Level Electrode

NRG 16-50 S

Original Installation Instructions

819013-01

 


background image

2

Contents

Usage for the intended purpose ..............................................................................................................4

Function .................................................................................................................................................4

Safety note .............................................................................................................................................5

Scope of supply ......................................................................................................................................5

Important notes

Page

NRG 16-50 S ..........................................................................................................................................6

Name plate/marking ...............................................................................................................................6

Dimensions NRG 16-50 S  ......................................................................................................................7

Technical data

NRG 16-50 S ..........................................................................................................................................8

NRG 16-50 S, step 1 ...............................................................................................................................9

NRG 16-50 S, step 2 ...............................................................................................................................9

Tools .......................................................................................................................................................9

Examples of installation ........................................................................................................................10

Key .......................................................................................................................................................11

Installation

Electrical connection

NRG 16-50 S with four-pole connector ..................................................................................................12

Connection of level electrode ................................................................................................................13

NRG 16-50 S with four-pole connector ..................................................................................................13

Tools .....................................................................................................................................................13

Wiring diagram .....................................................................................................................................14

Key .......................................................................................................................................................14

 


background image

3

Commissioning, fault indication and remedy

Danger .................................................................................................................................................15

Removing and disposing of electrode ....................................................................................................15

Note .....................................................................................................................................................15

Removing and disposing of electrode

NRG 16-50 S ........................................................................................................................................15

Contents  

– continued –

Page

 


background image

4

Important Notes

Usage for the intended purpose

The level electrode NRG 16-50 S is used in conjunction with level switch NRS 1-50 (de-energizing 

delay: 15 seconds) as water-level limiter for steam boilers and (pressurized) hot-water installations on 

board of seagoing vessels, mobile offshore platforms or river boats.  

Water level limiters switch off the heating when the water level falls below the set minimum level (low 

water). 

Function

When the water level falls below the low level, the level electrode is exposed and a low level alarm is 

triggered in the level switch NRS 1-50. This switchpoint “Low water level (LW)” is determined by the 

length of the electrode tip. 
After the de-energizing delay has elapsed, the two output contacts of the level switch NRS 1-50 will 

open the safety circuit for the heating. The equipment has a factory set default de-energizing delay of 

15 seconds to compensate for the the movements of the ship.
The self-monitoring function ensures that an alarm will also be triggered if the electrode insulation is 

contaminated or has developed a leak or if there is a malfunction in the electrical connection.
The level electrode is installed inside steam boilers, vessels or inlet lines of hot-water systems. The 

protective tube mounted on site (see section 

Examples of Installation

 (pages 10, 11)) ensures correct 

functioning.
If the level electrode is installed in an isolatable level pot outside the boiler, make sure that the 

 connecting lines are rinsed regularly. In addition, the logic unit SRL 6-50 is required to monitor the 

purging times and the purging sequence.
If the connecting lines for steam ≥ 40 mm and water ≥ 100 mm, the installation is considered to be 

internal. In this case the rinsing processes do not have to be monitored.

 


background image

5

Important Notes 

 – continued –

Safety note

Danger

When loosening the level electrode steam or hot water might escape!

This presents the risk of severe scalding all over the body!

It is therefore essential not to dismantle the level electrode unless the boiler pressure is 

 verified to be 0 bar.
The level electrode becomes hot during operation.

Risk of severe burns to hands and arms.

Before carrying out installation and maintenance work make sure that the equipment is 

cold.

Attention

The name plate specifies the technical features of the equipment. Do not commission or 

operate any item of equipment that does not bear its specific name plate.

Water level limiters are safety devices and must only be installed, wired and commissioned by 

 qualified and competent staff.
Retrofitting and maintenance work must only be performed by qualified staff who – through adequate 

training – have achieved a recognised level of competence.

Scope of supply

NRG 16-50 S 

1 Level electrode NRG 16-50 S, PN 40, DN 50 

1 Installation manual

 


background image

6

NRG 16-50 S

Technical data

Service pressure

 

PN 40, 32 bar at 238 °C

Mechanical connection 

Flange

 

PN 40, DN 50, DIN 2527, form B

Materials 

Sheath 1.4301, X5 CrNi18-10  

Flange 1.0460 / A 105 

Screw-in body 1.4571, X6CrNiMoTi17-12-2 

Measuring electrode 1.4571, X6CrNiMoTi17-12-2 

Electrode tip 1.4401, X5CrNiMo17-12-2  

Electrode insulation Gylon

® 

Four-pole connector Polyamid (PA)

Lengths available  

500 mm, 1000 mm, 1500 mm, 2000 mm

Electrical connection 

Four-pole connector, cable gland M 16

Protection 

IP 65 to EN 60529

Max. admissible ambient temperature 

70°C

Weight 

Approx. 4.5 kg (without electrode tip)

Approvals 

see data sheet

Gylon

®

  is a registered trademark of Garlock Sealing Technologies, Palmyra NY, USA

Name plate / marking

Equipment designation

Safety note

Disposal note
Pressure rating, flange type,  

material number

Manufacturer

Pressure/temperature rating

Fig. 1

 


background image

7

Technical data  

– continued –

Dimensions NRG 16-50 S

Fig. 2

NRG 16-50 S for  

marine applications

80

≤ 2000

295

∅  

165

Flange PN 40, DN 50, 
DIN 2527, form B  
bolt circle 

∅ 

125  

(4x 

∅  

18 for M 16)

 


background image

8

Fig. 3

1

2

3

4

Installation

NRG 16-50 S

8

9

9

Fig. 4

5

1

  Measuring electrode

2

 Bore

3

 Spring

4

 

Electrode tip

5

  NRG 16-50 S with four-pole connector

Key

6

  Anti-rotation element 

7

  Thermal insulation (provided on site) d=20 mm 

 

(outside of thermal insulation of steam boiler)

8

  Sealing surface

9

  Flange joint (provided on site)

0

  Connecting pipe socket (provided on site)

0

7

6

 


background image

9

Installation  

– continued –

NRG 16-50 S, step 1

1.  Screw electrode tip 

4

 into measuring electrode 

1

Fig. 3

2.  Carefully determine required measuring length of electrode. 
3.  Mark length of electrode tip 

4

.

4.  Unscrew electrode tip 

4

 from measuring electrode 

1

 and cut tip.

5.  After visual inspection screw electrode tip 

4

 into measuring electrode 

1

. Slide spring 

3

 along 

electrode tip 

so that its end completely enters the small hole 

2

.

NRG 16-50 S, step 2

6.  Check seating surfaces. 

Fig. 4

7.  Put flange joint 

9

 onto connecting pipe socket 

0

.

 Fig. 4

8.  Put level electrode onto connecting pipe socket and fix it with four bolts M 16.
9.  Tighten bolts in diagonally opposite pairs. The tightening torque depends on the flange joint used.

n

  Make sure that the sealing surface of the connecting pipe socket is accurately 

 machined!

n

  Do not bend electrode tip when mounting.

n

  Do not lag electrode body above the hexgonal section.

n

  Observe minimum spacing of 14 mm between measuring electrode / electrode tip and 

protection tube / level pot! 

Fig. 5, Fig. 6

n

  Observe the minimum spacings when installing the electrode!

Attention

Note

n

  For the approval of the boiler standpipe the relevant regulations must be considered.

n

  Refer to pages 10 for typical installation examples.

Tools

n

  Open-end spanner A. F. 13, DIN 3110, ISO 3318

n

 Scriber

n

 Hacksaw

n

  Flat file, medium cut, DIN 7261, form A

 


background image

10

Installation  

– continued –

g

Examples of installation for NRG 16-50 S

Fig. 6 

Level pot if electrode is used  

as external water-level limiter

a

Fig. 5 

Protection tube (provided on site)  

if electrode is used as internal water-level limiter

14

 2000

20

c

d

e

20

 

90°

10

14

 DN 50

b

Centre 

distance

 

DN 20

 

DN 20

DN 20

c

g

i

f

h

 

20

 

20

 


background image

11

Installation  

– continued –

a

  For the approval of the boiler standpipe with connecting flange the relevant regulations must  

 

be considered.

b

  Vent hole               

Provide vent hole as close to the boiler wall as possible! 

c

  Electrode tip 

8 mm

d

 

Protection tube 

 DN 80

e

  Distance between electrode tip and protection tube 

 14 mm

f

  Reducer DIN 2616-2, K-88.9 x 3,.2- 42.4 x 2.6 W

g

 

Low water (LW)

h

  Level pot ≥ DN 80

i

  High water HW

Key

 


background image

12

Fig. 7

q

p

n

m

j

k

l

o

Electrical Connection

NRG 16-50 S with four-pole connector

j

  Screw M 4

k

 Cover

l

  Upper part of the terminal box

m

  Connecting plate

n

  Insulating plate

o

  Contact plate of level electrode

p

  Cable strain relief

q

  Cable gland M 16 (PG 9)

Key

 


background image

13

Connection of level electrode

To connect the level electrode(s) use screened multi-core control cable with a min. conductor size  

0.5 mm

2

, e.g. LiYCY 4 x 0.5 mm

Max. length 100 m with an electrical conductivity of the boiler water > 10 μS/cm at 25 °C.
Wire terminal strip in accordance with the wiring diagram.

 Fig. 8, 9

 

Connect screens to terminals 5 and 13 and to the central earthing point 

(CEP) 

in the control cabinet.

Electrical Connection  

– continued –

  1.  Undo screw 

j

Fig. 7

  2.  Remove upper part 

l

 of the terminal box from the level electrode but leave insulating plate 

n

 on 

contact plate 

o

.

  3.  Remove cover 

k

.

  4.  Press connecting plate 

m

 out of upper part of the terminal box 

l

.

 

The upper part of the terminal box can be turned in steps of 90°.

  5.  Detach cable gland 

q

 and cable clamp 

p

 from upper part of the terminal box 

l

.

  6.  Run cable through cable gland 

q

 and upper part of the terminal box 

l

 and wire terminals of the 

connecting plate 

m

 in accordance with wiring diagram. 

Fig. 8

  7.  Press connecting plate 

into the upper part of the terminal box and align cable.

  8.  Fix cable with cable clamp 

p

 and cable gland 

q

.

  9.  Put cover 

in place and insert screw 

j

.

10.  Put upper part of the terminal box onto the level electrode and fix it with screw 

j

.

NRG 16-50 S with four-pole connector

Tools

n

  Screwdriver size 1

n

  Screwdriver size 2.5, completely insulated according to DIN VDE 0680-1

n

  Open-end spanner A.F. 18 (19) mm

 


background image

14

Electrical Connection  

– continued –

Wiring diagram

Fig. 10 

Electrical connection of level  

 

electrode with four-pole connector

Fig. 9  

Wiring diagram 

 

for equipment with TWO electrodes

r

r

s

s

Fig. 8  

Wiring diagram 

 

for equipment with ONE electrode

r

s

CEP

CEP

CEP

 


background image

15

Key

Stand-by input 1 / 2, 24 V DC, for connecting the logic unit SRL

s

  Level electrode NRG 1...-50S

CEP

 Central earthing point in control cabinet

Commissioning, fault indication and remedy

For additional information on commissiong procedures and troubleshooting refer to the installation 

manual of the level switch NRS 1-50. 

Danger

Removing and disposing of electrode

Removing and disposing of electrode

1.  Undo screw 

j

Fig. 7

2 . Detach upper part of the terminal box 

l

 from the level electrode. Before removing the equipment 

make sure that is is neither hot nor under pressure. 

For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or 

authorized agency in your country.

 

When loosening the level electrode steam or hot water might escape!

This presents the risk of severe scalding all over the body!

It is therefore essential not to dismantle the level electrode unless the boiler pressure is 

verified to be 0 bar.
The level electrode becomes hot during operation.

Risk of severe burns to hands and arms.

Before carrying out installation and maintenance work make sure that the equipment is 

cold.

Electrical Connection  

– continued –

Note

When ordering spare parts or replacement equipment please state the material number 

indicated on the name plate.

 