3-0252.090 Rev. A 01/16
Signet 0252 Configuration Tool
English
Operating Instructions
Description
Table of Contents
The 0252 Configuration Tool is a USB to Digital (S
3
L) convertor and Microsoft
®
Windows
®
compatible software program used for interfacing with Signet 9900
Transmitters and blind sensors via a computer.
The 0252 tool and software allows:
•
Set application parameters (Engineering units, 4 to 20 mA span, etc.)
•
Save the setting configuration data to a computer file.
•
Upload a previously stored configuration data file into the Signet product.
•
Monitor a sensor's performance and log the data to a file.
•
Reset the product settings to factory default condition.
Certain parameters (such as calibration) cannot be changed because access
to an external sensor is required.
Microsoft, Windows, and Windows Vista are registered trademarks of
Microsoft Corporation in the United States and other countries.
Warranty Statement
................................................................................ 2
Product Registration
............................................................................... 2
Safety Information
................................................................................... 2
Specifications
.......................................................................................... 2
Required Equipment
............................................................................... 3
Install Software
....................................................................................... 3
Run Software
.......................................................................................... 3
Set Software Language
.......................................................................... 3
Sensor Wiring (2250, 2350, 2450, 2750)
................................................
4
2551 Magmeter Wiring
............................................................................ 5
2552 Magmeter Wiring
............................................................................ 5
9900 Wiring
............................................................................................. 6
General Software Operation
................................................................... 6
Sensor Operation
....................................................................................
7
2551 & 2552 Operation
........................................................................8-9
9900 Operation
................................................................................ 10-11
Datalogger Operation
............................................................................ 12
Ordering Information
............................................................................. 12
•
English
•
Deutsch
•
Français
•
Español

Caution / Warning / Danger
Indicates a potential hazard.
Failure to follow all warnings may lead to
equipment damage, injury, or death
Electrostatic Discharge (ESD) /
Electrocution Danger
Alerts user to risk of potential damage to product
by ESD, and/or risk of potential of injury or
death via electrocution.
Note / Technical Notes
Highlights additional information or detailed
procedure.
Refer to your local Georg Fischer Sales office for the
most current warranty statement.
All warranty and non-warranty repairs being returned
must include a fully completed Service Form and
goods must be returned to your local GF Sales office
or distributor.
Product returned without a Service Form may not be
warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP,
chlorine electrodes, calibration solutions; e.g. pH
buffers, turbidity standards or other solutions) are
warranted out of box but not warranted against any
damage, due to process or application failures (e.g.
high temperature, chemical poisoning, dry-out) or
mishandling (e.g. broken glass, damaged membrane,
freezing and/or extreme temperatures).
Thank you for purchasing the Signet line of
Georg Fischer measurement products.
If you would like to register your product(s), you can
now register online in one of the following ways:
• Visit our website
www.gfsignet.com.
Under
Service and Support
click on
Product Registration Form
• If this is a pdf manual (digital copy),
Warranty Information
Product Registration
Safety Information
Specifications
Compatibility
Signet Products
...................
2250, 2350, 2450, 2750, 2551,
2552, and 9900 Transmitter
Operating System
................
Windows XP, Windows Vista,
Windows 7 (32 and 64 bit),
Windows 8, 8.1 (32 and 64 bit)
Windows 10 (32 and 64 bit)
General
Enclosure
.............................
ABS
Red Indicator
.......................
POWER ON
Blue Indicator
.......................
DATA COMMUNICATION
Input connections
................
3-terminal connectors,
max. 14 AWG
Electrical
Communication rate
............
Maximum 19.2 kbs
Input power
..........................
Supplied by USB interface
Output power
.......................
5 VDC ± 5%
Power consumption
.............
5 V @ 15 mA
Maximum current source
..... 50 mA
Maximum cable
...................
300 m (1000 ft)
Environmental
Storage Temperature
...........
-20 °C to 100 °C
(-4 °F to 212 °F)
Relative Humidity
.................
0 to 90% non-condensing
Operating Temperature
........
-15 °C to 55 °C
(5 °F to 131 °F) (module only)
Shipping Weight
................
0.22 kg (0.48 lb)
Standards and Approvals
CE, RoHS Compliant
China RoHS
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and,
(2) This device must accept any interference received,
including interference that may cause undesired
operation.
2
Signet 0252 Configuration Tool

Required Equipment
Install Software
Run Software
Set Software Language
Equipment:
• 3-0252 Tool: one USB to Digital (S
3
L) converter
• 1 m (3 ft) 9900 programming cable with terminal plug
• USB to USB extension cable
• Software installation CD
• PC / laptop with free USB port
• 24 VDC Isolated power source (Required to program
4 to 20 mA sensors, 2551 and 2552 only)
Application specific information:
2250, 2350, 2450, 2750:
• Engineering Units, 4 to 20 mA span
2551 & 2552:
• Engineering Units, K-Factor, Pipe ID, Timebase,
Averaging, Sensitivity, Noise Rejection,
Low Flow Cut-Off, 4 to 20 mA span
9900:
• Instrument Type (Flow, pH, ORP, Cond/Resist,
Pressure, Level, Temperature, 4 to 20 mA, Salinity)
• Sensor type specific settings
1. Insert the CD ROM into the computer's CD/DVD drive.
• If Autorun is enabled on the computer, the
installation wizard will start.
• If Autorun is disabled on the computer, use Windows
Explorer to browse the contents of the CD and
double-click on the setup.exe file.
2. Follow the prompts in the installation wizard to
complete installing the software.
1.
On the PC, click
Start
and select
Program Files
.
2.
Click on the
Georg Fischer Signet LLC
folder.
3.
Click on the
0252
folder.
4. Click on the
0252 Tool icon
.
5.
The 0252 software screen shown here should be
on the computer display.
NOTE:
Each time the 0252 software is launched, it
automatically checks for and applies updates.
Software version
is displayed by clicking on the
Help
menu, then clicking on
About
.
The 0252 software saves your language preferences. Each time the software is launched, the previous language
selection will be used. English is the default language.
1.
Click on the
File
menu in the upper left.
2.
Click on
Preferences
.
3.
A separate Preferences dialog box should be on the computer display.
4. Select the desired language from the drop-down menu.
Supported languages: English, French, German, Spanish, Italian, Portuguese, Chinese
5.
Click
Save
to set language preference.
Caution
Managed systems and network systems may
have security measures enabled that block the
installation of this program.
See the network administrator or IT (Information
Technology) staff if the software cannot be installed.
3
Signet 0252 Configuration Tool

Sensor Wiring
Signet 2250 Hydrostatic Level Sensor
Signet 2350 Temperature Sensor
Signet 2450 Pressure Sensor
Signet 2750 Submersible pH Sensor
Signet 2750 In-Line pH/ORP Sensor
White
Red
Black
+
S
-
USB
GND
Data
+5V out
USB
GND
Data
+5V out
Windows PC
Windows PC
Black
Red
White
1
2
3
4
White
Red
Black
+
S
-
USB
GND
Data
+5V out
USB
GND
Data
+5V out
Windows PC
Windows PC
Black
Red
White
1
2
3
4
White
Red
Black
+
S
-
USB
GND
Data
+5V out
USB
GND
Data
+5V out
Windows PC
Windows PC
Black
Red
White
1
2
3
4
White
Red
Black
+
S
-
USB
GND
Data
+5V out
USB
GND
Data
+5V out
Windows PC
Windows PC
Black
Red
White
1
2
3
4
White
Red
Black
+
S
-
USB
GND
Data
+5V out
USB
GND
Data
+5V out
Windows PC
Windows PC
Black
Red
White
1
2
3
4
4
Signet 0252 Confi guration Tool

2551 Magmeter Wiring
2552 Magmeter Wiring
JP2
FREQUENCY OUT
DIGITAL (S
L) OUT
3
Freq/Digital jumper
must be in Digital position
USB
GND
Data
+5V out
Windows PC
USB
GND
Data
+5V out
Windows PC
White
Red
Black
Isolated
24 VDC
+
-
White
Red
Black
1
2
3
4
1
2
3
4
JP2
FREQUENCY OUT
DIGITAL (S
L) OUT
3
Freq/Digital jumper
must be in Digital position
USB
GND
Data
+5V out
Windows PC
USB
GND
Data
+5V out
Windows PC
White
Red
Black
Isolated
24 VDC
+
-
White
Red
Black
1
2
3
4
1
2
3
4
Frequency or Digital (S
3
L) Output
USB
GND
Data
+5V out
Windows PC
Brown
Black
White
Blue
USB
GND
Data
+5V out
Windows PC
Isolated
24 VDC
+
-
*Wire 3
*Wire 2
*Wire 1
*Additional wire required
Brown
Black
White
Blue
White
Blue
Wire Nut
To -VDC
To GND
*Wire 3
*Wire 2
USB
GND
Data
+5V out
Windows PC
Brown
Black
White
Blue
USB
GND
Data
+5V out
Windows PC
Isolated
24 VDC
+
-
*Wire 3
*Wire 2
*Wire 1
*Additional wire required
Brown
Black
White
Blue
White
Blue
Wire Nut
To -VDC
To GND
*Wire 3
*Wire 2
4 to 20 mA Output
Frequency or Digital (S
3
L) Output
4 to 20 mA Output
CAUTION!
Do not connect power directly to the 0252 Confi guration Tool.
Improper power supply wiring can cause damage to the 0252 hardware
and computer. Turn 24 VDC Power OFF when wiring the magmeter.
CAUTION!
Do not connect power directly to the 0252 Confi guration Tool.
Improper power supply wiring can cause damage to the 0252 hardware
and computer. Turn 24 VDC Power OFF when wiring the magmeter.
5
Signet 0252 Confi guration Tool

9900 Wiring
1.
Disconnect power on the 9900.
2.
Unplug the sensor connector from the S
3
L/Frequency input jack on the 9900 and connect the 0252 Tool in its place.
3.
Reconnect power to the 9900.
V+
DATA
GND
SHLD
USB
GND
Data
+5V out
Windows PC
White
Red
Disconnect power on the 9900 prior to proceeding.
If the 9900 is using the Direct Conductivity/Resistivity Module, the module will need to be removed from the 9900.
Refer to the Direct Conductivity/Resistivity Module Instruction Sheet for instructions.
General Software Operation
Read
Loads the data from the connected device (sensor or transmitter) and updates the software’s display.
NOTE
: This will overwrite any changes made in the 0252 software since the last
Write
.
Write
Applies the data entered in the 0252 software to the connected device. Once you have entered the desired
setting changes in the software screens, press
Write
to load your new settings onto the connected device.
Save
Stores the entire 0252 settings confi guration, as currently displayed in the application, to a specifi ed location
on your computer. (You will be asked to select a fi le location and provide a fi le name)
Load
Opens a previously saved settings confi guration fi le. See
Save
function above.
NOTE:
The fi le must be a 0252 settings confi guration fi le.
The software will verify whether the user-selected fi le is the correct type.
Default
Resets all data on all application screens to a factory default condition. A confi rmation dialog box will be
presented with a warning explaining all un-saved confi guration information will be erased.
After resetting the software to a factory default condition, click
Write
to reset the connected device to a
factory default condition.
NOTE:
Performing the above reset to factory default condition will not change the input type on the
9900 Transmitter.
On all screens
Read, Write, Save, Load,
and
Default
buttons can be found in the lower right corner.
6
Signet 0252 Confi guration Tool

Sensor Operation
Application
settings:
2250
2350
2450
2750
1
Engineering units
in., ft, cm, m
˚C or ˚F
psi, kpa, bar
pH or (ORP)
Loop
Output settings:
2
4 mA Set Point
Min
0
-10 ˚C
(14 ˚F)
0
0 pH
(-1000 mV)
Max
-XU:
276.8 in., 23.07 ft,
703.1 cm, 7.03 m
-XL:
1384.0 in, 115.33 ft,
3515.0 cm, 35.15 m
100 ˚C
(212 ˚F)
10, 50, 250 psi
(69, 344.7,
1723.7 kpa)
(0.7, 3.5, 17.2 bar)
14 pH
(2000 mV)
3
20 mA Set Point
Min
0
-10 ˚C
(14 ˚F)
0
0 pH
(-1000 mV)
Max
-XU:
276.8 in., 23.07 ft,
703.1 cm, 7.03 m
-XL:
1384.0 in, 115.33 ft,
3515.0 cm, 35.15 m
100 ˚C
(212 ˚F)
10, 50, 250 psi
(69, 344.7,
1723.7 kpa)
(0.7, 3.5, 17.2 bar)
14 pH
(2000 mV)
Write
or
Save
settings:
4a
or
4b
Click “Write” to copy these settings to the product.
Click “Save” to save these settings to a local computer file for later use.
5
To use a saved file (from 4b):
1. Click “Load”
2. Navigate to the saved file
3. Select “Open”
4. Click “Write”
5. Click “Read” to confirm
7
Signet 0252 Configuration Tool

2551 & 2552 Operation
Application
settings:
Factory Set
2551 & 2552
1
Flow Units
m
m, ft, m
3
, L, ft
3
, US Gal, Imp. Gal, Acre in.
2
Time Base
sec
Sec, Min, Hour, Day
3
Pipe ID (Inside Diameter)
44.0
0 - 5000
4
Pipe ID Units
mm
mm, in.
5
K-Factor Units
Pulses / Liter
Pulses / Liter, Pulses / Gallon
6
K-Factor
65.76670
0.000100 - 999999.1
See Magmeter manual.
Available at
www.gfsignet.com
7
Averaging (in seconds)
14
1
/
10
, ¼, ½, 1, 1½, 3, 7, 14, 25, 50, 100
8
Sensitivity (%)
25
100, 50, 30, 25, 20, 15, 10, 8, 5, 2
9
Noise Rejection (Hz)
60
50 or 60
10
Low Flow Cut Off (% of full scale)
0
0 to 20% Full Scale
Loop
Output settings:
11
4 mA Set Point (Flow Units / Time Base)
0.00000
0.00000 - 999999.00000
12
20 mA Set Point (Flow Units / Time Base)
5.00000
Write
or
Save
settings:
13a
or
13b
Click “Write” to copy these settings to the product.
Click “Save” to save these settings to a local computer file for later use.
14
To use a saved file (from 13b):
1. Click “Load”
2. Navigate to the saved file
3. Select “Open”
4. Click “Write”
5. Click “Read” to confirm
8
Signet 0252 Configuration Tool

2551 & 2552 Operation
Notes:
Averaging
Set the time the Magmeter will use as the averaging period.
Example: With averaging at 14 seconds, each display is an average of the previous
14 seconds input. Use higher averaging times to smooth the display and current output
where the flow in the pipe is erratic.
Sensitivity
Set the percentage of change in the flow rate required to allow the Magmeter to override
AVERAGING and jump to a new flow rate immediately (2551 maximum range is 10 m/s).
See Magmeter manual for an explanation of Averaging and Sensitivity:
www.gfsignet.com
Noise Rejection
Select 50 Hz or 60 Hz according to local AC power specifications.
Low Flow Cut Off
Set the flow rate where all Magmeter outputs will be forced to zero.
When the flow rate drops below this value, the frequency output will be 0 Hz and the
current output will be 4 mA.
1
2
3
4
5
6
7
8
9
10
11 & 12
13
a
13
b
(General Software Operation, pg. 6)
9
Signet 0252 Configuration Tool

9900 Operation
Initiating Communication with the 9900:
1a
Factory Configured 9900 (new or reset):
1. If the display reads "PUSH Enter SELECT SENSOR" the 9900 is ready for communication.
2. Proceed to step 2 below.
1b
Previously configured 9900:
1. Press and hold
ENTER
for 3 seconds. The display will change to the MENU mode.
2. Press ▲ once. The OPTION menu will flash. Press
ENTER
3. The CONTRAST setting will be displayed.
Press ▲ twice (Gen II, III, IV) or press ▲ once (Gen I) to display REMOTE SETUP.
4. Press ► to edit REMOTE SETUP. If required, enter the security code.
5. Press ▲ to change the flashing NO to YES. Press
ENTER
to confirm change.
6. REMOTE SETUP should be flashing, indicating the 9900 is ready for communication with the 0252 Tool.
Set Instrument Type:
2
Select sensor type to be wired to the 9900 from the
drop-down menu at the top of the screen.
Flow, pH, ORP, Conductivity, Pressure, Level,
Temperature, 4 to 20 mA Input, Salinity
Application
settings:
3
Select the Input, Calibration, Loop, Relay, or Option tabs to choose the desired menu for the selected sensor.
4
Refer to the 9900 manual for details pertaining to specific settings for each sensor type and menu item.
Available at
www.gfsignet.com
. Click Products > Multi-Parameter Instruments > 9900 Transmitter
Write
or
Save
settings:
5a
or
5b
Click “Write” to copy these settings to the product.
Click “Save” to save these settings to a local computer file for later use.
6
To use a saved file (from 5b):
1. Click “Load”
2. Navigate to the saved file
3. Select “Open”
4. Click “Write”
5. Click “Read” to confirm
When configuration is complete:
7
Disconnect power from the 9900.
8
Disconnect the 0252 Tool from the 9900.
9
Reconnect the sensor or reinstall the Direct Conductivity/Resistivity Module.
10
Reconnect Power to the 9900.
To configure an additional 9900 Transmitter with the same settings:
11
Click "Save" to save these settings to a local computer file.
12
Wire another 9900 as shown on page 7.
13
Initiate communication with the 9900 via step 1a or 1b above.
14
Load the saved settings via step 6 above.
10
Signet 0252 Configuration Tool

9900 Operation
2
3
5a
5b
(General Software Operation, pg. 6)
11
Signet 0252 Configuration Tool

Ordering Information
Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057
For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com
3-0252.090 Rev. A 01/16 English
© Georg Fischer Signet LLC 2016
Mfr. Part No.
Code
Description
3-0252
159 001 808
0252 Configuration Tool
Replacement Parts
6682-3004
159 001 725
Replacement 9900 Terminal Block Plug
The 0252 can serve as a field data logger to download data directly into a *.csv (Comma Separated Value) file.
NOTE:
The 0252 does NOT have internal memory to store data.
It must be connected to a computer to use the datalog function.
1.
Select the sensor type and click on
Read
.
2.
Click the
Monitor
tab to open the datalog setup window.
3.
Enter the Logging Interval. This value represents the time between log records.
The minimum interval is 1 second, and the maximum interval is 86400 seconds (24 hours).
Example: If the Log Interval is set to 60 seconds, the 0252 will record the temperature once every minute.
4. The 0252 saves data files in *.csv format. The maximum number of records allowed for this type of file is
65535 records.
If the logging interval is 60 seconds = 1092 hours of continuous recorded data.
5.
Click
Log
and enter the file name for the 0252 to store the recorded data and click Save.
6.
Click
Log File
check box to enable logging. If you do not wish to save the data, skip to step 7.
7. Click
Graph
to start monitoring the sensor.
Datalogger Operation
1
2
3
5
7