G&F Manufacturing R-410A Service Manual

Made by: G&F Manufacturing
Type: Service Manual
Category: Heat Pump
Pages: 17
Size: 1.07 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

G&F Manufacturing 

Service Manual 

Version 2.0 

April 2010 

 

Any tech working on these units must read this manual. Any 

questions, please call service department from the job site.  

954-318-6900 

 


background image

Topics  

 

 

 

 

 

Page 

 
• 

Introduction to 410a

 

 

 

 

• Sequence of operation

 

 

 

 

• Control Board Operation

   

 

 

• Control Board Service Menu

 

 

 

 
• Service menu options

 

 

 

 

Language Select 

 

 

 

Remote T-Stat  

 

 

 

Pool Heat/Cool 

 

 

 

Pool- Cool 

 

 

 

 

Solar Control   

 

 

 

Time Delay 

 

 

 

 

Spa Timer 

 

 

 

 

Even Heat 

 

 

 

 

Temperature Scale 

 

 

 

Defrost Mode   

 

 

 

Evap Temp Calibration 

 

 

Water Temperature Calibration 

 

Load Defaults  

 

 

 

 

Board Diagnostic

 

 

 

 

 

No Flow 

 

 

 

 

Defrost  

 

 

 

 

Low Refrigerant Pressure 

 

 

Water Flow Lockout   

 

 

Evaporator Sensor Malfunction 

 

Water Sensor Malfunction 

 

 

 

Components of Service 

 

 

 

Charge  

 

 

 

 

Thermal Expansion Valve 

 

 

Compressor   

 

 

 

Fan 

 

 

 

 

 

 

Remove and Replace Parts

   

 

 

R&R Compressor 

 

 

 

R&R TXV and/or Filter Dryer 

 

10 

R&R Heat Exchanger  

 

 

10 

R&R Water Temperature Sensor 

 

10 

R&R Defrost/ Evaporator Sensor  

 

12 

R&R Water Pressure Switch   

 

12 

R&R Hi/ Low Pressure Switch 

 

12 

R&R Control Board   

 

 

12 

 
Installation of Heat Pump 

 

 

 

13 

Direction Placement 

 

 

 

 

13 

Air Flow Direction 

 

 

 

 

13 

Electrical Diagram

   

 

 

 

14 

Table of Content 

 


background image

  

WARNING:   

 

Only certified service providers to work on unit. Anyone else will void warranty. 

Only put your refrigerant gauges on these units as a last resort.

  

It is a package unit that has had many steps taken at the factory to assure the system is 

contaminant free. Almost all problems can be diagnosed without the use of gauges. 

  

WARNING:   

 

Turn off all electrical power to unit before servicing

 

Check to see that the unit is bonded and that the electric conduit is connected to the electrical      

box inside the unit. 

 

     

ATTENTION

:

  

 

If you find that it is mis-plumbed, un-bonded, etc. contact the warranty department and let 

them handle it. 

Do not bad mouth an installation!

 

Attention, Warning, and Caution boxes have been place through out this 

manual to help point out important information to look out for. 

   

Attention

- Points out important information to be aware of 

  

Warning

- Indicates an action that might void warranty

 

 

Caution

- Alerts service or user regarding safety issues. 

Page 3 

Introduction 

This manual was put together to introduce you to G&F Manufacturing’s 

new R-410A Swimming Pool Heat Pump. Please read the manual before 

you begin to service unit. If you have any questions, we have a 

dedicated service department to help you. 

 


background image

Sequence of Operation 

 
In  order  to  properly  diagnose  a  problem  you  must  understand  the  sequence  of  operation. 
When  the  pool  pump  comes  on  and  the  water  flows  through  the  heater,  the  water  pressure 
closes  the  normally  open  pressure  switch.  When  the  switch  closes,  the  control  board  then 
checks  the  thermostat  to  see  if  the  pool  water  temp  is  below  the  board  set  point.  If  it  is,  it 
checks  the  normally  closed  high  and  low  pressure  switches.  If  both  are  closed  it  will  then 
send 24v to the compressor/ fan contactor and the unit will start to heat or cool, depending on 
unit and mode.  

Note: There is a 5-minute delay on make timer built into the control board so it will 

have a delay before starting.

 

Control Board Operation 

 

The control board has an “LCD” display and was kept as simple as possible for ease of 

customer use, to minimize nuisance-programming calls, and to be able to handle most 

scenarios found in the field. 

 

The board will display which mode it is in (Pool Heat, Spa Heat). Simply raise or lower temp 

by pushing the Up or Down arrows. To switch modes simply push the “Mode” button to 

toggle from pool to spa. For Pool Cool, there will be a Heat / Cool setting in the service 

menu. We also added Auto Feature so you may set temp at max temp and min temp, and 

board will automatically heat or cool the pool/spa. The board also has the capability to 

control your solar system. 

Control Board Hidden Menu 

 
All options and calibrations are in a hidden menu. To access the hidden menu press and hold 
both up and down arrows simultaneously until first option appears on display. The board will 
also rest to Pool/Spa heat screen after 20 seconds of no activity. 

Control Board Options 

Use “Mode” Button To Toggle Through Options 

1

st

 Option: Language Select (English) 

(Options are: English, Spanish, French, Portuguese, German) Use arrows to toggle to 
selection, English is set as default. 

 

Page 4 

 


background image

 

     

ATTENTION

:

  

 

You will find the Pool/Spa remote is no longer necessary; the board is programmed to 

automatically recognize the switch and self-program. 

 

2

nd

 Option: Remote T- Stat (Disable)  

This option is used for external controller systems with its own thermostat such as an 
Aqua logic

!

 or Aqua link

!

. Default is disabled. To enable, push Up or Down arrows 

until display says “Enable.” 

3

rd

 Option:  Pool Heat/Cool (Disable)

 

Once this is enabled a Heat/ Cool setting will come up on display. The board will 
recognize when the temp of the pool has raise or dropped by 1˚ and will heat or cool 
the pool until it reaches set point again.  

(This option is only for Heat/Cool units.)

 

 4

th

 Option: Pool – Cool (Disable) 

  

Once this option is enabled, it will give you a pool cool mode on display, use “Mode” 
buttonto toggle (

This option is only for Heat/Cool units.)

 

 5

th

 Option: Solar Control (Disable) 

 

This option allows your pool heater (with additional wiring) to monitor the pool solar 
system’s performance and will automatically control the temperature.

  

 6

th

 Option: Time Delay  (5) 

Default is 5 minutes. You may temporarily set to 0 for service purposes, unit will reset 
to 5 Mins after 10 Mins have passed. 

7

th

 Option: Spa Timer (Continuous) 

This  option  is  for  rental  properties  or  homeowners  who  do  not  want  the  spa  left  on 
indefinitely.  Options  are  “Continuous”,  “Off”,  or  “Up  to  20  hours”  in  15-minute 
increments.  

 

CAUTION:

 

 

“Off” will not allow spa to run.

 

Page 5 

 


background image

8

th

 Option: Even Heat (Disabled) 

 

Will periodically turn pool pump on according to delay setting. Options are: Off, 0 Hr 
(for testing), 1 Hr, 2 Hr, 3 Hr, 4 Hr, Default is off 

9

th

 Option: Temperature scale (F) 

Sets display for Centigrade or Fahrenheit. Use arrows to toggle. 

10

th

 Option: Defrost Mode (Air Defrost) 

Options are Air Defrost and Reverse Cycle. This option is set at the factory. 

 

11

th

 Option: Evaporator Temperature Calibration 

For  calibrating  the  defrost  sensor  located  on  the  suction  line.  If  this  calibration  is 
changed it will show by how much in plus or minus at bottom of display. 

12

th

 Option:

 

Water Temperature Calibration 

This option is for calibrating the water temperature sensor and will show the amount of 
calibration in plus or minus at the bottom of display.  

13

th

 Option:

 

Load Defaults  

In this mode you can reload all defaults by pressing the up arrow once.

 

Board Diagnostics 

The control board will alert you to most problems. 

DISPLAY MESSAGES 

No Flow  

Means  the  water  pressure  switch  is  not  closed.  Check  water  flow  to  heater.  Make  sure  any 
water bypass valves are not redirecting water around heater, filter is clean, pump is on, and 
water level in pool is up in the middle of the pool tile, this prevents skimmer from sucking air 

Defrosting  

Means the suction line has dropped to 28 degrees. It will shut the unit down until it reaches 
40 degrees and the system will run again. 

Page 6 

 


background image

Low Refrigerant Pressure 

Low pressure cut out is 37 pounds cut in is 80 pounds. Unless the defrost sensor is way out of 
calibration, you should never see this code because of low ambient temperatures. You should 
only see this code if there is a refrigerant leak. Find and repair the leak. 

Water Flow Lockout 

 High  Refrigerant  pressure  is  540  cut  in  is  360.  This  error  code  is  almost  always  a  lack  of 
water flow, so check everything under “No Flow” before putting on gauges or condemning 
High Pressure switch. 

Evaporator Sensor Malfunction 

 This is a 10k sensor. If it is open or outside its range you’ll get this error. Check connections 
before replacing. 

Water Sensor Malfunction 

 This  is  also  a  10k  sensor.  If  it  is  open  or  outside  of  its  range  you’ll  get  this  error.  Check 
connections before replacing. 

 

     

ATTENTION

:

  

 

 This is a standard refrigeration system and most diagnostics are the same as air conditioners. 

However, you must keep in mind that the Heat Exchanger is the condenser and the large air 

coil around unit is the evaporator. The system consists of a compressor, water-cooled 

condenser, TXV, and air heated evaporator. 

 

 

     

ATTENTION

:

  

 

Diagnosing the refrigeration system is something all A/C technicians should know. However, 

there are a few points we would like to point out.

 

Page 7 

 


background image

Charge 

The system holds 4 pounds for Turbotec R-410A unit, because the sub cooling & super heat 
vary  greatly  with  air  and  water  temperature.  For  field  charging  we  use  a  condensing 
temperature of 24 degrees. After power is on and water has been running through unit for at 
least  5  minutes  your  high  side  temperature  should  be  24  degrees  above  water  temperature. 
Read on control board. Unless the ambient temperature is less than 62 degrees, we expect a 
superheat of at least 15 degrees. You may read the suction line temperature by pushing and 
holding  the  “Up”  arrow  on  control  board.  After  about  15  seconds,  the  board  will  display 
suction  line  temperature,  the  board  will  read  Evap  and  a  temp.  Please  wait  for  at  least  10 
minutes run time before checking superheat. 

 

     

ATTENTION:

  

 

Check temperature on both sides of filter. If more than 2 degrees different  

the filter is clogged. 

 

TXV (Thermal Expansion Valve) 

All  units  are  manufactured  with  adjustable  TXV’s.  If  you  suspect  the  TXV  needs  to  be 
adjusted, please call 954-318-6900 from the jobsite and technical support will walk through it 
with you. 

Compressor 

Broken valves, shafts, (not pumping) and shorted to ground are obvious problems. However, 
no  starts  are  commonly  misdiagnosed.  Check  the  capacitor  for  correct  MFD’s.  Check 
connections, voltage and open windings. If open windings, check to see if compressor is hot. 
If so, let it cool down, or run cool water over it before condemning. Check Ohm’s: common 
to run and common to start should equal run to start. If everything above is correct, then add 
hard start to capacitor. 

Fan 

Please  check  connections  and  capacitor  before  condemning  fan  motor.  If  you  do  have  to 
change fan motor ALWAYS change capacitor also. 

 

Page 8 

 


background image

Remove and Replace Parts 

 

     

ATTENTION:

  

 

 
Although the components of this system are the product of an engineer, the design of the unit 
was created by a service technician of 35 years. Therefore, wherever possible, the unit was 
put together with 

ease of service in mind

. Time is important to both your company and ours 

so when replacing refrigerant components please start with recovering refrigerant, and then 
move on to disconnecting component. 

R&R Compressor 

Turn power to unit off. Start recovery of refrigerant.  
Remove the 4 screws holding the top on unit.  
Cut wire tie on fan wire bundle outside of the control box.  
Lift top of unit, flip over and stand on end next to unit.  
Bleed run capacitor.  
Remove wires from compressor (Note: colors and positions)  
Unbolt compressor from base.  
Remove TXV bulb from suction line.  
When recovery is done cut out filter.  
Unsolder compressor and move through top.  
Solder in new Filter/ Dryer. Solder in compressor.  
Pressurize system and check for leaks.  
Start evacuation.  
Rebolt compressor to base.  
Rewire compressor and reinstall wire cover.  
Reinstall TXV bulb.  
Put top back on unit and rescreen.  
Change Capacitor once system has reached 500 microns of vacuum then charge system to.  
Turn power back on and check unit operation.  
Reinstall front cover. 

Page 

 


background image

R&R TXV and/ or Filter 

Turn off power. Start refrigerant recovery.  

Remove 4 screws holding top on unit.  

Cut wire tie holding fan wires bundled at side of control box.  

Lift top off, flip over and lay on end next to unit.  

After recovery has finished remove component from system.  

Replace with new filter/ dryer.  
Solder in new component.  
Leak check, start vacuum.  
Replace top on unit.  
After  vacuum  has  reached  500  microns,  charge  system  to  4  lbs  of  R-410A  for  Turbotec 
Titanium unit,  
Start unit and check operation. Replace front cover. 

R&R Heat Exchanger 

Turn off power. Start recovery of refrigerant.  

Cut wire tie holding fan wires bundled next to control box.  

Remove 4 screws holding top on unit.  

Lift top off, flip top over and lay on end next to unit.  

Cut or break female half of unions off back of unit.  

Cut wire ties holding PVC ells to bottom of base.   

When recovery is complete cut refrigerant filter out.  

Unsolder and remove heat exchanger through top of unit.  

Set new heat exchanger in base of unit.  

Solder in heat exchanger.  

Start system on vacuum.  

Rebolt heat exchanger to base.  

Restrap PVC ells to bottom of unit and glue on new female half of unions. Reinstall top.  

After system has reached 500 microns of vacuum, charge system to 4 pounds R-410A.  

Turn power on, check system operation, and reinstall front cover. 

 

     

ATTENTION:

  

 

Always cut the filter out, DO NOT UNBRAZE.

 

Page 10 

 


background image

R&R Fan Motor 

Turn off power. Remove front cover.  

Disconnect fan wires from contactor, capacitor and ground.  

Remove strain relief bushing and holding wires where they penetrate control box.  

Feed wires out of control box.  

Cut wire ties holding wires in a bundle.  

Remove plastic fan motor cap from fan guard.  

Remove 4 screws holding top on unit and remove top.  

Flip top over and lay on ground or on level surface.  

Loosen setscrew and then remove fan blade.  

Lift  one  side  of  top  up  to  a  45  degree  angle  and  remove  4  nuts  holding  fan  motor  to  fan 
guard.  

Lay top back down and remove motor.  

Reverse procedure to install new motor.  

Be  sure  to  reinstall  strain  relief  bushing  where  wires  penetrate  control  box  and  replace  fan 
motor capacitor. 

  

WARNING:   

 

DO NOT Cut old WTS wire and splice in new WTS 

 

R&R Water Temp Sensor 

 
Turn off power. Remove front cover. 
Unscrew water temp sensor (WTS) and take out. Screw in new WTS. 
Take old WTS spade clips off of the back of the board. 
Place new spade clip in same slot. 
Close HP up. 

 

     

ATTENTION:

  

 

The water temp probe is located on the lower water inlet elbow and is unserviceable. 

Therefore when it’s necessary to replace probe, drill a 3/8 hole in upper elbow and install 

new probe there. After it’s installed, wrap it once with cork tape then with closed cell 

insulation, then again with cork tape.

 

Page 11 

 


background image

R&R Defrost Sensor 

Turn off power. Remove front cover.  

Disconnect connectors from T-7 and T-8 on control board.  

Remove strain relief bushing where wires penetrate side of control box and feed sensor wires 
out of control box.  

On the suction line cut the cork tape and peel back exposing TXV bulb and strap.  

Loosen strap and slide old sensor out.  

Reverse procedure to reinstall being sure to reinsulate and reinstall strain relief bushing. 

R&R Water Pressure Switch 

Turn off power. Turn off water. Remove front cover.  
Remove wires from pressure switch.  
Remove 2 screws holding control box back to coil on right side of control box.  
Bend control box enough to get to back of flow switch.  
Cut tubing as close to flow switch as possible.  
Remove 1/2” nut holding flow switch to control box.  
Install new switch and reverse procedure. 

R&R High or Low Pressure Switch 

Turn off power. Remove front cover. 
Cut high-pressure switch wires near switch. 
Unscrew HP switch using back up wrench. 
Use leak lock when reinstalling switch. 
Remove strain relief bushing where wires penetrate control box. 
Feed old HP switch wires out and new HP switch wires in. 
Reinstall strain relief bushing. 
Install spades at HP terminals on control board. Start and check unit operation. 
Reinstall front cover. 

R&R Control Board 

Turn off power. Remove front cover.  
Loosen 4 screws holding control board to cover. 
Remove control board and let hang on wires.  
Push 4 screws through board and install new board.  
Remove wires from old board and install on new board one at a time, being sure to place 
wires from same terminals from old board to new board as you are taking them off.  
Turn power on. Start unit, check operation, and reinstall front cover. 

Page 12 

 


background image

 

Installation 

 

     

ATTENTION

:

  

 

Before installing this heater there are several things to consider for performance, 

serviceability and warranty.

 

Direction of Placement:

 

Access panel should always face out away from wall. If you must face the service panel 

toward the wall, leave a minimum of 24” between the wall and the unit. 

 

     

ATTENTION

:

  

 

You will not have a happy customer if they have to squeeze between the wall and the heater 

to use the controller. 

 

Placement:

 

Airflow is critical to the performance and efficiency of a heater, therefore leave as much 

space around and above heater as possible. Installations under palm trees, inside screened 

porches etc. may help hide unit but will drastically reduce the performance of the unit. You 
will not have a happy customer. The unions were to the side of the unit to keep pipes out of 

the way of the control panel so that they are not stepped on while adjusting controls or 

  

WARNING:   

 

Do not plumb the pipes back around front where pipes will be stepped on,  

or prohibit access to the front panel. 

Make sure unit is bonded and conduit is connected all the way up to the control box. 

 

 

     

ATTENTION

:

  

 

 

For a more detailed installation manual, please visit our website 

Gulfstreamheatpump.com

and the manual will be there for you to download. If no internet access, call service 

department 

954-318-6900

 and we will fax or mail a copy to you. 

Page 13 

 


background image

Page 14 

 


background image

Bill of Materials

 

Page 15 

DRAWING 

NO. 

COMPONENT DESCRIPTION 

PART NO. 

COMPRESSOR PLUG 

1001001 

FAN MOTOR, 2/5HP, 825 RPM 

1001002 

CONTROL 

1001003 

TEMP SENSOR, SUCTION 

1001004 

TEMP SENSOR, WATER 

1001005 

CONTACTOR, 2 POLE, 40A 

1001006 

TRANSFORMER, 40VA 

1001007 

CAPACITOR, 80UF, 370V 

1001028 

CAPACITOR, 7.5UF, 370V 

1001009 

10 

PRESSURE SWITCH, HIGH, 540 

1001054 

11 

PRESSURE SWITCH, LOW, 37 

1001055 

12 

WATER PRESSURE SWITCH 

1001012 

13 

TOP COVER 

3003014 

14 

BASE PAN 

3003013 

15 

FRONT PANEL 

3003015 

16 

TOP CAP 

3003033 

17 

ELECTRICAL BOX 

3003017 

18 

FAN BLADE, 3P24CCW36 

6006001 

19 

FAN GUARD 

6006008 

20 

EVAP GUARD, 32 X 86 

6006009 

21 

2" S-S UNION #200-100 

7007023 

22 

EVAPORATOR, 32 X 84 

8008078 

23 

FILTER/DRIER 

8008052 

24 

TXV 

8008081 

25 

CONDENSER, TI 

8008084 

26 

COMPRESSOR, HLH061T1LP6 

8008098 

 

 


background image

 

10K Sensor Ohms Chart 

OHM 

OHM 

OHM 

OHM 

OHM 

 

 

20 

46225 

40 

26100 

60 

15310 

80 

9297 

100 

5827 

 

 

21 

44879 

41 

25391 

61 

14921 

81 

9076 

101 

5697 

 

 

22 

43577 

42 

24704 

62 

14543 

82 

8861 

102 

5570 

 

 

23 

42318 

43 

24037 

63 

14176 

83 

8651 

103 

5446 

 

 

24 

41099 

44 

23391 

64 

13820 

84 

8447 

104 

5326 

 

 

25 

39919 

45 

22764 

65 

13473 

85 

8249 

105 

5208 

 

 

26 

38777 

46 

22156 

66 

13136 

86 

8056 

106 

5094 

 

 

27 

37671 

47 

21566 

67 

1209 

87 

7867 

107 

4982 

 

 

28 

36601 

48 

20993 

68 

12491 

88 

7684 

108 

4873 

 

 

29 

35565 

49 

20438 

69 

12182 

89 

7506 

109 

4767 

 

 

30 

34561 

50 

19900 

70 

11882 

90 

7333 

110 

4664 

 

 

31 

33590 

51 

19377 

71 

11589 

91 

7164 

111 

4563 

 

 

32 

32648 

52 

18870 

72 

11305 

92 

6999 

112 

4464 

 

 

33 

31737 

53 

18377 

73 

11029 

93 

6839 

113 

4368 

 

 

34 

30853 

54 

17899 

74 

10761 

94 

6683 

114 

4274 

 

 

35 

29998 

55 

17435 

75 

10500 

95 

6530 

115 

4183 

 

 

36 

29169 

56 

16985 

76 

10246 

96 

6382 

116 

4094 

 

 

37 

28365 

57 

16548 

77 

9999 

97 

6238 

117 

4007 

 

 

38 

27587 

58 

16123 

78 

9758 

98 

6097 

118 

3922 

 

 

39 

26832 

59 

15711 

79 

9525 

99 

5960 

119 

3839 

 

 

 

Page 16 

 


background image

 

  

WARNING:   

 

Using any company that is not certified by G&F Manufacturing will cause the 

warranty on the unit to void. 

SERVICE

 

 

All service must be handled by an Authorized Service Center.  Warranty may be void if a non-

authorized service representative does service.  Do not return the heater to your dealer, as they 

do not provide service. Before calling for assistance or service, please check the Troubleshooting 

section of this manual or call your dealer.  This may save you the cost of a service call.  If you still 

need help, follow the instructions below. 

 
 

 

!"#$%&"'&()'*"'+*,(%)"-'*.'&(//%)0'12'(,3''45678'9:;<=5>>'

 

 

When asking for help or service please provide a detailed description of the problem, your heater’s 

complete serial number, the purchase date and dealer purchased from.  This information will help 

us respond properly to your request. 

 

 

 
 

Keep a copy of the sales receipt showing the date of purchase.

 

Proof of purchase will assure you of in-warranty service.

 

 

 
 

MANUFACTURED BY:

 

G & F MANUFACTURING, INC. 

7902 INTERSTATE COURT 

NORTH FORT MYERS, FL 33917 

 

 
 

 

 

Page 17