Assembly Instruction
GfS Door Terminal
Safety on doors
Part No.: 790 000Part No.:

GfS Door Teminal
Part No.: 790 000
2
790000_Ai_GfS-Door_Terminal_1112_GB
The GfS Door Terminal is a compact device to steer up to
2 holding magnets which are mounted on emergency exit
doors. It includes emergency exit switch, flash light, buzz-
er and key switch. The housing is made out of solid stain-
less steel.
In order to make full use of all GfS Door Terminal features
and to assure the safety of the operator it is important to
act according to the following instructions.
Before connecting and operating the device please
read the operating manual carefully.
• The eletric installation must be executed by an
authorized installer
• Before opening the device the external power supply
has to be switched-off
• In case of system failure please disconect the device
and ask an authorized installer to repair it
• Please use the device just according to the following
instruction
This assembly instruction should be handed on to
the operator
INDROTUCTION/SAFETY INSTRUCTION
INSTALLATION
IMPORTANT:
Connect the GfS Door Terminal completely before
applying voltage.
• Mount the GfS Door Terminal on the wall with the
enclosed screws (see hole pattern). You can find the
different measures on page 4)
• Connect all required cables
• Tighten the screws of the emergency exit button
insertion (positioned horizontally)
• Tighten the screws of the cover of the LED-field
(positioned vertically)
• Now, apply the voltage
• Carry out function test
ATTENTION
GfS recommends to checks the functions of the
GfS Door Terminal every 6 months.
Weitergabe oder Vervielfältigung dieser Bedienungsanleitung, Verwer-
tung und Mitteilung ihres Inhalts sind nicht gestattet, soweit nicht
ausdrücklich zugestanden. Zuwiderhandlungen verpflichten zu Schadener-
satz. Alle Rechte für den Fall der Patenterteilung oder Gebrauchsmuster-
Eintragung vorbehalten.
Die Angaben in dieser Bedienungsanleitung können ohne vorherige
Ankündigung geändert werden. Die Zusammenstellung der Informationen
in dieser Bedienungsanleitung erfolgt nach bestem Wissen und Gewis-
sen. GfS – Gesellschaft für Sicherheitstechnik mbH übernimmt keine
Gewährleistung für die Richtigkeit und Vollständigkeit der gemachten An-
gaben. Insbesondere kann GfS – Gesellschaft für Sicherheitstechnik mbH
nicht für Folgeschäden aufgrund fehlerhafter oder unvollständiger Anga-
ben haftbar gemacht werden. Da sich Fehler, bei aller Sorgfalt nie vermei-
den lassen, sind wir für Hinweise jederzeit dankbar.
1200
850
Escape direction

Part No.: 790 000
GfS Door Teminal
3
790000_Ai_GfS-Door_Terminal_1112_GB
TECHNICAL DATA
Power supply
12V-24V DC
Consumption
State of activation 365 mA
(1 holding magnet)
State of alarm 150 mA
Degree of protection
IP 20
Output
1 incident message relay
Max. contact load DC
30V/0,5A
Operating temperature
-20C bis +60C
Dimensions
90 x 240 x 80 mm
Weight
ca. 1,6 kg
• 2x 32 LED (red/green) for displaying the actual status
• integrated buzzer with 100dB/ 1m
• integrated flash light
• emergency exit switch acc. to EN60947-5-1
• integrated key switch
• 2 mm thick, robust stainless steel housing
• integrated control unit
• reusable cover for emergency exit switch made
out of Macrolon
Input
• 12-24V/DC supply
• 1x single remote opening
• 1x permanent remote opening
• 2x holding magnet signals
• 1x door-too-long-open alarm
• 1x intrusion-alarm (or bridge), clamps briged = door
closed
• 2x sabotage alarm
• 2x predefined brightnesses of LED
• 1x fire alarm control system (with bridge normal
operation)
• 1x emergency exit switch with internal fail safe
contacts
• 1x reserve input
Output
• 2x holding magnet (electric escape route strikes)
• 1x RS-485 interface (bi-directional, half duplex) for
integration into building control systems
• 1x external sirène 24V, 0,5A OC
• 1x external flash light 24V, 0,5A OC
• 1x incident message relay (collective message)
30 V, 0,5 A
Conformity
This product complies with the essential requirements of
the R&TTE guideline 1999/5/EG. The certificate of
conformity you may request from your supplier.
Disposal
Dispose an obselet GfS Door Terminal at a a colleting
point for electronic waste or at your supplier. Dispose
the packaging material at a paper collecting point for
paper resp. plastic. You may not dispose an obsolte
device the general garbage.
Warrenty
Within the legal warrenty time we intend to repair all
defect devices, whether the defect is caused by the
material or assembly, or replace them. The warenty
expires after a third-party repair.
Service
In case of a system failure or a defect GfS Door Terminal
please contact the following address:

GfS Door Teminal
Part No.: 790 000
4
790000_Ai_GfS-Door_Terminal_1112_GB
DIMENSION
240
198
10
72
90
42
20
60
80
80
15
50
41.98

Part No.: 790 000
GfS Door Teminal
5
790000_Ai_GfS-Door_Terminal_1112_GB
TERMINAL DIAGRAM
Pos
Abb.
Function
Signal
1
GND
Operating voltage minus
Ground
2
+24V
Operating voltage plus
+24 V
3
FACS
Fire alarm control system
Floating contact or bridge to 4
4
FACS
Fire alarm control system
Floating contact or bridge to 3
5
NO1
Response magnet 1
Ground is switched, holding magnet 1 is energized (Hall Relay NO)
6
NO2
Response magnet 2
Ground is switched, holding magnet 2 is energized (Hall Relay NO).
In case that there is just 1 magnet, 6 and 7 must be bridged!
7
GND
Common GND Magnets
GND-Signal (Hall Relais COM)
8
Magnet-
Magnet- Coil 1 and 2
Negative connection for magnets
9
Magnet +
Magnet+ Coil 1 and 2
Positive connection for magnets
10
GND
Reference for remote opening
Signal ground
11
REM
Remote opening input Switch-on
GND resp. bridge 10 and 11 Opening command
12
GND
Reference contact for door contact
Signal GND
13
DC
Contact
Switch-on GND resp. bridge 12 and 13. Door closed
14
RS-485A
Communication
Data signals
15
RS-485B
Communication
Data signals
16
DST
Communication multi function port
Acc. to the required functions as input or output, also usable for communication
purposes with 1 wire
17
COM
Incident message relay COM
Floating contact 30 V/0,5 A max
18
NC
Incident message relay NC
Floating contact 30 V/0,5 A max
19
NO
Incident message relay
Floating contact 30 V/0,5 A max
20
ext. flash
External flash light
Open collector-output, 30V/ 0,5A max
21
ext. sir.
External siren
Open collector-output, 30V/ 0,5A max
22
GND
Reference for reserve and dim input Signal GND
23
Res1
Reserve input
Free function
24
Dim
Dim input
Switch-on GND resp. bridge 24 with 22. Dim command
1
GND
2
+ 24 V
3
FACS
4
FACS
5
NO 1
6
NO 2
7
GND
8
Mag –
9
Mag +
20
Dim
21
Res 1
22
GND
23
ext. sir.
24
ext. flash
10
GND
11
REM
12
GND
13
DC
14
RS485-A
15
RS485-B
16
DST
17
COM
18
NC
19
NO
12 V – 24 V
+

GfS Door Teminal
Part No.: 790 000
6
790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Alarm secured
LED ring with cross shines red
Incident message relay is activated, emergency exit switch
is illuminated, magnet is activated, door contact closed
(DC connected) as well as magnet 1 and 2.
red
Opening time delay
At the end of the opening time delay (5 sec. preset, adjustable)
the green LEDs blink slowly twice
and the GfS Door Terminal is activated again.
Precondition: Holding magnet and door contact are closed.
When the door is opened during the opening time delay and
no opening contact active, the status changes directly into
“Waiting for door too be closed”
green
Opening command 1
Turn key switch to the right.
LED ring with corners blink green.
Magnet is deactivated, the door may be opened once without
causing an alarm.
green
Opening command 2
Input “Remote” activated.
Opening command remains active as long as the GfS Door Terminal
receives the signal plus opening time delay.
green

Part No.: 790 000
GfS Door Teminal
7
790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Permanent opening
Permanent opening is active as long as Input “Remote” is activated.
Permanent opening with key switch: Turn key switch clockwise for
at least 5 sec., till LEDs expire. Remove key.
LEDs and emergency exit switch illumination are pulsing.
Door may be opened as long and as often as desired.
Magnets are permanently deactivated.
pulse
green
Waiting for door to be closed
The LEDs blink slowly green
at the end of the opening time.
In case that the holding magnet and door contact are not closed the
LEDs blink green for another 15 sec
(till conditions for activation are met).
blinks slowly
green
Door-too-long-open
If the door stays open for more than 15 sec. an alarm
“Door-too-long-open” is triggered.
Every 3 secs the green LEDs change for 200 ms into red,
while the internal and external buzzers are activated.
Deactivation of alarm
Close door (door reed contact, counter plate) or give again an
opening command (opening command 1 and 2 possible)
Intermitting
red/green LEDs
+ buzzer
Emergency exit switch alarm
Push emergency exit switch
Flash-light, buzzer (internal and external) are activated, deactivation
of incident message relay, magnets are seperated and deactivated
by the processor.
LEDs blink quickly green (as after opening command).
Reset of alarm just possible with key switch. Unlatch emergency
exit switch.
blinks green
+ siren
+ flash light

GfS Door Teminal
Part No.: 790 000
8
790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Fire alarm
In case of a central fire alarm clamp 3 and 4 are seperated, the
failure relay is deactivated. Holding magnets are seperated and
deactivated by the processor.
LEDs blink quickly green (like open). The emergency exit
switch illumination blinks in push-pull.
The deactivation of the alarm only with key switch (turn right)
possible.
blinks green
Intrusion, sabotage
In case that one of the two feedback loops of the holding magnets
or door contacts are interrupted, an intrusion alarm is triggered.
LEDs change from red to orange.
The incident message relay is deactivated, the external siren is
activated.
The magnet stays active!
Reset just possible with key switch (turn right).
In case that the PCB is removed (sabotage on the GfS Door
Terminal) he same alarm is triggered.
orange
+ siren

Part No.: 790 000
GfS Door Teminal
9
790000_Ai_GfS-Door_Terminal_1112_GB
PROGRAMMING
Programming
1
Turn key switch to the right (create status open)
2
Hold key switch left at least for 5 sec. till orange ring shines
3
Turn key switch to the left, release
4
Turn briefly key switch to the left. Repeat this in order to enter other programming modes
5
Turn key switch to the right in order to confirm the correct programming mode
6
Turn key switch to the right in order to change the status/ value
7
Turn key switch to the left in order to store the value and finish programming mode
Programming mode
1
Open time delay
2
Silent alarm
3
Accoustic alarm switch-off
orange
orange
orange
1x
1x
1x
Change opening time
Execute programming steps 1-3
Orange LED ring shines. Programming mode: opening time.
Start programming – execute step 5 (turn to the right)
(Confirm programming mode by turning key to the left)
Orange LED ring changes to red
1 green LED means 5 sec. opening time. By turning the key switch
to the right the opening time increases each time by additional 3
sec.
1 turns to the right: 8 sec
2 turns to the right: 11 sec
8 turns to the right: 29 sec
Each turn leads to 1 more LED to shine green (max. 8).
9 turns to the right: 5 sec
When the required opening time delay is set, turn key switch briefly
to the left (step 7 – end programming mode)
The LEDs blink quickly 4 times.
The new values are set. In case of a power break down, the
opening time remains stored.
1 LED green = 5 sec
rot
rot
2 LEDs green = 11 sec
1x
1x
store/ leave programm

GfS Door Teminal
Part No.: 790 000
10
790000_Ai_GfS-Door_Terminal_1112_GB
PROGRAMMING
Silent alarm
Execute programming steps 1-3
Execute step 4 once. (turn to the left)
The LED cross shines orange.
Execute programming step 5 (turn to the right).
Orange cross changes into green
(sirène will be triggered in case of an alarm)
Execute programming step 6 once in order to change to silent
alarm (turn to the right).
The LED cross shines red.
With any further execution of programming step 6 the setting
changes from green/accustic alarm to red/silent alarm.
Execute programming step 7 in order to end the programming.
orange
green
on
red
off
1x
1x
1x
store/leave programm
Automatic accoustic alarm switch-off
Execute programming step 1-3.
Execute step 4 twice (turn to the right).
Two orange half circles shine.
Execute step 5 (turn to the right).
Two half circles shine green.
Execute step 6 once (turn to the right).
LED half circles shine red.
Siren is automatically switched-off after 3 min.
With any further execution of programming step 6 the setting
changes from green/no automatic alarm switch-off to red/automatic
alarm switch-off.
Execute programming step 7 in order to end the programming.
orange
red
3 min
green
permanent
alarm
1x
1x
1x
store/leave programm

Part No.: 790 000
GfS Door Teminal
11
790000_Ai_GfS-Door_Terminal_1112_GB
SPARE PARTS
European Cylinder
Part No.
for insertion into GfS Door Terminal,
incl. 2 keys
901 375
2 replacement keys
901 376
Replacement cover for flash-light
Part No.
for the flash-light of the GfS Door
Terminal, red
799 000
Replacement cover for emergency exit switch
Part No.
for emergency exit switch of the GfS
Door Terminal made out of unbrakeable
Macrolon, transparent
799 001
Pictos
Part No.
for marking the use of the emergency exit switch
Regular print quality,
adhesive
921 390
Pictos
Part No.
for marking the use of the emergency exit switch
fluorescent,
adhesive
921 490

GfS – Gesellschaft für Sicherheitstechnik mbH