Operating manual
Switch amplifier
TS125 / TS225
Save for later reference.
www.ghm-messtechnik.de
Companies / brands of GHM
English

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
2
Table of contents
Page
1.
Intended use (areas of application) ............................................................................... 3
1.1.
Safety signs and symbols .................................................................................. 4
1.2.
Safety instructions ............................................................................................. 4
1.3.
Product liability and warranty ............................................................................. 4
1.4.
Standards and directives ................................................................................... 5
2.
Product description ........................................................................................................ 5
2.1.
Scope of delivery ............................................................................................... 6
2.2.
Functional principle ............................................................................................ 6
2.3.
Connection diagram........................................................................................... 7
2.4.
Type plate .......................................................................................................... 7
2.5.
Carrier rail bus - PowerRail................................................................................ 8
3.
Assembly and installation .............................................................................................. 9
3.1.
Mechanical assembly ........................................................................................ 9
3.2.
Electrical installation .......................................................................................... 9
4.
Controls and functional description ............................................................................. 10
4.1.
TS125...-1, TS125...-2, TS225...-1 TS225...-2: ............................................... 10
5.
Commissioning, maintenance and service .................................................................. 14
5.1.
Commissioning ................................................................................................ 14
5.2.
Maintenance .................................................................................................... 14
5.3.
Service ............................................................................................................. 14
6.
Technical data ............................................................................................................. 15
6.1.
Mechanical design / dimensions ...................................................................... 17
7.
Order code ................................................................................................................... 18
8.
Device transport and storage ...................................................................................... 18
9.
Returns ........................................................................................................................ 19
10.
Disposal ................................................................................................................... 19
11.
Imprint ...................................................................................................................... 19
12.
EU
Declaration
of Conformity ................................................................................ 20

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
3
1.
Intended use (areas of application)
Refer to the chapter 'Product description' for detailed specifications
for the area of application.
The operational safety of the device is only assured when used as
intended in accordance with the specifications in the operating manual.
Intervention beyond the actions described in the operating manual may only be
carried out by personnel authorised by the manufacturer for safety and warranty
reasons. Conversions or modifications made on one's own authority are
expressly prohibited.
Application-specific dangers can emanate from this device when used improperly
or not as intended.
Only device versions TS125L-Ex,TS125LP-Ex TS125M-Ex and
TS225M-Ex are permitted for use as accessory equipment for
connection of intrinsically safe sensors installed in Zones 0 or 1
and/or 20 or 21.
In the process, the safety-related characteristic data must be
observed.
The approval for all intrinsically safe equipment is voided if it has not
first been connected to an intrinsically safe circuit, because
compliance with the safety-related characteristic data must be 100%
guaranteed.
Therefore, a safety test must be carried out by the manufacturer
before later use as intrinsically safe equipment.
The devices TS125L-00, TS125LP-00 and all versions of the series
TS*****-Ex may be installed in Explosion Zone 2 under the following
conditions:
- Installation in a clean environment in a conductive, earthed housing
(switch cabinet) with a minimum protection rating of IP54.
- Transient overvoltages (with open switch contact) may not be
higher than 500V at the relay outputs.
- The connection terminals may only be disconnected in a de-
energised state
Applicable standards: EN60079-0 and EN60079-15.
General safety instructions, use
This operating manual must be kept in a location such that qualified personnel
can refer to it at all times.

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
4
Any processes described in this operating manual may only be carried out by
trained, qualified personnel who are authorised by the owner and wearing
protective clothing. All rights reserved.
1.1.
Safety signs and symbols
Warning notices are identified in this document as described under Table 1:
DANGER
Warning! This symbol warns of imminent danger which can
result in death, severe bodily injury, or severe property damage
in case of non-observance.
Attention! This symbol warns of potential dangers or harmful
situations which can cause damage to the device or to the
environment in case of non-observance.
Note! This symbol indicates processes which can have a direct
influence on operation or can trigger an unforeseen reaction in
case of non-observance.
1.2.
Safety instructions
Read the product description before commissioning the device. Ensure that there
are no limitations for use of the product for the relevant applications.
The owner is responsible for ensuring the fault-free operation of the
device. The owner is obligated to ensure compliance and to observe
the required work and safety measures of the current applicable
regulations for the entire duration of use.
1.3.
Product liability and warranty
Exclusion of liability:
The contents of the operating manual have been checked to ensure conformity
with the described device. However, deviations cannot be entirely ruled out.
Therefore, we cannot assume any guarantee for complete conformity. The
specifications in this document are checked regularly and any necessary
corrections are incorporated into subsequent versions. This document is subject
to technical changes. In addition, all claims are based on the valid 'Standard
Terms for the Supply of Products and Services of the Electrical Industry'.
GHM Messtechnik GmbH cannot inspect or repair any devices without
the required form having been filled in completely (refer to page 16
'Returns').
DANGER

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
5
1.4.
Standards and directives
Low-voltage Directive 2014/35/EU
Testing standard 60664-1: 2007
EMC Directive 2014/30/EU
Testing standard EN 61326-1: 2013
RoHS Directive 2011/65/EU
Testing standard EN50581: 2012
ATEX Directive 2014/34/EU
Testing standards EN60079-0: 2012, EN60079-11:2012, EN60079-15: 2010
Functional safety
Testing standards EN61508-1: 2010
(Issue years for testing standards belong to german versions)
2.
Product description
Switch amplifiers of the series TS125 and TS255 are used in switch cabinets for
the conversion and isolation of digital switching signals, optionally also in explosive
areas.
The devices are available in one- or two-channel versions.
All passive sensors, such as switching contacts, Namur initiators according to DIN
EN 60947-5-6, or passive electronic outputs of third-party devices, can be
connected to the optional intrinsically safe inputs.
The TS125 series in 12.5mm wide carrier rail housing offers relay outputs with
output make circuit.
The TS225 series in 22.5mm wide carrier rail housing offers relay outputs with
changeover function.
The devices may also be used in explosion zone 2 if they are installed in a suitable
housing.
Use in plants with functional safety SIL2 is also possible.
Input 1
Input 2
Relay A1
Relay A2
Power supply

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
6
2.1.
Scope of delivery
TS125 or TS225
this operating manual
2.2.
Functional principle
The output relay and the diodes are controlled at the device front depending on
the status of the measuring inputs.
A maximum voltage of 8V is applied at a connected Namur sensor via the input
terminals. The sensor must limit the flowing current to two thresholds in
accordance with the Namur specification. Current lower than 1.2mA is identified
by the sensor as inactive; current higher than 2.1mA is identified by the sensor
as active. The range between 1.2mA and 2.1mA applies as hysteresis.
Alternatively, a switch contact can be connected. Then no current flows in the
open state and approx. 8mA flows in the closed state, wherein the previously
mentioned requirements are also fulfilled.
The front-side DIP switches can be used to select whether the input state is
directly or inversely transferred to the corresponding output relay.
The devices also offer the possibility of monitoring the input lines for a short-
circuit or wire break with the appropriate DIP switch settings.
In this connection, a current flow of less than 0.2mA applies as a wire break and
a current flow higher than 7mA applies as a short-circuit. With activation of this
monitoring function, the relays open in the event of a fault and the front-side
LEDs blink red. With connection of a simple switch contact, the error monitoring
must not be connected, because the error conditions are, in principle, always
fulfilled.
In order to also monitor the connecting lines for a mechanical switch contact,
resistors can be wired to the inputs according to the connection diagram below.
In the process, it is assured that the error thresholds recognised by the device
are only actually exceeded and/or undercut in the event of an error.

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
7
2.3.
Connection diagram
2.4.
Type plate
The type plate includes the most important identification data
Type and article name
Technical data
Serial number / bar code

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
8
2.5.
Carrier rail bus - PowerRail
The power supply voltage supply of multiple devices can be concentrated in the
mounting carrier rail (TS35 ) of a bus system.
An equivalent version is available for the entire LP series of GHM carrier rail
devices in 12.5mm wide housing.
Before mounting the device to be supplied, a series-compatible bus adapter must
be connected on the carrier rail.
For this purpose, an adapter piece is required for each device. The supply of the
bus then takes place via a plug-in terminal strip.
In the device version TS125LP provided for this purpose, the supply terminals 11
and 12 on the upper side of the device are omitted.

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
9
3.
Assembly and installation
3.1.
Mechanical assembly
Carrier rail mounting TS35, DIN EN 60715
The mounting of multiple devices without spaces is only permitted on horizontally
mounted carrier rails.
The devices may be installed in Ex Zone 2 within an earthed, conductive housing
(switch cabinet) with protection rating IP54.
3.2.
Electrical installation
The device may only be installed by an electrician. The national and
international regulations for connection of electrical systems in the
respective user country apply.
Voltage supply in accordance with DIN EN 60664-1, SELV, PELV.
The power supply is connected at Connections 11 and 12 of the plug-in terminal
strip.
Terminals 41, 42 (Channel 1) and 51, 52 (Channel 2) are intended for the
sensors and/or input switches.
With TS125 the normally open relay outputs are at Terminals 31, 32
(Channel 1) and/or 21, 22 (Channel 2)
With TS225 the changeover relay outputs are at Terminals 31-33 (Channel 1)
and/or 21-23 (Channel 2).
DANGER

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
10
4.
Controls and functional description
4.1.
TS125...-1, TS125...-2, TS225...-1 TS225...-2:
1 or 2 channel switch amplifier
- Green operating display
Operating elements per channel Ch.1 / Ch.2
- LEDs A1/A2
: yellow
with active relay
blinks
red
(wire break or short-circuit)
- Switch INV
: off:
active input switches the assigned relay on
on:
active input switches the assigned relay off
- Switch ERR
: off:
error recognition inactive
on:
error recognition of wire break or short-circuit at
the input
Switches the assigned relay off with error status
(condition as delivered underlined)
Applications with functional safety (SIL2)
require switch
INV = off
and
ERR = on!

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
11
Ch.1 and Ch.2 switching behaviour
Input
Switch INV
Switch ERR
Relay
open (<0.2mA)
off
off
open
on
off
closed
on or off
on
open
inactive (0.4…1.2mA)
off
on or off
open
on
on or off
closed
active (2.1…6mA)
off
on or off
closed
on
on or off
open
short-circuit (>7mA)
off
off
closed
on
off
open
on or off
on
open

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
12
TS125...-F, TS225...-F
1-channel isolating amplifier with additional error relay or parallel relay. Also
enables simulation of a changeover contact in the narrow housing.
Operating elements
- Green operating display
- LED A1
: yellow with active Relay A1
blinks red with error status
(wire break or short circuit)
- LED A2
: yellow with active Relay A2
(if switch ERR-Ch.2 = off)
blinks red/yellow with active Relay A2 with
error status (if switch ERR-Ch.2 = on)
blinks red with inactive Relay A2 with
error status (if switch ERR-Ch.2 = on)
- Switch INV-Ch.1
: off:
active input Ch.1 switches Relay A1 on
on:
active input Ch.1 switches Relay A1 off
- Switch ERR-Ch.1
: off:
error recognition with Relay A1 inactive
on:
error recognition of wire break or short-circuit at
input Ch.1
Switches Relay A1 off with error status
- Switch INV-Ch.2
: off:
active input Ch.1 or alternatively on
error status*) switch Relay A2 on
on:
active input Ch.1 or alternatively on
error status*) switch Relay A2 off
- Switch ERR-Ch.2
: off:
error recognition with Relay A2 inactive
(Relay A2 switches parallel to Relay A1)
*)
on:
error recognition with Relay A2 active
(see Switch INV-Ch.2)
(condition as delivered underlined)
Applications with functional safety (SIL2)
requires switch
ERR-Ch.2 = on
and
INV-Ch.2 = on!
INV-Ch.1 = off, INV-Ch.2=on, ERR-Ch.2 simulates a changeover contact.
with Relay A1, A2.
(It must be ensured that
both contacts are open
with the device switched off)

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
13
Switching behaviour TS125...-F, TS225...-F (with error relay)
Input Ch.1 switches Relay A1 and A2
Standard relay A1
Input
Switch INV-
Ch.1
Switch ERR-
Ch.1
Relay A1
open (<0.2mA)
off
off
open
on
off
closed
on or off
on
open
inactive (0.4…1.2mA)
off
on or off
open
on
on or off
closed
active (2.1…6mA)
off
on or off
closed
on
on or off
open
short-circuit (>7mA)
off
off
closed
on
off
open
on or off
on
open
Error relay A2
Input (at Ch.1)
Switch INV-
Ch.2
Switch ERR-
Ch.2
Relay A2
open (<0.2mA)
off
off
open
on
off
closed
off
on
closed
on
on
open
inactive (0.4…1.2mA)
off
on or off
open
on
on or off
closed
active (2.1…6mA)
off
off
closed
on
off
open
off
on
open
on
on
closed
short-circuit (>7mA)
off
on or off
closed
on
on or off
open

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
14
5.
Commissioning, maintenance and service
5.1.
Commissioning
1. Ensure that the connection assignment takes place according to the
connection diagram and matches the power supply.
2. With connection of equipment for explosion-prone areas, ensure that the
device version has the appropriate approval.
3. With installation of the isolating amplifier in Zone 2, the device must be
installed in a switch cabinet with protection rating IP54.
4. Ensure that the terminals are firmly screwed in.
5. After switching on the power, check for the correct switching function.
Note:
After the supply voltage is applied, a check of the device function takes place
according to the requirements for functional safety.
The device is ready for operation after approximately 3 seconds.
The functional test also includes a load test of the supply voltage. The device
draws as much power as a maximum load for 2 seconds, which means 2 short-
circuited inputs and 2 energised relays. The load is only simulated, which means
the relays do not switch during this phase.
5.2.
Maintenance
Housing:
No cleaning or maintenance is required when operated as intended.
5.3.
Service
Service of the device is only possible at the factory.

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
15
6.
Technical data
Explosion protection
Device versions with intrinsicallsafe inputs for Zone 0/1
(TS125L-Ex.., TS125LP-Ex.., TS125M-Ex.., TS225M-Ex..)
Gas
II (1) G [Ex ia Ga] IIC/IIB
1)
Dust
II (1) D [Ex ia Da] IIIC
1)
1) BVS 14 ATEX E079 certificate
Installation in Zone 2
(only TS125L)
II 3 G Ex nA nC [ic] IIB T4 Gc
2)
2) Manufacturer's certificate, conditions of use on page 3
Device version TS125L without intrinsically safe inputs
Installation in Zone 2
(ATEX ignition protect. class 'n')
II 3 G Ex nA nC IIB T4 Gc
*)
*) Manufacturer's certificate, conditions of use on page 3
Wide-range power supply
Supply voltage
20..125VDC and 20..253VAC (47..63Hz), max.1.5W
ATEX limits for
intrinsically safe inputs:
U
o
= 8.7V; I
o
= 19mA; P
o
= 42mW
L
i
= 20µH; C
i
=10nF
Gr. IIB/IIIC
L
o
100µH
1mH
100mH
C
o
12.9µF
7.3µF
2.8µ
Gr. IIC
L
o
100µH
1mH
100mH
C
o
2.2µF
1.2µF
0.4µF
24V power supply
Supply voltage
24V DC +/-15%, max. 1.5W
ATEX limits for
intrinsically safe inputs:
U
o
= 8.7V; I
o
= 17mA; P
o
= 37mW
L
i
= 20µH; C
i
=10nF
Gr. IIB/IIIC
L
o
100µH
1mH
100mH
C
o
13.9µF
7.3µF
2.9µF
Gr. IIC
L
o
100µH
1mH
100mH
C
o
2.2µF
1.3µF
0.4µF
Additional data for all device types
Rated voltage
(non Ex-devices)
253V AC (acc. to EN60664-1; pollution degree 2,
overvoltage category II)
Rated voltage
Um (according to ATEX)
253V AC / 125V DC (acc. to EN6079-11)
Test voltage
3kV AC between
supply/input/relay switches voltage
Working temperature
-10..60°C
Storage temperature
-20..80°C
Air humidity
10..90% (no condensation)
EMC
acc. to EN61326-1

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
16
Measuring inputs
(in accordance with EN60947-5-6 Namur)
Open circuit voltage
approx. 8V
Short circuit current
approx. 8mA
Switching points
inactive <= 1.2mA,
active >= 2.1mA, hysteresis > 0.5mA
Error recognition
- Wire break
<0.2mA
- Short circuit
>7mA
Relay outputs
Switching voltage
<250V AC <2A <500VA
<125V DC <0.2A <25W
< 30V DC <2A <60W
Switching frequency
max. 5Hz
-delay
max. 30ms
Casing
Dimensions (WxDxH)
TS125: 12.5 x 114 x 108mm
TS225: 22.5 x 114 x 108mm
Material
PA6.6, light grey
Weight
TS125: 120g
TS225: 140g
Protection type
IP20
Screw terminals
0.2..2.5 mm², AWG 24..14, removable, coded
Push-in terminals (spring-type
terminals)
0.5..1.5 mm², AWG 25..16, double connection
(12A between the connections), removable, coded
Power rail
8A over the entire bus system
(Supply via removable terminals 0.2..2.5 mm², AWG 24..14)

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
17
Functional safety
SIL2 (parameters in accordance with EN61508 and SN29500)
Device type
B
HFT
0
Response time
Standard Mode -> Error Mode
30ms
Error Mode -> Standard Mode
ca. 2s (self reseting)
Wide-range supply
- 1-channel version
SFF 95.9%; DC 84.0%; PFH 1.91E-08 /h;
PFDavg
1 year
2 years
5 years
8.38E-05
1.68E-04
4.19E-04
- 2-channel version
SFF 94.6%; DC 79.3%; PFH 2.88E-08 /h;
PFDavg
1 year
2 years
5 years
1.26E-04
2.53E-04
6.31E-04
24V supply
- 1-channel version
SFF 95.6%; DC 82.6%; PFH 1.85E-08 /h;
PFDavg
1 year
2 years
5 years
8.10E-05
1.62E-04
4.05E-04
- 2-channel version
SFF 94.3%; DC 77.6%; PFH 2.82E-08 /h;
PFDavg
1 year
2 years
5 years
1.23E-04
2.47E-04
6.17E-04
6.1.
Mechanical design / dimensions

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
18
7.
Order code
1. 2. 3. 4.
TS - - -
1. Device version
125L
Housing width 12.5 mm, normally open relay contacts,
Supply voltage 24V DC +/- 15%
125LP
Housing width 12.5 mm, normally open relay contacts,
Supply voltage 24V DC +/-15% with carrier bus rail connection *)
125M
Housing width 12.5 mm, normally open relay contacts,
Wide-range supply 20..125 V DC, 20..250 V AC
225M
Housing width 22.5mm, changeover relay contacts,
Wide-range supply 20..125 V DC, 20..250 V AC
2. Explosion protection
00
No inherently safe inputs
Installation of devices TS125L and TS125LP in Zone 2 permitted,
in accordance with ATEX protection category 'n'
Ex
With installation of the devices outside the Ex area:
Inputs intrinsically safe in accordance with ATEX ignition
protection rating 'ia' for Zones 0 and 20
Devices TS125L and TS125LP
may only be installed in Zone 2
in accordance with ATEX protection category 'ic'
3. Number of channels
1
Single channel
2
Dual channel
F
Single channel with additional error relay or parallel relay
4. Options
00
No options
*) see separate Power-Rail information sheet
8.
Device transport and storage
Gentle and tension-free packaging of the housing must be ensured for transport
(no machine wrapping of the package).
The device must be stored in the environmental conditions specified in the
technical data.

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
19
9.
Returns
The legal regulations for environmental protection and our personnel
require that devices which are sent back which have come into
contact with liquid are handled without risk to people or the
environment.
If you send a device back to us for inspection or repair, we must request that you
strictly observe the following requirements:
On the GHM homepage under 'Downloads/forms' a return shipment form can be
downloaded.
The repair can be performed quickly and without call-back questions if:
1. a filled-in form is provided for each device,
2. the device has been cleaned and packaging which prevents damage to the
device is used, and
3. a safety data sheet for the measuring medium is affixed to the outside of the
package, if the device has come into contact with a critical substance.
10.
Disposal
Separation by material and recycling of device components and
packaging must take place when the device is disposed of. The valid
legal regulations and directives applicable at the time must be observed.
The device may not be disposed of with household waste. If the device should be
disposed of, return it to us with the return shipment form filled in under section 8.
We will then arrange for the proper disposal.
11.
Imprint
GHM Messtechnik GmbH
Standort Martens, Kiebitzhörn 18, 22885 Barsbüttel
Managing Director: Günther Oehler
Registered office:
Schloßstr. 6
,
88453 Erolzheim / Germany
Ulm District Court, Commercial Register Section B
730462
Copyright: GHM Messtechnik GmbH. All rights reserved. Reprints, digital use of
any type, and duplication may only take place with the written authorisation of
GHM Messtechnik GmbH.
DANGER

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
20
12.
EU Declaration of Conformity

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
21

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
22

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
23

GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
info@martens-elektronik.de
V1.09