MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
2
Quick Start Guide for Fan Applications
This guide is to simplify the start up of the
MA7200 PLUS Inverter series, 1 to 2 HP
, for fan
applications. It is not intended to replace the MA7200 PLUS Installation and Operation Manual, and
the user is urged review this manual. There are three methods of control or combinations thereof that
that may be selected;
Keypad, Analog Signal (external terminal), or Serial Communication
. Only
Keypad and analog signal control will be covered as Serial Communication is beyond the scope of
this manual. For serial communication control or special external control, the user is referred to the
MA7200 PLUS Installation and Operating Manual.
SAFETY FIRST!
Step 1
- Before Starting the Inverter
• Referring to the MA7200 PLUS Instruction Manual, please review and verify that the correct
inverter size for the associated motor was received free of damage. To ensure personnel safety
and to avoid equipment damage, follow the precautions and the installation procedures for
mounting, wiring, and operating environment.
CAUTION
-
To avoid damage to the inverter when removing the inverter cover
and/or LCD Operator, refer to Appendix B for the proper procedure.
• In accordance with applicable codes, make electrical connections to the motor and input power
terminals. (Refer to the block diagram, Fig. 4).
No other external connections should be made at
this time, as the initial control will be from the keypad.
Step 2
- Apply Power to the Drive
• Apply AC power to the Inverter and observe the LCD Display Line 1; it should read
“
Freq. Cmd 000.0
0
Hz
”. Line 2 should read “
TECO
”. The red LED on the
STOP
key should be
on
.
The
DRIVE
and
FWD
LED’s should be
on
. (See Fig. 1 below)
Step 3
- Set Drive to Run Mode
• If the red
DRIVE
LED is not on with AC power up, press the
PGRM / DRIVE
key until the red
Drive
LED is
on
. The Inverter is now in the
RUN
mode.
DRIVE FWD REV
SEQ
REF
REMOTE
DIGITAL OPERATOR JNEP-36
PRGM
DRIVE
DSPL
FWD
REV
EDIT
ENTER
RESET
RUN
STOP
Freq. Cmd 0
0
0.00Hz
TECO
LED
ON
LED
ON
FLASHING
LED
ON
Fig. 1 MA7200 PLUS Keypad
LOCAL
REMOTE

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
3
Step 4
- Check Fan Motor Operation
•
Enter
10.00Hz
for the frequency reference and set parameter
Sn-08 = 1
to disable Reverse
Direction operation.
Note
:
The output from the inverter is displayed in Hz as factory default. If
desired, the output may be displayed in per cent (%) of full speed. (see appendix)
0
to
;
key
Flashing
1
1 - Press the
key twice
2 - Press the
Flashing
key to
.
3 - Press the
2 Seconds
Flashing
1

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
4
•
Press the
RUN
key, and check the fan direction of rotation. If the direction is not correct, press
the
STOP
key and wait until the fan has come to a complete
STOP.
Next,
power down the
inverter.
Danger
After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards or
components.
•
Reverse any
two
of the fan motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next,
following
STEP 2,
power-up the inverter; the motor direction should now be correct.
Step 5
– Select Method of Control
•
Before selecting the method of control, verify that the inverter is in the
STOP
mode.
•
There are two methods of control or combinations thereof that may be selected;
Keypad
and
Analog Signal.
RUN / STOP Command -
Can be provided from the keypad or from an external contact
(see Fig. 2a).
Speed Reference –
Can be from the keypad or from an external analog signal (0 – 10 VDC or
4 – 20 mA). see Fig’s 3a,3b, and 3c.
•
The
RUN/STOP
method of control is set by parameter
Sn – 04
and the
Speed Reference
is set
by parameter
Sn – 05.
The following table shows the values to be set when selecting.
Value
Start / Stop
Sn – 04=
Speed Reference
Sn – 05=
*0 Keypad
Keypad
1
External Contact
External Analog
*
NOTE
The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad) No
further parameter changes are necessary if this is the desired method of control. If
External Contact set to Sn – 04 or External Analog set to Sn – 05 is desired then proceed
as follows.

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
5

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
6
•
After the method of control has been selected, if external control wiring is required, (e.g. external
analog),
power down the inverter before removing any covers or making any connections.
In the following pages are wiring examples for Start / Stop, E-Stop, Restart, and Analog
Connections.
Danger
After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards, or
components.

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
7
DIGITAL INPUT / OUTPUT terminal connections (1 – 2 HP)
Fig’s 2a, 2b, and 2c below show the control terminal connections for input control functions. The
connections shown are typical and the user is referred to the
MA7200 Manual
if additional
information is required. Fig. 2d shows an example for the use of the
Fault Output Relay
.
RUN
STOP

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
8
ANALOG INPUT terminal connections (1 – 2 HP)
Fig’s 3a,3b, and 3c.show the various analog input schemes that can be used to control the
output frequency and thus the speed of the fan motor when
External Analog
is selected by
Sn-05
in
Step 5
. Only one method may be used as the input source with Fig. 3a Potentiometer
Input being most common.

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
9
MA7200 PLUS BLOCK DIAGRAM
Fig. 4 is an overall basic electrical connection diagram for
MA7200 PLUS
inverters rated
1 to 2
HP
. It is used in conjunction with the other sections of this guide to give the user the ability to
successfully start up a Fan application. More detailed information is available in the
MA7200
PLUS Manua
l to which the user is referred if further information is required.

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
10
Appendix A-
Changing
display to read output speed in percent (%) of full speed.
The display is factory defaulted to show the inverter output frequency in
Hz
. If desired, the
display can be changed to show the output frequency as a
percentage
of full speed. To do this
parameter
Cn-28
must be changed from (00000) to (00001) as follows:
PRGM
DRIVE
DSPL
EDIT
ENTER
Cn – 01 -
key 3 times
Input Voltage
Flashing
To set parameter Cn-28 = 1
Keypad Steps
Resulting Display
1 - Press the
2 - Press the
3 - Press the
key until display shows
4 - Press the
key
key
An – 01 -
Freq. Cmd. 1
EDIT
ENTER
key to
save
6 - Press the
Entry Accepted
2 Seconds
PRGM
DRIVE
7 - Press the
key to return to the main display.
Flashing
Cn-28-
Cn-28 = 0000
0
key
Flashing
5 - Press the
Operator DSPL Unit
Operator DSPL Unit
Cn-28 = 0000
1
Operator DSPL Unit
(Display Percent)
Flashing
Cn-28 = 0000
1
Operator DSPL Unit

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
11
Appendix B -