Full Text Searchable PDF User Manual

KNX outdoor movement detector
GW 90787
Technical Manual

2
- General
In the following the device will be referred to as the
movement detector.
The movement block will only switch off when there is no
more movement in front of the device - in other words,
independently of the brightness.
The ETS application includes 5 independent movement
blocks, each with 4 output objects.
|
Note:
All of the settings described refer to ETS version 3,
but you can also use all the settings and functions
with ETS version 2.
The application files (vd2 and vd3) are configured in
such a way that the application loading time is
considerably reduced. When you convert an ETS 2
project to ETS 3, you lose this time saving. If you are
working with ETS 3, use the vd3 files.
Total possible addresses and connections:
254 addresses; 255 connections
|
Note:
If you switch back to the preset values in either ETS
2 or ETS 3 (by clicking "Standard"), all the values
that you have changed so far will be deleted. Any
group addresses which have been parametrised will
be lost.
|
Note
:
Due to the fact that various functions depend on
other functions, these dependent functions will not
be visible and selectable in the ETS unless the
preceding function has been enabled. If you de-select
functions or change parameters, group addresses that
have already been connected may be removed.
- Getting started quickly
When you insert the application in the ETS or click on the
"Standard" button, the ETS application will switch
automatically to minimum configuration.
In minimum configuration, it is possible to put the presence
detector into operation. For some application cases, the
minimum configuration is even adequate for practical use.
We also recommend opening minimum configuration as a
way of familiarising yourself with the application software
for the presence detector. Here all of the extended or more
complex parameters are disabled. In "Block configuration"
only the first "Movement" block is enabled for use. In the
"Telegrams" tab only output object 1 is enabled. This is a 1-
bit output object. At the start of movement this object sends
a 1 telegram and when the internal staircase timer has
elapsed it sends a 0 telegram. Each parameter can always be
tuned to its individual requirements. The brightness
threshold and the staircase timer always need to be adjusted
to suit requirements. Check the "Brightness" and "Times"
tabs.
In this way the corresponding objects are connected to a
KNX switch actuator.
To familiarise yourself with the extended and more complex
parameters see the following pages.
- General functions
The common safety pause
The application has a common safety pause system - in other
words, a safety pause triggered by the movement detector
will affect all blocks in the application. As specified in a
parameter the safety pause can be triggered at the status
feedback object (safety pause) when there is an OFF
telegram or when there is an OFF and ON telegram.
The status feedback object of the switching/dimming
actuator must be connected to the feedback safety pause
object of the movement detector.
Once a safety pause has been started, signals from the
movement sensor will no longer be evaluated for this period
of time. An elapsed staircase timer cannot be started by a
movement during an active safety pause and an ongoing
staircase timer cannot be retriggered by a movement.
An ongoing staircase timer is not affected by a safety pause
being activated. In other words, the staircase timer will run
through in the usual way.
|
Note:
Optical feedback can only be avoided by selecting
the right installation location for the movement
detector and the lighting. The safety pause system
and the safety pause object of the application cannot
compensate for all planning mistakes.
Communication objects
You can select the following communication objects:
General:
Parameter
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Function
Object name
Type
Prio
Flags Behaviour
Safety pause Status feedback
object
1 bit
Low
WC
Receive
1/1/1
1/1/2
Switch object
Status feedback obj.
Switch
Actuator
Status feedback obj.
Safety pause
Movement
Detector
Switch object

3
- General brightness evaluation:
The current brightness can be determined by the internal
brightness sensor, by an external communication object or
by both dependencies. The relationship between internal
and external values can be parametrised while doing this.
Communication objects
You can select the following communication objects:
General:
Parameter
For actual value correction you will need a luxmeter. The
measured values are then input into the application software
of the presence detector.
When intense sunlight is shining onto the reference area or
the installation location, the measurements should not be
taken. Under certain circumstances darkening the room may
improve the measurement results.
- Movement block
Basic function of a movement block
A staircase timer is "integrated" into a movement block.
When the ambient brightness is too low
and
a movement is
detected, the movement block transmits an ON telegram to
the bus. When no further movement is detected the staircase
timer starts. An OFF telegram is transmitted to the bus after
a parametrised time.
Brightness is measured
only
at the moment when the first
movement is detected. If further movement is detected, an
OFF telegram is
not
transmitted, irrespective of brightness
changes. The staircase timer starts only when movement is
no longer detected, and an OFF telegram is transmitted after
the parametrised time period.
Block configuration
Up to five movement blocks are available. In the default
setting, block 1 is enabled.
Parameter
Movement detection
The device has a detection angle of 220°.
To suppress disturbance variables or if delayed activation is
required, a dead time for the start of movement can be
activated. The dead time is started after movement has been
detected (start of movement). The start of movement action
(transmitting a telegram to the bus) can take place if a
movement is still detected within the movement time after
the dead time has elapsed.
In master mode or normal mode the movement time
corresponds to the staircase timer in the diagram above. In
slave mode or monitoring mode the movement time
corresponds to the cycle time. In practice a large number of
applications can be implemented by means of the various
blocks.
Block diagram of movement block
A block diagram clarifies the relationships between the
individual dependencies.
General
Parameter
Setting
Safety pause via status feedback
object
Disabled
For OFF telegram
For ON and OFF telegram
Safety pause (1 - 20) seconds
1-20, preset:
2
Function
Object name
Type
Prio
Flags Behaviour
External
sensor
Actual value input
2 bytes Low
WCT
U
Transmit/
receive/
update
General
Parameter
Setting
Actual value (brightness)
From internal sensor
From object, actual value input
From internal sensor and object
Taking the separately measured lux
value (0% - 100%) into account
0% - 100%, in 5% steps;
preconfiguration
50%
Block configuration
Parameter
Setting
Movement block X
Enabled
Disabled
ON
OFF
S
w
itc
h
object
Mo
vement
Time
Time
Dead
Time
Movement
Time
Dead
Time
Movement
Time
Movement
Time
Movement
Time

4
Movement evaluation
As has already been stated above, the movement sensor
input into movement detection.
The master trigger object is brightness-dependent and with
an ON telegram simulates a movement; an OFF telegram is
ignored.
The trigger object is brightness-independent and also
simulates a movement for an ON telegram . Whether the
trigger object can switch the lighting off early when there is
an OFF telegram can be parametrised.
|
Note:
The master trigger object and the trigger object do
not appear in the ETS until the device operating
mode has been set to "Master mode". See "Block X,
general" tab, parameter: "Operating mode". The
master/trigger object ignores the dead time (for Dead
time, see above) and reacts without a delay. More
detailed information about the master/trigger object
may be found later on.
Communication objects
You can select the following communication objects:
Block X, general movement sensors:
Parameter
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Move
Sensor
Master
Trigger
Brightness
sensor
Always-
dark obj.
Trigger obj.
Disable obj.
Movement
detection
Brightness obj.
Brightness
evaluation
Output obj.
1-4
Disable
function
Times
Telegrams
Function
Object name
Type
Prio
Flags Behaviour
Block X
Range
1 byte Low
WC
Receive
Block X, general - movement
sensors
Parameter
Setting
Advanced settings
Enabled
Disabled
The following settings are only
visible when "Disabled".
Sensitivity (for all sensors)
High
Medium
Low
Range adjustable
Potentiometer
Parameter
Range
(only visible by "Parameter")
10% - 100% (in 10% steps)
preconfiguration:
100%
The following settings are only
visible when "Enabled".
Range object (for all sensors)
Disabled
Enabled
Dead time, start of movement (for all
sensors)
Disabled
Enabled
Time base
1 min
, 1s
Time factor (1 - 255)
3
, (1-255)

5
- Brightness evaluation
Brightness evaluation of a movement detector:
The movement detector changes to non-brightness-
dependent mode once the start of movement action (sending
an ON telegram) has been carried out. Here freshly detected
movements can retrigger the staircase timer. The movement
detector cannot process the brightness jump and there is not
even any setting of a hysteresis.
Brightness
The brightness threshold can be parametrised separately for
each of the five movement blocks. Each block has its own
"Brightness" tab. A staircase timer be started (depending on
parametrisation of the device) and an ON telegram
transmitted to the bus only after the value is below the
parametrised brightness threshold and the movement
detector detects a movement. The brightness threshold can
be set between 3 and 1000 lux.
Via the "Brightness threshold object" "Enabled" or
"Disabled" you can select whether the brightness threshold
should be changed via the bus. This can be useful when
several movement detectors are installed in a building. The
brightness threshold can be changed using the "Brightness
threshold - Block X" object via the ETS or an IP touch panel,
for example. The brightness threshold is set to the same
level in all parts of the building.
Brightness object 1 bit
The brightness object sends a 1-bit value on the bus. If the
parametrised brightness threshold is not reached, an ON
telegram can be transmitted. If the parametrised brightness
threshold is exceeded, an OFF telegram can be transmitted.
Inverted transmission can also be set.
Always-dark object
In the case of an enabled "always-dark object", darkness can
be simulated internally in the movement detector depending
on the object value. The "always-dark object" is used with
master/slave circuits. Planning master/slave circuits is
described further below.
Communication objects
You can select the following communication objects:
Block X, general brightness:
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Block X, general movement
sensors sector X
Parameter
Setting
Sensitivity
High
Medium
Low
Range adjustable
Via parameters
Via Potentiometer
Overwrite range during download
Enabled
Disabled
Range
10% - 100% (in 10% steps)
preconfiguration:
100%
Change range via object
Disabled
Enabled
Staircase timer
ON
OFF
Switch object
Movement
Time
Time
Time
Brightness
Staircase timer
Staircase timer
Staircase timer
Staircase timer
Brightness
threshold
Function
Object name
Type
Prio
Flags Behaviour
Block X
Brightness threshold 2 bytes Low
WC
Receive
Block X
Brightness object
1 bit
Low
CT
Transmit
Block X
Always-dark object 1 bit
Low
WC
Receive
ON
ON
OFF
Brightness
Brightness
object
Brightness threshold
Too bright
Too dark
t
t

6
Parameter
- Operating modes
The operating mode in which this block operates is specified
in the application software for each block (movement blocks
1 - 5). The following operating modes are available:
– Normal operation
– Master mode
– Slave mode
– Monitoring mode
Depending on the operating mode different parameters and
communication objects will be displayed. Each operating
mode can operate brightness-dependently or non-
brightness-dependently.
Normal operation
In this operating mode the movement detector does not have
any external trigger objects (master trigger object, trigger
object). Telegrams cannot be sent cyclically and this means
a master-slave system cannot be set up. In the default
setting, the movement detector transmits an ON telegram at
the start of movement and transmits an OFF telegram when
the movement time (staircase timer) has expired.
|
Note:
Use the "Normal operation" setting when the
movement detector is working for itself alone. In
other words, one movement detector is used for each
room and it switches one light or one light panel.
Master mode
With master mode all of the possible parameters and
communication objects of the movement detector are
available. A master-slave system can be set up with the aid
of the master trigger object or the trigger object. In the
default setting, the movement detector transmits an ON
telegram at the start of movement and transmits an OFF
telegram when the movement time (staircase timer) has
expired.
Slave mode
In slave mode the default setting is that ON telegrams are
sent cyclically when a movement is detected. These
telegrams are intended for the master trigger object or for the
trigger object of the master.
Monitoring mode
In monitoring mode the default setting is that ON telegrams
are sent cyclically when a movement is detected. At the end
of the movement time (cycle time with movement) OFF
telegrams are transmitted cyclically.
|
Note:
Use the "Monitoring mode" setting when the
movementmovement detector is being used for room
monitoring and telegrams are to be sent cyclically on
the bus.
Block X, general brightness
Parameter
Setting
Movement detection is
brightness-dependent
independent of brightness
Brightness threshold adjustable via
Parameters
Potentiometer
Overwrite brightness threshold
during download
Enabled
Disabled
Brightness threshold (3 - 1000 lux)
see "General" tab
3 - 1000 lux; preconfiguration:
130
Brightness threshold object
Disabled
Enabled
Brightness object 1 bit
Do not send
Transmit
Transmit inverted
Always-dark object (= not
brightness-dependent)
Disabled
Enabled
Switch on at movment
Enabled
Disabled

7
Communication objects
You can select the following communication objects:
Block X, general:
Parameter
|
Note:
When toggling between operating modes the
"Brightness" and "Times" tabs change.
- Telegrams
For each movement block the "Action at start of movement"
can be set as a function of the operating mode.
Normal operation:
– "Send immediately"
– "Do not send"
Master mode:
– "Send immediately"
– "Send immediately and then cyclically"
– "Do not send"
Slave mode:
– "Send immediately and then cyclically" (is permanent
setting in the background of the application software, is
not displayed in the parameters)
Monitoring mode:
– "Send immediately and then cyclically" (is permanent
setting in the background of the application software, is
not displayed in the parameters)
The behaviour after the "End of movement time" can also be
set as a function of the operating mode.
Normal operation:
– "Send after staircase timer/remaining time has elapsed"
– "Do not send"
Master mode:
– "Send after staircase timer/remaining time has elapsed"
– "Send after staircase timer has elapsed and then
cyclically"
– "Do not send"
Slave mode:
– "Do not send" (is permanent setting in the background of
the application software, is not displayed in the
parameters)
Monitoring mode:
– "Send at end of cycle time when there is movement and
then cyclically" (is permanent setting in the background
of the application software, is not displayed in the
parameters)
Four output objects are available for each of the five
movement blocks and they can be enabled via the
application software. A transmission pause between the
individual output objects can be set for each block.
|
Note:
Five movement blocks and four output objects per
movement detector means that 20 switching/value
objects in all are available.
Function
Object name
Type
Prio
Flags Behaviour
The objects
are only
visible in
"Master
mode"
operating
mode.
Block X
Master trigger
object
1 bit
Low
WC
Receive
Block X
Trigger object
1 bit
Low
WC
Receive
Block X, general
Parameter
Setting
Operating mode
Normal operation
Master mode
Slave mode
Monitoring mode

8
Parameter
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Output for switching/value object X
For each output object you can select between a 1-bit, 1-byte
(0% - 100%), 1-byte (0 - 255) and 2-byte object. The
telegram values should be parametrised for the start of
movement and for the end of the movement time. Here an
object can transmit its current value or a defined value to the
bus.
|
Note:
The current value can be transmitted by a time
switch, for example. During the night a lower byte
value is transmitted to the output object of the
movement detector than in daytime hours.
Communication objects
You can select the following communication objects:
Block X general - telegrams - output for switching/value
object X:
Parameter
|
Note:
The parameter settings shown below are
dependent
on the operating mode and the object settings (1 bit,
1 byte or 2 bytes). Depending on the parametrisation
some parameters will not be displayed!
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
|
Note regarding 2-byte parameter settings:
Depending on the setting of the object type value
there will be new parameters; depending on the
parametrisation the values can be input immediately
or are determined via sign x basic value x factor.
- Staircase timer
The staircase timer or cycle time can be parametrised via a
time base x factor. With "Normal operation" and "Master
mode" operating modes the "Staircase timer" is
parametrised. With "Slave mode" and "Monitoring mode"
operating modes the "Cycle time" is parametrised.
|
The "Times" tab has some parameter displays and
selectable objects which are
dependent
on the
operating mode set.
|
Note:
In "Slave mode" and "Monitoring mode" operating
modes no further objects are displayed by
modification on the "Times" tab.
Self-adjusting staircase timer
The movementmovement detector is equipped with a "Self-
adjusting staircase timer". When the "Self-adjusting
staircase timer" is enabled, the movement detector can start
a brief overshoot time when someone is in the room for a
short time. If they remain in the room longer, a long
overshoot time is started.
The parameters "Time base", "Minimum time factor",
"Time factor for learning step", "Maximum time factor" and
"Sensitivity of the learning step" are available for the "Self-
adjusting staircase timer." If there is only a brief movement
in front of the movement detector, the overshoot time (until
switch-off) will be close to the "Minimum time factor" x
"Time basis". If movements last longer, a "Time factor for
learning step" will be added to the staircase timer up to the
maximum, depending on what learning sensitivity has been
Block X, general telegrams
Parameter
Setting
Action at start of movement
Send immediately
Do not send
Send immediately and then
cyclically
When movement time elapsed
Send after staircase timer/
remaining time has elapsed
Do not send
"Send after staircase timer/
remaining time has elapsed and
then cyclically"
Output object X (1 - 4)
Enabled
Disabled
Pause between two telegrams (3 -
255) x 100 ms
3 - 255; preconfiguration:
5
Function
Object name
Type
Prio
Flags Behaviour
Block X
Switch object X
1 bit
Low
WCT Transmit/
receive
Block X
Value object X
1 byte Low
WCT Transmit/
receive
Block X
Value object X
2 bytes Low
WCT Transmit/
receive
Block X general telegrams output
switching/value object X
Parameter
Setting
Object
1 bit
1 byte 0% - 100%
1 byte 0 - 255
2 bytes
At start of movement
Transmits defined value
Transmits its value
Value
ON telegram
OFF telegram
0% - 100%
0 - 255
When movement time elapsed
Transmits defined value
Transmits its value
Value
ON telegram
OFF telegram
0% - 100%
0 - 255

9
set. Once the time set on the staircase timer has elapsed, a
restart takes place with "Minimum time factor".
Communication objects
Operating mode: Normal operation
You can select the following communication objects:
Block X, general times:
Parameter
Operating mode: Normal operation
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Communication objects
Operating mode: Master mode
You can select the following communication objects:
Block X, general times:
Parameter
Operating mode: Master mode
|
Note:
The parameter settings include various functions
which depend on other functions. Depending on the
Function
Object name
Type
Prio
Flags Behaviour
Block X
Time factor,
staircase timer
1 byte Low
WC
Transmit
Block X, general times
Parameter
Setting
Via movement, time is
Retriggerable
Not retriggerable
Staircase timer adjustable via
Parameters
Potentiometer
Overwriting staircase timer during
download
Enabled
Disabled
Self-adjusting staircase timer (always
retriggerable)
Disabled
Enabled
The following settings are only
visible when "Self-adjusting staircase
timer" is "disabled".
Time factor staircase timer object
Disabled
Enabled
Time base, staircase timer
1 min
1 s
1 hr
Time factor for staircase timer (1 -
255)
1 - 255; preconfiguration:
25
The following settings are only
visible when "Self-adjusting staircase
timer" is "enabled".
Minimum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
5
Time factor for learning step (1 - 255)
Staircase timer
1 - 255; preconfiguration:
1
Maximum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
25
Sensitivity of learning step
1 - 5; preconfiguration:
4
1 = slow
5 = sensitive
Function
Object name
Type
Prio
Flags Behaviour
Block X
Master trigger
object
1 bit
Low
WC
Transmit
Block X
Trigger object
1 bit
Low
WC
Transmit
Block X
Time factor,
staircase timer
1 byte Low
WC
Transmit

10
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Communication objects
Operating mode: Slave mode
|
Note:
No objects for "Time factor" or objects for
"Triggering" are displayed.
Parameter
Operating mode: Slave mode
Communication objects
Operating mode: Monitoring mode
|
Note:
No objects for "Time factor" or objects for
"Triggering" are displayed.
Parameter
Operating mode: Monitoring mode
- Disable function
The movement detector can be disabled with the aid of the
disable object; here the activation time point can be
download / bus voltage recovery or reception of a disable
telegram. The activation telegram for the disable function
can be an ON telegram or an OFF telegram. At the start of
disablement (if enabled via parameter) a telegram can be
sent via the corresponding output object. Cyclic
transmission makes sense with, for example, monitoring
since certain bus devices require a cyclically transmitted
OFF telegram. When the disable function is disabled, the
current status of the movement detector is restored (an
ongoing staircase timer is not stopped/start of movement
actions or action when movement time elapses is
transmitted).
Communication objects
You can select the following communication objects:
Block X, general:
Block X, general times
Parameter
Setting
Master triggering is (brightness-
dependent)
Enabled
Disabled
Via movement/master trigger object,
time is
Retriggerable
Not retriggerable
Master trigger object includes the
safety pause
Enabled
Disabled
Triggering is (not brightness-
dependent)
Enabled
Disabled
Switch off staircase timer via trigger
object
Enabled
Disabled
Via trigger object, time is
Retriggerable
Not retriggerable
Trigger object includes the safety
pause
Enabled
Disabled
Staircase timer adjustable via
Parameters
Potentiometer
Overwriting staircase timer during
download
Enabled
Disabled
Self-adjusting staircase timer (always
retriggerable)
Disabled
Enabled
The following settings are only
visible when "Self-adjusting staircase
timer" is "disabled".
Time factor staircase timer object
Disabled
Enabled
Time base, staircase timer
1 min
1 s
1 hr
Time factor for staircase timer (1 -
255)
1 - 255; preconfiguration:
25
The following settings are only
visible when "Self-adjusting staircase
timer" is "enabled".
Minimum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
5
Time factor for learning step (1 - 255)
Staircase timer
1 - 255; preconfiguration:
1
Maximum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
25
Sensitivity of learning step
1 - 5; preconfiguration:
4
1 = slow
5 = sensitive
Block X, general times
Parameter
Setting
Cyclic interval during movement
Time base
1 min
1 s
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Block X, general times
Parameter
Setting
Cyclic interval during movement
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Cyclic interval when movement time
has elapsed
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Function
Object name
Type
Prio
Flags Behaviour
Block X
Disable object
1 bit
Low
WC
Receive

11
Parameter
|
Note regarding 2-byte parameter settings:
Depending on the setting of the object type value
there will be new parameters; depending on the
parametrisation the values can be input immediately
or are ascertained via sign x basic value x factor.
- Changing specific parameters via the bus
The following parameters can be modified via the bus:
– "Time factor, staircase timer"
– "Range"
– "Brightness threshold"
|
Note:
Following bus voltage failure and recovery the
modified values will be retained.
Communication objects
You can select the following communication objects:
Block X, general times:
Block X, general movement sensors:
Block X, general brightness:
Parameter
- Master/slave planning via the trigger object or master
trigger object
General information regarding the trigger object and
master trigger object
The trigger object acts on the staircase timer
without
brightness measurement. Object value "1" starts the
staircase timer (start of movement action) while further "1"
telegrams retrigger the staircase timer, if enabled.
Object value "0" can switch the staircase timer off (end of
movement time action), if enabled.
The master trigger object acts on the staircase timer
with
brightness measurement. Object value "1" starts the
staircase timer (start of movement action) while further "1"
telegrams retrigger the staircase timer, if enabled.
Object value "0" has no meaning as regards the master
trigger object.
The parameters "Trigger object observes the safety pause"
(enabled/disabled) and "Master trigger object observes the
safety pause" (enabled/disabled) determine the effect of the
safety pause on the two external trigger objects.
Block X, general
Parameter
Setting
Disable function
Disabled
Enabled
Block X, general - disable function
Parameter
Setting
Activation time point of disable
function
Active during telegram reception
After download / bus voltage
recovery
Block
For object value "1"
For object value "0"
Behaviour at the start of Telegrams
block on Output object 1-4 tab
Do not transmit a telegram
Transmit telegram
Behaviour at the start of Telegrams
block on Output object 1-4 tab (only
visible at master- or monitoring
mode)
Transmit cyclic telegram
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
30
Block X general telegrams output
switching/value object X
Parameter
Setting
At start of block
OFF telegram
ON telegram
1 byte 0% - 100%
1 byte 0 - 255
2 bytes floating point or value
Function
Object name
Type
Prio
Flags Behaviour
Block X
Time factor,
staircase timer
1 byte Low
WC
Receive
Function
Object name
Type
Prio
Flags Behaviour
Block X
Range
1 byte Low
WC
Receive
Function
Object name
Type
Prio
Flags Behaviour
Block X
Brightness
threshold
2 bytes Low
WC
Receive
Block X, general times
Parameter
Setting
Time factor staircase timer object
Disabled
Enabled
Block X, general movement
sensors
Parameter
Setting
Range object (for all sensors)
Disabled
Enabled
Block X, general brightness
Parameter
Setting
Brightness threshold object
Disabled
Enabled

12
Application example 1:
Slave as movement detector (not brightness-dependent) and
master as movement detector (not brightness-dependent)
– System not brightness-dependent
– Slave transmits ON telegrams cyclically after movement
– Master switches on actuator when movement detected or
trigger
– Master retriggers staircase timer when movement
detected or trigger
– Master switches off when staircase timer elapses
– Cycle time slave maximum staircase timer / 2
– Staircase timer retriggerable via movement / master
trigger / trigger
Application example 2:
Slave as movement detector (not brightness-dependent) and
master as movement detector (brightness-dependent)
– Master evaluates brightness locally
– Slave transmits ON telegrams cyclically after movement
– Master switches on actuator upon movement detection or
master trigger if it is too dark
– Master retriggers staircase timer upon movement
detection or trigger, if previously switched on
– Master switches off when staircase timer elapses
– Cycle time slave maximum staircase timer / 2
– Staircase timer retriggerable via movement / master
trigger / trigger
Application example 3:
Slave as movement detector (brightness-dependent) and
master as movement detector (brightness-dependent)
– Master and slave evaluate the brightness
– Slave sends ON telegrams cyclically upon movement
detection if it is too dark or "Always-dark object" is "1".
– Master switches on actuator upon movement detection, if
it is too dark
– Master switches on actuator upon trigger
– Master retriggers staircase timer upon movement
detection or trigger, if previously switched on
– Master switches off when staircase timer elapses
(always-dark object again "0")
– Cycle time slave maximum staircase timer / 2
– Staircase timer retriggerable via movement / master
trigger / trigger
Behaviour on application/recovery of the bus voltage
The actual value input (external sensor), the status feedback
object (brightness value dimming actuator) can transmit
read requests depending on the parametrisation.
The operating mode status feedback message and the
brightness object can be transmitted depending on the
parametrisation.
Switch actuator
Switch obj.
Switch obj.
Switch obj.
Status feedback obj.
Status feedback obj.
1 to n slaves
Movement slave
Not
brightness-dep.
Movement master
Not
brightness-dep.
Trigger obj.
or master
trigger obj.
Switch actuator
Switch object
Master trig. obj. Switch obj.
Switch obj.
Status feedback obj.
Status feedback obj.
1 to n slaves
Movement slave
Not
brightness-dep.
Movement master
Brightness-dep.
Switch actuator
Switch obj.
Trigger obj.
Switch obj.
Switch obj.
Status feedback obj.
Status feedback obj.
1 to n slaves
Always-
dark
obj.
Movement slave
Brightness-dep.
Movement master
Brightness-dep.
+39 035 946 111
8.30 - 12.30 / 14.00 - 18.00
lunedì ÷ venerdì - monday ÷ friday
+39 035 946 260
sat@gewiss.com
www.gewiss.com
24h
GEWISS
- MATERIALE ELETTRICO