PDF User Manual

  1. Home
  2. Manuals
  3. EasyIO FG32 User Manual

EasyIO FG32 User Manual

Made by: EasyIO
Type: User Guide
Category: Controller
Pages: 18
Size: 0.88 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

FG 32 DDC – pre release user guide – V1.4

 

 

 

 

 

 

 

 

 

FG32 pre-release user guide

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

 

Document Change Log 

 

01

st

 Nov 2012 

Document created.  

 

14

th

 Nov 2012 

Added new chapter for restoring FG32 back to default apps.  
Added in new chapter for Changing IP address 
Jumpers setting diagram updated on page 8. Watchdog jumpers settings added.  

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

 

Table of Contents 

Introduction ............................................................................................................................................ 4 

Device Info .............................................................................................................................................. 5 

Device Specifications .............................................................................................................................. 5 

Device Dimension ................................................................................................................................... 6 

Input / Output Configurations ................................................................................................................ 7 

Jumper Configurations ............................................................................................................................ 8 

Connecting to FG32 Sedona DDC via Sedona workbench ...................................................................... 9 

Install platform files and kits files ....................................................................................................... 9 

Login Details .......................................................................................................................................... 12 

Troubleshoot ......................................................................................................................................... 13 

Checklist point 1. ............................................................................................................................... 13 

Checklist point 2. ............................................................................................................................... 13 

Changing IP address .............................................................................................................................. 14 

Restoring FG32 back to default apps .................................................................................................... 15 

Technical Support ................................................................................................................................. 18 

 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Introduction 

 

We are getting ready to release our new FG series of Controllers, starting with the EasyIOFG32 DDC 
controller, product reference: EasyIO-FG-GC-32.  
 
It is equipped with two 32-bit Processors, the first in the Automation industry, with an ARM9 200 
MHz Samsung processor, an ARM M3 Cortex for the I/O management and A-D processing, and also 
with a Linux 2.6 OS for premium performance.  Later in 2013 we will be adding Graphics capability to 
serve up html templates that will be stored on the Micro SD card. BACnet and Modbus will also be 
added in 2013. TCOM is available now and is encouraged for premium performance with Niagara. 
 

 

The Build bootloader can now be carried out remotely. No more manual service button 
needed is used.  

 

 

Firmware upgrading now can be done remotely and without any assistant.  

 

 

Firmware upgrading is via ftp client.  

 

 

In this user guide is just a pre-release internal use user guide.  

 
 
 
Note: Information in this document is accurate at the time of documented. Actual information may 
change/defer without notice.  
 
This document in only intended for the beta testing process. 
 
 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Device Info 

 Device Info 

 Model 

EasyIO-FG-32 

 Description 

EasyIO-FG32 Sedona series: 32 I/O Controller 

 Name 

FG32 DDC 

 

Device Specifications 

Mechanical 

 Dimensions 

233mm x 124mm x 44mm (approx) 

 Material 

UL Approved Plastic 

 Weight 

700g 

  

 Electrical 

 Power Supply 

24V AC +/- 5% or 24V DC +20%/-15% 

 Consumption 

TBC 

 Operating Temperature  32 to 150 Deg-F (0 to 65 Deg-C) 

 Storage Temperature 

-4 to 150 Deg-F (-20 to 65 Deg-C) 

 Operating Humidity 

10% to 95% relative humidity non-condensing 

  

 

Communication (Details of EIA-485 will TBC) 

 Physical Interface 1 
(Port 1) 

EIA-485 (BUS A,B) Two-wire, Half Duplex 

Modbus Baud Rate 

Speed:(9.6K, 19.2k, 38.4K, 57.6K, 115.2K bit/s), Data Bit:(8 bits), 
Parity:(None, Even, Odd) 

Bacnet Baud Rate 

Speed:(9.6K, 19.2k, 38.4K, 76.8K), Data Bit:(8 bits), Parity:(None) 

 Physical Interface 2 
(Port 2) 

EIA-485 (BUS A,B) Two-wire, Half Duplex 

Modbus Baud Rate 

Speed:(9.6K, 19.2k, 38.4K, 57.6K, 115.2K bit/s), Data Bit:(8 bits), 
Parity:(None, Even, Odd) 

 Bacnet Baud Rate 

Speed:(9.6K, 19.2k, 38.4K, 76.8K), Data Bit:(8 bits), Parity:(None) 

Ethernet Support 

IP, TCP, UDP, ICMP, HTTP,FTP 

Application Support 

Sedona (at the moment)and TCOM driver

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Device Dimension 

 

Below are the dimensions for the EasyIO FG32.  
 

 

Top View. Width including connectors are approx 124mm 

 
 

 

Side view and back view.  

Improve DIN rail mounting for easy dismantling. 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Input / Output Configurations 

Input/Output Configuration 

 1 - Universal Input 

16 Channels 

         Voltage 

0 - 10V DC (+/-0.005V)  

         Current 

0-20mA DC 

         Resistance 

0 - 30K (+/-10 Ohm), 0 - 10K (+/-5 Ohm), 0 - 1.5K (+/-1 Ohm) 

         Thermistor 

10K, 10K Shunt, 1K Balco, 1K Platinum : All (+/-0.01 Deg-C) 

UI as Digital Input 

Voltage Free Contact 

 2 - Digital Output 

8 Channels 

         Type 

Relay Contacts, SPST NO, 48VA at 24VAC, Pilot Duty 

 3 - Universal Output 

8 Channels (12 bits resolution) 

         Type 

Current: 0 - 20mA, 4 - 20mA (up to 800 Ohm load) 
Voltage: 0 - 10V 
Open Collector Output, Max Current Rating: 0.3A Max 

 

 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Jumper Configurations 

 

 

 

 

 

 

 

 

 

:  Current  

 

 

 

 

 

    : On , EOL terminated 

 
 

 

 

 

 

 

 

 

:  Voltage 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    : Off , EOL Not terminated 

 

 

 

 

 

 

 

 

:  Open Collector  

 

 

 

 

 

 

 

 

 

 

 

 

                                                                                                 

 = Resistance 

Watchdog  enable   = 

=  Voltage 

Watchdog  disable  = 

 

 
=  Current 

 

 

Universal Input 

Jumper Settings 

Universal 

Output Jumper 

EIA 485 Jumper 

Settings 

Watchdog  

Jumpers Settings 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

 

Connecting to FG32 Sedona DDC via Sedona workbench 

 

In order to connect to the new EasyIO FG32 DDC, some files are needed. EasyIO FG32 has a different 
sedona platform, files and kits. These kits are hardware dependent. 
 
Follow the below instructions before connecting to the controller via Sedona Workbench.  
 

Install platform files and kits files 

 

Step  1 

Get the required files from easyIO technical support at 

support@easyio.com

 

 

Step 2 

Close the workbench.  
Open sedona folder in the Niagara installation directory;  
 

Niagara Version 

Sedona directory 

Niagara Ax 3.5.xx 

Niagara\niagara 3.5.xx\sedona\ 

Niagara Ax 3.6.xx 

Niagara\niagara 3.6.xx\sedonaBundles\sedona 
1.1.xx\sedona\ 

Niagara Ax 3.7.xx 

Niagara\niagara 3.7.xx\sedona\ 

 

Step 3 

Copy and merge the 2 folders that obtain from easyIO technical support.  

The 2 folders are :

platform

 and 

kits 

For Niagara Ax 3.5 User go to 

step 4. 

For Niagara Ax 3.6 User go to 

step 5. 

For Niagara Ax 3.7User go to 

step 6. 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

10 

 

 

Step 4 

For Niagara Ax 3.5.xx user. Drag and drop it in to the sedona root folder. Hit “Yes” on the pop up to 
merge the files.  

 

 

 

 

 

 

 

 

 

 

 

 

 

Step 5 

For Niagara Ax 3.6.xx user. Drag and drop it in to the sedona root folder. Hit “Yes” on the pop up to 
merge the files.  

 

 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

11 

 

Step 6 

For Niagara Ax 3.7.xx user. Drag and drop it in to the sedona root folder. Hit “Yes” on the pop up to 
merge the files.  

 

 

Step 7 

Re-open workbench and connect to EasyIO FG32 controller.  
 
 
 
 
 
 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

12 

 

Login Details 

 
EasyIO FG32 details are as below.  
 
Sedona Login 
Username  

: admin 

Password  

: <no password> 

 
Default IP address  

: 192.168.10.11 

Default Subnet   

: 255.255.255.0 

Default Gateway  

: 0.0.0.0 

 

Note : 
In order to login, the host PC (laptop) has to be in the same subnet.  
Example:  
IP address :  192.168.10.123  
Subnet       :  255.255.255.0 

 
 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

13 

 

Troubleshoot 

 

In order to make sure all the files are copied correctly into the directory, follow below checklist to 

verify all the files are in place.  

Checklist point 1. 

 

Platform file is in the platform folder.  

 

 
 

Checklist point 2. 

 
2 additional kits are in the kits folder. 

easyioFG

 and 

easyioFGDDC.  

 

 

 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

14 

 

Changing IP address  

 
By default the controller IP address is at 192.168.10.11.  
Changing the IP address can only be done via sedona workbench at the moment.  
 

Step 1 

Login to the FG32 via sedona workbench. Locate the object 

“IP” 

under the sedona service folder.  

 

 

 

Step 2 

Go into the property sheet of the “IP” object.  
 

      
 
 

 
Current IP address that is assign to 
the controller 

 

 

 

New IP address field. Keyin the 
requires IP address in these fields.  
Make sure the IP address and 
subnet is correct before saving.  

 

Step 3 

Save the sedona apps and cycle power.  
 

 

Step 4 

Reconnect to the sedona via Sedona workbench with the new assigned IP address. 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

15 

 

Restoring FG32 back to default apps 

 
At the moment, there are 2 ways to restore the sedona apps for FG32 controller.  
 
The first way is where you could still gain access to the controller via sedona workbench. By 
manually selecting all the objects and delete it. The “

SAVE

” action is needed.  

 
Then a reboot or restart of the VM will erase all the objects in the sedona apps.  
 
The second way of restoring the FG32 back to default apps is via ftp client software. This way can be 
use as well if the FG32 sedona VM is not connectable and the controller keep rebooting due to some 
incompatible sedona apps loaded.  When this happen, the watchdog will kick in and will not allow 
the sedona VM to boot at all, hence a rebooting cycle will occur.  
 

Note :

  

A easyIO 30P sedona apps CANNOT be loaded into the easyio FG32 as the sedona apps from a 30P 
backup is hardware dependent. Doing so will corrupt the FG32 sedona VM and the controller will 
keep rebooting the sedona VM, hence the controller is not accessible via Sedona Workbench.  

 

If the rebooting cycle occurs, the status LED will blinks for fast for a few times then light up steady for 
approx 10 seconds.

  

 

 

If the above note happen, follow the below steps to regain sedona connection. Below steps can be 
use for restoring the FG32 to default apps as well.  
 
Email to 

support@easyio.com

 to request for the FG32 default apps.  

 
 

 

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

16 

 

Step 1 

Refer to page 8, jumpers settings locate the “

watchdog jumpers settings”. 

Disable the watchdog by 

shorting pin 2 and 3.  
If the watchdog is disable, the device should be able to run the ICMP command (Ping).  
 
Skip step 1 and step 2 if the controller is not in rebooting cycle mode.  Refer to above note for 
rebooting cycle mode.  
 

Step 2 

Power off the controller and let it discharge for about 5 seconds and power it up again. The 
rebooting cycle will end. The controller will boot up and the status LED will blink approx 2 blinks per 
second with a short pause.  
 

Step 3 

Open any ftp client software, in this case “filezilla”. 
 
Login details to FG32 build in FTP server as below;  
 
IP address : 

this is the last IP address that the FG32 had. Default is at 192.168.10.11

 

Username :

 root 

Password : 

1234

 

 
Port : 

21

 

 

 

 
 
 
Step 4 

Unzipped the backup file email by easyIO tech support.  
 

 

 

Step 5 

Transfer the app.sab and kit.scode in to the FG32 “mnt ” folder. MNT folder is at the root of the 
FG32 directory.  
 
Overwrite the existing files in the FG32.  

 


background image

FG 32 DDC – pre release user guide – V1.4

 

17 

 

 

 

 

Step 6 

After transfer is successful, cycle power of the controller and re-enable the watchdog jumpers(refer 
page 8).  
 
 

Step 7 

Connect to the FG32 via sedona workbench. If above steps done correctly, sedona workbench 
connection will be good.  

 

 


background image

FG 32 DDC – pre release user guide – V1.4

 

18 

 

Technical Support 

 

For technical support issues please contact technical support person as below ; 

Email :

support@easyio.com