miniZ

Quick Start Guide

Congratulations on purchasing the miniZ Daylight
Harvesting Controller. The miniZ is designed to be
easy to install and configure with a few simple steps.

Simplest Install Steps:

1.

Physically install unit and any peripherals

2.

Terminate power & control wiring

3.

Enable AutoCal & Auto Burn-In

4.

Power up system

5.

Installation & configuration complete!

Supplement this guide with the full installation manual 
provided for more advanced applications.

 


background image

Control Input: US Models 120VAC & 277VAC terminals, Canadian Models 120VAC & 347VAC terminals
Neutral
Circuit 1 Line
Circuit 1 Load

AutoCal – enable
automatic self-calibration

Configuration Jumpers

Switch Inputs

+ Momentary
+ Maintained
+ Supports SPDT Center Off Switches
+Annunciator/Pilot Light Support

Photocell Input

Supplies +24vdc
Expects +0-10vdc return

Occupancy Sensor Input

Supplies +24vdc
Expects +24vdc return

Emergency Input

Also can be configured

as Occupancy Sensor disable

Photocell Disable

Temporarily disables

daylight harvesting mode

Time Clock

Turns off lights 

when input receives +24VDC

Load Shed

Lights dim 

to shed level when 

input receives +24

Daylight Harvesting
Target – Manual
Adjustment

HVAC and/or
Emergency Output
Relays*

Zone 1 Output (0-10V)*
Circuit 2 Line
Circuit 2 Load
Zone 2 Output (0-10V)*
Zone 3 Output (0-10V)*

1/2" nipple for convenient
connection to junction box

*Varies depending on model

Low Voltage Terminal & Configuration Board

Step 1:

Remove the manual and the miniZ product from the box.

2

 


background image

3

3

miniZ All Models Quick Configuration Guide

REFER TO MANUAL FOR ADVANCED SETUP AND OPERATION

 


background image

4

4

Step 2:

Refer to the Quick Connection Guides found on pages 11-15 of this
guide to connect the line voltage and low voltage circuits. Select the
diagram based on the model you have purchased.

Note:

The dimming models have the 0-10V control output wires leaving the

miniZ controller through the same nipple as the supply and load circuit wires.
They are color coded to different zones as indicated in the manual.

For two zone applications:

• Zone 1 should be connected to the luminaires closest to the daylit area such

as the windows or skylights. This is generally accepted to be approximately
12’ to 15’ from the daylight source.

• Zone 2 should be connected to the luminaires in the next area beyond 15’ to

approximately 25’ from the daylight source.

For three zone applications:

• Zone 1 should be connected to the luminaires closest to the daylight area

such as the windows or skylights. This is generally accepted to be
approximately 8’ to 10’ from the daylight source.

• Zone 2 should be connected to the luminaires in the next area beyond 10’ to

approximately 15’ from the daylight source.

• Zone 3 should be connected to the luminaires beyond the 15’ area.

 


background image

5

5

5

Zone #1 receives most effect from daylight

Zone #2 receives moderate effect from daylight

Photocell

Wall Mount
Occupancy
Sensor

miniZ

Windows along exterior wall

120/277v

Zone #3 receives least effect from daylight

S

Typical Classroom
3-Zone miniZ
Application

 


background image

6

6

Step 3:

Connect the photocell, occupancy sensor (if used), and the wall station
control per the Quick Connect Guides.

Note:

The two zone MZD20 can have two separate wall station controls (see

manual) to operate each zone independently in the manual mode only. If only
one wall station control is used, jumper the two switch input terminals to
control both zones.

Step 4:

Turn the power on to the circuit. The luminaires will come on.

 


background image

7

7

7

3-zone miniZ Application

2000

2000

ZD31

ZB5

MZ

MZ-2

MZ-1

MZ-3

Fixture Types

105W 0-10V Flourescent 

 


background image

8

miniZ Application

ZD22

ZB5

MZ

MZ-2

MZ-1

1000

1000

To

Distribution

Panel

Fixture Types

135W 0-10V Flourescent 

 


background image

9

ZD22

ZB5

ZB5

MZ

MZ-2

MZ-1

1000

1000

To

Distribution

Panel

Dual Room miniZ Application

Fixture Types

135W 0-10V Flourescent 

 


background image

10

Step 5:

In a closed loop configuration, move the Auto-Cal switch to the ON
position as shown in the manual to activate.

Note:

This feature operates the luminaires at full output for a period of 24 hours.

During this time, the miniZ will record the lowest foot-candle reading from the photocell
and record that value as the target illumination. The target illumination is the level that
the miniZ will maintain with the load control output as daylight is available to the
space. The lights will automatically raise or lower (dimmed models) based on how
much daylight is contributing to the overall foot-candle value present to the photocell.

Step 7:

Adjust the proportional dimming output (dimmed models only). The miniZ
has proportional dimming using only one photocell input. To optimize the
light level balance in the space, adjustment to the daylight harvesting
threshold trim pots may be necessary.

For a 2 zone application:

• The zone closest to the daylight source (zone 1) should be turned to 10 or full

clockwise. The next zone (zone 2) should be adjusted to 4 on the dial. This will
balance the dimming so that the light level across the space is more uniform.

For a 3 zone application:

• The trim pots should be zone 1 = 10, zone 2 = 7 and zone 3 = 3.

Step 6:

If the fluorescent lamps are new, move the Burn-In switch to the ON
position as shown in the manual to activate the 100 hour Burn-In feature.
This will keep the lamps from dimming until 100 hours of operating time.
After that they will operate in the dimmed mode.

Note:

Both the Auto-Cal and the Burn-In can occur at the same time.

 


background image

miniZ Quick
Configuration Guide

11

REFER TO MANUAL

FOR ADVANCED

SETUP AND
OPERATION

MODELS:

MZB00-102 &

MZB00-C02 

 


background image

12

miniZ Quick
Configuration Guide

REFER TO MANUAL

FOR ADVANCED

SETUP AND
OPERATION

MODELS:

MZB02-102 &

MZB02-C02 

 


background image

REFER TO MANUAL

FOR ADVANCED

SETUP AND
OPERATION

MODELS:

MZD20-102 &

MZD20-C02 

13

miniZ Quick Configuration Guide

 


background image

REFER TO MANUAL

FOR ADVANCED

SETUP AND
OPERATION

MODELS:

MZD22-102 &

MZD22-C02

miniZ Quick 
Configuration 
Guide

14

 


background image

REFER TO MANUAL

FOR ADVANCED

SETUP AND
OPERATION

MODELS:

MZD30-102 &

MZD30-C02

miniZ Quick Configuration Guide

15

15

 


background image

16

Leviton Manufacturing Co., Inc., Lighting Management Systems Division

20497 SW Teton Ave, Tualatin, OR  97062-8812 USA
PO Box 2210, Tualatin, OR  97062  USA

US Customer Service : (800) 736-6682
Fax: (503) 404-5594  
US Tech Support: (800) 959-6004

Visit our Website at: http://www.leviton.com/LMS

PK-93452-10-00-0A                                                                                                                                                                   G-7666/D7 sw