

 

 

 

TECHNICAL SPECIFICATIONS

 

VRT600

 

VRT600 –U

 

 

 

POWER SUPPLY

 

 

 

 

 

Supply rated values 

230 Vac ±10% 

50/60 Hz 

  12Vac-Vdc ±10%   

50/60Hz 

 

 

INPUTS

 

 

 

 

 

1 contact enabling remote control (ENABLE) 

 

 

 

 

2 motor line supply inputs 250Vac (15 A max) 50/60 Hz max 

 

 

 

 

Connections on extractable terminal blocks 

 

 

 

 

OUTPUTS

 

 

 

 

 

1 fault sensor or operating failure (FAULT) relay 

SPDT

  

 

 

 

 

Output relay with 5A-250Vac-res COS

Ф

=1 contacts. 

 

 

 

 

6 outputs M1-M2-M3-M4-M5-M6 : 250Vac max ±10% 5A max 50/60Hz. 

SPST

 

 

 

 

 

DIMENSIONS

 

 

 

 

 

100x100 mm– din43700-depth 131mm (terminal block included) 

Hole 92 x 92 mm 

Hole 92 x 92 mm 

 

 

TEST AND PERFORMANCE

 

 

 

 

 

Construction in compliance with CE regulations 

 

 

 

 

Protection from electrical interference EN 61000-4-4 

 

 

 

 


background image

VRT600 SERIES

 

 

 
 
 

 

 

 

TECHNICAL SPECIFICATIONS

 

VRT600 SERIES

 

VRT600 U SERIES

 

 

 

TEST AND PERFORMANCE

 

 

 

 

 

Dielectric strength 1500 Vac for 1 minute: supply - relay fault, supply - remote. 

 

 

 

 

Ambient operating temperature from –20°C to +60°C 

 

 

 

 

Humidity 90% non-condensing 

 

 

 

 

Housing NORYL 94 _V0 

 

 

 

 

Absorption 7.5VA (max) 

 

 

 

 

Electronic protection only on customer's request 

 

 

 

 

Polycarbonate IP65 front 

 

 

 

 

DISPLAY AND DATA MANAGEMENT

 

 

 

 

 

LED’s alarm: undercurrent, overcurrent. 

 

 

 

 

LED’s running: remote, local 

 

 

 

 

LED’s prg setting, cal. 

 

 

 

 

Initial AUTO-TUNING to set up motors' operation 

 

 

 

 

Front button to START/STOP motors locally 

 

 

 

 

Front alarm RESET button 

 

 

 

 

Access to programming through front button 

 

 

 

 


background image

7

VRT600 SERIES

 

 

 

 

 

16 

17 

 
 
 

15 

 

14 

13 

 

12 

 

 
 

 

11 

 

10 

 
 
 
 
 

 

8                                   7                  6 

7 6 

1MN0050 REV. 0 

 

 

 

1) 

Control unit series 

10) 

PRG/SET button: entering programming 
and going on to the following step 

2) 

Active (running) ventilation LED (green) 

11) 

Programming phase ON PRG LED (yellow) 

3) 

LED (red) warning motors M1-M2-
M3-M4-M5-M6 are in over-current 

12) 

Current variation LED (yellow) 

4) 

LED (yellow) warning motors M1-M2-
M3-M4-M5-M6 are in under-current 

13) 

Fans' local management LED (yellow) 

5) 

Fixing block 

14) 

Fans' remote control LED (green) 

6) 

Fans' local START/STOP button 

15) 

Programming selection LED (yellow) 
(% In, start d., trip d.) 

7) 

Fans' control mode REM/LOC button 
(REMOTE or LOCAL) 

16) 

Monitoring delay LED (yellow) at start up 
start d. 

8) 

ENT/RESET button: alarm reset and 
programming data selection 

17) 

Release delay LED (yellow) trip d. 

9) 

Motors' auto-tuning phase LED (yellow) 

 

 

 

 

 

 

FRONT PANEL

 

 


background image

VRT600 SERIES

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

Drill a 92 x 92 mm hole in the panel sheet. 

 
 
 

 
 
 
 
 
 
 
 
 
 

 
 

 

 
 
 
 
 
 
 
 

 

1MN0063 REV. 0 

 

1) Control 

unit 

2) 

Panel hole dimensions (+0.8mm tolerance) 

3) Identification 

label 

 

 

 

Fix the unit securely with the blocks supplied. 

 
 
 
 
 
 
 
 
 
 

1 2 

4  

 

1MN0008 REV. 0 

 

1) Control 

unit 

3)  Fixing 

screw 

2) 

Fixing block 

4) 

Crosshead screwdriver #1X100mm 

 MOUNTING  

 


background image

9

VRT600 SERIES

 

 

 

VRT600 SERIES

 

 
 
 
 
 
 
 
 
 

 

 
 
 
 

 

 
 
 
 
 
 
 
 
 

 

1MN0050 REV. 0 

 

 

1)  M4-M5-M6 motor line connection               

(5A max) 

5)  M1-M2-M3 motor line connection                

(5A max) 

2)  M4-M5-M6 fan line supply 230Vac ±10% 

15 amp.max 50-60Hz. 

6)  Remote enabling contact ENABLE 

3)  Control unit supply 

230 Vac ±10% 50-60 Hz 7.5 VA 

7)  FAULT relay (fault signal) 

4)  M1-M2-M3 fan line supply 230Vac ±10% 

15 amp.max 50-60Hz. 

 

 

 

Note: with the power to the unit ON, the FAULT relay switches, contacts 8-9 open (NO) and 7-9 closed (NC).

 

 

 

FAULT  8-9 NC: ALARM FAULT OR POWER OFF 

               FAULT  7-9: NC POWER ON

 

ELECTRICAL CONNECTIONS 

 


background image

10 

VRT600 SERIES

 

 

 

VRT600 U SERIES

 

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

 
 
 
 
 
 
 
 
 

 

1MN0051 REV. 0 

 

 

1)  M4-M5-M6 motor line connection                

(5A max) 

5) 

M1-M2-M3 motor line connection               
(5A max) 

2)  M4-M5-M6 fan line supply 230Vac ±10% 

15 amp.max 50-60Hz. 

6) 

Remote enabling contact ENABLE 

3)  Control unit supply 

12Vac-dc ±10% 6.5VA 

7)  FAULT relay (fault signal) 

4)  M1-M2-M3 fan line supply 230Vac ±10% 

15 amp.max 50-60Hz. 

 

 

 

Note: with the power to the unit ON, the FAULT relay switches, contacts 8-9 open (NO) and 7-9 closed (NC).

 

 

 

                FAULT  8-9 NC: ALARM FAULT OR POWER OFF 

              FAULT  7-9: NC POWER ON

 

 


background image

11

VRT600 SERIES

 

 

 

POWER SUPPLY

 

 

The VRT600 control unit must be supplied with 230Vac 

±

10% 50/60Hz. The VRT600 - U 

control unit must be supplied with 12 Vac - Vdc 50/60Hz. 

According to the model purchased, check the connection diagrams on pages 9 and 10. 

 

A variation in the network voltage of over 10% might cause alarms because of the current variation in the load. 

 

If the electrical system is affected by harmonic frequencies, alarm warnings might be triggered because of the 
consequent variation in the current absorbed by the motors. 

 

It is good practice to make sure that the level of system harmonics is not such as to cause malfunction or damages to 
all the connected electrical and electronic instruments, in compliance with the regulations in force for the type of 
system. 

 
 

OPERATION

 

 

When switched on, the device carries out a LAMP TEST and is set either in REMOTE or LOCAL mode, according to  
how it was set before being switched off. 

 

In REMOTE mode the fans are activated when contact 52-53 closes, which must be connected to the FAN contact of 
the temperature control unit. 

 

In LOCAL mode the fans are activated by pressing the <START-STOP> button. The status of operation is stored in 
case of power failure. 

 
 
 

HOW TO CHECK THE ALARM STATUS

 

 

 

Running LED OFF: 

no ventilation activation control 

 

Running LED ON: 

REMOTE or LOCAL ventilation activation 

 

Over- and under-current LEDs OFF: 

motor operating correctly 

 

Over-current LED ON: 

motor stopped due to over-current 

 

Under-current LED ON: 

motor working + under-current alarm signal 

 

Under-current LED flashing: 

motor disconnected while auto-tuning 

 

Over-current LED ON: 

motor consumption >5.5A (immediate trip without any delay) 

 

All LEDs flashing: 

corrupted memory error (ech); press reset and repeat the programming procedure 

 

 

N.B.: 

A motor in a state of alarm or the interruption of supply to the device make contacts 8-9 of the FAULT relay close. 

 
 

HOW TO RESET A MOTOR IN ALARM

 

 

To reset an alarm due to under-current or over-current, press the RESET button after carrying out the necessary 
checks and any repairs might be required. 

 
 

OPERATION WITH BAR 400 OR 600 

 

 

The 400 and 600 bars are fitted with low current variation motors in case of a motor block. 

To optimise the operation 

of the VRT600 control unit with these bars, we recommend the alarm threshold is programmed at 5%.

 

 
 
 
 
 

                  IMPORTANT  NOTE:  if  an  existing  control  unit  must  be  replaced  with  a  new  one,  to  guarantee  its 
correct and safe operation, all the connecting terminals must be replaced with the new terminals supplied, on 
condition the brand of the new terminals is different from the one of the previously installed ones. 

 

 


background image

12 

VRT600 SERIES

 

 
 

 

 

 

VRT600 and VRT600 U 

 

 

 

 

STEP

 

 

PRESS

 

 

EFFECT

 

 

PRESS

 

 

NOTES

 

 

 

 
 

 

 

 
 

Programming start

 

 

 
 

Keep pressing for 5 seconds until the ON 

PRG LED switches ON. 

 

 

 
 

 

 

 
 

Programming 

“%In”

 

 

 

Set the maximum current variation allowed as a 

percentage (5-10-20-30%) of the In. rated 

value. 

 

Default 5% 

 

 

 

 

Going to the 

"start 

d."

 programming step 

 

Start delay: fan start time during which no 

alarm is generated 

 

 

 
 

 

 

 

Selection of the time in seconds 

"

start d."

 

 

 

Select the desired time                       

(5-10-20-30 sec.) 

 

Default 5 

 

 

 

 

 

 

Going to the 

"trip d."

 

programming step 

 

 

Trip delay: time during which the 

alarm persists, necessary 

for signalling 

 

 

 
 

 

 

 

Selection of the time in seconds  

“trip d.”

 

 

 

Select the desired time (5-10-

20-30 sec.) 

 

Default 5 

 

 

 
 
 
 

 

 

 
 
 

 

Motor start 

for automatic calibration 

CAL LED ON 

 

 

To perform the "automatic calibration" all motors 

must be connected as per final configuration. 

At the START the motors are 

switched ON for 60 seconds, the 

CAL LED flashes and LEDs 0-5-10-

20-30 light up in sequence. 

When the calibration is completed, the 

control unit resets and goes  

into REMOTE mode 

 

 

 
N.B.: any connection or programming errors might cause fan malfunctions. 

 

 
 
         ATTENTION:  
 

We recommend you check the control unit before starting the device. 

  

The default parameters set by TECSYSTEM might not suit your requirements.    

  

Programming the device is the end user’s responsibility: the set alarm thresholds and the enabled functions 
described in this manual must be checked (by a specialized technician) referring them to the application and 
system characteristics on which the control unit is installed.

 

PROGRAMMING  

 


background image

13

VRT600 SERIES

 

 

 

 

 

The purchased product is covered by manufacturer's or seller's warranty as per the "Tecsystem s.r.l.'s General 
Conditions of Sale" available at www. tecsystem.it and/or the purchase agreement drawn up.  
Said Warranty is valid only when the Product fails due to reasons attributable to TECSYSTEM srl, such as manufacturing 
faults or faulty components. 
The Warranty is invalid when the product is tampered with / modified, connected incorrectly, causing voltages outside the 
permitted limits, non-compliant with the use and installation technical specifications, as described in this instruction 
manual. 
The Warranty is always ex our Corsico works, as stated in the "General Conditions of Sale". 

 

 

 

TROUBLESHOOTING 

CAUSES AND SOLUTIONS

 

 

 

 

The control unit does not switch on and the supply to 
terminals 40-42 is correct. 

Check that: the connector is correctly inserted into its housing, 
the wires are tightened, there is no evidence of burning on the 
connectors.  Disconnect the power supply, carry out the above 
and reconnect. 

 

 

 

M1-M2-M3-M4-M5-M6 over-current red LED ON 

 

Check the condition of the fans and replace any faulty ones. Re-
program the device. 

 

 

 

M1-M2-M3-M4-M5-M6 under-current yellow LED ON

 

Check the condition of the fans, the cables and the supply.             
Re-program the device. 

 

 

 

All the LEDs are flashing 

 

Memory error, press RESET and repeat the programming 
procedure. 

 

 

 

All the LEDs are ON 

 

Likely microcontroller fault, return the device to Tecsystem for 
repair. 

 

Contact 

TECSYSTEM Technical Department if the problem persists. 

 

 

 
 

 

 

 

 

European directives 2012/19/EC (WEEE) and 2011/65/EC (RoHS) have been approved to reduce electrical and 
electronic waste and promote the recycling and reuse of the materials and components of this equipment, cutting down 
on the disposal of the residues and harmful components of electrical and electronic materials. 

 

All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant 
to the European directive 2002/96/EEC on electrical and electronic waste (WEEE). Any electrical or electronic 
equipment marked with this symbol must be disposed of separately from normal domestic waste. 

 

Returning used electrical devices: contact TECSYSTEM or the TECSYSTEM agent for information on the correct 
disposal of the devices. 

 

TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the 
correct and environmentally-friendly disposal of its devices. 

WARRANTY REGULATIONS 

EQUIPMENT DISPOSAL 

 


background image

14 