Full Text Searchable PDF User Manual

Genvex A/S
•
Sverigesvej 6
•
DK-6100 Haderslev
•
Tel.: +45 73 53 27 00
•
salg@genvex.dk
•
genvex.dk
GES ENERGY S
GES ENERGY M
PASSIVE VENTILATION WITH WIRING
DIAGRAM FOR OPTIMA 100 AND
OPTI MA 250
INSTALLATION MANUAL
UK / Version 30.04.2014

2
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Table of contents
GES Energy - Installation ...............................................4
Mounting .........................................................................5
Duct connection ..............................................................6
Condensate drain ...........................................................6
Duct system ....................................................................7
Insulation of ducts in cold loft spaces .............................7
Insulation of ducts in warm spaces.................................8
Reheating of supply air ...................................................8
Electrical connection.......................................................9
Inspection and commissioning of the appliance .............9
Optimum commissioning of the appliance ......................9
Maintenance of the appliance.......................................10
Fault finding ..................................................................12
PCB and Wiring Diagrams............................................13
EU-Declaration of conformity........................................16

3
When installing the GES Energy follow these instructions:
1) Turn off the electricity before opening the unit
2) Install an air tight water trap on a non-freezing location to
compensate for the fan pressure.
3) The height of the water trap
must be
at least 50 mm.
4) Make sure that the drain flows downwards all the way
from the unit.
5) Pour 1 liter water into the drip tray of the unit to verify that
it is drained properly. Before each heating season make
sure that the drain is filled with water.
6) If freezing of the water trap occurs, it is necessary to
install a thermostat and electrical heater to prevent
freezing when the temperature drops below +2 C°.
7) Air flow adjustments must be made on both supply
and exhaust air sides before use of the machine. It is
important supply and exhaust air volumes are balanced.
8) It is recommended to keep the ducts closed until the unit
is started and the system is adjusted.
This instruction must be followed. If the condensate drain
is not made according to this instruction, GENVEX A/S can
not be made responsible for any additional damages, which
have nothing to do with the GENVEX unit.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
3
Subject to Technical Modifications of GES Energy Small and GES Energy Medium

1: Frisk luft
2: Udsugning
3: Afkast
4: Indblæsning
5: Modstrømsvarmeveksler
6: Indblæsningsventilator
7: Udsugningsventilator
8: Friskluftfilter
9. Udsugningsfilter
10: El-kasse
11: Kondensvandsbakke
12: Kondensvandsafløb
13: 230V/50Hz
14: By-pass
9
11
10
14
12
1
2
3
4
13
7
5
6
8
72,7
60,7
550
42
1014
24
32
1088
1056
550
135
280
128,6
265
1: Frisk luft
2: Udsugning
3: Afkast
4: Indblæsning
5: Modstrømsvarmeveksler
6: Indblæsningsventilator
7: Udsugningsventilator
8: Friskluftfilter
9. Udsugningsfilter
10: El-kasse
11: Kondensvandsbakke
12: Kondensvandsafløb
13: 230V/50Hz
14: By-pass
9
11
10
14
12
1
2
3
4
13
7
5
6
8
72,7
60,7
550
42
1014
24
32
1088
1056
550
135
280
128,6
265
1: Frisk luft
2: Udsugning
3: Afkast
4: Indblæsning
5: Modstrømsvarmeveksler
6: Indblæsningsventilator
7: Udsugningsventilator
8: Friskluftfilter
9. Udsugningsfilter
10: El-kasse
11: Kondensvandsbakke
12: Kondensvandsafløb
13: 230V/50Hz
14: By-pass
11
12
1
2
3
4
13
7
5
8
72,7
60,7
550
42
1014
24
32
1088
1056
550
135
280
128,6
265
4
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
GES Energy 1 - Installation
The GES Energy 1 is supplied in a vertical version (as
shown) or a horizontal version.
The vertical version cannot be used as a horizontal
version and vice versa. One of the reasons being that the
condensate water would not reach the condensate drain if
the unit would be turned around.
The unit must be positioned so that the condensate drain
with a necessary trap can be properly led to an internal
drain. In the winter period a unit may produce up to 6
litres of condensate water per day. To allow access for
service and maintenance, there must be a clear space of a
minimum of 600 mm in front of the unit.
Weight: 32 kg
The vertical version cannot be used as a
horizontal version and vice versa. One of the
reasons being that the condensate water would
not reach the condensate drain if the unit
would be turned around.
1: Fresh air
2: Exhaust air
3: Extract air
4: Supply air
5: Counter current heat exchanger
6: Supply air fan
7: Extract air fan
8: Fresh air filter
9. Extract air filter
10: Electrical box
11: Condensate tray
12: Condensate drain/outlet
13: 230V/50Hz
14: By-pass (Option)

5
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Mounting
GES Energy is supplied with an universal wall mount
ing kit.
Wall mounting (vertical)
GES Energy can be mounted directly on the wall
with visible or unvisible wall mounts.
Closet mounting (vertical)
GES Energy is created to fit into a closet with (60
x 60 cm) as shown. You can place the unit on the
universal mounting kit as shown.
Horizontal Mounting
GES Energy is always supplied with rubber feet
mounted like on the vertical version. By horizontal
version it is necessary to remove the rubber feet and
place them on the left site of the unit (the bottom).
A
A
Visible wall mounts
unvisible wall mounts
Closet mounting
gummifødder, som leveret
ved vandret montage af
maskinen skal de leverede
gummifødder flyttes til
positioner som anvist her
bunden af maskinen i tilfælde
at maskinen monteres vandret
D
E
F
C
1
2
3
4
B
A
3
2
1
5
C
D
4
6
7
8
A
B
14-08-2009
1
Oprettet Dato:
Revision:
Kg
Vægt:
Betegnelse:
Tegn. Nr.:
Blad 1 af 1
A3
010324-1
GES Energy liggende u. bypass
General tolerance hvor intet andet er angivet: ISO 2768-m
Skala:1:5
Revisions Dato:
02-01-2007
Lokation:
Laying Mounting
By a laying version
the rubber feets
have to be placed
here
The bottom of a laying
unit
Rubber feets
as delivered

6
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
No water in the siphon = water damage
supply air
extract air
fresh air
exhaust air
50
100
Laying GES Energy
Standing GES Energy
100
50
Duct connection
All duct connections are with a yellow sticker indicating the
type of ventilation pipe to be connected.
Connect the supply air :
Duct system from the unit to the supply outlet in the living
area.
Connect the extract air :
Duct system from wet rooms to the unit.
Connect the fresh air :
Duct system from fresh air roof cowls/external grills from or
the ground collector to the unit.
Connect the exhaust air :
Duct system from unit to the escaping roof cowls/external
grills.
Condensate drain
The units produce up to 6 litres of condensate per day. It is
therefore important that the condensate drain is correctly
executed and that the unit has a slight fall towards the
condensate drain.
The condensate drain pipe must be air tight for example by
bending a copper pipe as an siphon (see sketch to the left).
Use an armed water hose between the drain connecting
piece on the unit and the siphon and tightend it in both
ends with a collar band.
From the siphon and to the internal outlet there must be
a necessary fall on 1%. The condensate drain must be
fitted with a water trap as there is negative pressure in the
chamber in which the condensate tray is mounted.
If the unit is installed in a cold loft space, the condensate
drain pipe must be insulated to prevent freezing of the
condensate in the pipe. However, it is recommended that
the water trap is installed in a heated space below to
ensure that the water in it does not freeze.
If installation problems make it impossible to secure the
condensate drain pipe from freezing by insulation, it will be
necessary to mount a thermostat-controlled heating tape
round the condensate drain pipe.
Optimal operation is achieved by mounting a
connector piece Ø 160 mm in each outlet of the
GES Energy and tighten them with the supplied
collar bands.
While operating there will be a low pressure in
the unit it will therefor be neccesary to make
sure that the height difference is min. 50 mm
to the water in the siphon.

3 m
1 m
3 m
7
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Duct insulation, alt. A
Duct insulation, alt. B
Faulty duct insulation
Duct system
It is recommended that the duct system is executed in
spiral ducting connected with rubber ring seal fittings in
order to provide a leak-free and durable duct system.
To achieve a satisfactory low sound level from the unit,
sound locks must always be fitted to the supply and extract
duct system between the unit and the first supply and
extract fittings.
It is recommended that air speeds in the ducts are
dimensioned at sufficiently low level to prevent noise from
the supply and extract fittings.
When positioning fresh air and extract roof cowls/grills,
make sure the two air flows do not intercept, causing
escaping air to be drawn in again.
It is recommended that grills are placed on the north or
east side of the house to provide optimum comfort.
Minimum distance: 3 m between supply and exhaust air
Insulation of ducts in cold loft spaces
In order to exploit the unit’s high recovery potential
(efficiency), it is necessary to insulate the ducts correctly.
Genvex recommends as follows:
Supply and extract ducts:
To minimise heat losses from the duct system in cold loft
spaces, the supply and extract ducts must be insulated
with a minimum of 100 mm insulation. If insulation form
alternative A is used, it is recommended that it is executed
with two layers of 50 mm lamella mats with paper or foil
externally and with staggered joints between the two
layers. If the ducts are laid on the rafter foot, alternative B
may be used. The insulation must always be tightly packed
round the ducts.
Fresh air and escaping ducts in cold spaces:
It is recommended that fresh air and escaping ducts
are insulated with a minimum of 50 mm insulation. The
fresh air duct is insulated to prevent warm air in the loft in
summer from heating up the fresh air. Take care to seal the
termination where the escaping duct is led through the roof
or through the gable end, in order to avoid condensation
damage.
Refer to your local distributor for guidance on national
insulation directives.

8
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Insulation of ducts in heated spaces
Genvex recommends as follows:
Supply and extract ducts:
In warm loft spaces the supply and extract channels must
be insulated with 50 mm insulation.
Supply and extract air ducts led through heated spaces in
dwellings do not require insulation. If the supply air duct
has cooling, bypass or earth heat exchanger installed it
must be insulated.
Fresh air and exhaust ducts:
In warm loft spaces and warm rooms in dwellings the fresh
and exthaust air ducts must be insulated with minimum 50
mm insulation. In addition, the insulation must be covered
externally with plastic film or aluminium foil in order to
avoid condensate in the insulation.
We recommend an insulation of 100 mm on the fresh air
duct when installing a earth heat exchanger.
Refer to your local distributor for guidance on national
insulation directives.
Reheating of supply air
As the counter current heat exchanger cannot extract all
the heat from the extract air and supply it to the supply air,
the supply air will be about 1-4°C colder than the room
temperature in the dwelling for the whole winter season.
If this lower supply temperature is insupportable during
cold periods, a water-based or electrical reheating surface
can be mounted for reheating the supply air up to room
temperature.
Water-based reheating surface
To protect the water-based reheating surface from frost
burst, a frost protection thermostat must be fitted to the unit
and the surface insulated. The frost protection thermostat
sensor is mounted behind the fins of the water-based
reheating surface. The sensor for controlling the motor
valve is mounted in the supply air channels approx. 500
mm downstream of the water-based reheating surface
in order not to be affected by the radiant heat from the
heating element. The water supply to the water-based
reheating surface must be executed by an authorised
plumbing and heating engineer.
Electrical reheating surface
The sensor for controlling the electrical heating surface
is mounted in the supply air channel approx. 500 mm
downstream of the electrical reheating surface in order
not to be affected by the radiant heat from the heating
element.

9
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Electrical installation
The electrical connection must be carried out by an
authorised electrical engineer.
See accompaning electric diagram.
The cable between the unit and the control panel is a 4-
conductor cable for Optima 250, with a maximum length
of 50m and a 8-conductor cable for Optima 100 with a
maximum length of 10m.
Inspection and initial adjustment of appliance
To achieve optimum running of the unit it must be initially
adjusted with air measuring equipment.
To start up the unit before adjustment, do as follows:
Before starting up the unit:
1: Check that the Genvex unit is correctly mounted and
that all ducts are insulated as required.
2: Check that hatches can be opened so that service and
maintenance on the unit can be carried out.
3: Check that filters are clean (may be dirty from
installation work).
4: Check that the condensate drain is correctly mounted
with water trap and is protected from freezing. Pour 1
litre water into the condensate tray and make sure it
can run unhindered through the condensate drain pipe.
5: Set all supply valves such that the valve closest to the
unit is opened three turns from closed position, while
the furthest is open eight turns from closed position.
Open the intermediate valves by 4-7 turns depending
on how far they are from the unit.
6: If a reheating surface has been mounted on the unit,
set the supply temperature to 0-3°C below the room
temperature in the dwelling.
The unit can now be started up and be allowed to run until
initial adjustment with air measurement equipment has
taken place.
Optimum initial adjustment of plant
Air measuring equipment is used.
Before starting initial adjustment, check that the 6 points
in the inspection and initial adjustment section have been
carried out. Then start up the unit:

10
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
G4 = Standard filter (Coarse filter class G4)
F7 = Pollen filter (Fine filter class F7)
Close filter
Open filter
Maintenance of plant
Turn off the electricity for the unit before
opening it
Filters
:
When the filter timer reaches the set value for filter
change, “Alarm!” will show in the screen saver and ”Chg.
filter” will flash. This means that it is time to clean/change
the filters.
Switch the unit off on the switch on the control panel
or the switch on the electrical panel. Open the front
doors and remove the filters. When the filters have been
cleaned/replaced, close the front doors and reset the
filter alarm by holding down the button below the filter
symbol, until ”Alarm!”, “Chg. Filter” and the exclamation
mark disappears in the filter symbol. The unit reverts to
normal operation.
If the wish is an other time interval this can be adjust in
the User menu.
The fresh air filter (F7) is in the left site of the unit and it
is higher than the extract air filter (G4).
Do not vacuum or clean at high air pressure. It
will damage the filter!

11
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
12: Kondensvandsafløb
11: Kondensvandsbakke
9. Udsugningsfilter
7: Udsugningsventilator
6: Indblæsningsventilator
5: Modstrømsvarmeveksler
14: By-pass
13: 230V/50Hz
10: El-kasse
8: Friskluftfilter
4: Indblæsning
3: Udsugning
2: Afkast
1: Frisk luft
3
1
4
2
13
265
128.6
550
280
135
550
24
32
60.7
1014
42
1056
1088
The four farest screws which are holding the fan have to be
removed before the fan can be taken out.
12: Kondensvandsafløb
11: Kondensvandsbakke
9. Udsugningsfilter
7: Udsugningsventilator
6: Indblæsningsventilator
5: Modstrømsvarmeveksler
14: By-pass
13: 230V/50Hz
10: El-kasse
8: Friskluftfilter
4: Indblæsning
3: Udsugning
2: Afkast
1: Frisk luft
3
1
4
2
13
265
128.6
550
280
135
550
24
32
60.7
1014
42
1056
1088
condensate drain
counter current heat exchanger
snap lock
,
condense tray
Condensate drain:
When changing the filter in August/September,
before outside temperatures falls to 5°C, check the
condensate drain for blockage by dirt and check that
there is water in the water trap.
Pour 1 litre water into the condensate tray and make sure it
can run off without problems. If the condensate drain does
not work, this could lead to water damage in the dwelling.
Countercurrent heat exchanger:
Inspect the countercurrent heat exchanger every year. If it
is dirty, remove it and wash in warm soapy water and then
rinse, possibly in the bathroom using the shower head.
Before the counter current heat exchanger can be moved,
the front of the condense tray have to be opened. There is
a snap lock in the right site of the condense tray.
Fans:
Every year check the two fan wheels for dirt. If they are
dirty they may be cleaned with a brush, bottle washer
etc. Remember to shot down the power.
By demounting the front it is important to remove the
filters before the front is removed.
Supply and extract valves:
Clean the valves by wiping with a dry cloth. Make sure the
valve does not rotate, causing a change in the air volume.
Service
If you are unable to maintain your unit yourself, you
can sign a service agreement with the Genvex service
department. If any faults arise in the unit, contact the
Genvex service department.

12
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Troubleshooting
Safety thermostat in electrical heater
(optional equipment)
If an error occurs on an electrical heater, the safety ther-
mostat will disconnect.
The heater is equipped with a fire thermostat that auto
-
matically cuts off the power supply, if the temperature
exceeds 80 °C. If the temperature decreases, the heater
automatically re-engages.
As an additional security there is a built-in thermal cut-out,
which disengages if the temperature exceeds 110 °C. Re-
engaging must be done manually.
Does not apply to PTC electrical heaters.
The system is not running
Unit stopped
Possible error:
• Fuse in main board has blown, no power to unit.
• One of the fuses on the circuit board of the unit is-
blown.
• Loose wire, no power to unit.
• Loose wire between unit and control panel.
• Faulty or incorrectly set week program.
• Filter timer has switched the system off.
Condensed water is leaking from the unit
Possible error:
• Condensation outlet blocked by dirt.
• The condensation outlet is not adequately protected
against freezing at low outdoor temperatures.
Air faults
No supply air:
Possible error:
• Faulty supply air fan
•
Clogged supply air fi lter
• Clogged fresh air grill due to dirt and leaves during the
fall and snow and ice during the winter.
• Fuse on the circuit board is blown.
• The unit is in defrost mode (supply air fan stops)
• Incorrect value set in User menu item 2.
No extract air:
Possible error:
• Faulty extract air fan
•
Clogged extract air fi lter.
• Fuse on the circuit board is blown
Cold supply air:
Possible error:
• Clogged heat changer.
• Faulty extract air fan.
•
Clogged extract air filter.
• Electrical reheater is disconnected at the over heat-
ing thermostat (only units with electrical reheater
installed).
• Air in the heating pipes, faulty thermostat / motorvalve,
incorrect setting of control panel.
Within the guarantee period (0-2 years):
The installer from whom you have bought the system.
After the guarantee period (2 years ->):
The installer from whom you have bought the system or
the Genvex service department (+45 7353 2765).
Before calling, please write down the data from the inscrip-
tion plate (silver plate on the unit).
Alarms
Filter timer
The control has a filter timer to guarantee that the filter is
changed and that optimal operation is established. When
the timer reaches the set value, “Chg. filter” will flash in
the display until the filters have been changed.
When the filters have been changed, the button for the
filter symbol must be held down until ”Alarm!”, “Chg. Filter”
and the exclamation mark disappears and the unit reverts
to normal operation.
Com error
This error appears when there is no communication
between the display and control. Check that the wiring is
correct on terminals 21 to 24.
21 Signal
22 Signal
23 10 Volt
24 0 Volt
Frost protection error
This error message will be displayed if a water reheater
is fitted to the system and the temperature of the water
reheater is too low, causing a danger of frost burst.
The control will stop the system and open the motor-
operated valve to keep the heater warm.

13
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
08-04-2014
L1 =Humidistat
L2 =Display
L3 =Sensors T1,T3,T4,T7
L4 =Humidity sensor P1
L6 =Sensors T8, T9
L8 =External stop
L11=0-10V Water valve and
0-10V Belimo bypass
L17=0-10V extract air fan and
0-10V supply air fan
Q=Fuse
H1 =Mains connection 230 VAC
H2 = (R2) Electric Reheater 230VAC
H3 = (R3) Electric Preheater 230VAC
H2,H3 =Max. load total 1800W COS
Ф
1
H6 = (R10) Water valve, Belimo Bypass 230VAC
H7 = (R10) Fan, extract air 230VAC
H8 = (R12) ON/OFF Bypass 2x230VAC
H9 = (R10) Fan, supply air 230VAC/bypass
H16= (R8) AUX relay 230VAC max. 20W
H17= (R9) AUX relay 230VAC max. 20W
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3 4
4
4
4
4
4
5
5 6
6
7
7 8
8
L1
L2
L3
L6
L8
L11
H2
H3
H7
H6
H8
H9
H17
H16
ES960C
PE
PE
L17
A
B
Q
1=
1.
6A
Q
2=
2.
5A
H1
L4
Q3=0.5A
Q4=0.5A
Q1= H8,H16,H17
Q2= H6,H7,H9
Q3= L1-L17
Q4= L1-L17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3 4
4
4
4
4
4
5
5 6
6
7
7 8
8
PCB
ES960
for Optima 250 Design

14
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
Wiring Diagram Optima 250 Design
with ES960
PCB
-
-
+
+
M1
M2
N
N
N
L
L
0-10V
0-10V
0-10V
0-10V
L
L
L
L
N
N
N
N
N
L
+5V
0V
Signal
08-04-2014
0V
+10V
-
-
+
+
Mains connection
1x230VAC, L-N-PE
Max: 13A
H2 and H3 Max.
load total
1800W
Aux. relay R9
1x230V 50Hz
ONLY control current
Genvex
Humidistat
Potential-free
contact
must be used
Sensor Frost
Sensor, extract air
Sensor, exhaust air
Sensor, fresh air
Sensor, supply air
Sensor Option
External stop
EC fan
Extract air
Blue
Yellow
EC fan
Supply air
Blue
Yellow
Water valve
EC fan
Extract air
ON/OFF
Bypass
Brown
Brown
Blue
Blue
Yellow/green
Yellow/green
Water valve
Belimo
Bypass
Humidity sensor
White
Red
Blue
EC fan
Supply air
Aux. relay R8
1x230V 50Hz
ONLY control current
Red - Brown
Blue - Green
Yellow - White
Belimo
Bypass
Electric Reheater
Electric Preheater
Black
Black
White
White
12
3
H
y≥
S
et
12
3
1
2
1
2
H1
1
2
1
2
H2
1
2
1
2
H3
1
2
1
2
H6
1
2
1
2
H7
1
2
3
1
2
3
H8
1
2
1
2
H9
1
2
1
2
H
16
1
2
1
2
H
17
L
1
2
1
2
L1
1
2
3
4
1
2
3
4
L2
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
L3
1
2
3
4
1
2
3
4
L4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
L6
1
2
1
2
L8
1
2
3
4
1
2
3
4
L11
1
2
3
4
1
2
3
4
L17
M1
M1
M2
M2
M3
M3
M5
N
P1
PE
PE
PE
T1
T3
T4
T7
T8
T9
21
22
23
24
21
22
23
24
OPTIMA DESIGN
M4
M4

15
Subject to Technical Modifications of GES Energy Small and GES Energy Medium
PCB
ES951
and Wiring Diagram for Optima 100 Design
Electrical Heater/Preheater
230V
230V
230V
230V
Sensor Heater/Preheater
Connection
for Dataloging
Genvex
Hygrostat
Potentialfree
Contact
Must be used
Sensor Exhaust air
EC-Fan
Exhaust
Max 1,0A
EC-Fan
Supply
Max 1,0A
EC-Fan
Supply
Max 1,0A
EC-Fan
Exhaust
Max 1,0A
Mains
1x230VAC, 50Hz
MAX Fuse 10A
Must be connected
to earth
Yell/Green
Yell/Green
Brown
Brown
Blue
Blue
Blue
Blue
Blue
Yellow
Yellow
Yellow
Red
+5V
GND
+5V
1
2
L1
1
23
1
2
3
4
L2
1
2
3
4
5
6
7
8
L3
1
2
H1
1
2
H3
1
2
H7
1
2
3
H8
1
2
H9
L1
M1
M2
M4
N
PE
PE
PE
T1
90°C
manu
PE
L
N
PE
T4
T9
M1
M2
1
2
3
4
L6,1
5
6
7
8
L6,2
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
4
4
4
4
5
5
5
6
6
7
7
8
8
L1
L2
L3
L6
H3
H7
H8
H9
ES951
PE
PE
R2
R4
Q
1=
1,
6A
H1
L4
R3
R1
21
22
23
24
C1
C2
C3
C4
OPTIMA 100 DESIGN
K3
K4
K5

16
Subject to Technical Modifications of GES Energy Small and GES Energy Medium

Genvex A/S
•
Sverigesvej 6
•
DK-6100 Haderslev
•
Tel.: +45 73 53 27 00
•
salg@genvex.dk
•
genvex.dk
Our Units and Controls – Your Choice
Genvex has more than 40 years of experience in creating quality units
providing optimum indoor climate with excellent energy efficiency. Our
systems employ the newest technologies in heat recovery and have
heat recovery rates of up to 96%. The systems are continuously
optimised with the newest technologies.
Advanced controls ensure that as little energy as possible is used for
reaching an optimum level of comfort.
Today’s and future construction place greater and greater requirements
for energy-friendly, yet compact systems. We at Genvex are aware of
this and are continuously developing solutions that meet these needs.
For example, a brilliant solution for decentralised housing ventilation is
a range hood solution with full integration to the system’s control which
ensures that the most efficient ventilation system is achieved with the
simplest installation.