1. Introduction 
 
2. Characteristics 
 
3. Purpose 
 
4. Basic Specification 
    4-1. Type name 
    4-2. Specifications 
 
5. Wiring Diagram 
    5-1. Outside view of terminal block 
    5-2. Explanation of terminal block 
 
6. Configuration and Operation Principle 

6-1 Power circuit configuration diagram 
6-2 Control board configuration diagram 

 
7. Display 

7-1 Parameter setting 
7-2 Monitoring 

 
8. Outside dimension 
 
9. Trial run recommendation sequence 
 
10. Fault and Warning Description 
    10-1. Fault list 
    10-2. Fault Cause and Action 

10-3. Warning list 
10-4. Warning Cause and Action 
10-5. Warning Display 

 

11. Caution for operation 

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

2

 

 

1. Introduction 

The all-digital battery charger (BCU) developed by HANMI TECHWIN is a 

device  that  charges  the  battery  by  making  high-speed  switching method 
using 3-phase AC power using IGBT. 

BCU (Battery Charging Unit) monitors and protects battery status in real 

time to provide optimal operating environment. 

 

2. Characteristics 

  Simplicity 

Charge automatically with battery capacity (AH) and battery rating setting only.

 

  Monitoring charging voltage and current through LCD   

Charge voltage, current and charge capacity are displayed, so you can check it 

immediately without any additional measuring equipment. 

  Small, lightweight 

It  is  compact  and  lightweight  because  it  does  not  adopt  transformer  and 

large capacitor, and it is easy to handle. 

  Battery diagnostic function 

It  continually  checks  the  battery's  overvoltage,  discharge  end  voltage  and 

other conditions to ensure that it is always in top condition.

 

  Equal charge function 

Equalization charging is performed when the voltage between the terminals of 

the battery  and the specific gravity of the electrolyte is  not  uniform  and  the 
performance can not be fully demonstrated. This function charges the battery 
at a constant voltage (117% of the battery rating) during Equalizing time.       

When the set time has elapsed and the equal charge is completed, 

the auto 

run parameter is automatically switched to floating charge if the parameter 
is set to ON. If it is OFF, the output is stopped.

 

  Recovery charge function 

  When  the  battery  voltage  is  below  the  discharge  end  voltage  (75%  of  the 

rated voltage), it automatically operates in the recovery charge (RC) mode and 
is  also  possible by key operation. The recovery charge is  slightly higher  than 
the battery rated voltage for safety, and when the battery voltage exceeds the 
rated  voltage,  it  charges  to  115%  of  the  battery  rating.  When  the  recovery 
voltage and current reaches the appropriate level (voltage is 115% and current 
is  battery  capacity  /  50  or  less),  depending  on  the  setting  of  Auto  Run,  it 
changes to a floating charge or standby state. 

 


background image

Industrial Battery Charger TDC-9030 

 

3

 

 

HANMI TECHWIN. CO., LTD.

 

 

 Enhanced fault diagnosis 

  Improved safety by checking the battery itself and wiring. 

 

3. Purpose 

◆ Industrial Battery Charger 

 

 
4. Basic Specification 
  4-1. Type name 

TDC - 9030 -  

T

AIHWA

D

EVELOPMENT

BATTERY 

C

HARGER

FAN POWER
 1 : 110 V
 2 : 220 V

REVISION

DEVELOPMENT DATE
   

3

 : MONTH

 90 

: 2009(year)

 

 

 

4-2. Specifications 

         

Specifications 

Contents 

Power supply 

3Ø AC 220V   

Operating 

voltage 

AC 85 ~ 265 [V] 

FAN Power 

  AC 110 / 220 [V] 

Operating 

temperature 

  -20 ~ 85 [℃] 

Output signal 

  WARNING OUT   
(Mechanical contact : AC250V/DC30V, 5A) 
  FAULT OUT   
(Mechanical contact: AC250V/DC30V, 5A) 

weight 

  11.5 Kg 

 
 
 

 

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

4

 

 

5. Wiring Diagram 
    5-1. Outside view of terminal block 

T

S

R

P

B

N

STACK

(TDC-9030Series)

L2

L1

 

 

WA

WB

WC

FA

FB

FC

NO

NC

COM

NO

NC

COM

(PCB)

 

 

5-2. Explanation of terminal block 

Terminal 

Mark 

Designation 

Function 

Rating 

CN103 

WA 

NORMAL OPEN 

WARNING OUTPUT 

AC250V / 5A 

DC 30V / 5A 

WB 

NORMAL CLOSE 

WC 

COMMON 

FA 

NORMAL OPEN 

FAULT OUTPUT 

FB 

NORMAL CLOSE 

FC 

COMMON 

LINE1 

L1 

CONTROL POWER 

  PCB POWER 

AC 85V ~ 

AC265V 

LINE2 

L2 

CONTROL POWER 

  PCB POWER 

BUSBAR 

  Source Voltage 

  R PHASE INPUT 

 

  Source Voltage 

  S PHASE INPUT 

 

  Source Voltage 

  T PHASE INPUT 

 

DC OUTPUT (+) 

  LOAD OUTPUT (+) 

 

DC OUTPUT (+) 

  BATTERY OUTPUT(+)     

DC COMMON (-) 

  COMMON (-) 

 

 

 


background image

Industrial Battery Charger TDC-9030 

 

5

 

 

HANMI TECHWIN. CO., LTD.

 

 

6. Configuration and Operation Principle 

MAIN

CNTR

R

Fuse

SMPS

S

T

P

B

N

D2

SW1

RECT.

TB

L2

L1

Warning
Fault

LC

N

SV
BV
G1

E1

OH

IGND

 

[figure 1] Diagram 

 

 

  6-1. Power circuit configuration diagram 

 
 
 
 
 
 
 
 
 
 
 

Mark 

Designation 

Function 

Remarks 

Source Voltage (R Phase) 

  Input Voltage 

 

Source Voltage (S Phase) 

   

 

  Source Voltage (T Phase) 

 

 

  Positive Voltage 

Output Voltage(Load) 

 

Battery Voltage 

Output Voltage(Battery) 

 

  Neutral Node 

Output Voltage(Common)   

P

B

N

R

S

T

G1

E1

G2

E2

20A

SV

BV

N

LC

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

6

 

 

 
 

6-2. Control board configuration diagram 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Mark 

Designation 

Function 

Remarks 

CN301 

SV 

Source Voltage 

Voltage / Current 

Feedback 

 

BV 

Battery Voltage 

LC 

Load Current 

Neutral Node 

CN103 

WA 

Warning NO 

Warning Output 

 

WB 

Warning NC 

WC 

Warning Common 

FA 

Fault NO 

Fault Output 

 

FB 

Fault NC 

FC 

Fault Common 

CN201 

G1 

Gate Signal 1 

IGBT Gate Signal 

 

E1 

Emitter Signal 1 

CN401 

+12V 

PCB Power (+12V) 

PCB Power 

 

GND 

Ground (0V) 

CN102 

OH 

Overheat 

Thermostat 

( 85℃ NO ) 

 

COM 

Common 

SET

RUN

UP

EQU

DN

REC

O

H

C

O

M

T

H

E

R

M

A

L

S

W

IT

C

H

+12V

GND

POWER

WA WB WC FA FB FC

STATUS OUTPUT

G

1
E

1

/C

2

IG

B

T

M

O

D

U

L

E

S

V

B

V

L

C

N

V

O

L

T

A

G

E

F

E

E

D

B

A

C

K

RESET

T.H. ELEMA

P9062A-04

TP201

TP201

  (GND)

PWR

CN201

CN301

C

N

1

0

3

CN102

C

N

4

0

1

LD401

 


background image

Industrial Battery Charger TDC-9030 

 

7

 

 

HANMI TECHWIN. CO., LTD.

 

 

 

7. Display 

  7-1. Parameter setting 

          7-1-1. Parameter type and description 

Parameter

 

Setting

 

Range 

Default 

Auto Run 

OFF / ON 

 

OFF 

Batt. Voltage 

 

24 ~ 240 [V] 

216 V 

Batt. Capacity 

 

10 ~ 300 [AH] 

100 AH 

Output Current 

 

1.0 ~ 30.0 [A] 

Capacity / 20 

Equalizing Time 

 

30 ~ 180 [min] 

120 min 

*Max. Current 

 

1.0 ~ 30.0 [A] 

20.0 A 

*Halt on WDR 

OFF / ON 

 

ON 

                    Caution 1) In case of actual use after the test run, be sure to set Auto Run to 

ON to charge the battery automatically. 

Caution 2) The mark ‘*’ can not be arbitrarily adjusted by the user. 

        ① Auto Run : Set which mode to start at initial startup 

- This parameter is used when the MCU starts to operate due to Power 

ON or Reset. If it is set to OFF, start and stop of charging can be 
controlled with the RUN key. 

② Batt. Voltage : Set the battery voltage. 

- If 18 batteries of 12V are used in series, set to 12 × 18 = 216 [V]. 

The  Floating  Charge  charges  111%  of  the  battery  voltage  and  the 
Equalized Charge charges the constant voltage / constant current to 
117% of the battery voltage. 

③ Batt. Capacity : Set the battery capacity. 
    - If the battery capacity is 100AH, setting 100 will automatically set the   

parameter ‘Max. Out Current’ to 5A, which is the charging standard 

for   

20 hours. 

④ Output Current : Sets the output current limit. 
    - Set the current that the charger can output at maximum. This limit   

setting allows you to safeguard your battery and circuit, especially   
when large currents can flow, such as a recovery charge. 

⑤ Equalizing Time : Set the equal charge time. 

⑥ *Max. Current : An overcurrent fault occurs when the charger exceeds   

the set current. 

⑦ *Halt on WDR : Set or cancel the self-diagnosis function of the MCU.

 

 

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

8

 

 

7-1-2. How to set parameters 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

7-2. Monitoring 

    7-2-1. Initial Screen 

 
 
 
 

 

 

7-2-2. Screen during driving 

 

 
 
 
 

 
 
 

DCV :

   

 

DC voltage on the DC-Link side

Indication of 
operation status

Output Current

3

O

 

UT :

0   0

 

V

 

0 . 0  

Battery Voltage

0 V

[ RD ]

.

A

0

2 4

DCV :

   

 

DC voltage on the DC-Link side

Output Current

3

O

 

UT :

0   0

 

V

 

5 . 0  

Battery Voltage

0 V

[ F L ]

.

A

0

2 4

RD, FL, EQ, RC

# Initial 
  Screen

SET(1sec)

SET(1sec)

UP

DOWN

   

   

      

     

UP

DOWN

Press SET key for 1 sec. In 

parameter state to return to 

initial screen

SET

SET

Adjust the setting value 

by UP and DOWN

  All parameter settings except '*' are 
    the same

Parameters with Asterisk(*) are not user 
configurable

  Ba

   

1

 

t

              6

 

  V  

 

       

t .   V o l t a g e    

2

 

 

   

 

   

    

     

   

O

 

 

              F

 

F    

 

       

Au t o

RUN

     

 

 

 

   

 

   

    

 

   

.

        2     0

 

  A  

 

       

Ma x .

c u r r e n

0

 

 

 

 

t

UP

DOWN

      

     

O

   

.

 

u

        1 0   0

 

  A  

 

       

t p u t

Cu r r e n t

 

 

 

       

 

      

     

   

2

                0

 

  mi

 

       

u a l i z i n g   t i

1

 

 

n  

 

   

    

e

UP

DOWN

 

q

E

m

     

  

 

 

      

 

O

 

N

 

 

 

     

Au t o

RUN

     
  

 

     

DOWN

UP

UP

DOWN

   

   

      

     

  Ba

   

0

 

t

              0

 

  A  

 

       

t .   Ca p a c i t y  

1

H

 

   

 

   

    

DCV :

   

 

3

O

 

UT :

0   0

 

V

 

0 . 0  

0 V

[ RD ]

.

A

0

2 4

   

 

   

UP

DOWN

 

   

O

       

    N

 

 

 

 

       

Ha l t

o n WDR

 

 

 

 

 

*

*

Can not be set in RUN mode(FL, EQ, 
RC) 
[Monitorable]

 


background image

Industrial Battery Charger TDC-9030 

 

9

 

 

HANMI TECHWIN. CO., LTD.

 

 

8. Outside dimension 

 

MODEL : TDC-9030-
SN :

DATE : 20     .      .     .   MAD E I N KOREA

BATTERY CHARGER UNIT

THE LEADER OF INDUSTRIAL ELECTRONICS

HANMI TECHWIN. CO., LTD.

http:/ /www.hanmitw.com/

G

D

A

C

F

B

E

4-Ø 7

  The above dimensions may be changed to improve 
the product.

246.0 mm

300.0 mm

208.2 mm

234.0 mm

361.0 mm

200.0 mm

A

B

C

D

E

F

G

DIMENSION

 

 

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

10

 

 

9. Trial run recommendation sequence 

    1) Be sure to check the polarity of battery power before applying power. 
      [Caution] Be extremely careful not to connect the battery (+) to the output 
(B)  of  the  controller,  as  this  may  damage  the  diodes  and  reactors  of  the 
controller. 

2) Apply single-phase AC [L1, L2] power for PCB power supply. 
3) If 'PF' fault message is displayed on the LCD, press and hold SET key to   

enter parameter setting mode. 

4) Press UP, DOWN, SET Key[Refer to parameter setting method] to set Batter   

AH  and  Auto  Run  to  OFF.  Then  press  and  hold  the  SET  key  to  exit  the 

setting mode and a 'PF' fault message will be displayed again. 

5) Apply 3 phase power of the controller to clear the fault and check the LCD   

window display. 

6) Make sure that the SV voltage matches the actual input source voltage and   

that the BV voltage is at 0V. 

    7) Apply battery voltage and verify BV voltage matches actual battery voltage. 

8) Press the RUN key to charge the battery while observing the OC [Output   

Current] current. 

9) If the current and voltage are not abnormal, press the RUN Key again to 

stop charging. 

10) Press and hold SET key to set Auto Run to ON in parameter   

setting mode. 

    11) Press the RUN key to charge the battery.   

Check battery polarity and wiring status

PCB power supply L1, L2 power supply

POWER FAULT occurrence

Parameter setting

SET Key(1Sec)

   Auto Run  : OFF
   Batt. Capacity :Battery capacity

SET, UP, DN Key

SET Key(1Sec)

POWER FAULT occurrence

3-phase input MCCB ON

SV: Voltage check (input power)

Check BV after battery voltage 

MCCB ON

Check operation status

(OC and BV observations)

RUN  Key

In the Ready state, press the SET key to 

set Auto Run to ON

RUN  Key

Battery charge status observation

RUN  Key

 

 

 


background image

Industrial Battery Charger TDC-9030 

 

11

 

 

HANMI TECHWIN. CO., LTD.

 

 

10. Fault and Warning Description 

10-1. Fault list 

NO 

Display 

Cause 

[FAULT] GATE-DRV 

IGBT Gate Driver Damage 

[FAULT] WATCHDOG 

Abnormal operation of MCU 

[FAULT] OVR-CURR 

Overcurrent 

[FAULT] BAD BATT 

Battery failure 

 

10-2. Fault Cause and Action 

LIST 

Cause and Action 

[FAULT] 

WATCHDOG 

Watchdog    / Abnormal MCU function 

If the MCU malfunctions momentarily due to noise or other external 

conditions 

☞  Reset the MCU. 

[FAULT] 

GATE-DRV 

Gate Driver Defect / Damaged Gate Driver 

If the IGBT Gate Driver is physically damaged 

☞  Turn off all the power and then turn it on again. 

   If the fault persists, replace the PCB because it is a physical damage. 

[FAULT] 

OVR- CURR 

Over Current / Overcurrent 

  Overcurrent flows above set current 

☞  Check the output wiring.

 

[FAULT] 

BAD BATT 

Bad Battery / Discharge 

If current is not flowing even when voltage is continuously applied 

to the battery 

☞  Check the battery condition. 

☞  Charge the battery in Equal Charge [EQU Key] mode.

 

10-3 Warning list 

NO 

Display 

Cause 

PF 

Power Fault 

PL 

Power Too Low 

OH 

Over Heat 

OV 

Over Voltage 

LV 

Low Voltage 

 


background image

TDC-9030 Industrial Battery Charger 

HANMI TECHWIN. CO., LTD.

 

 

12

 

 

10-4 Warning Cause and Action

 

LIST 

Cause and Action 

PF 

Power Fault / Abnormal input power 

Input power (AC power) is not applied. 

  Check the input power line. If there is no problem 

 

  Check the fuse inside the unit for burnout 

PL 

Power Too Low / Input Power Undervoltage 

The input voltage is lower than the set battery voltage. 

  Check the input power line. 

OH 

Over Heat 

  Unit temperature is over 85 

  Check the ambient temperature and the air circulation inside the unit 

  Check whether the fan is abnormal, check the connection of the unit 

internal temperature sensor. 

OV 

Over Voltage / Overcharge 

The battery voltage is overcharged (25% or more of the rated voltage). 

  Check if charging stops and charging starts when the battery voltage 

is discharged to the rated voltage. 

  Make sure the battery voltage setting is correct 

LV 

Low Voltage / Overdischarge 

Battery voltage is over-discharged (less than 25% of rated voltage). 

  Make  sure  that  it  is  charging.  The  warning  is  released  when  the 

battery continues to charge and the battery voltage is reached. 

 
10-5 Warning Display 
 

 
   

     
                                           
 
 

*

 

If it is displayed like this, it is charged to 5A with input voltage of 220VAC (DCV 300V).   

However, the battery voltage (OUT: 140V) does not reach the rated voltage (216V Setting)   

and LV Warning (low voltage) is displayed.       

          * It operates normally even during alarm. (Reset is not required) 

     

DCV :

   

 

Warning status display (flashing)

3

O

 

UT :

0   0

 

V

 

5 . 0  

0 V

[ F L ]

.

A

0

1 4

PF,PL,OH,OV,LV

LV

 


background image

Industrial Battery Charger TDC-9030 

 

13

 

 

HANMI TECHWIN. CO., LTD.

 

 

11. Caution for operation 

1)  This  product  contains  sensitive  electronic  components.  Opening  the 

lid of the product and touching the electronic components at will is 
dangerous and may cause a fatal malfunction. 

2)  Be  sure  to  turn  off  all  power  supply  when  replacing  PCB  and 

maintenance.  High  Voltage  inside  the  product  may  cause  fatal 
injuries. 

3)  Although  this  product  is  designed  to  withstand  noise  and  surge  in 

power  supply.  However,  excessive  noise,  surge,  etc.  may  cause 
abnormal operation, so please use stable power as much as possible. 

4) Always use the correct rated product for the device protection fuse. 
5)  If  any  information  not  explained  in  this  manual  is  displayed  on  the 

display, please contact us at 031-498-9270.