Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

 

 

General 

 

The GH-800 is specially developed to provide intelligent HVAC energy management 

of vacant rooms of lodging industry. With this system installed, hotelier can effectively 

reduce the energy expense from HVAC operation. The system utilizes reliable 

sensing technology and sophisticated logic control software to verify the occupancy 

status of guestroom. When guestroom is physically occupied, the system will allow 

the occupant to operate HVAC according to personal requirement. After the room is 

vacant, the system will automatically shut off the unnecessary HVAC operation to 

reduce energy consumption and equipment wear. To ensure optimum performance 

of the system, please carefully read this instruction before installing.

 

 

Applications 

 

Benefits 

 

  Resort/Hotel/Motel Guestrooms        

  School/College Dormitories 

  Timeshare Vacation Units 

  Military Lodging Facility 

  Commercial Offices 

  Conference Rooms 

 

  Reduce building energy consumption 

  Reduce equipment operation load 

  Prolong operation life of equipment 

  Reduce building management cost 

  Enjoy comfort of automatic control

 

Features 

  Smart Guestroom Occupancy Verification

 

  Superior RFI/EMI immunity

 

  High density pyroelectric infrared detection zones

 

  Fail-safe system operation protection ensure HVAC operation even system failure 

  HVAC start cycle delay enabled 

  Programmable temperature high-low setbacks for unoccupied mode 

  Occupancy status signal output 

  Audible & visible test indication 

  24V/dry contact selectable output 

  Corner/Wall mount available 

  Multi-directional adjustment 

  Optional HVAC slave sensor connectivity 

 

 

 

 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

Specification 

 Master Sensor

 

Model 

GH-MS1 

Infrared sensor & Detection Pattern 

110° Dual element 

Power supply 

24 ± 2 VAC/DC 

Current drain 

Standby: 20 mA, Operating: 10 mA 

Relay output 

Form C (NC-COM-NO), 24V or dry contact selectable 

Max. switching current 

NO: 5A, NC: 3A, resistive load 

Max. switching voltage 

AC: 250V, DC: 30 V 

High / Low temperature setback 

High - 26/28/30°C (79/82/85°F) , Low - 11/13/15°C (51/55/59°F) - via jumper setting 

Detection Pattern 

110°wide, 15m (50ft) long @25°C(77°F) 

Warm-up period 

25 ± 2 seconds 

Restart cycle protection 

2 minutes, can be disabled 

Test indication 

Buzzer (audible) and LED (visible) , can be disabled 

Housing material 

ABS 

Protection class 

IP 31 

Operating temperature 

-10°C ~ 60°C (14°F ~ 140°F) 

Mounting height 

1.8 – 3.6m 

RFI immunity 

Av. 20V/m (10 – 1,000 MHz) 

Detectable speed 

0.1 – 3.0 m/sec 

Operating humidity 

Max. 95% RH non-condensated 

Dimension 

112 x 66 x 45 mm (4.4 x 2.6 x 1.8 inch) 

 Power Pack 

Model 

PP-1 

Power supply 

90 ~ 277 VAC 

Power output 

24 VDC, 200 mA max. 

HVAC Relay output 

Normally Closed (fail-safe) 

Max. switching current 

10A, resistive load 

Max. switching voltage 

250V 

Housing material 

ABS, flame-proof 

Operating temperature 

-10°C ~ 60°C (14°F ~ 140°F) 

Operating humidity 

Max. 95% RH non-condensated 

Dimension 

110 x 52.5 x 30 mm (4.3 x 2.1 x 1.2 inch) 

 

System Component in GH-800 

 

GH-MS1 Master Sensor

 

GH-MS1 is the master sensor of Standalone HVAC Room Energy Sensor. It consists of a high 
sensitivity passive infrared (PIR) motion sensor  and sophisticated microprocessor with 
intelligent logic control in an aesthetically pleasing housing. It should be mounted on the wall 
(corner mount recommended) to detect the presence of human by sensing the movement of 
body heat energy. In addition to the guest presence detection and verification, the GH-MS-1 
also provides various operation settings and component connections of the system. To avoid 
the room becoming too hot or too cold during unoccupied period, thus requires excessive time 
and energy to cool down or warm up, the GH-MS1 also features a programmable secondary 
thermostat (via jumper) with various high and low temperature limit settings. The HVAC will be 
activated if room temperature exceeds the set range. 

 

 

PP-1 Power Pack

 

This power pack not only provides 24 VDC power supply for GH-MS1, but also controls the 
operation of HVAC unit. The GH-MS1 has a fail-safe design. In case that GH-MS1 Master 
Sensor is malfunction, the HVAC unit can still be operated manually as without using the GH-
MS1 master sensor.

 

GH-MC Door Sensor

 

The GH-MC Door sensor is a pair of magnetic contact to verify open/closed status. It should be 
wired to the corresponding terminals of GH-MS1 to report the open/closed status of the door. 
Once the door is opened, the GH-MS1 will enter into “standby” mode to detect the guest 
presence. If motion is detected, the GH-MS1 will verify the room as “occupied” status and allow 
guest to operate the thermostat and set the temperature of HVAC unit by themselves. If no 
motion is detected within a period of time, then GH-MS1 will verify the room “vacant” and then 
shut off the HVAC operation. Note: The GH-MS1 will automatically shut off the HVAC operation 
if any sensor connected door or window is left open for more than 5 minutes.

 

 
 
 
 

 

    ALTON CONTROLS SDN. BHD. 

www.alton.com.my 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

 

Termination Diagram 

 
 
 
 
 
 

 
 

To connect the wires between GH-MS1 and other components of the system, the terminals of GH-MS1 should be connected with correct 
wire to ensure optimum performance. Each terminal block of GH-MS1 are described as follow in the left to right sequence. 

 

 

SLA 

This terminal and terminal “GND” are for connection with the N.O. output of slave sensor. If multiple slave sensors are used, 
 the connection should be made in parallel. 
 

GND 

This ground terminal normally pairs with SLA or DSW for connection of slave sensor or door switch. 
 

DSW 

This terminal and terminal “GND” are for connection with the door switch. If multiple door/window switches are used, the  
connection should be made in series. 
 

-OCC+ 

These two terminals provide occupancy status output for guest-in-room detection. 
 

-24V+ 

These two terminals are for the input of 24V power supply from power pack. 
 

NC 

This terminal and terminal “COM” form the Normally Closed (NC) output of GH-MS1. 
 

COM

 

Common pole of relay output. 
 

NO 

“NO” and terminal “COM” form Normally Open (NO) output of GH-MS1. 

 
 
 
 

 

 

 

 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

Wiring Technique 

CAUTION 

  HVAC units may contain AC mains power. To prevent electric shock, ensure that AC mains is OFF before 

connecting with HVAC units.  

  Do NOT take shortcuts when connecting the HVAC power circuits. 

 

Wiring Techniques 

Conceal the sensor wiring by “fishing” the wire from hollow wall or partition. 
Drill an adequate hole behind the sensor, so that the sensor can cover the hole. 
Drop a string with a small weight inside the wall to bottom. 
Drill another hole on wall at the carpet level. Use a stiff wire with a hook to pull the string out from the hole. 
Pull the cable to the door switch, HVAC unit and slave sensor, if necessary 
Use proper tool to tuck the wire under the edge of carpet. 
Alternatively, staple the wire in the corner and cover it with vinyl corner molding to match room decor. 
Wiring should be completed and concealed in a manner that it will not be damaged by hotel guest or housekeeper. 

 

Mount the Sensor (GH-MS1) 

1. Remove the sensor cover by releasing the locking screw at the bottom of the housing. 
2. Carefully remove the circuit board by releasing the fixing screw. 
3. For corner mount (recommended), use the mounting holes on both 45° slopes to mount the base. 
4. Lead the cable into the base. Replace the circuit board on the base and fixed with screw. 
 

Coverage Pattern and Dimension 

 
 

 
 

Mounting Guide 

 

 
 
 

Mount the sensor without bracket 

1. Open the front cover by loosening the locking 
    screw. 
2. Remove the PCB from the bottom case with 
care. 
3. Mount the bottom case on the wall with proper 
    knockout holes. 
4. Lead the cable into the case and replace the PCB 
   for wiring connection 

Mount the sensor with bracket 

1. Mount the base of mounting bracket on the 
    selected position as shown. 
2. Lead the cable through the central tunnel of 
    mounting bracket. 
3. Open the front cover by loosening the 
locking bolt. Lead the cable into the case and 
fix the mounting 
bracket with the bottom case of sensor. 
4.  Connect  the  cable  to  the  corresponding   
    terminals. 
 
 
 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

    

 

 

 

Mount the Door Switch 

1. Select a proper position on the door frame. Drill a3/4” hole on the frame for switch recess. Use the spacer  
    as a guide, drill two 1/8” holes for fixing.  
2. Lead the wires and connect to the terminal block of switch. Insert the switch and fix with pop rivets or screws.

 

 

Select Mounting Location of GH-MS1 Master Sensor 

Selection a proper mounting location of the GH-MS1 is very important in assuring optimum performance of the 
system. Improper location of GH-MS1 may result in poorer performance. Following hints should be fully noticed 
before installation. 
 
Reflective materials (mirrors, shiny metal sheets, marble, tiles  etc) could reflect the infrared energy emission. 

 
 

 

The sensor should be mounted at 
8 ft. above the floor, preferably 
in a corner that has a good field 
of view to the movements of hotel 
guest. 

 

The sensor is more 
sensitive to the 
movements across the 
detection zones than 
those toward or away 
the sensor.

 

 

AVOID facing the sensor toward 
any object likely to change 
temperature rapidly, such as 
electric heater or fireplace.

 

 

AVOID mounting the 
sensor where it will 
receive direct sunlight 
or 
direct draft of 
heating/cooling vents.

 

 

AVOID locating the sensor where 
its detection zones may be 
blocked by doors, draperies or 
curtains. 

 

 

 

 
 
Recommended sensor locations 

      The numbers indicated represent order of preference.

 

 

Recommended Mounting Locations in order  Preference

 

 

 

 
 
 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 

 

 
 
 
 

Jumper Setting 

1.   Low temperature limit 
This jumper allows the selection of 3 different low temperature limits in which the GH-MS1 master sensor will 
automatically operate the HVAC when room temperature is lower than the set value. The sensor detects the room 
temperature once every 5 minutes. To disable the low temperature limit, remove the jumper. This function will only 
operate when room is unoccupied. 

 

2.  High temperature limit 

  This jumper allows the selection of 3 different temperature limits in which the GH-MS1 master sensor will     
  automatically operate the HVAC when room temperature is higher than the set value. The sensor detects the room    
  temperature once every 5 minutes. To disable the high temperature limit, remove the jumper. This function will only  
  operate when room is unoccupied. 
 

3.   Relay output format 

  This jumper allows the selection of relay output format. Place the jumper on both pins will make the relay contact     
  with 24V power. If dry contact (no load) output is required, remove the jumper off the pins (disconnect the pins). 
 
  4.   Restart delay enable/disable 
  This jumper allows to enable/disable the 2-minute short start cycle protection. With this restart delay enabled, the 

HVAC will start operating after 2 minutes. This restart delay is generally required by the individual Packaged 
Terminal Air Conditioner (PTAC) unit to protect the compressor damaging from frequent activations. To disable 
short start protection, place the jumper at disable position. 

 

5.   Test/normal 
This jumper allows to enable/disable the LED and buzzer indication. When jumper is placed at “TEST” position, the 
LED will light for approximately 2 seconds whenever the motion is detected and the buzzer will beep. If jumper is 
placed at “NORMAL” position, the LED will NOT light when sensor detects the motion. But it will blink about 10 
seconds after the GH-MS1 activate the HVAC. This indication will help the maintenance staff to check if the GH-
MS1 system is working normal. 
 
 
 
 
 
 
 
 
 
 
 
 

 

GH-MS1 Master Sensor Description 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

 

1. After wiring connection is completed, ensure the jumper JP7 is placed at “TEST” mode. Replace and fasten the 
front cover with the locking screw. 

  Whenever power is applied on the GH-MS1, please wait for about 25 seconds for sensor to warm-up. During 

warm-up period, the buzzer will sound beep-beep (each beep lasts 1 second). Both LED and relay will be activated. 
The activated GH-MS1 means the HVAC unit will NOT operate due to its fail-safe design. 
 
2. When warm-up period expires, the buzzer stops sounding, LED lights off, but relay will still be active. 
 
3. DOOR SENSOR TEST - Open the door, the buzzer should sound constantly until the door is closed. 

 If the buzzer does not sound while door is opened, check the door switch and ensure correct wiring connection 

between door switch and GH-MS1. 
 

4. SLAVE SENSOR TEST - If NO slave sensor is installed, please skip this test. The detection of slave sensor 

should be tested after the door switch function is tested okay. Walk across in the room of slave sensor installed, 
the LED of slave sensor will light on whenever it detects the movement. The buzzer of GH-MS1 will sound one 
long beep (1 sec.) and - one short beep (0.2 sec.) when slave sensor is activated. 

 If the buzzer does not sound when slave sensor detects the movement but the LED of slave sensor is working,  

         check the wiring between slave sensor and GH-MS1. 
 

5.  MASTER SENSOR TEST – Walk across in the room of master sensor installed. The LED will light on and the  
    buzzer will sound beep-beep (0.2 sec.) whenever master sensor detects the movement. The HVAC unit will    
    operate at least 30 seconds for every detection. 

 If no further movement is detected within 30 seconds after the last detection, the HVAC unit will stop operating. 

 

After the system operation test completed, ensure to place the jumper JP7 to “NORMAL” position for normal 
operation of the system. The normal operation of GH-800 is quite sophisticated. Many different operation modes 
and statuses are carefully managed and controlled by the microprocessor. Various modes and statuses are 
described as follow:- 
 

Standby Mode 

If the room is vacant, the system will enter into “standby” mode after the warm-up time expires. Under standby 
mode, the HVAC unit will not operate. 
 

Temp-control Status 

While room is unoccupied, the temperature sensor of GH-MS1 will measure the room temperature every 5 minutes. 
When room temperature goes higher or lower than the high/low setting, the HVAC unit will automatically operate 
until the room temperature goes back to the set range. Once the room temperature returns to the set range, the 
system will return to “standby” mode. This function will only operate if jumper heads are set in place and HVAC unit 
is “ON”. 
 

Occupied Mode 

If master or any slave sensor detects the movement during standby mode, the system will enter into “occupied” 
mode. Under the “occupied” mode, the hotel guests can manage or set the room temperature via the HVAC wall 
unit according to their preference. 

 
Door-open Status 

Whenever the door is opened, the system will detect it and enter into “door-open” status. The HVAC unit will 
operate and LED will flash for 10 seconds. The LED flash is to indicate that the system function is normal. If the 
door is left open for more than 5 minutes, the system will shut off the HVAC unit until the door is closed. 

 

Delay Status 

Once the door is closed, the system will enter into “delay” status. During this 10-second period, the system will 
remain as its original mode.

 

 
Waiting Mode 

The system will enter into “Waiting” mode after the second delay status expires. If master or any slave sensor 
detects the movement during waiting mode, the system will enter into “occupied” mode. If no movement is detected 
within 5 minutes, then system will enter into “standby” mode. 

System Testing 

System Operation 

 


background image

Standalone HVAC Room Energy Sensor 

 

 

 

 

G

G

G

G

ESA

ESA

ESA

ESA

 

 

 
 

 

 

 

After final installation of the unit, no routine maintenance is required. The GH-800 is not field serviceable and should 
be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief 
description of the problem plus any relevant application notes. 
 

System Flow Chart 

Maintenance 