GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

This guide is provided by LEWCO, Inc. to assist its customers in becoming familiar with how LEWCO Inc. sets 

up and uses the Eurotherm Controllers to test equipment prior to shipping.  This document does not replace 

respective Eurotherm user’s manuals and anyone using any of the Eurotherm products mentioned here is 

responsible for obtaining and understanding the user’s manual before using any of these controllers.  The user 

is responsible for setting up and configuring these devices to meet their own application requirements, not 

limited to but including adjusting set points, and setting up alarms. 

If you do not have a manual for your controller or just wish to view an online version of it, please use the 

following link: 

http://www.eurothermonline.com/search?searchwords=manuals&searchsmall_4920=

 

 

3216 AND 3216i  INSTRUCTION 

This set of instructions will work for both the 3216 Process Controller and 3216i FM approved High Limit 

controller. 

 

BUTTON  LEGEND:

 

 

 

 

 

 

 

 

 

 

 


background image

                                                       

  

 

 

 

 

GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

 

TO CHANGE  ENGINEERING UNITS (°F TO 

°

C

)

 

Press and hold the 

PAGE

 button until 

LEv1

 shows in the upper display and 

GOTO 

shows in the lower 

display. Select access level will scroll through the lower display. 

 

Press the 

UP

 and 

DOWN

 arrows and change 

LEv1

 to 

LEv2

 

 

The word 

CODE 

will be shown in the lower display and a 

“0”

 will be shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the 

“0”

 to a 

“2”

 

 

Press the 

SCROLL

 button until 

UNITS

 is shown in the lower display and the current units are shown in 

the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change to desired units 

°F

 

 

 

TO CHANGE  THERMOCOUPLE TYPE: 

 

Press and hold the 

PAGE

 button until 

LEv3

 shows in the upper display and 

GOTO 

shows in the lower 

display. Release the 

PAGE

 button. 

 

The word 

CODE 

will be shown in the lower display and a 

“0”

 will be shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the 

“0”

 to a 

“3”

 

 

Press the 

PAGE

 button until 

INPUT

 is shown in the lower display.  

 

Press the 

SCROLL

 button until 

IN.TYP

 is shown in the lower display and the current type is shown in 

the upper display 

(J.TC) 

 

Press the 

UP

 and 

DOWN

 arrows and change to desired units type 

 

Press the 

SCROLL

 button to save 

 

Press and hold the 

PAGE

 button again and until 

CONF

 is in the upper display and 

GOTO

 is in the 

lower display  

 

Press the 

UP

 and 

DOWN

 arrows and change 

LEv3

 to 

LEv1

 

 

Controller will cycle power and automatically restart. 
 

3216  INSTRUCTION 

The 3216 Process Controller is a 1/16-DIN highly precise temperature controller.

 

 

 

OPERATION: 

 

Provides simple and precise temperature control

 

 

 

TO CHANGE SET POINT: 

 

Press the 

UP

 and 

DOWN

 arrows until desired set point is reached 

 

 

 

 


background image

                                                       

  

 

 

 

 

GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

 

TO CHANGE THE TEMPERATURE RANGE: 

NOTE

: The range high value RNG.H should never be set higher than the maximum temperature of the 

oven/drum cabinet. Doing so may cause damage to the unit. Customer assumes responsibility for any 
damages caused by changing the range high limit. 

 

 

Press and hold the 

PAGE 

(1

st

 on the left) button until 

Lev3

 shows in the upper display and 

GOTO 

shows in the lower display.  

 

Press the 

UP

 and 

DOWN

 arrows and change 

Lev3

 to 

conf

 

 

The word 

CODE 

will be shown in the lower display and a 

“0”

 will be shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the 

“0”

 to a 

“4”

 

 

Press the 

PAGE

 button until 

INPUT

 is shown in the lower display 

 

Press the 

SCROLL

 button until 

RNG.H 

is shown in the lower display and the current maximum 

temperature is shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the value to the desired temperature range  

 

Press the 

PAGE 

button unit 

sp

 is shown in the lower display 

 

Press the 

SCROLL 

button until 

sp.hi

 is shown in the lower display and the current maximum 

temperature is shown in the upper display 

 

Press the 

UP 

and 

DOWN

 arrows and change the value to the desired set point range 

 

Press and hold the 

PAGE

 button until 

conf

 shows in the upper display and 

GOTO

 shows in the lower 

display 

 

Press the 

UP 

and 

DOWN 

arrows and change 

conf 

to 

LEV1

 

 

Controller will cycle power and automatically restart 

 
NOTE

: This procedure can be repeated to change the low range rng.L and low set point sp.lo  

 

This high and low range will determine the maximum and minimum temperature set point of the 
unit. 

 

 

TO VIEW THE WORKING OUTPUT: 

 

Press the 

SCROLL

 ( 2nd from the left) button 

 

Press the 

UP

 and 

DOWN

 arrows value will show between 

0-100%

 

NOTE

: If heat output is on OP1 or OP2 will show in the upper left hand corner of the controller 

 
 
 
 
 

 


background image

                                                       

  

 

 

 

 

GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

 

TO AUTOTUNE THE CONTROLLER: 

 

Press and hold the 

PAGE 

(1

st

 on the left) button until 

LEv1

 shows in the upper display and 

GOTO 

shows in the lower display. Select access level will scroll through the lower display. 

 

Press the 

UP

 and 

DOWN

 arrows and change 

LEv1

 to 

LEv2

 

 

The word 

CODE 

will be shown in the lower display and a 

“0”

 will be shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the 

“0”

 to a 

“2”

 

 

Press the 

SCROLL

 button until 

A.TUNE

 is shown in the lower display and 

OFF

 is shown in the upper 

display 

 

Press the 

UP

 and 

DOWN

 arrows and change the

 OFF

 to 

ON

 

NOTE

: When Autotune is running TUNE will flash in the upper display. When this stops flashing the 

Autotune is complete.  

 

3216i  INSTRUCTION

 

The 3216i is a 1/16-DIN FM approved alarm indicator with one FM Approved form C relay output. Terminals 
AA, AB, and AC are dedicated to this Alarm.  
 

 

OPERATION:

 

 

If an alarm set point is exceeded or a sensor failure occurs, the alarm relay will change state. Once the 
sensor fault and PV return to a safe state and have been acknowledged the relay will return to their 
original state. 

 

 

TO ACKNOWLEDGE / RESET THE ALARM RELAY: 

 

The alarm relay is FM approved and must be manually acknowledged. Once the process variable has 
returned to a safe value and the alarm is acknowledged the relays will automatically reset. The alarm 
can be acknowledged by pressing the 

PAGE 

and 

SCROLL

 buttons at the same time. 

 

 

 

 

 

 

 

 

 

 


background image

                                                       

  

 

 

 

 

GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

 

TO CHANGE THE TEMPERATURE RANGE: 

NOTE

: The range high value RNG.H should never be set higher than the maximum temperature of the 

oven/drum cabinet. Doing so may cause damage to the unit. Customer assumes responsibility for any 
damages caused by changing the range high limit. 

 

 

Press and hold the 

PAGE 

(1

st

 on the left) button until 

Lev3

 shows in the upper display and 

GOTO 

shows in the lower display.  

 

Press the 

UP

 and 

DOWN

 arrows and change 

Lev3

 to 

conf

 

 

The word 

CODE 

will be shown in the lower display and a 

“0”

 will be shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the 

“0”

 to a 

“4”

 

 

Press the 

PAGE

 button until 

INPUT

 is shown in the lower display 

 

Press the 

SCROLL

 button until 

RNG.H 

is shown in the lower display and the current maximum 

temperature is shown in the upper display 

 

Press the 

UP

 and 

DOWN

 arrows and change the value to the desired temperature range  

 

Press and hold the 

PAGE

 button until 

conf

 shows in the upper display and 

GOTO

 shows in the lower 

display 

 

Press the 

UP 

and 

DOWN 

arrows and change 

conf 

to 

LEV1

 

 

Controller will cycle power and automatically restart 

 

 

TO CHANGE ALARM SET POINTS: 

 

Press the 

SCROLL

 button. The display will show the current set point in the upper display and 

A1.HI

 in 

the lower display 

 

Press the 

UP

 and 

DOWN

 arrows until desired set point is reached 

 

Press the 

PAGE

 button to exit 

 

NOTE

Set Limit Controller Set Point at 20 degrees F. over maximum operating temperature. 

 

Electric Drum Heating Cabinets: 300

°

 F + 20

°

 F = 320

°

 F. 

 

Steam Drum Heating Cabinets: 300

°

 F + 20

°

 F = 320

°

 F. 

 

High Humidity Drum Heating Cabinets: 190

°

 F + 20

°

 F = 210

°

 F. 

 
 
 
 
 
 

 

 


background image

                                                       

  

 

 

 

 

GENERAL INSTRUCTION GUIDE

 

EUROTHERM 3216 & 3216i CONTROLLERS 

 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

 

TO ADJUST THE ALARM HYSTERESIS VALUE: 

Hysteresis 

is the difference between the point at which the alarm switches 

ON

 and the point at which 

it switches 

OFF

. It is used to prevent relay chatter. 

 

Press the

 SCROLL

 until 

A1.HYS

 is shown in the lower display the current hysteresis value is shown in 

the upper display.  

To adjust the hysteresis value, use the 

UP

 or 

DOWN

 button; the minimum value is 1