INSTALLATION INSTRUCTIONS

ENERGY RECOVERY VENTILATOR

SERIES MB, MC, MD, ME, MF & MG

Energy recovery COMPONENT certi

fi

  ed to the ARI Air-to-

Air Energy Recovery Ventilation Equipment Certi

fi

 cation 

Program  in accordance with ARI Standard 1060-2000. 
Actual performance in packaged equipment may vary.

ETL Certi

fi

 ed per UL 1995 and CSA 22.2

97B0042N04

Rev.: 04 April, 2014

Installation Instructions For Energy Recovery Ventilator (Fixed) 

For Stand Alone Rooftop Application

Inspection 

Upon receipt of shipment at the job site, carefully check the 
shipment against the bill of lading. Make sure all units have 
been received. Inspect the carton or crating housing of each 
Rooftop Unit and inspect each unit for damage. Assure that 
the carrier makes proper notation of any shortages or damage 
on all copies of the freight bill and that he completes a Carrier 
Inspection Report. Concealed damage not discovered during 
unloading must be reported to the carrier within 15 days of 
receipt of shipment. 

NOTE: It is the responsibility of the 

purchaser to 

fi

 le all necessary claims with the carrier.

Storage 

Upon the arrival of  equipment at the job site, immediately store 
units in a clean, dry area. Do not stack units. 

Do not remove 

equipment from pallets until equipment is required for 
installation.

Unit Protection

Cover rooftop units on the job site. Cap the open ends of pipes. 
In areas where painting, plastering, roo

fi

 ng, or the spraying of 

fi

 reproof material has not been completed, all due precautions 

must be taken to avoid physical damage to the units and 
contamination by foreign material. 

Physical damage and 

contamination may prevent proper start-up and may result 
in costly equipment cleanup.

Application

Field supplied balancing dampers in duct are recommended.

Recovery Wheel Mode

The Recovery Wheel mode is accomplished by two blowers 
providing continuous exhaust of stale indoor air and 
replacement by equal amount of outdoor air. Energy recovery 
is achieved by slowly rotating the energy recovery wheel within 
the cassette frame work. In winter, the ERV adsorbs heat 
and moisture from the exhaust air stream during one half of a 
complete rotation and gives them back to the cold, drier intake 
air supply during the other half rotation. In summer, the process 
is automatically reversed. Heat and moisture are absorbed 
from incoming fresh air supply and transferred to the exhaust 
air stream. This process allows outdoor air ventilation rates 
to be increased by factors of three or more without additional 
energy penalty or increase in size of heating or air conditioning 
systems.

Rigging Unit For Lifting

1.  Maximum weight 300-1200 lbs. See Physical Data Table.
2.  Remove crating.
3.  All panels must be in place for rigging.
4.  Remove barometric exhaust hood from door marked 

fi

 lter 

access. Install barometric exhaust hood over exhaust blower 
outlet.

5.  Forklift channels must be removed from the base of
 ERV. 
6.  Position unit and provide service access to ERV control 

access door and wheel.

7.  Duct work should be installed into roof curb before installing 

ERV on curb.

8.  Roof curb gasket must be applied to all top surfaces of the 

curb. 

9.  Position unit on roof curb and provide service access to ERV 

control access door and wheel.

 

CAUTION!

 

CAUTION! 

Danger of sharp metallic edges. Can cause 

injury. Take care when servicing unit to avoid accidental 

contact with sharp edges.

 

WARNING!

 

WARNING! 

Electric shock hazard. Can cause injury or death. 

Before attempting to perform any service or maintenance, 

turn the electrical power to unit OFF at disconnect switch(es). 

Unit may have multiple power supplies.

 

WARNING!

 

WARNING! 

To avoid equipment damage, do not use these 

units as a source of heat during the construction process. 

The mechanical components and 

fi

 lters used in these units 

will quickly become clogged with construction dirt and debris 

which may cause system damage.

 

WARNING!

 

WARNING! 

The installation of water-source heat pumps and 

all associated components, parts, and accessories which 

make up the installation shall be in accordance with the 

regulations of ALL authorities having jurisdiction and MUST 

conform to all applicable codes. It is the responsibility of 

the installing contractor to determine and comply with ALL 

applicable codes, regulations and ANSI/NFPA No. 70

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

2

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

This Page Intentionally Left Blank

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

3

c l i m a t e m a s t e r . c o m

Installation

1.   Attach duct work to duct 

fl

 anges on roof curb.

2.   Set ERV on curb. Verify ERV is positioned on curb 

properly.

3.   Remove barometric exhaust hood from door marked 

fi

 lter access. Install barometric exhaust hood over 

exhaust blower outlet.

4.   Remove ERV control access panel to connect 

fi

 eld 

wiring.

5.   Route class II low voltage wire (3 conductor) from 

thermostat or energy management through small 
bushing in end panel of ERV. 

See wiring diagram.

a. Thermostat (dependent) - connect in parallel at 

rooftop unit with “G”, “C” and  “W”. Then connect 
matching color at terminal 1, 2, and 3 respectively 
on ERV circuit board.

b. Energy Management - provide +24 VAC to “1” and 

common, 24 VAC to “2” terminals on ERV circuit 
board.

c. Thermostat (dedicated) - splice into +24 vac 

(blue wire) at (control circuit board) transformer 
connection run wire to “R” terminal. Then run 
another wire from “G” terminal to ERV (control 
circuit board) terminal block #1.

6.   All electrical connections must conform to any local 

codes and current National Electric Codes (NEC) and 
Canadian Electric Codes (CEC). Refer closely to unit 
wiring diagram in unit and/or in these instructions for 
proper wiring connections.

7.   Refer to the unit nameplate for minimum circuit 

ampacity (MCA) and maximum overcurrent protection 
size (fuse).

8.   Electrical data is listed on unit rating plate and motor   

name plates.

9.   Connect line voltage power supply to ERV fuse block 

in control box of unit from disconnect switch. 

See 

wiring diagram.

10. Ground unit with a suitable ground connection either 

through unit supply wiring or an earth ground.

Note: Unit voltage entries must be sealed  
weather tight after wiring is complete.

11. Remove motor access panels. Locate belts fastened 

to blower assembly. Install belt onto motor and blower 
pulley. Adjust motor sheave to correct blower RPM for 
CFM and external static pressure requirements. See 
charts in this instruction. Multiple pulley arrangements 
are available to meet the entire range.

12.  Replace access panel onto the ERV unit and secure.
13. Restore power to unit.
14. Cleanup once unit is operating properly, caulk 

any open joints, holes or seams to make the units 
completely air and water tight. 

15. Leave this instruction manual with owner or in an 

envelope to be kept near unit.

Operation
(How It Works)

The unit contains an Energy Recovery Wheel (ERW) 
that is a new concept in rotary air-to-air heat exchangers. 
Designed as a packaged unit for ease of installation and 
maintenance, only the connection of electrical power is 
required to make the system operational.

When slowly rotating through counter 

fl

 owing exhaust 

and fresh air streams the ERW adsorbs sensible heat 
and latent heat from the warmer air stream and transfer 
this total energy to the cooler air stream during the 
second half of its rotating cycle. Rotating at 50-60 
revolutions per minute, the wheel provides constant 

fl

 ow 

of energy from warmer to cooler air stream. The large 
energy transfer surface and laminar 

fl

 ow through the 

wheel causes this constant 

fl

 ow of recovered energy 

to represent up to 85% of the difference in total energy 
contained within the two air streams.

Sensible and latent heat are the two components of total 

 

CAUTION!

 

CAUTION! 

Blower speed must be adjusted for the given 

external static pressure and air

fl

 ow (CFM) requirements. If 

blower speed is not adjusted  for conditions, possible motor 
over loading can occur.

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

4

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

heat. Sensible heat is energy contained in dry air and 
latent heat is the energy contained within the moisture 
of the air. The latent heat load from the outdoor fresh air 
on an air conditioning system can often be two to three 
times that of the sensible heat load and in the winter it is 
a signi

fi

 cant part of a humidi

fi

 cation heat load.

During both the summer and winter, the ERW transfers 
moisture entirely in the vapor phase. This eliminates wet 
surfaces that retain dust and promote fungal growth as 
well as the need for a condensate pan and drain to carry 
water.

Because it is constantly rotating when in the air stream, 
the ERV is always being cleaned by air, 

fi

 rst in one 

direction then the other. Because it is always dry, dust or 
other particles impinging on the surface during one half 
cycle, are readily removed during the next half cycle.

During the heating season, when outdoor air 
temperatures are below 10ºF, it is recommended to use 
the (optional) low ambient kit (

fi

 eld installed).

Low Ambient Kit is appropriate for climates with limited 
HVAC system operation when outdoor temperatures are 
below 10ºF.

The frost threshold is the outdoor temperature at which 
frost will begin to form on the ERV wheel. For Energy 
Recovery Ventilators, the frost threshold is typically below 
10ºF. Frost threshold is dependent on indoor temperature 
and humidify. The table shows how the frost threshold 
temperatures vary depending on indoor conditions.

Because Energy Recovery Ventilators have a low frost 
threshold, frost control options are not necessary in many 
climates. Where outdoor temperatures may drop below 
the frost threshold during the ERV operational hours, 
exhaust only frost control option is available.

Low Ambient Kit (Optional)

Low Ambient Kit turns off the supply blower when outdoor 
temperatures fall below the frost threshold. The exhaust 
only thermostat set points are 

fi

 eld adjustable. Supply 

fan operation is automatically restored when the exhaust 
air temperature rises above the thermostat set point. 
Provisions for introducing make-up air into the building 
when the supply blower is off to avoid depressurization 
should be considered.

Recovery Wheel Mode

On a thermostat call for blower operation in heating, 
cooling or continuous blower, the ERW will rotate 
between fresh air and exhaust air streams. Both the 
fresh air and exhaust air blowers will also be operating to 
overcome the air resistance of the ERV.

System Check

1.   Disconnect main power.
2.   Turn to “Cont” for blower operation on thermostat 

controlled models.

3.   Restore power to unit. Observe ERV wheel rotation 

and both fresh air and exhaust air blowers are 
operating.

 

NOTE: If Low ambient kit is used the jumper 
between TB37-5 & TB37-6 should be removed. 
Also if system check out is being conducted at 
low ambient temperatures, technician should  
be aware that this kit can cause system not to 
operate.

4.   Verify that the ERV (3) three phase blower motors 

are phased sequentially ensuring correct rotation and 
operation.

 

a. Disconnect power.

 

b. Reverse any two 

fi

 eld power leads to the ERV. 

c. Reapply power.

5.   Verify that both blower motors are operating under 

their full load AMP rating (FLA). The FLA can be 
found on each motor and the unit nameplate.

A.  Return Damper Settings

 

Manually adjust position of 

fi

 eld installed dampers to 

balance air 

fl

 ow.

B.  Air Flow / Blower Speed Adjustment

 

Blower speed selection is accomplished by changing 
the sheave setting on both fresh air and exhaust air 
blowers. To set ERV for the required air 

fl

 ow (CFM), 

the external static pressure applied to the ERV (duct 
static) must be known. See the CFM vs External 
Static Pressure chart for the appropriate unit to 
determine the correct blower RPM for the speci

fi

 ed 

CFM and External Static Pressure.

FROST THRESHOLD TEMPERATURE

INDOOR RH AT 70ºF

FROST THRESHOLD

TEMPERATURE

20%

0ºF

30%

5ºF

40%

10ºF

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

5

c l i m a t e m a s t e r . c o m

After blower speed adjustments have been made. Ensure 
that when the belt is replaced it is tensioned correctly. 
The motor mounting plate can be adjusted to tension the 
belt. If using a belt tension checker, adjust the span to the 
appropriate setting and check the belt defection force. 
The belt de

fl

 ection force should be between 5-8 lbs or the 

lowest tension at which the belt will not slip under peak 
load conditions.
1.  Disconnect main power to unit before making 

adjustment to economizer and/or ERV unit.

2.  Replace ERV control access cover.
3.  Set thermostat to normal operating position.
4.  Restore power to unit.

Maintenance

1.   All motors use pre-lubricated sealed bearings; no 

further lubrication is necessary.

2.   Make visual inspection of motors, belts and wheel 

rotating bearings during routine maintenance.

3.   Eight pie-shaped segments, are seated on stops 

between the segment retainer which pivots on the 
wheel rim and secured to the hub and rim of wheel. 
Annual inspection of the self cleaning wheel is 
recommended. With power disconnected, remove 
ERV access panels (rear) and unplug [J150 & P150] 

(Refer to wiring  diagram in this instruction 
manual)

. Remove segment and wash with water and/

or mild detergent.

4.   To install wheel segments follow steps A through 

E . 

See Figure 1. 

Reverse procedure for segment 

removal.
A. Unlock two segment retainers (one on each side of 

the selected segment opening.

B. With the embedded stiffener facing the motor side, 

insert the nose of the segment between the hub 
plates.

C. Holding segment by the two outer corners, press 

the segment towards the center of the wheel 
and inwards against the spoke 

fl

 anges. If hand 

pressure does not fully seat the segment, insert 
the 

fl

 at tip of a screw driver between the wheel 

rim and outer corners of the segment and apply 
downward force while guiding the segment into 
place.

D. Close and latch each segment retainer under 

segment retaining catch.

E. Slowly rotate the wheel 180º. Install the second 

segment opposite the 

fi

 rst for counterbalance. 

Rotate the two installed segments 90º  to balance 
the wheel while the third segment is installed. 

Rotate the wheel 180º again to install the fourth 
segment opposite the third. Repeat this sequence 
with the remaining four segments.

Pulley Kit Installation

The units are shipped from the factory at the low static 
setting. Pulley kits are available for the medium and high 
static settings. To install a pulley kit.
1.   Check content of pulley kit, if pulley kit contains:

a. An adjustable sheave and a 

fi

 xed pitch pulley then 

remove belt and both motor and blower pulley

b. An adjustable sheave then remove the motor 

pulley.

c. A 

fi

 xed pitch pulley then remove the blower pulley.

2.  Replace pulley(s) with the pulley(s) from pulley kit. 

Make sure each pulley is installed with a key. Tighten 
the set screw on the pulley(s) to 100 in.lb.

3.   Install the belt that came with the pulley kit. Tension 

belt as explained in the blower speed adjustment 
section.

4.   Check the speed of the blower. Adjust the motor 

sheave to increase or decrease the speed of the 
blower. See blower adjustment section.

B

C

A

D

E

D

HUB

SEGMENT

SPOKE

SEGMENT RETAINER CATCH

WHEEL RIM

SEGMENT RETAINER

Figure 1

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

6

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

EXHAUST AIR

FRESH AIR

RETURN AIR

TREATED AIR

ERV with Hor i zon tal Ductwork

(bal anc ing damper(s) field sup plied)

Features and Notes:

1.  Stand alone design allows higher levels of outdoor air 

to be introduced into the a/c space.

2.  Static test ports provided to verify intake and exhaust 

CFM.

3.  Balancing damper(s) is 

fi

 eld provided when connected 

to ductwork. System will not operate properly without

 balancing 

damper.

4.  See blower performance charts for air

fl

 ow at various 

E.S.P.

5.  Filter rack with 2" pleated 

fi

 lters included.

A

B

C

D

D

E

I

G

H

F

H

ERV Data

Dimensional Data

ERV Series

CFM Range

A

B

C

D

E

F

G

H

I

MB

300-1100

44.75

32.13

33.50

11.00

27.00

4.00

4.25

2.88

2.50

MC

1200-2000

54.38

37.25

37.50

12.00

30.00

5.87

5.13

4.06

1.63

MD

1200-2800

52.25

42.63

43.56

14.00

32.00

8.69

5.25

4.25

2.88

ME

2000-3600

60.00

46.69

57.37

16.50

39.50

12.00

5.50

4.05

5.88

MF

3000-4600

60.00

52.69

57.37

16.50

39.50

12.00

8.69

5.50

5.88

MG

4600-6200

72.00

70.88

63.63

19.50

39.50

17.53

14.50

8.70

6.60

M Series Stand Alone ERV’s for Side by Side Indoor Application

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

7

c l i m a t e m a s t e r . c o m

Notes:

1.

Remove jumper to install field optional low ambient switch.

2.

Se lec tive volt age ter mi nals for proper unit volt age.

3.

Optional low ambient switch.

4.

Optional motorized intake damper.

5.

Op tional Stop, Start and Jog Con trol.

6.

For energy man age ment systems connect +24v to “G” and common 24v to “C”.

MB-C

208/230-1-60

ERV UNIT SCHE MATIC DIAGRAM

COM PO NENT CODE

A131

Fixed Re lay Board

B26

Mo tor, Ex haust Air

B27

Mo tor, Fresh Air

B28

Mo tor, Des ic cant Wheel

B30

Mo tor, Damper (Op tional)

C23

Ca paci tor, Wheel Mo tor

C25

Ca paci tor, Ex haust Air

C26

Ca paci tor, Fresh Air

DL43

De lay, Cy cle Timer (Op tional)

F29

Fuse

J33

Jack, Cy cle Con trol (Op tional)

J34

Jack, Cy cle Con trol Har ness (Op tional)

J40

Jack, Cy cle  (Op tional)

J48

Jack, Con trol Box (Fresh Air)

J50

Jack, Con trol Box (Wheel)

J51

Jack, Con trol Box (Ex haust Air)

J56

Jack, Con trol Box (Damper)

J148

Jack, Fresh Air Mo tor Har ness

J150

Jack, Wheel Mo tor Har ness

J151

Jack, Ex haust Air Mo tor Har ness

J160

Jack, Damper Mo tor Har ness

K94

Re lay, On/Off (Op tional)

K163

Con tac tor, Ex haust Air Mo tor

K164

Con tac tor, Fresh Air Mo tor

P33

Plug, Cy cle Con trol (Op tional)

P34

Plug, Cy cle Con trol Har ness (Op tional)

P40

Plug, Wheel Cy cle (Op tional)

P48

Plug, Fresh Air Mo tor Har ness

P50

Plug, Wheel Mo tor Har ness

P51

Plug, Ex haust Air Mo tor Har ness

P56

Plug, Damper Mo tor Har ness

P148

Plug, Fresh Air Mo tor

P150

Plug, Wheel Mo tor

P151

Plug, Ex haust Air Mo tor

P160

Plug, Damper Mo tor

S23

Ther mo stat - Low Am bi ent (Op tional)

S26

Switch, Low Am bi ent (Op tional)

S51

Switch, Door

S125

Switch, Am bi ent Over ride (Op tional)

T27

Trans former, Con trol

T28

Trans former, Step- down (Op tional)

WIRE COLOR

BK

Black

BL

Blue

GR

Green

GY

Gray

OR

Or ange

PK

Pink

RD

Red

WH

White

YL

Yel low

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

8

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

Notes:

1.

Remove jumper to install field optional low ambient switch.

2.

Step-down transformer assembly for 460/575 volt units.

3.

Se lec tive volt age ter mi nals for proper unit volt age.

4.

Optional low ambient switch.

5.

Optional motorized intake damper.

6.

Op tional Stop, Start and Jog Con trol.

7.

For energy man age ment systems connect +24v to “G” and common 24v to “C”.

MB-G

208/230-3-60

460-3-60

575-3-60

COM PO NENT CODE

A131

Fixed Re lay Board

B26

Mo tor, Ex haust Air

B27

Mo tor, Fresh Air

B28

Mo tor, Des ic cant Wheel

B30

Mo tor, Damper (Op tional)

C23

Ca paci tor, Wheel Mo tor

DL43

De lay, Cy cle Timer (Op tional)

F29

Fuse

J33

Jack, Cy cle Con trol (Op tional)

J34

Jack, Cy cle Con trol Har ness (Op tional)

J40

Jack, Cy cle  (Op tional)

J48

Jack, Con trol Box (Fresh Air)

J50

Jack, Con trol Box (Wheel)

J51

Jack, Con trol Box (Ex haust Air)

J56

Jack, Con trol Box (Damper)

J148

Jack, Fresh Air Mo tor Har ness

J150

Jack, Wheel Mo tor Har ness

J151

Jack, Ex haust Air Mo tor Har ness

J152

Jack, Trans former (High Volt age)

J160

Jack, Damper Mo tor Har ness

K94

Re lay, On/Off (Op tional)

K163

Con tac tor, Ex haust Air Mo tor

K164

Con tac tor, Fresh Air Mo tor

P33

Plug, Cy cle Con trol (Op tional)

P34

Plug, Cy cle Con trol Har ness (Op tional)

P40

Plug, Wheel Cy cle (Op tional)

P48

Plug, Fresh Air Mo tor Har ness

P50

Plug, Wheel Mo tor Har ness

P51

Plug, Ex haust Air Mo tor Har ness

P56

Plug, Damper Mo tor Har ness

P148

Plug, Fresh Air Mo tor

P150

Plug, Wheel Mo tor

P151

Plug, Ex haust Air Mo tor

P152

Plug, Trans former (High Volt age)

P160

Plug, Damper Mo tor

S23

Ther mo stat - Low Am bi ent (Op tional)

S26

Switch, Low Am bi ent (Op tional)

S51

Switch, Door

S125

Switch, Am bi ent Over ride (Op tional)

T27

Trans former, Con trol

T28

Trans former, Step- down (Op tional)

WIRE COLOR

BK

Black

BL

Blue

GR

Green

GY

Gray

OR

Or ange

PK

Pink

RD

Red

WH

White

YL

Yel low

ERV UNIT SCHE MATIC DIAGRAM

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

9

c l i m a t e m a s t e r . c o m

MB

Des ic cant Wheel for Roof top Unit

208- 230V (1 PH)

ERV UNIT WIR ING DIAGRAM 

Notes:

1.

Remove jumper to install field optional low ambient switch.

2.

Se lec tive volt age ter mi nals for proper unit volt age.

3.

Optional low ambient switch.

4.

Optional motorized intake damper.

5.

Op tional Stop, Start and Jog Con trol.

6.

For energy man age ment systems connect +24v to “G” and common 24v to “C”.

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

10

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

MB-MG

Des ic cant Wheel for Roof top Unit

208- 230/460/575V (3 PH)

ERV UNIT WIR ING DIAGRAM 

Notes:
1. Remove jumper to install field optional low ambient switch.
2. Step-down transformer assembly for 460/575 volt units.
3. Se lec tive volt age ter mi nals for proper unit volt age.
4. Optional low ambient switch.
5. Optional motorized intake damper.
6. Op tional Stop, Start and Jog Con trol.
7. For energy man age ment systems connect +24v to “G” and common 24v to “C”.

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

11

c l i m a t e m a s t e r . c o m

Mist Eliminator Filter in Intake Hood (1.5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

300

N/A

N/A

1075

1280

1390

1535

1635

500

N/A

1065

1275

1355

1505

1615

1670

700

1060

1270

1370

1525

1610

1660

1790

900

1310

1455

1520

1605

1655

1820

1960

1100

1445

1515

1625

1725

1815

1955

2035

Barometric Hood, 2" Pleated Filters (1.5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

300

N/A

1075

1180

1290

1445

1565

1645

500

N/A

1170

1285

1375

1470

1605

1725

700

1065

1280

1370

1465

1600

1680

1800

900

1255

1360

1460

1460

1590

1675

1865

1100

1445

1455

1585

1670

1750

1860

1935

SUPPLY

EXHAUST

Low 

1000-1300         Standard Unit

Medium  1300-1700         Optional Kit

High 

1750-2200         Optional Kit 

RPM Range

Mist Eliminator Filter in Intake Hood (2HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

1200

1100

1225

1315

1405

1440

1695

1725

1400

1220

1275

1400

1480

1620

1730

1790

1600

1225

1345

1475

1615

1715

1775

1890

1800

1335

1465

1610

1710

1765

1880

1930

2000

1380

1585

1680

1755

1815

1920

N/A

Barometric Hood, 2" Pleated Filters (2HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

1200

1045

1170

1380

1475

1635

1720

1805

1400

1115

1330

1470

1570

1725

1745

1850

1600

1320

1460

1565

1680

1790

1840

1940

1800

1415

1560

1725

1780

1885

1930

2045

2000

1490

1660

1770

1875

1920

1985

N/A

SUPPLY

EXHAUST

RPM Range

Low 

1000-1300         Standard Unit

Medium  1300-1700         Optional Kit

High 

1700-2080         Optional Kit 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Blower RPM for MB

Blower RPM for MC

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

12

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

Mist Eliminator Filter in Intake Hood (3HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

1200

N/A

N/A

985

1115

1255

1390

1445

1600

N/A

975

1090

1190

1320

1320

1525

2000

960

1085

1185

1315

1410

1410

1550

2400

1080

1240

1310

1405

1485

1485

1650

2800

1230

1395

1505

1535

1595

1595

1775

Barometric Hood, 2" Pleated Filters (3HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

1200

N/A

N/A

1050

1210

1315

1375

1465

1600

N/A

1020

1200

1285

1365

1465

1545

2000

1010

1190

1320

1355

1540

1580

1660

2400

1155

1315

1425

1545

1660

1735

1785

2800

1290

1450

1600

1725

1755

1825

1880

SUPPLY

EXHAUST

RPM Range

Low 

950-1320           Standard Unit

Medium  1325-1565         Optional Kit

High 

1570-1880         Optional Kit 

Mist Eliminator Filter in Intake Hood (3HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

2000

820

930

1015

1095

1160

1245

1315

2400

920

1010

1090

1155

1240

1305

1405

2800

1000

1085

1150

1235

1295

1410

1500

3200

1130

1200

1260

1395

1430

1495

1565

3600

1190

1385

1420

1455

1510

N/A

N/A

Barometric Hood, 2" Pleated Filters (3HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

2000

780

890

970

1065

1130

1235

1275

2400

885

965

1060

1125

1230

1270

1340

2800

945

1055

1120

1225

1265

1355

1405

3200

1050

1135

1255

1325

1350

1415

1460

3600

1125

1250

1305

1340

1415

N/A

N/A

SUPPLY

EXHAUST

RPM Range

Low 

700-1025           Standard Unit

Medium  1030-1305         Optional Kit

High 

1325-1575         Optional Kit 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Blower RPM for MD

Blower RPM for ME

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

13

c l i m a t e m a s t e r . c o m

Mist Eliminator Filter in Intake Hood (5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

3000

925

1035

1110

1140

1235

1315

1350

3400

1030

1120

1185

1225

1310

1345

1385

3800

1100

1150

1240

1335

1385

1420

1455

4200

1165

1245

1375

1435

1460

1505

1550

4600

1230

1315

1335

1470

1525

1585

1655

Barometric Hood, 2" Pleated Filters (5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

3000

985

1085

1155

1280

1325

1370

1440

3400

1060

1150

1270

1320

1365

1430

1480

3800

1145

1265

1335

1400

1450

1475

1505

4200

1240

1330

1375

1460

1470

1515

1560

4600

1305

1400

1420

1485

1525

1550

1650

SUPPLY

EXHAUST

RPM Range

Low 

780-1020           Standard Unit

Medium  1000-1315         Optional Kit

High 

1315-1700         Optional Kit 

Mist Eliminator Filter in Intake Hood (5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

4600

820

910

990

1020

1135

1165

1225

5000

885

965

1040

1100

1160

1225

1280

5400

910

1000

1095

1155

1215

1275

N/A

5800

960

1060

1145

1205

1265

1290

N/A

6200

1020

1110

1195

1255

1275

N/A

N/A

Barometric Hood, 2" Pleated Filters (5HP)

External Static Pressure (in water)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

4600

875

935

1000

1025

1140

1175

1190

5000

910

975

1040

1130

1190

1200

1280

5400

945

1015

1095

1150

1230

1275

N/A

5800

990

1060

1125

1175

1265

N/A

N/A

6200

1010

1110

1195

1200

N/A

N/A

N/A

SUPPLY

EXHAUST

RPM Range

Low 

700-900           Standard Unit

Medium  900-1100         Optional Kit

High 

1100-1300       Optional Kit 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only 

Blower RPM for MF

Blower RPM for MG

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

14

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

CLIMA

TE MASTER, INC.

LIMITED EXPRESS 

W

ARRANTY/ LIMIT

A

TION OF

 REMEDIES 

AND LIABILITY

It is expressly understood that unless a statement is speci

fi

 cally 

identi

fi

 ed as a warranty

, statements made by Climate Master

, Inc., a Delaware corporation, (“CM”) or its representatives, relating to 

CM’

s products, whether oral, 

written or contained in any sales literature, catalog or any other agreement, are not express warranties and do not form a part

 of the basis of the bar

gain, but are merely CM’

s opinion or commendation of CM’

s products.

EXCEPT

 AS SPECIFICALL

Y

 SET

 FOR

TH HEREIN, 

THERE IS NO EXPRESS 

W

ARRANTY

 AS 

T

ANY

 OF

 CM’S PRODUCTS. CM MAKES NO 

W

ARRANTY

 AGAINST

 LA

TENT

 DEFECTS. CM MAKES 

NO 

W

ARRANTY

 OF

 MERCHANT

ABILITY

 OF

 THE GOODS OR OF

 THE FITNESS OF

 THE GOODS FOR 

ANY

 P

AR

TICULAR PURPOSE.

GRANT

 OF

 LIMITED EXPRESS 

W

ARRANTY

CM warrants CM products purchased and retained in the United States of 

America and Canada to be free from defects in material a

nd workmanship under normal use and maintenance as follows: (1) 

All complete air condition-

ing, heating and/or heat pump units built or sold by CM for twelve (12) months from date of unit start up or eighteen (18) mont

hs from date of shipment (from factory), whichever comes 

fi

 rst; (2) Repair and replacement parts, 

which are not supplied under warranty

, for nintey (90) days from date of shipment (from factory).  

All parts must be returned t

o CM’

s factory in Oklahoma City

, Oklahoma, freight prepaid, no later than sixty (60) days after 

the date of the failure of the part; if CM determines the part to be defective and within CM’

s Limited Express 

W

arranty

, CM sha

ll, when such part has been either replaced or repaired, return such to a factory recognized dealer

contractor or service or

ganization, F

.O.B. CM’

s factory

, Oklahoma City

, Oklahoma, freight prepaid. 

The warranty on any parts re

paired or replaced under warranty expires at the end of the original warranty period.

This warranty does not cover and does not apply to: (1) 

Air 

fi

 lters, fuses, refrigerant, 

fl

 uids, oil; (2) Products relocated after initial installation; (3) 

Any portion or component of any system that is not supplied 

by CM, regardless 

of the cause of the failure of such portion or component; (4) Products on which the unit identi

fi

 cation tags or labels have been removed or defaced; (5) Products on which payment to CM is or has been in default; (6) Product

which have defects or damage which result from improper installation, wiring, electrical imbalance characteristics or maintenan

ce; or are caused by accident, misuse or abuse, 

fi

 re, 

fl

 ood, alteration or misapplication of the prod-

uct; (7) Products which have defects or damage which result from a contaminated or corrosive air or liquid supply

, operation at

 abnormal temperatures, or unauthorized opening of refrigerant circuit; (8) Mold, fungus or bacteria 

damages; (9) Products subjected to corrosion or abrasion; (10) Products manufactured or supplied by others; (1

1) Products which

 have been subjected to misuse, negligence or accidents; (12) Products which have been operated 

in a manner contrary to CM’

s printed instructions; or (13) Products which have defects, damage or insuf

fi

 cient performance as a result of insuf

fi

 cient or incorrect system design or the improper application of CM’

s products.

CM is not responsible for: (1) 

The costs of any 

fl

 uids, refrigerant or other system components, or associated labor to repair or replace the same, which is incurred as a result

 of a defective part covered by CM’

s Limited Express 

W

arranty;  (2) 

The costs of labor

, refrigerant, materials or service incurred in removal of the defective part, or in obtaining

 and replacing the new or repaired part; or

, (3) 

T

ransportation costs of the defective part from the installa-

tion site to CM or of the return of any part not covered by CM’

s Limited Express 

W

arranty

.

Limitation:

 This Limited Express 

W

arranty is given in lieu of all other warranties. If, notwithstanding the disclaimers contained herein, 

it is determined that other warranties exist, any such warranties, including without limita-

tion any express warranties or any implied warranties of 

fi

 tness for particular purpose and merchantability

, shall be limited to the duration of the Limited Express 

W

arranty

.

LIMIT

A

TION OF

 REMEDIES

In the event of a breach of the Limited Express 

W

arranty

, CM will only be obligated at CM’

s option to repair the failed part or

 unit or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed. If 

after written notice to CM’

s factory in Oklahoma City

, Oklahoma of each defect, malfunction or other failure and a reasonable n

umber of attempts by CM to correct the defect, malfunction or other failure and the remedy fails 

of its essential purpose, CM shall refund the purchase price paid to CM in exchange for the return of the sold good(s). Said re

fund shall be the maximum liability of CM. 

THIS REMEDY

 IS 

THE SOLE 

AND EXCLUSIVE 

REMEDY

 OF

 THE BUYER OR 

THEIR PURCHASER 

AGAINST

 CM FOR BREACH OF

 CONTRACT

, FOR 

THE BREACH OF

 ANY

 W

ARRANTY

 OR FOR CM’S NEGLIGENCE

 OR IN STRICT

 LIABILITY

.

LIMIT

A

TION OF

 LIABILITY

CM shall have no liability for any damages if CM’

s performance is delayed for any reason or is prevented to any extent by any e

vent such as, but not limited to: any war

, civil unrest, government restrictions or restraints, strikes 

or work stoppages, 

fi

 re, 

fl

 ood, accident, shortages of transportation, fuel, material, or labor

, acts of God or any other reason beyond the sole control 

of CM. 

CM EXPRESSL

Y

 DISCLAIMS 

AND EXCLUDES 

ANY

 LIABIL-

ITY

 FOR CONSEQUENTIAL

 OR INCIDENT

AL

 DAMAGE IN CONTRACT

, FOR BREACH OF

 ANY

 EXPRESS OR IMPLIED 

W

ARRANTY

, OR IN 

T

OR

T

, WHETHER FOR 

CM’

s NEGLIGENCE OR 

AS 

STRICT

 LIABILITY

.

OBT

AINING W

ARRANTY

 PERFORMANCE

Normally

, the contractor or service or

ganization who installed the products will provide warranty performance for the owner

. Sh

ould the installer be unavailable, contact any CM recognized dealer

, contractor or service or

ganiza-

tion. If assistance is required in obtaining warranty performance, write or call:

Climate Master

, Inc. • Customer Service • 7300 S.W

. 44th Street • Oklahoma City

, Oklahoma 73179  (405) 745-6000

NOTE: Some states or Canadian provinces do not allow limitations on how long an implied warranty lasts, or the limitation or ex

clusions of consequential or incidental damages, so the foregoing exclusions and limitations may 

not apply to you. 

This warranty gives you speci

fi

 c legal rights, and you may also have other rights which vary from state to state and from Canadian province to Canadian provi

nce.

Please refer to the CM Installation, Operation and Maintenance Manual for operating and maintenance instructions.

                    

  

 *LC083*

  

Rev

.:  1

1/09 

LC083 

 


background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

15

c l i m a t e m a s t e r . c o m

Notes

 


background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

M (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

16

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

Revision History

*97B0042N04*

97B0042N04

ClimateMaster works continually to improve its products. As a result, the design and speci

fi

 cations of each product at the time of order may be 

changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for 
speci

fi

 c information on the current design and speci

fi

 cations. Statements and other information contained herein are not express warranties and 

do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products. For the latest 
version of this document go to climatemaster.com.
ClimateMaster is a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org. 

 

© ClimateMaster, Inc. 2013 

7300 S.W. 44th Street

Oklahoma City, OK 73179

Phone: 405-745-6000

Fax: 405-745-6058

climatemaster.com

Date:

Item:

Action:

04/04/14

Logos - page 1 & 16

Updated

11/21/13

Created