GUIDA RAPIDA

PER LA MESSA IN SERVIZIO DELL’APPARECCHIATURA

DI RIFASAMENTO FISSA O AUTOMATICA

ALL65 rev7 jan18 cod.10098513

1 / 12

NOTA DI SICUREZZA

L’accesso ai componenti interni per installazione, regolazione, ispezione e manutenzione deve essere affidato
esclusivamente a personale qualificato incaricato allo scopo. Qualsiasi operazione deve essere svolta in conformità alla
legislazione e alla normativa vigenti in materia di sicurezza personale e tramite l’utilizzo di strumenti di protezione adeguati.
Interventi non autorizzati potrebbero causare il malfunzionamento o il danneggiamento del quadro di rifasamento. In tal caso,
le clausole di garanzia e la responsabilità del Fabbricante perderebbero automaticamente di validità.

Il Fabbricante non si riterrà responsabile per danni diretti o indiretti causati a persone o cose in caso di errato

montaggio delle apparecchiature o di un loro uso non adeguato.

COLLEGAMENTO ALLA RETE

Collegare le tre fasi della linea ai morsetti contrassegnati 1-2-3 o R-S-T (L1-L2-L3). Porre particolare attenzione
al dimensionamento della linea di alimentazione dell’apparecchiatura di rifasamento e di eventuali organi di
manovra e/o protezione in quanto devono essere dimensionati per poter sopportare almeno una corrente pari a
1,5 volte la corrente nominale della batteria.

COLLEGAMENTO DEL CAVO DI TERRA

Collegare il cavo di terra all’apposita connessione predisposta sull’apparecchiatura. La dimensione del conduttore
di terra dovrà essere almeno pari al 60% del conduttore di fase (esempio: cavo di fase da 120mm

2

– cavo di terra

almeno 72mm

2

).

Terminate le operazioni soprariportate dare tensione all’apparecchiatura. Nel caso di apparecchiature non
automatiche la messa in servizio è terminata.
Le operazioni successive possono essere eseguite unicamente su apparecchiature di rifasamento automatiche.

ATTENZIONE: tutti i parametri del regolatore sono impostati in fabbrica ad eccezione del valore del

primario del TA. Per modificare altri valori consultare il manuale del regolatore di potenza reattiva in

allegato all’apparecchiatura (scaricabile anche dall’area download del sito www.icar.com) ed

eventualmente contattare il servizio Assistenza ICAR PQS.

IMPOSTAZIONE DEL REGOLATORE DI POTENZA REATTIVA

Regolatore RPC 5LGA

All’accensione dell’apparecchiatura il display del regolatore visualizzerà la scritta “Ct” lampeggiante.

Premere il tasto ▲ per inserire il valore del primario del trasformatore amperometrico.  

Inserito il valore premere il tasto

per confermare.

Regolatore RPC 8LGA

All’accensione dell’apparecchiatura il display del regolatore visualizzerà la scritta “Ct” lampeggiante.

Premere il tasto ▲ per inserire il valore del primario del trasformatore amperometrico.  

Inserito il valore premere il tasto

per confermare.

 


background image

ICAR PQS

ALL65 rev7 jan18

2 / 12

Regolatore RPC 8BGA

Descrizione del fronte

Tasti di navigazione



Tasto di conferma

Led di allarme

!

Porta ottica per connessione WIFI e USB

Impostazione parametri funzionali

Alla prima messa in tensione del rifasatore, le operazioni da fare sono:

a)

Inserire data e ora. Il regolatore propone la schermata:

In questa schermata aumentare o diminuire con i tasti



i valori numerici. Utilizzare i tasti



per

spostarsi da un numero all’altro. Confermare con il tasto

.

b) Inserire la lingua desiderata. Il regolatore propone la schermata:

confermare con il tasto

per passare alla schermata LINGUA.

In questa schermata selezionare la lingua con i tasti



. Confermare con il tasto

.

c) Inserire il valore del primario del TA esterno. Il regolatore propone la schermata:

confermare con il tasto

per passare alla schermata PRIMARIO TA.

In questa schermata selezionare il valore del primario del TA con i tasti



. Confermare con il tasto

.

Per eventuali modifiche successive del valore del primario del TA, selezionare il menù IMPOSTAZIONI, quindi il
menù M02 GENERALE. Selezionare la voce P02.01 PRIMARIO TA. Operare come sopra.

 


background image

ICAR PQS

ALL65 rev7 jan18

3 / 12

Schermata principale

Campo testo descrittivo. Può essere modificato dal menù IMPOSTAZIONI

M01 UTILITA’

P01.09 DESCRIZ. IMPIANTO

Cosφ istantaneo dell’impianto. IND= induttivo, CAP= capacitivo

Stato degli step comandati dal regolatore. Simbolo nero: step attivato. Simbolo
grigio: step disattivato. Simbolo assente: uscita non utilizzata. Numero grigio:
step temporaneamente non disponibile (ad esempio: appena disinserito).
Fattore di potenza medio settimanale, calcolato sugli ultimi 7 giorni.
Temperatura attuale nel quadro, stato della ventola ( = ferma;

= in funzione)

AUT= regolazione automatica del cosφ; MAN= funzionamento manuale

Potenza reattiva mancante (segno +) o in eccesso (segno -) rispetto al cos

φ

target impostato
Valore istantaneo del THD% della tensione concatenata

Valore istantaneo del THD% della corrente di linea, nel punto di installazione del
TA

Con i tasti



si naviga tra le diverse schermate disponibili. Con il tasto

si accede alla schermata MENU’

PRINCIPALE. Con i tasti



si accede alla visualizzazione degli altri step eventualmente presenti oltre quelli

della schermata 1/4.

Schermata menù principale

Selezionare il menù desiderato con i tasti



. Confermare con

. Il menù selezionato si colora in negativo, e

compare al centro una sua descrizione testo.

Selezionare questa icona per impostare il funzionamento in manuale (MAN).

Selezionare questa icona per impostare il funzionamento automatico (AUT).

Descrizione e significato degli allarmi

CODICE ALLARME

SIGNIFICATO

A01

Sottocompensazione

Tutti gli step disponibili sono inseriti, ma il cos

φ

rimane più induttivo

del setpoint.

A03

Corrente impianto troppo bassa

La corrente circolante sugli ingressi amperometrici è inferiore alla
minima consentita dal range di misura.
Condizione che si può verificare normalmente se l’impianto non ha
carico.

A04

Corrente impianto troppo alta

La corrente circolante sugli ingressi amperometrici è superiore alla
massima consentita dal range di misura.

A05

Tensione impianto troppo bassa

La tensione misurata è inferiore alla soglia impostata con P17.14.

A06

Tensione impianto troppo alta

La tensione misurata è superiore alla soglia impostata con P17.13.

 


background image

ICAR PQS

ALL65 rev7 jan18

4 / 12

CODICE ALLARME

SIGNIFICATO

A07

Temperatura quadro troppo alta

La temperatura del quadro è superiore alla soglia impostata con
P17.06.

A08

Sovraccarico corrente
condensatori

Il sovraccarico dei condensatori calcolato è superiore alle soglie
impostate con P17.08 e/o P17.09.

A09

Microinterruzione

Si è verificata una microinterruzione sugli ingressi voltmetrici di
durata superiore a 8ms.

A11

Allarme protezione armoniche
modulo nr.n
Corrente troppo alta

La corrente RMS misurata sul modulo MCP5 è più elevata della
soglia impostata con P18.n.06.

A12

Allarme protezione armoniche
modulo nr.n
THD-I troppo alto

Il THD di corrente misurato dal modulo MCP5 è più elevato della
soglia impostata con P18.n.07.

A19

Errore Comunicazione Slave x

Lo slave nr. X non risponde alla comunicazione del master.
Probabile problema sul collegamento RS485.

A20

Pulizia filtro aria

Eseguire la pulizia del filtro di ingresso aria del sistema di
ventilazione.

A21

Manutenzione ordinaria

Verificare le correnti assorbite dai singoli gradini, l’efficienza dei
fusibili e dei contattori.

A22

Manutenzione straordinaria

Eseguire le operazioni indicate in A20 e A21 e verificare condizioni
condensatori o contattare il servizio di assistenza tecnica.

COLLEGAMENTO DEL TRASFORMATORE AMPEROMETRICO DI LINEA

Il trasformatore amperometrico deve essere montato sulla fase non interessata dal prelievo del segnale
voltmetrico da parte del regolatore di potenza reattiva (solitamente la fase L1 siglata anche con R) e prima della
derivazione per l'alimentazione del quadro di rifasamento (il trasformatore deve misurare la corrente dei carichi
più quella del quadro di rifasamento, vedasi schema sul manuale del regolatore).
Il TA deve essere di classe 0,5 o 1 con potenza apparente di almeno 6VA. Se in serie al TA sono presenti altri
carichi verificare il loro assorbimento e conseguentemente aumentarne la potenza apparente. Se la distanza del
TA dall’apparecchiatura è minore o uguale a 20m utilizzare, per il collegamento, cavi da 4mm

2

, in caso contrario

aumentare la sezione dei cavi (per maggiori informazioni consultare l’Assistenza Tecnica).

INFORMAZIONI E ASSISTENZA TECNICA

Per maggiori informazioni rivolgersi a:

ICAR Power Quality Solutions by ORTEA S.p.A. - Tel. +39 02 9591 7800

www.icar.com
Assistenza Tecnica:

tech.cv@icar.com

 


background image

QUICK GUIDE

FOR THE COMMISSIONING OF FIXED OR AUTOMATIC

POWER FACTOR CORRECTION EQUIPMENT

ALL65 rev7 jan18 cod.10098513

5 / 12

SAFETY NOTICE

Access to inner components for installation, setting, inspection and maintenance must be granted only to qualified personnel
in charge of such operations. Any activity must be carried out in compliance with the enforced regulations and legislation
concerning personal safety and using adequate protective tools. Unauthorized interventions might result in damaging or
compromising the power factor correction unit operation; in such case, the warranty clauses and the Manufacturer’s liability
would cease to be valid automatically.

The Manufacturer shall not be liable for direct or indirect damage caused to persons or objects in case of incorrect

installation or misuse of the unit.

CONNECTION TO THE MAINS

Connect the three mains phases to the terminals marked 1-2-3 or R-S-T (L1-L2-L3). Pay special attention to the
dimensioning of the power supply line to the power factor correction system and any operating and/or protective
devices, as they should be rated to withstand a current equal to 1.5 times the rated current of the capacitor bank.

CONNECTION OF THE EARTH WIRE

Connect the earth (ground) lead to the relative connection provided on the unit. The earth conductor size should
be equal at least to 60% of the phase conductor (e.g.: phase conductor, size 120mm

2

– earth conductor, size at

least 70mm

2

).

After the above described operations, proceed to switch on the unit. For non-automatic units, commissioning is
now terminated.
The operations in the following should only be carried out on automatic power correction units.

NOTE: all controller parameters are set at the factory except for the CT primary value. To change any

other values, please refer to the reactive power regulator manual attached to the equipment (also

available from the download site ww.icar.com) or contact ICAR PQS Service.

PRESETTING OF THE REACTIVE POWER REGULATOR

RPC 5LGA Regulator

At the start, the display will show a flashing “CT” notice.

Press the ▲ key and dial Current Transformer primary current. Once the setting is done, press the 

key to

confirm.

RPC 8LGA Regulator

At the start, the display will show a flashing “CT” notice.

Press the ▲ key and dial Current Transformer primary current. Once the setting is done, press the 

key to

confirm.

 


background image

ICAR PQS

ALL65 rev7 jan18

6 / 12

RPC 8BGA Regulator

Front description

Navigation keys



Confirmation key

Alarm LED

!

Optical port for WIFI e USB connection

Parameters set-up

At the first power up of the automatic power factor correction equipment, carry out the following operations:

a) Enter date and time. The power factor regulator shows the page:

In this page, increase or decrease the numerical values with the



keys. Use the



keys to move

from one number to the other. Confirm with the

key.

b) Enter the desired language. The power factor regulator shows the page:

confirm with the

key to switch to the LANGUAGE page.

In this page, select the language with the



keys and confirm with the

key.

c) Enter the external CT primary value. The power factor regulator shows the page:

confirm with the

key to switch to the CT PRIMARY page.

In this page, select the CT primary value with the



keys and confirm with the

key.

For any further modifications of the CT primary value, select the SETUP menu, then the M02 GENERAL
menu. Select the parameter P02.01 CT primary value. Repeat the above operations.

 


background image

ICAR PQS

ALL65 rev7 jan18

7 / 12

Main page

Descriptive text field. It can be changed from the SETUP menu

M01 UTILITY

P01.09 SITE ID

System real time cosφ. IND= inductive, CAP= capacitive

State of steps controlled by the controller. Black symbol: step inserted. Gray
symbol: step not inserted. Absent symbol: exit not used. Gray number: step
temporarily not available (for example: step just switched off)
Weekly true power factor, calculated on the last 7 days
Equipment internal temperature and fan status (

= stop;

= start)

AUT= automatic mode; MAN= manual mode
Reactive power missing (with “+” indication) or reactive power in surplus (with “-“

indication) compared to the set target cosφ

Phase to phase voltage real time THD%

System current real time THD%, in the CT installation point

With the



keys it is possible to move through the available pages. With the

key, the MAIN MENU page is

accessed.
With the



keys, to the display of additional steps that may be present in addition to those of the page 1/4 is

accessed.

Main menu

Select the desired menu with the



keys and confirm with the

key. The selected menu is highlighted in

reverse and at the centre a text description appears.

Select this icon to set the MANUAL MODE (MAN).

Select this icon to set the AUTOMATIC MODE (AUT).

Description and meaning of the alarms

CODE ALARM

MEANING

A01

Under-compensation

All the available steps are connected but the

cosφ

is still

more inductive than the setpoint.

A03

Current too low

The current flowing in the current inputs is lower than
minimum measuring range.
This condition occurs normally if the plant has no load.

A04

Current too high

The current flowing in the current inputs is lower than
minimum measuring range.

A05

Voltage too low

The measured voltage is lower than the threshold set with
P17.14.

 


background image

ICAR PQS

ALL65 rev7 jan18

8 / 12

CODE ALARM

MEANING

A06

Voltage too high

The measured voltage is higher than the threshold set with
P17.13.

A07

Panel temperature too high

The panel temperature is higher than threshold set with
P17.06.

A08

Capacitor current overload

The calculated capacitor current overload is higher than
threshold set with P17.08 and/or P17.09.

A09

No-Voltage release

A no-voltage release lasting more than 8ms has occurred
on the line voltage inputs

A11

Harmonic protection Module nr. n Current
too high

The RMS current measured by the MCP5 module n is
higher than threshold set with P18.n.06.

A12

Harmonic protection Module nr. n THD-I too
high

The current THD measured by the MCP5 module n is
higher than threshold set with P18.n.07.

A19

Slave xx link error

The slave nr. X does not communicate with the master.
Check the RS-485 wiring.

A20

Clean the air filter

Clean the air intake filter of the ventilation system.

A21

Routine maintenance

Check each step current, fuses and contactors.

A22

Extraordinary maintenance

Perform the operations in A20 and A21 and check the
capacitors conditions or contact technical service.

CONNECTION OF THE LINE CURRENT TRANSFORMER

Mount the current transformer on the phase not concerned with the pick-up of the voltage signal by the reactive
power regulator (usually phase L1, also marked by R) and before the branch supplying the power factor
correction board (the transformer should measure the current of the loads plus that of the power factor correction
board).
The current transformer should be of class 0.5 or 1, with apparent power equal to at least 6VA. If other loads are
present in parallel to the current transformer, check their power consumption and increase the apparent power if
necessary. When the distance of the current transformer from the unit is less than or equal to 20mt, use 4mm

2

cables for the connection; if not, increase the size of the cables (for further information, consult the Service
department).

INFORMATION AND SERVICE

For more information, please contact:

ICAR Power Quality Solutions by ORTEA S.p.A. - Tel. +39 02 9591 7800

www.icar.com
Service:

tech.cv@icar.com

 


background image

GUIDE RAPIDE

POUR LA MISE EN SERVICE DES BATTERIES DE

CONDENSATEURS FIXXES OU AUTOMATIQUES

ALL65 rev7 jan18 cod.10098513

9 / 12

INFORMATIONS SUR LA SÉCURITÉ

L'accès aux composants intérieurs pour l'installation, le réglage, l'inspection et l'entretien ne doit être accordé qu'au
personnel qualifié chargé de ces opérations. Toute activité doit être effectuée en conformité avec les réglementations et la
législation appliquées en matière de sécurité personnelle et en utilisant des outils de protection adéquats. Les interventions
non autorisées pourraient endommager ou compromettre le fonctionnement de l'unité de correction du facteur de puissance;
dans ce cas, les clauses de garantie et la responsabilité du fabricant cesseraient d'être valides automatiquement.

Le fabricant n'est pas responsable des dommages directs ou indirects causés aux personnes ou aux objets en cas

d'installation ou d'utilisation incorrecte de l'appareil.

CONNECTIONS AU RESEAU D’ALIMENTATION

Connecter les trois phases du réseau aux terminaux marqués 1-2-3 ou R-S-T (L1-L2-L3). Faire particulièrement
attention au dimensionnement des câbles entre la source d’énergie et le système de correction du facteur de
puissance, de même les systèmes d’enclenchement (sectionneur) et ou de protection (disjoncteur) doivent être
calibrés de manière à supporter un courant égal à 1.5 fois le courant nominal traversant le banc de
condensateurs.

CONNECTION A LA TERRE

Connecter le fil de terre à la borne correspondante de l’équipement. Le dimensionnement du fil de terre devra
être au minimum égal à 60% de la section des fils de phase. (pour example : pour une section de fil de phase de
120mm

2

, la section du fil de terre devra être au minimum de 70mm

2

).

Après réalisation des opérations décrite ci-dessus, vous pourrez procéder à la connexion de la batterie. Cette
dernière opération clos la mise en service des batteries non automatisées.
Les opérations suivantes ne concernent que les équipements automatiques de compensation de phase.

Veuillez prendre note que les contrôleurs sont systématiquement paramétrés en usine à l’exception du

courant primaire du transformateur de courant qui devra être entré par vos soins. Pour modifier les

paramètres, veuillez vous référer au manuel du contrôleur d’énergie réactive fourni avec l’équipement

(également disponible sur le site ICAR: www.icar.com) ou contacter le service technique d’ICAR.

MISE EN SERVICE DU CONTROLEUR D’ENERGIE REACTIVE

Régulateur RPC 5LGA

A l’enclenchement du relais de démarrage, l’écran correspondant laissera apparaitre en mode flash l’inscription
“Ct”.

A  ce  moment  presser  la  touche  ▲  jusqu’à  introduction  de  la  valeur  effective  du  courant  primaire  du 

transformateur de courant. Cette opération effectuée, presser la touche

pour confirmation.

Régulateur RPC 8LGA

A l’enclenchement du relais de démarrage, l’écran correspondant laissera apparaitre en mode flash l’inscription
“Ct”.

A  ce  moment  presser  la  touche  ▲  jusqu’à  introduction  de  la  valeur  effective  du  courant  primaire  du 

transformateur de courant. Cette opération effectuée, presser la touche

pour confirmation.

 


background image

ICAR PQS

ALL65 rev7 jan18

10 / 12

Régulateur RPC 8BGA
Description de la face avant

Touches de navigation



Touche de confirmation

Led d’alarme

!

Port optique pour WIFI

et connexion USB

Paramétrage

Opérations initiales de paramétrage des équipements de compensation d’énergie réactive :

a) Entrer la date et l’heure. Le contrôleur d’énergie réactive indique la page :

Sur cette page augmentez ou diminuez les valeurs numériques à l’aide des touches



. Utiliser les

touches



pour passer d’une valeur à une autre. Confirmez avec la touche

.

b) Sélectionnez le langage désiré. Le contrôleur d’énergie réactive indique la page :

Confirmez avec la touche

pour atteindre la page de sélection LANGUE.

Sur cette page selectionnez le langage à l’aide des touches



.Confirmez avec la touche

.

c) Entrez la valeur du courant primaire du TI. Le contrôleur d’énergie réactive indique la page :

Confirmez avec la touche

pour atteindre la page de sélection PRIMAIRE TI.

Sur cette page sélectionnez la valeur de courant du primaire du TI



.Confirmez avec la touche

.

Pour toute modification importante de la valeur de courant primaire du TI, sélectionnez le menu
REGLAGES, puis le menu M02 GENERAL. Sélectionnez le paramètre P02.01 valeur primaire TI. Répétez
les opérations ci-dessus.

 


background image

ICAR PQS

ALL65 rev7 jan18

11 / 12

Page principale

Plage de description en texte. Cette plage peut être modifiée à partir du menu
REGLAGES

M01 UTILITAIRE

P01.09 DESCRIP.LIEU

Valeur de cosφ. en temps réel    IND= inductif, CAP=  capacitif

Etat des gradins contrôlés par le régulateur. Symbole noir= gradins
enclenchés. Symbole gris= Gradins non enclenchés. Absence de symbole :
Sortie non utilisée. Nombre gris= gradins temporairement non disponibles
(exemple : Gradins venant juste de se déclenchés).
Facteur de puissance hebdomadaire, calculé sur la base des 7 derniers jours.
Température interne de l’appareillage.
Etat système de ventilation (

= stop;

= start)

AUT= mode automatique; MAN=mode manuel.
Puissance réactive manquante (si indication “+”) ou puissance réactive en

trop (si indication “-“) comparée au cosφ. désiré.

Distorsion harmonique en pourcentage de la tension phase/phase de
l’installation en temps réel.
Distorsion harmonique en pourcentage du courant de l’installation en temps
réel.

A l’aide des touches



il est possible de balayer les différentes pages disponibles. Avec la touche

on peut

accéder au menu principal.
Avec les touches



il est possible d’accéder à d’éventuels autres gradins disponibles en addition de ceux

figurant en page 1/4.

Menu principal

Sélectionnez le menu désiré avec les touches



. Confirmez avec la touche

. Le menu sélectionné est

coloré par la négative, et apparaît dans son centre un texte descriptif
Select the desired menu with the



keys and confirm with the

key. The selected menu is highlighted in

reverse and at the centre a text description appears.

Sélectionnez cette icone pour passer en MODE MANUEL (MAN)

Sélectionnez cette icone pour passer en MODE AUTOMATIQUE (AUT).

Description et signification des alarmes

CODE ALARM

SIGNIFICATION

A01

Sous compensation

Tous les gradins sont connectés mais le

cosφ

est encore plus

inductif que la valeur désiré.

A03

Courant trop bas

Le courant de l’installation mesuré est inférieur au minimum
requis pour la mesure.
Ce genre de condition apparait en général lorsque l’installation
n’a pas de charge.

 


background image

ICAR PQS

ALL65 rev7 jan18

12 / 12

CODE ALARM

SIGNIFICATION

A04

Courant trop élevée

Le courant de l’installation mesuré est supérieur au maximum
acceptable pour la mesure.

A05

Tension trop basse

La tension mesuré est plus basse que le seuil paramétré avec
le P17.14.

A06

Tension trop élevée

La tension mesuré est plus élevé que le seuil paramétré avec
le P17.13.

A07

Température trop élevée

La température dans l’appareillage est plus élevé que le seuil
paramétré avec le P17.06.

A08

Condensateur en surcharge de courant

Le courant calculé de surcharge du condensateur est supérieur
que le seuil paramétré avec P17.08 et/ou P17.09.

A09

Micro-coupure

Aucune tension d’entrée n’a été détecté en entrée sur une duré
supérieure à 8mn.

A11

Module de protection des harmoniques
nr. n Courant trop élevé

Le courant efficace (RMS) mesuré par le module MCP5 est
plus élevé que le seuil paramétré avec le P18.n.06.

A12

Module de protection des harmoniques
nr. n THDI% trop élevé

Le courant THD mesuré par le module MCP5 est plus élevé
que le seuil paramétré avec le P18.n.07.

A19

Esclave xx erreur de lien

L’esclave nr. X ne communiqué pas avec le maitre. Vérifiez la
connexion du RS-485.

A20

Nettoyez le filtre à air

Nettoyer le filtre interne du système de ventilation

A21

Maintenance de routine

Vérifier les courants de chaque gradin, l’état des fusibles et des
contacteurs.

A22

Maintenance exceptionnelle

Réaliser les opérations en A20 et en A21 et vérifier les
contactes des supports techniques des condensateurs.

CONNECTION SUR LE RESEAU DU TRANSFORMATEUR DE COURANT (TC)

Montez le transformateur de courant sur la phase non concernée par le signal de tension raccordé au régulateur
de puissance (couramment la phase L1 également marquée R) et en amont de la connexion pilotant
l’équipement de compensation. (Le transformateur doit mesurer le courant de la charge plus le courant de
l’équipement contrôlant le facteur de puissance).
Le courant de transformateur doit être de classe 0,5 or 1 avec une puissance apparente d’au moins 6VA. Si
d’autres charges sont présentes en parallèle sur le transformateur de courant, vérifiez leur puissance de
consommation ; si nécessaire augmentez la puissance apparente. Quand la distance entre le TC et l’équipement
de compensation est inférieure ou égale à 20m, utilisez des câbles de 4mm

2

pour les connections. Sinon

augmentez la taille des câbles, (pour plus d’information, veuillez consulter le service technique d’ICAR).

INFORMATION ET SERVICE

Pour information, veuillez contacter :

ICAR Power Quality Solutions by ORTEA S.p.A. - Tel. +39 02 9591 7800

www.icar.com
Service:

tech.cv@icar.com