TABLE  OF  CONTENTS 

 

1. 

SPECIFICATION 

PARTS 

IDENTIFICATION 

.............................................................................2 

 

2. 

OPERATION 

FUNCTION 

OF 

PARTS

....................................................................................3,  4 

A.  Cooling  Operation 

B.  Function  of  Parts 

3. 

LOCATION 

REQUIREMENTS

.......................................................................................................4 

 

4. 

INSTALLATION 

PROCEDURES

  ..................................................................................................5 

 

5. 
STORAGE.

......................................................................................................……………………..5 

 

6. 
CLEANING

  ..................................................................................................……………………….6 

 

7.  TROUBLESHOOTING  GUIDE

..............................................................................………..…....7, 


 

8. 

WIRING 

DIAGRAM

………………………….........................................................………..…….......9 

 

9.  EXPLODED  VIEW  &  SERVICE  PARTS  LIST 

A. 

C12E..................................................................................................................................10, 

11 
 
 

FOR  YOUR  SAFETY 

 

Please  read  the  following  safety  precaution  before  servicing  the  watercooler. 

1)  Check  if  an  electric  leakage  occurs  in  the  appliance. 

2)  To  prevent  electric  shock,  unplug  prior  to  servicing. 

3)  In  case  of  testing  with  power  on,  wear  rubber  gloves  to  prevent  electric  shock. 

 


background image

3


4)  When  using  an  instrument  or  replacing  a  part  for  repairing,  check  it  is  applied  to 

rated  voltage  current  and  capacity. 

5)  Prevent  water  from  flowing  into  electric  elements  in  mechanical  parts. 

6)  When  carrying  or  tilting  the  appliance,  remove  all  the  objects  on  it. 

7)  If  the  cooling  cycle  is  out  of  order,  contact  nearest  authorized  service  center  for 

maintenance,  repair  and  adjustment. 

 

1.  SPECIFICATION  &  PARTS  IDENTIFICATION 

MODEL 

C12E  (CHILLER) 

DIMENSION 

410W

×

210D

×

290H(mm) 

WEIGHT 

12.5kg 

CONSUMPTION 

120W 

TEMP  CONTROL 

AUTO 

TANK 

Stainless  Steel 

COLD 

CAPACITY 

5.0 

/h  (10 ) 

ELECTRICAL 

220-240V,  50/60Hz.  110-127V,  50/60Hz. 

Check  the  available  power  supply  against  the  watercooler  data  plate  to  assure  correct  electrical  service. 

 

 


background image

4


 

 

 
 
 
 

2.  OPERATION  &  FUNCTION  OF  PARTS 

 

 

 

 


background image

5


 

A.  Cooling  Operation 

The  vapor  refrigerants  that  compressed  to  high  temperature  &  high  pressure  conditions  in  the 

compressor,  turn  into  liquid  refrigerant  of  high  temperature  and  high  pressure  passing  through  the 
condenser,  and  then  turn  into  the  liquid  refrigerants  of  low  temperature  and  low  pressure  conditions  by 
passing  through  the  capillary  tubes.  The  liquid  refrigerant  of  low  temperature  &  low  pressure  absorbs 
the  surrounding  heat  while  evaporating  in  the  evaporator.  Then,  it  is  sucked  in  the  compressor  by 

turning  into  saturated  vapor. 

 

B.  Function  of  Parts 

 

Compressor:  Compresses  the  vapor  refrigerant  sucked  from  the  evaporator  and  discharges  it  to 
condenser 

 

Condenser:  Changes  the  compressed  vapor  refrigerant  into  the  liquid  refrigerant  by  cooling. 

 

Drier:  Removes  moisture  and  dirt  inside  pipes 

 

Capillary  tube:  Reduces  the  pressure  of  liquid  refrigerant  and  evaporates  it  in  the  evaporator 
under  constant  pressure. 

 

Evaporator:  Absorbs  the  surrounding  heats  while  evaporating  the  liquid  refrigerant,  cools  down 
water  inside  of  cold  water  tank. 

 

Cold  water  thermostat:  Senses  the  temperature  of  cold  water  tank  and  controls  the  electric  power 
supply  to  the  compressor  automatically  in  order  to  keep  the  constant  temperature  of  cold  water. 

 

Over  Load  Protector  (OLP):  Protects  the  compressor  and  operates  when  rising  up  to  abnormal 
temperature  or  energizing  over  current.   

 

PTC  Starter:  Starts  up  the  motor  of  compressor.   

 

Drain  cap:  By  opening  this,  you  may  drain  out  remaining  water  in  hot  water  tank  when  cleaning 
or  not  using  cooler  for  a  long  period  of  time. 

 

3.  LOCATION  REQUIREMENTS 

A.

 

This  unit  is  intended  to  be  installed  underneath  a  conventional  kitchen  sink,  in  a  cabinet  not  less 
than  36”"  (914mm)  wide  (inside  dimension).  Chiller  may  be  installed  in  any  location  in  the  cabinet 
base  as  long  as  there  is  a  minimum  of  5”"  (127mm)  between  unit  and  cabinet  walls.  In  order  to 
have  necessary  air  exchange  for  the  unit,  a  free  air  opening  of  at  least  60  square  inches  (387 
cm

²

)  should  be  provided  in  the  kitchen  counter.  The  opening  should  be  located  as  close  to  the 

unit  as  possible  and  can  be  made  in  the  ‘ toe  space  of  the  counter’  or  ‘ above  the  toe  space’ 

B.

 

Make  sure  installation  ground  is  flat  and  even.  -  Unbalanced  placement  may  cause  excessive 
noise  and  trembling  of  the  cooler. 

C.

 

Coolers  are  for  indoor  use  only.  Keep  away  from  direct  sunlight  and  excessive  moisture. 

D.

 

Avoid  harmful  gas  or  excessive  heat. 

 

 


background image

6


4.  INSTALLATION  PROCEDURES 

A.

 

Connect  the  1/4”OD  tubing  between  water  inlet  of  chiller  and  the  supply  water  hose  with  pressure 
rating  suitable  for  use  with  the  application.  The  tubing  must  be  acceptable  for  use  with  potable 
water. 

B.

 

Using  the  1/4”OD  tubing  included  with  the  (gooseneck)  faucet,  connect  on  water  outlet  of  chiller. 
-Flush  water  in  lines  before  installing  gooseneck  faucet. 
-Acceptable  supply  water  pressure  is  15~100  PSI  (100~700kPa) 

CAUTION:  TO  PREVENT  PROPERTY  DAMAGE  DUE  TO  WATER  LEAKAGE,  SEEK  INSPECTION  BY 

PLUMBERS  TO  SEE  THE  WATER  PRESSURE  IS  LESS  THAN  100PSI  (690KPA)  BEFORE  YOU  CONNECT 

THE  SUPPLY  WATER  HOSE. 

C.

 

Slowly  open  supply  water  valve.  By  opening  faucet  lever,  let  water  flows  for  about  one  minute. 
Check  all  the  connections.   
-Purge  off  all  air  from  all  water  lines  by  opening  faucet  lever.  Steady  stream  assures  all  air  is 
ventilated. 

D.

 

Prior  to  drinking,  flush  water  through  chiller  for  at  least  5  minutes. 

E.

 

Check  the  available  power  supply  against  the  chiller  data  plate  to  assure  correct  electrical  service. 

F.

 

Plug  in  chiller  and  the  chiller  will  be  ready  to  serve  you  cold  water  in  30  minute  after  installation 

CAUTION:  FAILURE  TO  ABIDE  BY  ABOVE  PROCEDURE  CAN  CAUSE  PHYSICAL  DAMAGE  ON  THE 

COOLER.

 

 

5.  STORAGE 

A.

 

Unplug  power  cord. 

B.

 

Open  faucet  until  water  is  room  temperature. 

C.

 

Close  the  source  water  valve. 

D.

 

Disconnect  the  water  pipe  from  the  product. 

E.

 

Place  a  bucket  beneath  the  drain  pipe.  Open  the  drain  cover  and  cap.  Then,  drain  the  remaining 
water. 

F.

 

When  storing,  ensure  it  stands  on  its  erect  position  on  the  flat  and  even  ground.  (Do  not  lay  the 
product  on  its  sides  down  or  upside  down.) 

G.

 

When  not  use  for  a  long  period  of  time,  conduct  product  cleaning  before  you  put  in  storage. 

CAUTION:  FAILURE  TO  ABIDE  BY  ABOVE  PROCEDURE  MAY  INCUR  PHYSICAL  DAMAGE  ON  THE 

COOLER.

 

 

7.  TROUBLESHOOTING  GUIDE 

 


background image

7


TROUBLE 

POSSIBLE  CAUSE 

REMEDY 

REFRIGERATION  SYSTEM

 

No  electric  power  to  outlet. 

Turn  on  electric  power  outlet. 

The  thermostat  is  misadjusted  or 
defective. 

Adjust  or  replace  the  thermostat,  as 
necessary. 

The  wires  leading  to  the  thermostat  are 
defective  or  are  not  connected. 

Check  the  internal  wiring. 
Make  repairs  as  necessary. 

The  line  voltage  is  low. 

Check  the  line  voltage.  It  must  be  at 
least  90%  of  minimum  voltage. 

The  compressor  over-load 
Protector  (OLP)  is  defective. 

Replace  the  defective  over-load 
protector. 

The  starting  relay  (PTC)  is  defective. 

Replace  the  starting  relay. 

A.  Compressor  does 
not  run. 

The  compressor  is  defective. 

Replace  the  compressor. 
Return  cooler  to  authorized  service 
center  or  factory  for  repair. 

Poor  ventilation. 

Minimum  side  &  rear  clearance  4" 

The  condenser  is  dirty  or  restricted. 

Clean  the  condenser  or  relocate  the 
unit  to  prevent  restricting  the 
condenser. 

The  thermostat  is  defective.  (the 
contacts  are  shorted  or  the  control  is 
not  adjusted  properly) 

Replace  or  adjust  the  thermostat  as 
necessary. 

B.  Water  is 
adequately  chilled, 
but  cooler  runs 
excessively  or 
continuously. 

The  ambient  temperature  is  high. 

It  is  normal  for  the  cooler  to  run 
continuously  at  high  ambient 
temperatures. 

There  has  been  a  substantial  loss  in 
the  sealed  system's  charge  of 
refrigerant. 

If  refrigerant  leak  is  suspected,  return 
cooler  to  authorized  service  center  or 
factory  for  repair. 

C.  The  cooler 
compressor  runs 
continuously,  but  I 
do  not  have  cold 
water. 

The  compressor  is  defective. 

Same  as  above. 

The condenser is dirty or restricted. 

Clean the condenser and relocate the 
cooler to prevent restricting the condenser. 

The cold water thermostat is set high and 
or the cooler is in a high ambient 
environment. 

Check the thermostat setting. 
Adjust the setting as necessary. 

Usage of the cold water system is greater 
than the cooler capacity. 

Inform the customer of the cold water 
system's maximum capacity. 

The temperature of supply water is too high  Wait for a moment until cold water is made 
The refrigeration system is overcharged or 
undercharged. 

D. The cooler 
excessively 
and the cold water is 
not 
cold  enough. 

There is a partial restriction in the 
refrigeration system. 

Return cooler to authorized service center 
or factory for repair. 

E. The cooler has a 

If wattage readings are normal, the 

Replace the thermostat. 

 


background image

8


thermostat may be defective. 

Replace the thermostat. 

The thermostat is improperly set for the 
prevailing environmental conditions and 
cooler usage. 

Adjust the thermostat. 

short running cycle. It 
is cooling, but does not 
run long enough to 
cool water to the 
required level. 

The compressor motor is defective, 
causing the cooler to cycle on the overload 
protector. 

Replace the compressor. 
Return cooler to authorized service center 
or factory for repair. 

F. A. The cold water 
flows slowly or not at 
all. 

The cold water thermostat is so much low, 
causing ice to build up in the reservoir, 
blocking water flow. 

Defrost cooler. 
Adjust the temperature control. 

NOISE

 

The  cooler  is  not  level. 

The  cooler  must  be  leveled. 
Place  the  cooler  on  even  surface. 

A  section  of  the  tubing  inside  the 
cooler  is  touching  other  parts  of  cooler, 
causing  noise  to  be  generated  due  to 
vibration. 

Adjust  position  of  the  tubing  to  make 
sure  it  is  not  in  contact  with  any  other 
parts. 

Check  the  connection  of  the  fixed 
screws. 

Completely  connect  the  fixed  screws. 

A.  There  is 
excessive  noise 
coming  from  the 
cooler,  but  it  is 
otherwise  operating 
normally. 

The  compressor's  operation  is  noisy 
because  of  inherent  conditions. 

Advise  the  customer  of  the  cooler's 
normal  operating  sounds. 

WATER  LEAKAGE

 

A.  Leakage  through 
inside  of  appliance 

The  cold  water  tank  leaks. 

Return  chiller  to  authorized  service 
center  or  factory  for  repair. 

OTHERS 

Mineral concentration of supplied water is 
somewhat high. 

This product does not include filters. 
Change the existing filter or use a proper 
one. 

A.  Odd  taste  and 
smell  in  Water 

No use for a long time. 

Continue to let the water flow until it runs 
clear. 

When using a water pressure regulator. 

Adjust a regulator according to it’ manual or 
contact a qualified engineer. 

B.  Strong  water  flow 

Supplied water pressure is set up too high 
originally. 

Install a regulator that can control the 
pressure or contact a qualified engineer. 

 

 

 

 