Models beginning with MO, MK, 7B, 6S, 6F or 5B 

The Mini Meter™

 

 

Product Description 

Technical Specifications 

Installation Instructions 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

Contents 

 

1. Product Description .................................................................................................................................2 

1.1 General Description……...........................................................................................................2 
1.2 Meter Features...........................................................................................................................2 
1.3 Meter Certifications ..................................................................................................................3 
1.4 Physical Description .................................................................................................................3 

1.4.1 Single Meter..............................................................................................................3 
1.4.2 Enclosures.................................................................................................................4  

2. Technical Specifications ..........................................................................................................................5 

2.1 Electrical Specifications…........................................................................................................6 
2.3 Input/Output Connections.........................................................................................................6 

Display Specifications.......................................................................................................7 
          General Display Information ..................................................................................7 

3. Installation Instructions............................................................................................................................8 

3.1 Explanation of Warning Symbols ............................................................................................8 
3.2 Safety Precautions.....................................................................................................................8 
3.3 Preparation ................................................................................................................................9 
3.4 List of Materials....................................................................................................................... .9 
3.5 Mounting the Enclosure .......................................................................................................... .9 

3.5.1 Mounting Location ...................................................................................................9 
3.5.2 Drilling Conduit Holes............................................................................................ 10 
3.5.3 Mounting Procedure and Conduit Installation.........................................................10 

3.6 Installation of Voltage Lines................................................................................................... 11 
3.7 Variations and Installation of Current Transformers ............................................................ .11 

General Requirements...................................................................................................... 12 

3.8 Testing the Installation.............................................................................................................14 

4. Maintenance............................................................................................................................................ 15 
5. Troubleshooting/FAQ..............................................................................................................................15 
6. Contact Information.................................................................................................................................16 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co, Inc. 

 

 

List of Figures 
 

Figure 1: Single Mini Meter and Epoxy Encapsulated Module......................................................... 3 
Figure 2: Small Enclosure Outline and Mounting Dimensions......................................................... 4 
Figure 3: Mini Meter Connections and Display................................................................................ 6 
Figure 4: Mounting the Enclosure ……........................................................................................... 10 
  

List of Tables 
 

Table 1: Electrical and Environmental Specifications....................................................................... 5 
Table 2: I/O connections.....................................................................................................................7 
Table 3: LED Display Indicators........................................................................................................7 
  

 

 

 

1.  Product Description 

1.1  General Description 

The Leviton Mini Meter

™ is a self-powered, current transformer (CT) rated 

electronic kilowatthour (kWh) meter designed for permanent connection to an 
electrical service. Mini Meters come in single element (2-wire) and dual element (3-
wire) configurations.   

1.2 Meter Features 

  Revenue-grade accuracy with solid-core or easy to install split core CTs 

  Built in LCD that display or external mechanical counter 

  Encapsulated model for harsh environments (Model Number prefixes 5B) 

  Multiple load monitoring with a single meter 

  AMR compatible isolated pulse outputs 

  Reverse-phase LED indicator 

  5-year warranty 

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

1.3 Meter Certifications 

  UL Recognized Component for us in US or Canada 

  Conforms to accuracy requirements set forth in ANSI C12.10 

  Certified to California Division of Measurement Standards 

  Approved by the California Energy Commission for use in California Solar 

 

1.4 Physical Description  

 

1.4.1 Single Meter  

Figure 1 below shows the dimensions of a single Mini Meter or Epoxy 
Encapsulated case and cover.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

1.4.2 Enclosures 

Mini Meter and Epoxy Encapsulated module enclosures mounting drawings are 
shown below in figure 2. 
 

 

 

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

2. Technical Specifications 

2.1 Electrical Specifications 

Mini Meters and Epoxy Encapsulated Modules fall under UL Circuit Category III: a 
device for measurements performed in the building installation. The electrical 
specifications for Mini Meters are given in the table below. 
 
Input Configurations    

 

 

 

1 Phase, 2 wire  
1 or 2 Phase, 3 wire 

 

Supply Voltage Range  

 

 

 

Min. 102 VAC 

(L1 or L2 to Neutral)    

 

 

 

Max. 138 VAC 

 

Maximum Input Power, L1 and L2    

 

8 VA 

 
Maximum Rated Current

1  

 

 

 

440 A primary for 400 A models 
220 A primary for 200 A models 
110 A primary for 100 A models 

0.11 A secondary for 0.1 A secondary models 
0.22 A secondary for 0.2 A secondary models 

 

Line Frequency  

 

 

 

 

50-60 Hz 

 
Power Factor Range    

 

 

 

0.5 to 1.0, leading or lagging 

 
Accuracy  

 

 

 

 

 

+/- 0.5% of registration @ 1.0pf. 2 to 200 A 
+/- 0.75% of registration @ 0.5pf, 2 to 200 A 

 

Operating Temperature Range 

 

 

-30 to +60 degrees C 

 
Rated Pollution Degree

2  

 

 

 

 
Rated Relative Humidity  

 

 

 

80% 

 

Terminal Blocks: 
Dinkle/International Connector 

 

 

4.4 in-lb of torque maximum 

    EK508-11P or equiv. 

 

 
Table 1: Electrical and environmental specifications 

 
 
 
 

1

Product approved for use with included Leviton Current Transformers, as follows: 

 

400A  

 

200A 

 

100A 

 

2

Pollution Degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by 

condensation must be expected. 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

2.2 Input/Output Connections and User Display 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Inputs (wire connections)

  

 

 

Description 

 
L1  

Black wire, voltage input, Line 1, 
120V with respect to neutral 

 

 

 

 

 

  

 

 

White wire, Neutral input 

 
L2 

Red wire, voltage input, Line 2, 120V 
with respect to neutral (7B and 5B 
models only) 

 

CT Inputs  

 

CT1 : X1  

Current Transformer input, CT1. 
Colored wire of CT 1 

 
CT1 : X2  

Current Transformer input, CT1. White 
wire of CT1 

 
CT2 : X1  

Current Transformer input, CT2.Colored 
wire of CT2 (7B and 5B models only)

 

 
CT2 : X2  

Current Transformer input, CT2. White 
wire of CT2 (7B and 5B models only)

 

Figure 3: Mini Meter connections and display 

Power LED 

Load LED 

Optional LCD 

Display area

 

Reverse Phase 

LED 

Sealing Studs 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

Outputs 

 

 
10, Isolated Output (10 Wh/P, Kh = 10)  

 

Isolated pulse output: 5 watthours on, 5 
watthours off, referenced to ISOL COM 

NOT TO BE USED FOR FIELD WIRING

 

 
100, Isolated Output (100 Wh/P, Kh=100)  

Isolated pulse output: 50 watthours on, 50 
watthours off, referenced to ISOL COM 

 
1000, Isolated Output (1 kWh/P, Kh=1000)  

Isolated pulse output: 500 watthours on, 500 
watthours off, referenced to ISOL COM (not 
available on models with T suffix) 

 
ISOL COM  

Isolated common for 10/100/1000 isolated 
outputs  

 
Counter (kh = 100 or kh = 1000)*  

 

 

For 12 VDC electro-mechanical counter 

 
Counter (kh = 100 or kh = 1000)*  

For 12 VDC electro-mechanical counter 

 
+12 VDC 

 

 

 

 

 

12 VDC output; current rating is 3 mA max.

 

(MMS and MMD models only) 

 
 

Table 2: I/O connections 

 

*Recommend Leviton mechanical counter  (1 kWh models), (0.1 kWh models), or equivalents

 

LED Indicators

  

 

 

Description 

Power LED (green)    

 

Illuminates when the meter is supplied with proper voltage 

 
Load LED (green)  

50% duty cycle (at constant load) LED to verify proper 
meter function when connected to a load. At 200 watts, 
LED will illuminate for 1.5 minutes, then turn off for 1.5 
minutes; with no load, LED will remain on or off 

 
Reverse Phase LED (red)  

Illuminates when a problem with meter phasing exists. 
With no load, LED may be on or off. See CT installation 
section for instructions.  

 
LCD Display    

 

 

Optional LCD display that shows total kWh 

 

Table 3: Display indicators 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

3. Installation Instructions 

The following section contains installation and wiring instructions for the Leviton Mini 
Meter

™.  If technical assistance is required at any point during the installation, contact 

information can be found at the end of this manual.  Leviton is not responsible for 
damage to the meter caused by incorrect wiring.

3.1. Explanation of Warning Symbols 

 

 

Indicates the need to consult the operation manual due 
to the presence of a potential risk. 

 

 

 

Indicates the presence of electric shock hazards.  Prior 
to proceeding, de-energize the circuit and consult the 
operation manual. 

 

 

 

 

 

 

3.2 Safety Precautions

  

WARNING

 

 

 

Installation of electric meters requires working with possibly hazardous 
voltages.  These instructions are meant to be a supplement to aid 
trained, qualified professionals.   

 

 

Turn off all power supplying the equipment before performing any wiring 
operations.  Use a properly rated voltage sensing device to confirm 
power is off.

 

 

 

Bonding is not automatic for metal conduit connections; separate 
bonding is to be provided.

 

 

 

Installations should be done in accordance with local codes and current 
National Electric Code requirements. 

 

 

Equipment used in a manner not specified by this document impairs the 
protection provided by the equipment.

 

 

Failure to follow these warnings could result in serious injury or death.

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

 

 

 

 

3.3 Preparation 

1. Verify the model number and electrical specifications of the device being installed 
to confirm they are appropriate for the intended electrical service (see Section 2). 

2. Consult local codes for any possible permits or inspections required before 
beginning electrical work. 

3. Ensure the conduit for the installation is flexible and non-metallic.  For outdoor 
applications conduit and conduit fittings must be rated for UL Type 4x outdoor 
enclosures.  Failure to use the appropriate conduit impairs the degree of equipment 
protection.   

4. Make sure all tools to be used during installation have proper insulation ratings. 

5. Look at the Meter and inside the electrical panel for possible exposed wire, broken 
wire, damaged components or loose connections. 

3.4 List of Materials 

  Mini Meter or Epoxy Encapsulated Module small enclosure and associated mounting 

material.  

  Line 1, Line 2, and Neutral hook-up wires as needed for the electrical service. 

  Wires must be 18 AWG or larger and insulated for 300 VAC min. 

  Current Transformers (CTs): This product is designed for use with Leviton CTs  

  Flexible, non-metallic conduit and fittings; UL Type 4X for outdoor applications. 

3.5 Mounting the Enclosure 

 

 

3.5.1 Selecting a Mounting Location 

  Meter installations require a switch or circuit breaker as part of the building 

installation. 

  The switch or circuit breaker must be marked as the disconnecting device for 

the meter. 

  It is recommended that the enclosure be mounted near the disconnecting 

device in an area with adequate ventilation. 

  The enclosure should not be positioned in a manner that makes it difficult to 

operate the disconnecting device. 

  Ensure that the CT and voltage lead lengths (and conduit lengths) are capable 

of reaching the enclosure from the load center. 

  If a suitable mounting location near the load center cannot be found, additional       

in-line fuses or circuit breaker may be required in accordance with NEC regulations. 
 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

10 

  

 

3.5.2 Drilling Conduit Holes 

The bottom panel and lower half of the side panels work best for conduit opening 
locations in outdoor single meter enclosures. Select the location the makes wire 
installation easiest for the given environment. If the side panels are used, holes 
should be centered approximately half an inch from the bottom of the enclosure. 
Hole sizes must be appropriate to fittings, and large enough to fit all voltage and 
CT wiring (4-7 18 AWG min. wires insulated for 300 V min.). Care should be 
exercised to keep drill bit away from components inside the enclosure. 

Type 4X 

conduit and fittings must be used in order to maintain the outdoor rating of 
the enclosure. 

 

3.5.3 Mounting Procedure and Conduit Installation 

1. Attach the mounting brackets to the back of the enclosure with the four 
provided screws.. 
 
2. Fasten the enclosure to the selected surface via mounting holes. 
 
3. Verify that the enclosure is not loose and that all connections are secure. 
 
4. Attach the conduit between enclosure and load center, routing wires as 
necessary for later use. 
 
5. Make sure the conduit fittings are aligned properly and tightened securely to 
prevent moisture from entering the enclosure (outdoor applications). 

 

Figure 4: Mounting the Enclosure

 

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

11 

  

 

3.6 Installation of Voltage Lines 

 

 

1

. Field wired voltage connections are made to the Mini Meter terminal block.  The rated 

torque for these terminal blocks is 4.4 in-lb, and can be used with solid and stranded 
copper wires, at 12-18 AWG. 
 
2. Verify that branch circuit fuse specifications meet local electric codes.  
 
3. Connect 18 AWG min., 300 V min. insulated wiring for Line voltages and Neutral to 
the appropriate locations in the breaker panel, in accordance with all national and local 
electrical codes; see Figure 9 for wiring diagram. 
 
4. Route wires through the conduit if not already done. 
 
5. Trim the wire to the appropriate length to avoid coils of excess wiring. 
 
6. Strip wiring to approximately .300 inches if needed and connect to the appropriate 
terminals. Wires should be tightened so that they are held snuggly in place, but do not to 
over-tighten, as this may compress and weaken the conductor. 

 

 

3.7 Installation of Current Transformers 

 

 

 

To reduce risk of electric shock, always open or disconnect 
the circuit from the power distribution system of a building 
before installing or servicing current transformers. 

 

 

 

In accordance with NEC, CTs may not be installed in any panel 
board where they exceed 75% of the wiring space of any cross-
sectional area. 

 

 

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

12 

 

 

General Requirements: 

 

Splices on the CT leads must be within the meter enclosure, not inside the conduit. 
Leviton provided CT leads are 24 inches minimum. Wire insulation should be stripped so 
that the bare conductor length that connects to the meter terminal block does not exceed 
0.300 inches. 

 

CTs should be securely fastened such that they will not slide down to live terminals. 

 

Wires should be tightened so that they are held snuggly in place, but do not to 
overtighten, as this may compress and weaken the conductor. 

 

Current and voltage inputs must be installed ‘in phase’ for accurate readings (e.g. CT1 on 
Line 1, CT2 on Line 2) 

 

 

 

 

 

 

Leviton solid core CTs 

Installing solid core CTs 
1.  Route CT wires through the conduit if not already done. 
2.  Trim the wire to the appropriate length to avoid coils of excess wiring. 
3.  Strip wiring to approximately .300 inches and connect to the appropriate 

terminals as described above. 

4.  With power turned off, disconnect each monitored conductor and slide on a 

CT, ensuring the CT is correctly oriented as noted above. 

5.  Reconnect the conductors. 

Failure to install CTs in the correct orientation and on the correct phase will lead to inaccurate 
meter readings. 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

13 

 

 

 

 

 

 

3-Phase, 4 wire hookup diagram 

Leviton  

 

 

Leviton  

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

14 

 

 

3.9 Testing the Installation 

 

Testing Voltage 

 

 
The power LED illuminates when the Mini Meter or Epoxy Encapsulated Module 
has a proper power supply. Voltage should also be tested using an AC Voltmeter 
to verify that the voltage across voltage line terminals (L1 to Neutral and L2 to 
Neutral) is not in excess of the maximum rated voltage. 
 

 

CT Reverse Phase Indicator 

 

Mini Meters and EE Modules have a red reverse phase indicator LED as 
described in section 2.3. 

There must be a load drawing a minimum of 1 A 

connected to the meter in order for the reverse phase LED to function 
correctly

. If a proper load is connected, and the LED is illuminated, power down 

the voltage supply and verify that CTs are installed correctly. 
 

 

Load LED 

 

The load LEDs are described in section 2.3. These LEDs should be pulsing at 
50% duty cycle when the meter is connected properly and a constant load is 
applied.   
 
 

3.10 Securing the Enclosure 

In accordance with safety requirements, enclosures must be secured using the 
provided key lock once installation is complete. The purpose of the lock is to 
prevent access to live parts that pose potential safety risks. To install the lock, 
slide through the provided holes on the clamp side of the enclosure and fasten 
securely. 

 

 

 

 

 

 

 

www.

.com

information@itm.com

1.800.561.8187

 


background image

 

Mini Meter Installation Manual 

 

Leviton Manufacturing Co., Inc. 

15 

 

 

4. Maintenance

 

Properly installed meters with sound connections and secure conduit fittings should 
not require user maintenance. If the meter is functioning abnormally, consult the 
FAQ/Troubleshooting guide.

 

5.  Troubleshooting/FAQ

 

Problem 

Solution 

 

 

1.  Power LED not illuminated 

  Check to make sure all connections are 

wired  

  Test the voltage being supplied to the 

meter using an AC voltmeter 

  With power off, remove any additional 

line fuses and test with ohmmeter 

 

 

2.  Load LED not flashing 

  Verify CT connections and orientations  

  Make sure there is sufficient load to 

draw a significant current 

  Test the voltage being supplied to the 

meter using an AC voltmeter 
 

3.  Registered consumption low 

  Check to make sure the reverse phase 

LED is not on 

  Even if the reverse phase light is off, 

double-check CT orientations.  One CT 
installed in the incorrect direction 
doesn’t always illuminate the reverse 
phase LED 

  Make sure that current and voltage 

connections are in phase  

  Check power connections and fuses 

 

 

4.   Reverse phase LED illuminated 

  Verify orientation and connection of CT 

wires  

  Ensure that phasing is correct (CT1 on 

Line 1, CT2 on Line 2) 

  Verify that a load drawing more than 1 

Amp is connected to the meter 

 

 

 