MA7200

 

PLUS

 INVERTER 

SERIES

FAN Quick Start Manual

1 to 2 HP 

Models- MA7200 -2001/2-N1 (230V) 

&  

           MA7200-4001/2-N1 (460V)

              

Rev. 1.2 – April 14

th

  2008

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

2

Quick Start Guide for Fan Applications 

This guide is to simplify the start up of the 

MA7200 PLUS Inverter series, 1 to 2 HP

, for fan 

applications. It is not intended to replace the MA7200 PLUS Installation and Operation Manual, and 
the user is urged review this manual. There are three methods of control or combinations thereof that 
that may be selected; 

Keypad, Analog Signal (external terminal), or Serial Communication

. Only 

Keypad and analog signal control will be covered as Serial Communication is beyond the scope of 
this manual. For serial communication control or special external control, the user is referred to the 
MA7200 PLUS Installation and Operating Manual. 

  
       SAFETY FIRST! 
 

Step 1

 - Before Starting the Inverter 

• Referring to the MA7200 PLUS Instruction Manual, please review and verify that the correct 
  inverter size for the associated motor was received free of damage. To ensure personnel safety 
  and to avoid equipment damage, follow the precautions and the installation procedures for 
  mounting, wiring, and operating environment.

 

 

CAUTION

 - 

To avoid damage to the inverter when removing the inverter cover 

and/or LCD Operator, refer to Appendix B for the proper procedure.  
 

• In accordance with applicable codes, make electrical connections to the motor and input power 
  terminals. (Refer to the block diagram, Fig. 4). 

No other external connections should be made at 

this time, as the initial control will be from the keypad.   

 

Step 2

 - Apply Power to the Drive 

• Apply AC power to the Inverter and observe the LCD Display Line 1; it should read 
  “

Freq. Cmd 000.0

0

Hz

”. Line 2 should read “

TECO

”. The red LED on the 

STOP

 key should be 

on

.  

  The 

DRIVE

 and 

FWD

 LED’s should be 

on

. (See Fig. 1 below) 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Step 3

 - Set Drive to Run Mode 

• If the red 

DRIVE 

LED is not on with AC power up, press the

 PGRM / DRIVE

 key until the red  

  

Drive

 LED is 

on

. The Inverter is now in the 

RUN 

mode. 

DRIVE FWD REV

SEQ

REF

REMOTE

DIGITAL OPERATOR JNEP-36

PRGM
DRIVE

DSPL

FWD

REV

EDIT

ENTER

RESET

RUN

STOP

Freq. Cmd 0

0

0.00Hz

TECO

LED 

ON

LED 

ON

FLASHING

LED 

ON

Fig. 1 MA7200 PLUS Keypad

LOCAL

REMOTE

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

3

 

Step 4

 - Check Fan Motor Operation 

 

Enter 

10.00Hz

 for the frequency reference and set parameter 

Sn-08 = 1 

 to disable Reverse

 

Direction operation. 

Note

The output from the inverter is displayed in Hz as factory default. If 

desired, the output may be displayed in per cent (%) of full speed. (see appendix) 

 

0

  to 

;

key  

Flashing

1

1 - Press the

key twice

2 - Press the

Flashing

key to 

3 - Press the 

2 Seconds

Flashing

1

 

 

 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

4

 

Press the 

RUN

 key, and check the fan direction of rotation. If the direction is not correct, press 

the 

STOP 

key and wait until the fan has come to a complete 

STOP.

 Next, 

power down the 

inverter.

 

    

 

   

Danger 

After the power has been turned OFF, wait at least 5 minutes until the charge 
indicator extinguishes completely before touching any wiring, circuit boards or 
components.  

 

Reverse any 

two

 of the fan motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next, 

following 

STEP 2,

 power-up the inverter; the motor direction should now be correct. 

 

 
 
Step 5

 – Select Method of Control  

 

Before selecting the method of control, verify that the inverter is in the 

STOP

 mode. 

 

There are two methods of control or combinations thereof that may be selected; 

Keypad

 and 

Analog Signal.

  

 

        RUN / STOP Command - 

Can be provided from the keypad or from an external contact 

                                                 

 (see Fig. 2a). 

           Speed Reference – 

Can be from the keypad or from an external analog signal (0 – 10 VDC or 

                                            4 – 20 mA).  see Fig’s 3a,3b, and 3c. 

 

 

The 

RUN/STOP

 method of control is set by parameter 

Sn – 04

 and the 

Speed Reference

 is set 

by parameter 

Sn – 05.

 The following table shows the values to be set when selecting.  

 
 

Value 

Start / Stop         

Sn – 04=

Speed Reference           

Sn – 05=     

*0 Keypad 

 

Keypad 

External Contact  

External Analog 

 

   *

 

NOTE

 

       

The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad)  No 

        further parameter changes are necessary if this is the desired method of control. If 
        External Contact 
set to Sn – 04 or External Analog set to Sn – 05 is desired then proceed 
        as follows.  

 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

5

 

 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

6

 

 

 

After the method of control has been selected, if external control wiring is required, (e.g. external 
analog), 

power down the inverter before removing any covers or making any connections. 

 

In the following pages are wiring examples for Start / Stop, E-Stop, Restart, and Analog 
Connections.

 

    

   

Danger 

After the power has been turned OFF, wait at least 5 minutes until the charge 
indicator extinguishes completely before touching any wiring, circuit boards, or 
components.  
 

 
 
 
 
 
 
 
 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

7

DIGITAL INPUT / OUTPUT   terminal connections (1 – 2 HP) 

Fig’s 2a, 2b, and 2c below show the control terminal connections for input control functions. The 
connections shown are typical and the user is referred to the 

MA7200 Manual

 if additional 

information is required. Fig. 2d shows an example for the use of the 

Fault Output Relay

.  

 
 
 

 

RUN

STOP

 

 
 
 
 
 
 
 
 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

8

ANALOG INPUT   terminal connections (1 – 2 HP) 

Fig’s 3a,3b, and 3c.show the various analog input schemes that can be used to control the 

      output frequency and thus the speed of the fan motor when 

External Analog 

is selected by  

     

 

Sn-05 

in 

Step 5

. Only one method may be used as the input source with Fig. 3a Potentiometer 

      Input being most common.

  

 

 
 

 
 
 
 
 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

9

MA7200 PLUS BLOCK DIAGRAM 

Fig. 4 is an overall basic electrical connection diagram for 

MA7200 PLUS

 inverters rated 

1 to 2 

      HP

. It is used in conjunction with the other sections of this guide to give the user the ability to 

      successfully start up a Fan application. More detailed information is available in the 

MA7200 

      PLUS Manua

l to which the user is referred if further information is required.

 

 
 
 

 

 

 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

10

Appendix A- 

      Changing

 

display to read output speed in percent (%) of full speed. 

 
      

The display is factory defaulted to show the inverter output frequency in 

Hz

. If desired, the 

       display can be changed to show the output frequency as a 

percentage

 of full speed. To do this 

       parameter 

Cn-28 

must be changed from (00000) to (00001) as follows:

  

 

PRGM

DRIVE

DSPL

EDIT

ENTER

Cn – 01 -

key 3 times

Input Voltage

Flashing

To set  parameter Cn-28 = 1 

Keypad Steps  

Resulting Display

1 - Press the 

2 - Press the 

3 - Press the 

key until display shows

4 - Press the 

key 

key 

An – 01 -

Freq. Cmd. 1 

EDIT

ENTER

key to 

save

6 - Press the 

Entry Accepted

2 Seconds

PRGM

DRIVE

7 - Press the 

key to return to the main display. 

Flashing

Cn-28-

Cn-28 = 0000

0

key   

Flashing

5 - Press the 

Operator DSPL Unit

Operator DSPL Unit

Cn-28 = 0000

1

Operator DSPL Unit

(Display Percent) 

Flashing

Cn-28 = 0000

1

Operator DSPL Unit

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 


background image

                                     MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual 
    _______________________________________________________________ 
 

     ______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

11

 
Appendix B - 
    Removing the LCD Digital Operator and Inverter Cover(s) 
 

 