PDF User Manual

  1. Home
  2. Manuals
  3. Genvex GES Energy S Installation Manual

Genvex GES Energy S Installation Manual

GES Energy M

Made by: Genvex
Type: Installation Manual
Category: Ventilation
Pages: 17
Size: 3.45 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

Genvex A/S 

 Sverigesvej 6 

 DK-6100 Haderslev 

 Tel.: +45 73 53 27 00 

 salg@genvex.dk 

 genvex.dk

GES ENERGY S

GES ENERGY M

  

PASSIVE VENTILATION WITH WIRING

DIAGRAM FOR OPTIMA 100 AND 

OPTI MA 250

INSTALLATION MANUAL

UK / Version 30.04.2014

 


background image

2

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Table of contents

GES Energy - Installation ...............................................4

Mounting .........................................................................5

Duct connection ..............................................................6

Condensate drain ...........................................................6

Duct system ....................................................................7

Insulation of ducts in cold loft spaces .............................7

Insulation of ducts in warm spaces.................................8

Reheating of supply air ...................................................8

Electrical connection.......................................................9

Inspection and commissioning of the appliance .............9

Optimum commissioning of the appliance ......................9

Maintenance of the appliance.......................................10

Fault finding ..................................................................12

PCB and Wiring Diagrams............................................13

EU-Declaration of conformity........................................16

 


background image

3

When installing the GES Energy follow these instructions:

1) Turn off the electricity before opening the unit

2)  Install an air tight water trap on a non-freezing location to 

compensate for the fan pressure.

3)  The height of the water trap 

must be

 at least 50 mm.

4) Make sure that the drain flows downwards all the way 

from the unit.

5)  Pour 1 liter water into the drip tray of the unit to verify that 

it is drained properly. Before each heating season make 

sure that the drain is filled with water. 

6) If freezing of the water trap occurs, it is necessary to 

install a thermostat and electrical heater to prevent 

freezing when the temperature drops below +2 C°.

7) Air flow adjustments must be made on both supply 

and exhaust air sides before use of the machine. It is 

important supply and exhaust air volumes are balanced.

8)  It is recommended to keep the ducts closed until the unit 

is started and the system is adjusted.

This instruction must be followed. If the condensate drain 

is not made according to this instruction, GENVEX A/S can 

not be made responsible for any additional damages, which 

have nothing to do with the GENVEX unit.

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

3

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

 


background image

1: Frisk luft

2: Udsugning

3: Afkast

4: Indblæsning

5: Modstrømsvarmeveksler

6: Indblæsningsventilator

7: Udsugningsventilator

8: Friskluftfilter

9. Udsugningsfilter

10: El-kasse

11: Kondensvandsbakke

12: Kondensvandsafløb

13: 230V/50Hz

14: By-pass

9

11

10

14

12

1

2

3

4

13

7

5

6

8

72,7

60,7

550

42

1014

24

32

1088

1056

550

135

280

128,6

265

1: Frisk luft

2: Udsugning

3: Afkast

4: Indblæsning

5: Modstrømsvarmeveksler

6: Indblæsningsventilator

7: Udsugningsventilator

8: Friskluftfilter

9. Udsugningsfilter

10: El-kasse

11: Kondensvandsbakke

12: Kondensvandsafløb

13: 230V/50Hz

14: By-pass

9

11

10

14

12

1

2

3

4

13

7

5

6

8

72,7

60,7

550

42

1014

24

32

1088

1056

550

135

280

128,6

265

1: Frisk luft

2: Udsugning

3: Afkast

4: Indblæsning

5: Modstrømsvarmeveksler

6: Indblæsningsventilator

7: Udsugningsventilator

8: Friskluftfilter

9. Udsugningsfilter

10: El-kasse

11: Kondensvandsbakke

12: Kondensvandsafløb

13: 230V/50Hz

14: By-pass

11
12

1

2

3

4

13

7

5

8

72,7

60,7

550

42

1014

24

32

1088

1056

550

135

280

128,6

265

4

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

GES Energy 1 - Installation

The GES Energy 1 is supplied in a vertical version (as 

shown) or a horizontal version.

The vertical version cannot be used as a horizontal 

version and vice versa. One of the reasons being that the 

condensate water would not reach the condensate drain if 

the unit would be turned around.

The unit must be positioned so that the condensate drain 

with a necessary trap can be properly led to an internal 

drain. In the winter period a unit may produce up to 6 

litres of condensate water per day. To allow access for 

service and maintenance, there must be a clear space of a 

minimum of 600 mm in front of the unit.

Weight: 32 kg

 

The vertical version cannot be used as a 

 

horizontal version and vice versa. One of the 

 

reasons being that the condensate water would 

 

not reach the condensate drain if the unit 

 

would be turned around.

1: Fresh air

2: Exhaust air

3: Extract air

4: Supply air

5: Counter current heat exchanger

6: Supply air fan

7: Extract air fan

8: Fresh air filter

9. Extract air filter

10: Electrical box

11: Condensate tray

12: Condensate drain/outlet

13: 230V/50Hz

14: By-pass (Option)

 


background image

5

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Mounting

GES Energy is supplied with an universal wall mount 

ing kit. 

Wall mounting (vertical)

GES Energy can be mounted directly on the wall 

with visible or unvisible wall mounts. 

Closet mounting (vertical)

GES Energy is created to fit into a closet with (60 

x 60 cm) as shown. You can place the unit on the 

universal mounting kit as shown.

Horizontal Mounting

GES Energy is always supplied with rubber feet 

mounted like on the vertical version. By horizontal 

version it is necessary to remove the rubber feet and 

place them on the left site of the unit (the bottom). 

A

A

Visible wall mounts

unvisible wall mounts

Closet mounting

gummifødder, som leveret

ved vandret montage af 

maskinen skal de leverede

gummifødder flyttes til

positioner som anvist her

bunden af maskinen i tilfælde

at maskinen monteres vandret

D

E

F

C

1

2

3

4

B

A

3

2

1

5

C

D

4

6

7

8

A

B

14-08-2009

1

Oprettet Dato:

Revision:

Kg

Vægt:

Betegnelse:

Tegn. Nr.:

Blad 1 af 1

A3

010324-1

GES Energy liggende u. bypass

General tolerance hvor intet andet er angivet: ISO 2768-m

Skala:1:5

Revisions Dato:

02-01-2007

Lokation:

Laying Mounting

By a laying version 

the rubber feets 

have to be placed 

here

The bottom of a laying 
unit

Rubber feets 
as delivered

 


background image

6

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

No water in the siphon = water damage

supply air

extract air

fresh air

exhaust air

50

100

Laying GES Energy

Standing GES Energy

100

50

Duct connection

All duct connections are with a yellow sticker indicating the 

type of ventilation pipe to be connected.

Connect the supply air        :

Duct system from the unit to the supply outlet in the living 

area.

Connect the extract air        :

Duct system from wet rooms to the unit.

Connect the fresh air         :

Duct system from fresh air roof cowls/external grills from or 

the ground collector to the unit.

Connect the exhaust air         :

Duct system from unit to the escaping roof cowls/external

grills.

Condensate drain

The units produce up to 6 litres of condensate per day. It is 

therefore important that the condensate drain is correctly 

executed and that the unit has a slight fall towards the 

condensate drain. 

The condensate drain pipe must be air tight for example by 

bending a copper pipe as an siphon (see sketch to the left). 

Use an armed water hose between the drain connecting 

piece on the unit and the siphon and tightend it in both 

ends with a collar band.

From the siphon and to the internal outlet there must be 

a necessary fall on 1%. The condensate drain must be 

fitted with a water trap as there is negative pressure in the 

chamber in which the condensate tray is mounted.

If the unit is installed in a cold loft space, the condensate 

drain pipe must be insulated to prevent freezing of the 

condensate in the pipe. However, it is recommended that 

the water trap is installed in a heated space below to 

ensure that the water in it does not freeze.

If installation problems make it impossible to secure the 

condensate drain pipe from freezing by insulation, it will be 

necessary to mount a thermostat-controlled heating tape 

round the condensate drain pipe.

Optimal operation is achieved by mounting a 

connector piece Ø 160 mm in each outlet of the 

GES Energy and tighten them with the supplied 

collar bands.

While operating there will be a low pressure in 

the unit it will therefor be neccesary to make 

sure that the height difference is min. 50 mm 

to the water in the siphon.

 


background image

3 m

1 m

3 m

7

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Duct insulation, alt. A

Duct insulation, alt. B

Faulty duct insulation

Duct system

It is recommended that the duct system is executed in 

spiral ducting connected with rubber ring seal fittings in 

order to provide a leak-free and durable duct system. 

To achieve a satisfactory low sound level from the unit, 

sound locks must always be fitted to the supply and extract 

duct system between the unit and the first supply and 

extract fittings.

It is recommended that air speeds in the ducts are 

dimensioned at sufficiently low level to prevent noise from 

the supply and extract fittings.

When positioning fresh air and extract roof cowls/grills, 

make sure the two air flows do not intercept, causing 

escaping air to be drawn in again.

It is recommended that grills are placed on the north or 

east side of the house to provide optimum comfort.

Minimum distance: 3 m between supply and exhaust air

Insulation of ducts in cold loft spaces

In order to exploit the unit’s high recovery potential

(efficiency), it is necessary to insulate the ducts correctly.

Genvex recommends as follows:

Supply and extract ducts:

To minimise heat losses from the duct system in cold loft 

spaces, the supply and extract ducts must be insulated 

with a minimum of 100 mm insulation. If insulation form 

alternative A is used, it is recommended that it is executed 

with two layers of 50 mm lamella mats with paper or foil 

externally and with staggered joints between the two 

layers. If the ducts are laid on the rafter foot, alternative B 

may be used. The insulation must always be tightly packed 

round the ducts.

Fresh air and escaping ducts in cold spaces: 

It is recommended that fresh air and escaping ducts 

are insulated with a minimum of 50 mm insulation. The 

fresh air duct is insulated to prevent warm air in the loft in 

summer from heating up the fresh air. Take care to seal the 

termination where the escaping duct is led through the roof 

or through the gable end, in order to avoid condensation 

damage.

Refer to your local distributor for guidance on national 

insulation directives.

 


background image

8

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Insulation of ducts in heated spaces

Genvex recommends as follows:

Supply and extract ducts:

In warm loft spaces the supply and extract channels must 

be insulated with 50 mm insulation.

Supply and extract air ducts led through heated spaces in 

dwellings do not require insulation. If the supply air duct 

has cooling, bypass or earth heat exchanger installed it 

must be insulated.

Fresh air and exhaust ducts:

In warm loft spaces and warm rooms in dwellings the fresh 

and exthaust air ducts must be insulated with minimum 50 

mm insulation. In addition, the insulation must be covered 

externally with plastic film or aluminium foil in order to 

avoid condensate in the insulation.

We recommend an insulation of 100 mm on the fresh air 

duct when installing a earth heat exchanger.

Refer to your local distributor for guidance on national 

insulation directives.

Reheating of supply air

As the counter current heat exchanger cannot extract all 

the heat from the extract air and supply it to the supply air, 

the supply air will be about 1-4°C colder than the room 

temperature in the dwelling for the whole winter season. 

If this lower supply temperature is insupportable during 

cold periods, a water-based or electrical reheating surface 

can be mounted for reheating the supply air up to room 

temperature.

Water-based reheating surface

To protect the water-based reheating surface from frost 

burst, a frost protection thermostat must be fitted to the unit 

and the surface insulated. The frost protection thermostat 

sensor is mounted behind the fins of the water-based 

reheating surface. The sensor for controlling the motor 

valve is mounted in the supply air channels approx. 500 

mm downstream of the water-based reheating surface 

in order not to be affected by the radiant heat from the 

heating element. The water supply to the water-based 

reheating surface must be executed by an authorised 

plumbing and heating engineer.

Electrical reheating surface

The sensor for controlling the electrical heating surface 

is mounted in the supply air channel approx. 500 mm 

downstream of the electrical reheating surface in order 

not to be affected by the radiant heat from the heating 

element.

 


background image

9

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Electrical installation

The electrical connection must be carried out by an 

authorised electrical engineer.

See accompaning electric diagram.

The cable between the unit and the control panel is a 4- 

conductor cable for Optima 250, with a maximum length 

of 50m and a 8-conductor cable for Optima 100 with a 

maximum length of 10m.

Inspection and initial adjustment of appliance

To achieve optimum running of the unit it must be initially

adjusted with air measuring equipment.

To start up the unit before adjustment, do as follows:

Before starting up the unit:

1:  Check that the Genvex unit is correctly mounted and 

that all ducts are insulated as required.

2:  Check that hatches can be opened so that service and 

maintenance on the unit can be carried out.

3:  Check that filters are clean (may be dirty from 

installation work).

4:  Check that the condensate drain is correctly mounted 

with water trap and is protected from freezing. Pour 1 

litre water into the condensate tray and make sure it 

can run unhindered through the condensate drain pipe.

5:  Set all supply valves such that the valve closest to the 

unit is opened three turns from closed position, while 

the furthest is open eight turns from closed position. 

Open the intermediate valves by 4-7 turns depending 

on how far they are from the unit.

6:  If a reheating surface has been mounted on the unit, 

set the supply temperature to 0-3°C below the room 

temperature in the dwelling.

The unit can now be started up and be allowed to run until

initial adjustment with air measurement equipment has

taken place.

Optimum initial adjustment of plant

Air measuring equipment is used.

Before starting initial adjustment, check that the 6 points 

in the inspection and initial adjustment section have been 

carried out. Then start up the unit:

 


background image

10

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

G4  =  Standard filter (Coarse filter class G4)
F7   =  Pollen filter (Fine filter class F7)

Close filter

Open filter

Maintenance of plant 

         

 Turn off the electricity for the unit before 

           opening it

Filters

:

When the filter timer reaches the set value for filter 

change, “Alarm!” will show in the screen saver and ”Chg. 

filter” will flash. This means that it is time to clean/change 

the  filters.

Switch the unit off on the switch on the control panel 

or the switch on the electrical panel. Open the front 

doors and remove the filters. When the filters have been 

cleaned/replaced, close the front doors and reset the 

filter alarm by holding down the button below the filter 

symbol, until ”Alarm!”, “Chg. Filter” and the exclamation 

mark disappears in the filter symbol. The unit reverts to 

normal operation.

If the wish is an other time interval this can be adjust in 

the User menu. 

The fresh air filter (F7) is in the left site of the unit and it 

is higher than the extract air filter (G4).

Do not vacuum or clean at high air pressure. It 

will damage the filter!

 


background image

11

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

12: Kondensvandsafløb

11: Kondensvandsbakke

9. Udsugningsfilter

7: Udsugningsventilator

6: Indblæsningsventilator

5: Modstrømsvarmeveksler

14: By-pass

13: 230V/50Hz

10: El-kasse

8: Friskluftfilter

4: Indblæsning

3: Udsugning

2: Afkast

1: Frisk luft

3

1

4

2

13

265

128.6

550

280

135

550

24

32

60.7

1014

42

1056

1088

The four farest screws which are holding the fan have to be 
removed before the fan can be taken out.

12: Kondensvandsafløb

11: Kondensvandsbakke

9. Udsugningsfilter

7: Udsugningsventilator

6: Indblæsningsventilator

5: Modstrømsvarmeveksler

14: By-pass

13: 230V/50Hz

10: El-kasse

8: Friskluftfilter

4: Indblæsning

3: Udsugning

2: Afkast

1: Frisk luft

3

1

4

2

13

265

128.6

550

280

135

550

24

32

60.7

1014

42

1056

1088

condensate drain

counter current heat exchanger

snap lock

condense tray

Condensate drain:

When changing the filter in August/September, 

before outside temperatures falls to 5°C, check the 

condensate drain for blockage by dirt and check that 

there is water in the water trap.

Pour 1 litre water into the condensate tray and make sure it 

can run off without problems. If the condensate drain does 

not work, this could lead to water damage in the dwelling.

Countercurrent heat exchanger:

Inspect the countercurrent heat exchanger every year. If it 

is dirty, remove it and wash in warm soapy water and then 

rinse, possibly in the bathroom using the shower head. 

Before the counter current heat exchanger can be moved, 

the front of the condense tray have to be opened. There is 

a snap lock in the right site of the condense tray. 

Fans:

Every year check the two fan wheels for dirt. If they are 

dirty they may be cleaned with a brush, bottle washer

etc. Remember to shot down the power. 

By demounting the front it is important to remove the 

filters before the front is removed.

Supply and extract valves:

Clean the valves by wiping with a dry cloth. Make sure the 

valve does not rotate, causing a change in the air volume.

Service

If you are unable to maintain your unit yourself, you 

can sign a service agreement with the Genvex service 

department. If any faults arise in the unit, contact the 

Genvex service department.

 


background image

12

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Troubleshooting

Safety thermostat in electrical heater 

(optional equipment)

If an error occurs on an electrical heater, the safety ther-

mostat will disconnect. 

The heater is equipped with a fire thermostat that auto

-

matically cuts off the power supply, if the temperature 

exceeds 80 °C. If the temperature decreases, the heater 

automatically re-engages.

As an additional security there is a built-in thermal cut-out, 

which disengages if the temperature exceeds 110 °C. Re-

engaging must be done manually.

Does not apply to PTC electrical heaters.

The system is not running 

Unit stopped

Possible error:

•  Fuse in main board has blown, no power to unit.

•  One of the fuses on the circuit board of the unit is-

blown.

•  Loose wire, no power to unit.

•  Loose wire between unit and control panel.

•  Faulty or incorrectly set week program.

•  Filter timer has switched the system off.

Condensed water is leaking from the unit

Possible error:

•  Condensation outlet blocked by dirt.

•  The condensation outlet is not adequately protected 

against freezing at low outdoor temperatures.

Air faults

No supply air:

Possible error:

•  Faulty supply air fan

• 

Clogged supply air fi lter

•  Clogged fresh air grill due to dirt and leaves during the 

fall and snow and ice during the winter.

•  Fuse on the circuit board is blown.

•  The unit is in defrost mode (supply air fan stops)

•  Incorrect value set in User menu item 2.

No extract air:

Possible error:

•  Faulty extract air fan

• 

Clogged extract air fi lter.

•  Fuse on the circuit board is blown

Cold supply air:

Possible error:

•  Clogged heat changer.

•  Faulty extract air fan.

• 

Clogged extract air filter.

•  Electrical reheater is disconnected at the over heat-

ing thermostat (only units with electrical reheater 

installed).

•  Air in the heating pipes, faulty thermostat / motorvalve, 

incorrect setting of control panel.

Within the guarantee period (0-2 years):

 

The installer from whom you have bought the system. 

After the guarantee period (2 years ->):

 

The installer from whom you have bought the system or 

the Genvex service department (+45 7353 2765). 

 

Before calling, please write down the data from the inscrip-

tion plate (silver plate on the unit).

Alarms 

Filter timer

The control has a filter timer to guarantee that the filter is

changed and that optimal operation is established. When

the timer reaches the set value, “Chg. filter” will flash in

the display until the filters have been changed.

When the filters have been changed, the button for the

filter symbol must be held down until ”Alarm!”, “Chg. Filter”

and the exclamation mark disappears and the unit reverts

to normal operation.

Com error

This error appears when there is no communication

between the display and control. Check that the wiring is

correct on terminals 21 to 24.

21 Signal
22 Signal
23 10 Volt
24 0 Volt

Frost protection error

This error message will be displayed if a water reheater 

is fitted to the system and the temperature of the water 

reheater is too low, causing a danger of frost burst.  

The control will stop the system and open the motor- 

operated valve to keep the heater warm.

 


background image

13

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

08-04-2014

L1  =Humidistat

L2  =Display

L3  =Sensors T1,T3,T4,T7

L4  =Humidity sensor P1

L6  =Sensors T8, T9

L8  =External stop

L11=0-10V Water valve and 

         0-10V Belimo bypass

L17=0-10V extract air fan and

         0-10V supply air fan

Q=Fuse

H1  =Mains connection 230 VAC

H2  = (R2) Electric Reheater 230VAC

H3  = (R3) Electric Preheater 230VAC

H2,H3 =Max. load total 1800W COS

Ф

1

H6  = (R10) Water valve, Belimo Bypass 230VAC

H7  = (R10) Fan, extract air 230VAC

H8  = (R12) ON/OFF Bypass 2x230VAC

H9  = (R10) Fan, supply air 230VAC/bypass

H16= (R8) AUX relay 230VAC max. 20W

H17= (R9) AUX relay 230VAC max. 20W

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

3

3

3

3

3

3

3 4

4

4

4

4

4

5

5 6

6

7

7 8

8

L1

L2

L3

L6

L8

L11

H2

H3

H7

H6

H8

H9

H17

H16

ES960C

PE

PE

L17

A

B

Q

1=

1.

6A

Q

2=

2.

5A

H1

L4

Q3=0.5A

Q4=0.5A

Q1= H8,H16,H17

Q2= H6,H7,H9

Q3= L1-L17

Q4= L1-L17

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

3

3

3

3

3

3

3 4

4

4

4

4

4

5

5 6

6

7

7 8

8

PCB 

ES960 

for Optima 250 Design

 


background image

14

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Wiring Diagram Optima 250 Design 

with ES960 

PCB

-

-

+

+

M1
M2
N

N

N

L

L

0-10V

0-10V

0-10V

0-10V

L

L

L

L

N

N

N

N

N

L

+5V

0V

Signal

08-04-2014

0V

+10V

-

-

+

+

Mains connection

1x230VAC, L-N-PE

Max: 13A

H2 and H3 Max.

load total 

1800W

Aux. relay R9

1x230V 50Hz

ONLY control current

Genvex

Humidistat

Potential-free

contact

must be used

Sensor Frost 

Sensor, extract air

Sensor, exhaust air

Sensor, fresh air

Sensor, supply air

Sensor Option

External stop

EC fan

Extract air

Blue

Yellow

EC fan

Supply air

Blue

Yellow

Water valve

EC fan

Extract air

ON/OFF

Bypass

Brown

Brown

Blue

Blue

Yellow/green

Yellow/green

Water valve

Belimo

Bypass

Humidity sensor

White
Red
Blue

EC fan

Supply air

Aux. relay R8

1x230V 50Hz

ONLY control current

Red - Brown
Blue - Green
Yellow - White

Belimo

Bypass

Electric Reheater

Electric Preheater

Black

Black

White

White

12

3

H

y≥

S

et

12

3

1

2

1

2

H1

1
2

1
2

H2

1
2

1
2

H3

1
2

1
2

H6

1
2

1
2

H7

1
2
3

1
2
3

H8

1
2

1
2

H9

1
2

1
2

H

16

1
2

1
2

H

17

L

1
2

1
2

L1

1
2
3
4

1
2
3
4

L2

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

L3

1
2
3
4

1
2
3
4

L4

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

L6

1
2

1
2

L8

1
2
3
4

1
2
3
4

L11

1
2
3
4

1
2
3
4

L17

M1

M1

M2

M2

M3

M3

M5

N

P1

PE

PE

PE

T1

T3

T4

T7

T8

T9

21
22
23
24

21
22
23
24

OPTIMA DESIGN

M4

M4

 


background image

15

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

PCB 

ES951 

and Wiring Diagram for Optima 100 Design

Electrical Heater/Preheater

230V

230V

230V

230V

Sensor Heater/Preheater

Connection

for Dataloging

Genvex

Hygrostat

Potentialfree

Contact

Must be used

Sensor Exhaust air

EC-Fan

Exhaust

Max 1,0A

EC-Fan

Supply

Max 1,0A

EC-Fan

Supply

Max 1,0A

EC-Fan

Exhaust

Max 1,0A

Mains

1x230VAC, 50Hz

 MAX Fuse 10A

Must be connected

to earth

Yell/Green

Yell/Green

Brown

Brown

Blue

Blue

Blue

Blue

Blue

Yellow

Yellow

Yellow

Red

+5V

GND

+5V

1

2

L1

1

23

1

2

3

4

L2

1

2

3

4

5

6

7

8

L3

1

2

H1

1

2

H3

1

2

H7

1

2
3

H8

1

2

H9

L1

M1

M2

M4

N

PE

PE

PE

T1

90°C

manu

PE

L

N

PE

T4

T9

M1

M2

1

2

3

4

L6,1

5

6

7

8

L6,2

1

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

2

3

3

3

3

3

4

4

4

4

5

5

5

6

6

7

7

8

8

L1

L2

L3

L6

H3

H7

H8

H9

ES951

PE

PE

R2

R4

Q

1=

1,

6A

H1

L4

R3

R1

21

22
23

24
C1

C2

C3

C4

OPTIMA 100 DESIGN

K3

K4

K5

 


background image

16

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

 


background image

Genvex A/S 

 Sverigesvej 6 

 DK-6100 Haderslev 

 Tel.: +45 73 53 27 00 

 salg@genvex.dk 

 genvex.dk

Our Units and Controls – Your Choice

Genvex has more than 40 years of experience in creating quality units 
providing optimum indoor climate with excellent energy efficiency. Our
systems employ the newest technologies in heat recovery and have
heat recovery rates of up to 96%. The systems are continuously
optimised with the newest technologies.
 
Advanced controls ensure that as little energy as possible is used for
reaching an optimum level of comfort. 

Today’s and future construction place greater and greater requirements 
for energy-friendly, yet compact systems. We at Genvex are aware of 
this and are continuously developing solutions that meet these needs. 
For example, a brilliant solution for decentralised housing ventilation is 
a range hood solution with full integration to the system’s control which 
ensures that the most efficient ventilation system is achieved with the 
simplest installation.