Full Text Searchable PDF User Manual

User Manual
97B0055N02
Created: 5/8/12
ATC32U01 iGate™ Communicating,
Programmable Thermostat
Table of Contents
Section Title
Page
1.0
Temperature Adjustment
3
2.0
Operating Mode Selection
3
3.0
Fan Mode Selection
4
4.0 Humidity
Level
Adjustment 4
5.0
Main Menu Options Overview
5
5.1
Date
and
Time
6
5.2
Hold
6
5.3
Program
8
Section Title
Page
5.4
Fan
8
5.5
Mode
8
5.6
Other
Settings
9
5.7
Security
Lockout
12
5.8
Night
Setback
12
6.0 Service
Needed
13
7.0 Revision
History
14

This page was intentionally left blank.

3
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
1.0 Operating Mode Selection
To set the Operating Mode of your thermostat, navigate to the
MODE
user option on the Home Screen using the left/right
arrow buttons and press the center button. The Operating
Mode Menu shows the possible Operating Modes with the
currently active Operating Mode highlighted. Use the up/
down arrow buttons to select the desired Mode for use and
press the center button to save your selection. The following
Modes are available:
•
Off
(default): No equipment operation
•
Auto
: Thermostat automatically controls the
equipment to run either heating or cooling
depending on the setpoints.
•
Cool
: Thermostat controls cooling equipment
depending on Cooling setpoint
•
Heat
: Thermostat controls heating equipment
depending on Heating setpoint
•
Emergency Heat
: Thermostat controls auxiliary
heat. No compressor operation.
2.0 Temperature Adjustment
To adjust the temperature on the thermostat, use the left/
right arrow buttons to select the
TEMP
user option on the
Home Screen and then press the center button or press the
up or down arrow key. The Temperature Adjustment Display
appears and shows either one (in Heat, Cool, or Emergency
Heat modes) or both (in Auto mode) temperature setpoints.
Adjust the setpoints using the up/down arrow buttons.
Navigate between setpoints using the left/right arrow buttons.
Press the center button to save changes.
•
Heat Setpoint
(default 60°F): options: 55°F to
Maximum Heating Setpoint Limit (section 5.6.8)
•
Cool Setpoint
(default 80°F): options: Minimum
Cooling Setpoint Limit (section 5.6.8) to 95°F
NOTE 1
: The thermostat must be in any mode other than
OFF (section 2) to adjust temperature setpoint(s).
NOTE 2
: The thermostat forces a 2°F “dead-band” between
the Heating and Cooling setpoints. While adjusting
the Heating setpoint, the Cooling setpoint may be
automatically increased to enforce a 2°F “dead-
band”. Likewise, while adjusting the Cooling
setpoint, the Heating setpoint may be automatically
reduced to enforce a 2°F “dead-band”.
NOTE 3
: In programmable mode, the
TEMP
option provides
the ability to temporarily modify setpoint(s) until
the start time of the next program schedule event.
While in non-programmable mode, the TEMP
option provides the ability to modify the setpoint(s).
68
°
RH 41%
10/13/11
8:25 AM
FAN AUTO
HUMID ON
AUTO
SETPOINT
HEAT 62
COOL 82
RH
FAN MENU
TEMP
MODE
70
°
COOL
HOLD THIS
TEMPERATURE
UNTIL 5:00 PM
CHANGE
SAVE
PREVIOUS
TEMP
74
°
SET
HEAT
69
°
RH 41%
10/13/11
8:27 AM
FAN AUTO
HUMID ON
AUTO
SETPOINT
HEAT 62
COOL 82
RH TEMP
FAN MENU
MODE
AUTO
OPERATING MODE MENU
SAVE
OFF
COOL
HEAT
EMERGENCY
PREVIOUS
CHANGE MODE
HEAT
ClimateMaster’s ATC32U** Communicating, Programmable Thermostat is the perfect compliment to your ClimateMaster Geo-
thermal Heat Pump System and represents a signifi cant advancement in thermostat communicating technology. For home-
owners, the ATC32U** provides highly customizable climate control features designed to maximize comfort and reduce the
amount of energy consumed by your ClimateMaster Geothermal Heat Pump System. Please read the following instructions
carefully to maximize the comfort and cost-saving potential of your ClimateMaster Geothermal Heat Pump System and thanks
for choosing ClimateMaster for your home comfort needs.

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
4
G e o t h e r m a l H e a t P u m p S y s t e m s
3.0 Fan Mode Selection
To adjust the Fan Mode on your thermostat, use the left/
right arrow buttons to select the
FAN
user option from the
Home Screen and then press the center button. The Fan
Menu shows up to 3 possible Fan Operating Modes with the
currently active Fan Operating Mode highlighted. Use the
up/down arrow buttons to select the desired Fan Mode and
press the center button to save your selection. You may
choose from the following Fan Modes:
•
Auto
(default): Fan only runs with a call for
heating/cooling
•
Continuous On
: Fan runs continuously with or
without a call for heating/cooling
•
Programmed Fan
(in Programmable Mode): Fan
runs per Program Schedule settings (reference
section 5.3).
4.0 Humidity Level Adjustment
NOTE 1
: The thermostat must be confi gured by installer for
humidity control to access the humidity setpoint(s).
To adjust the Relative Humidity level on your thermostat,
use the left/right arrow buttons to select the
RH
user
option on the Home Screen and then press the center
button. The Humidity Control screen shows either one (with
Humidifi cation or Dehumidifi cation enabled alone) or both
(with BOTH enabled) humidity setpoints. Adjust the setpoints
using the up/down arrow buttons. Press the center button to
save changes.
•
Humidifi cation Setpoint
(default 40%): options:
10% to 45% (in 5% increments)
NOTE
: Humidifi er must be installed to set humidifi cation
setpoint.
•
Dehumidifi cation Setpoint
(default 60%):
options: 45% to 80% (in 5% increments)
NOTE 2
: The thermostat forces a 10% “dead-band” between
the Humidifi cation and Dehumidifi cation setpoints.
While adjusting the Dehumidifi cation setpoint,
the Humidifi cation setpoint may be automatically
reduced to enforce a 10% “dead-band”. However,
the Dehumidifi cation setpoint will not be
automatically increased to enforce a 10% “dead-
band” while adjusting the Humidifi cation setpoint.
The maximum range for the Humidifi cation setpoint
may be limited by the Dehumidifi cation setpoint.
NOTE 3
: If an outdoor sensor is present, the Humidifi cation
setpoint will be calculated automatically for optimal
comfort.
FAN MENU
SAVE
CONTINUOUS ON
HEAT
PREVIOUS
SELECT OPTION
PROGRAMMED FAN
AUTO
69
°
RH 40%
10/13/11
8:27 AM
FAN AUTO
OFF
RH TEMP
MENU
FAN
MODE
42
%
HUMIDITY
HUMIDITY CONTROL
HUMIDITY SETTING 40%
DEHUMID SETTING 60%
70
°
RH 38%
10/12/11
5:22 PM
FAN AUTO
AUTO
TEMP
MENU
FAN
MODE
HUMID ON
RH
SETPOINT
HEAT 70
COOL 78

5
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
5.0 Main Menu Options Overview
MENU
5.1 DATE AND TIME
5.1.1 AUTO DAYLIGHT SAVING
5.1.2 SET DATE AND TIME
5.1.3 DISPLAY DATE AND TIME
5.2 HOLD
5.3 PROGRAM
5.4 FAN
5.5 MODE
5.6 SETTINGS
5.6.1 SCREEN SETTINGS
5.6.1.1
Fahrenheit or Celsius
5.6.1.2
12 or 24 Hour Clock
5.6.1.3
Language
5.6.1.4
Contrast
5.6.1.5
Backlight
On
Time
5.6.1.6
Date
Display
5.6.2 OFFSETS
5.6.2.1
Temperature
Offset
5.6.2.2
Anticipator
5.6.2.3
Differential
5.6.2.4
Humidity
Offset
5.6.3 CYCLES PER HOUR
5.6.4 AUTO CHANGEOVER TIME
5.6.5 PROGRAM SETTINGS
5.6.5.1
Smart
Recovery
5.6.5.2
Events Per Day
5.6.5.3
Smart Heat Staging
5.6.5.4
Electric Heat Lockout
5.6.5.5
Demand
Reduction
5.6.6 INTERMITTENT FAN
5.6.7 SERVICE INFORMATION
5.6.7.1
Fault
Status
5.6.7.2
Temperature
Status
5.6.7.3
Clear Fault History
5.6.7.4
System
Status
5.6.8 SETPOINT LIMITS
5.6.9 DEMAND REDUCTION
5.7 SECURITY LOCKOUT
5.8 NIGHT SETBACK
5.8.1 SETPOINTS
5.8.2 OVERRIDE
5.8.3 DEMAND REDUCTION
5.8.4 FAN OPERATION
5.8.5 DEHUMIDIFICATION
NOTE
: All of the following menu functions are
accessed by scrolling to the MENU user option
on the Home Screen and then pressing the
center button.
NOTE
: All menu options may not be present depending on
your thermostat’s confi guration.

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
6
G e o t h e r m a l H e a t P u m p S y s t e m s
MAIN MENU
SET DATE AND TIME
HOLD
SECURITY LOCKOUT
PROGRAM
FAN
MODE
SETTINGS
HOLD MENU
PERMANENT
PREVIOUS
SELECT OPTION
VACATION
5.2.1 VACATION (Hold)
This feature can suspend the program schedule by
using specifi ed heating/cooling setpoints for extended
periods of time.
5.2.1.1 HOLD TEMPERATURE
Set the Vacation Hold heating/cooling setpoints.
The Vacation Hold Temperature Display Mode
shows either one (in Heat, Cool, or Emergency
Heat modes) or both (in Auto mode) temperature
setpoints. Adjust the setpoints using the up/down
arrow buttons. Navigate between setpoints using
the left/right arrow buttons. Press the center
button to save changes.
Access main menu by selecting
MENU
on the main screen.
5.1 DATE AND TIME
The thermostat can be programmed for daylight savings, date
and time, and to display date and time on the main screen.
5.1.1
AUTO DAYLIGHT SAVING
When enabled, the thermostat automatically adjusts
the time for daylight savings time.
5.1.2
SET DATE AND TIME
To set the current date and time, use the up/down
arrow buttons. Press the center button to save
changes.
5.1.3
DISPLAY DATE AND TIME
When enabled, the thermostat will display the date and
time (section 5.1.2) on the top line of the Main screen.
NOTE
: When the thermostat is confi gured for non
programmable mode by installer the Display Date and
Time setting defaults to NO.
Section 5.2 and 5.3 will not be displayed if the
thermostat is set as “non-programmable” in installer
settings (contact your dealer to change).
69
°
RH 40%
10/13/11
8:27 AM
FAN AUTO
OFF
TEMP
FAN
MODE
RH
MENU
MAIN MENU
SET DATE AND TIME
HOLD
SECURITY LOCKOUT
PROGRAM
FAN
MODE
SETTINGS
5.0 Main Menu
5.2 HOLD (Temperature)
The thermostat can be programmed to hold the temperature
and override the program schedule for a set time. The
thermostat can accommodate any hold schedule, whether the
temperature hold is desired for a few hours or a few weeks.
NOTE 1
: The thermostat must be in any mode other than
OFF (section 2) to set a vacation/permanent hold.
NOTE 2
: The thermostat must be confi gured for
programmable mode by installer) to access the
Hold modes.

7
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
5.2.1.2 HOLD TIME
Set the Vacation Hold time period.
Adjust the date using the up/down arrow buttons.
Press the center button to save changes.
•
Date (default current Date):
in 1 day
increments
•
Time (default current Time):
in 10 minute
increments
5.2.2 PERMANENT
The thermostat can be programmed to hold the
temperature and override the program schedule
permanently.
The Permanent Hold Display Mode shows either one
(in Heat, Cool, or Emergency Heat modes) or both
(in Auto mode) temperature setpoints. Adjust the
setpoints using the up/down arrow buttons. Navigate
between setpoints using the left/right arrow buttons.
Press the center button to save changes.
• Heat Setpoint (default current Heat
Setpoint): valid range:
55°F – Maximum
Heating Setpoint Limit (section 5.6.8)
• Cool Setpoint (default current Cool
Setpoint):
valid range: Minimum Cooling
Setpoint Limit (section 5.6.8) – 95°F
NOTE
: The thermostat forces a 2°F “dead-band”
between the Heating and Cooling setpoints. While
adjusting the Heating setpoint, the Cooling setpoint
may be automatically increased to enforce a 2°F
“dead-band”. Likewise, while adjusting the Cooling
setpoint, the Heating setpoint may be automatically
reduced to enforce a 2°F “dead-band”.
70
°
HOLD THIS
TEMPERATURE
UNTIL 5:00 PM
CHANGE
SAVE
PREVIOUS
TEMP
74
°
SET
HEAT
COOL
70
°
COOL
HOLD THIS
TEMPERATURE
UNTIL 5:00 PM
CHANGE
SAVE
PREVIOUS
TEMP
74
°
SET
HEAT
• Heat Setpoint (default current Heat Setpoint):
valid range: 55°F to Maximum Heating Setpoint
Limit (section 5.6.8)
• Cool Setpoint (default current Cool Setpoint):
valid range: Minimum Cooling Setpoint Limit
(section 5.6.8) to 95°F
NOTE
: The thermostat forces a 2°F “dead-band”
between the Heating and Cooling setpoints. While
adjusting the Heating setpoint, the Cooling setpoint
may be automatically increased to enforce a 2°F
“dead-band”. Likewise, while adjusting the Cooling
setpoint, the Heating setpoint may be automatically
reduced to enforce a 2°F “dead-band”.

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
8
G e o t h e r m a l H e a t P u m p S y s t e m s
5.3.1 CREATE / EDIT SCHEDULE
This function allows you to set the time, heat setting,
cool setting, and fan operation for each program
schedule event of the day.
NOTE 1:
To adjust the number of program schedule
events per day, reference the Program Settings
(section 5.6.5.2).
MAIN MENU
SET DATE AND TIME
HOLD
SECURITY LOCKOUT
PROGRAM
FAN
MODE
SETTINGS
SELECT OPTION
PREVIOUS
TUESDAY
WEDNESDAY
COPY
THURSDAY
SATURDAY
FRIDAY
EVERY DAY
SUNDAY
WEEKENDS
WEEKDAYS
PROGRAM MENU
MONDAY
SAVE
10:00P 62 82 AUTO
SLEEP
PREVIOUS
RETURN
5:00P 70 78 AUTO
LEAVE
8:00A 62 82 AUTO
6:00 A 70 78 AUTO
WAKE
HEAT COOL FAN
MONDAY
5.3 PROGRAM
The Program Display Mode includes options to copy
schedules as well as create/edit schedules for individual days
or schedules for groups of days.
Event
Heat
Cool
Fan (see NOTE 2)
Day - 6:00A
70ºF
78ºF
Auto
Night - 10:00P
62ºF
82ºF
Auto
SELECT OPTION
MONDAY
PREVIOUS
TUESDAY
WEDNESDAY
COPY
THURSDAY
SATURDAY
FRIDAY
EVERY DAY
SUNDAY
WEEKENDS
WEEKDAYS
PROGRAM MENU
5.4 FAN (Fan Mode)
Refer to Section 3.
5.5 MODE (Operating Mode)
Refer to Section 2.
NOTE 2:
The Fan Mode (section 3) must be set to
Programmed Fan to access the fan operation for
each schedule event setting.
5.3.2 COPY
Copy can be used to copy one day’s program
schedule to another day or multiple other days.
Default daily program schedule for 4-event schedule
(see NOTE 1):
Default daily program schedule for residential 2-event
schedule (see NOTE 1):
Default daily program schedule for 4-event schedule
(see NOTE 1):
Event
Heat
Cool
Fan (see NOTE 2)
Wake - 6:00A
70ºF
78ºF
Auto
Leave - 8:00A
62ºF
82ºF
Auto
Return - 5:00P
70ºF
78ºF
Auto
Sleep - 10:00P
62ºF
82ºF
Auto
Event
Heat
Cool
Fan (see NOTE 2)
Active - 6:00A
70ºF
78ºF
Auto
Idle - 6:00P
62ºF
82ºF
Auto
Default daily program schedule for business 2-event
schedule (see NOTE 1):

9
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
5.6 OTHER SETTINGS
5.6.1 SCREEN SETTINGS
Adjust the Screen settings using the up/down arrow
buttons. Press the center button to save changes.
• Fahrenheit or Celsius (default Fahrenheit):
adjusts the temperature scale
• 12 or 24 Hour Clock (default 12 Hour Clock):
adjusts the clock format
• Language (default English)
• Contrast (default 4):
adjusts the screen contrast
- options: 1 to 15
• Backlight On Time (default 30 seconds):
After
a button press, the backlight stays on for the
selected amount of time - options: 30 to 120
seconds, ON (in 30 second increments)
• Date Display (default MM/DD/YY):
adjusts the
date
format
5.6.2 OFFSETS
Not recommended for user access. Contact your
dealer for changes.
5.6.3 CYCLES PER HOUR
Not recommended for user access. Contact your
dealer for changes.
5.6.4 AUTO CHANGEOVER TIME
Not recommended for user access. Contact your
dealer for changes.
5.6.5 PROGRAM SETTINGS
Set additional system parameters related to program
scheduling and system operation.
5.6.5.1
SMART
RECOVERY
Smart recovery is a feature designed to save
energy by gradually adjusting temperatures. When
it is time for a program schedule temperature
change, smart recovery begins working in
advance, turning the system on and off as needed
to slowly adjust the indoor temperature so that
it reaches the program temperature setpoints at
the time you set. Rather than waiting to start the
equipment until the program time has occurred.
Adjust the Smart Recovery setting using the up/
down arrow buttons. Press the center button to
save changes.
•
Events Per Day (default On):
options: ON,
OFF
NOTE 1
: The thermostat must be confi gured for
programmable mode by installer to access the
Smart Recovery setting.
NOTE 2
: Auxiliary heat will not be used during
Smart Recovery.
5.6.5.2 EVENTS PER DAY
NOTE: The thermostat must be confi gured for
programmable mode by installer to access the
Events per Day setting.
Events Per Day sets the number of program
schedule events for each day. An event is a period
of time scheduled with a certain heat setpoint, cool
setpoint, and fan mode.
Adjust the Events Per Day setting using the up/
down arrow buttons. Press the center button to
save changes.
•
Events Per Day (default 4 events):
options:
4-Residential, 2-Residential, 2-Business
5.6.5.3 SMART HEAT STAGING
When there is auxiliary heating demand, Smart
Heat Staging defi nes the minimum amount of
time to wait before activating auxiliary heating. If
you fi nd that the thermostat is operating auxiliary
heating equipment too quickly/slowly, this setting
allows for adjustment to correct the temperature
algorithm.
Adjust the Smart Heat Staging setting using the up/
down arrow buttons. Press the center button to
save changes.
•
Smart Heat Staging (default Off):
options:
OFF, 5 – 120 minutes (in 5 minute increments)
5.6.5.4 ELECTRIC HEAT LOCKOUT
Electric heat lockout keeps electric heat turned off
if the outdoor temperature is above the specifi ed
temperature so as only to use electric heat when
necessary.
Adjust the Electric Heat Lockout setting using the
up/down arrow buttons. Press the center button to
save changes.
•
Electric Heat Lockout (default Off):
options:
OFF, 5 – 60°F (in 5°F increments)
NOTE
: An outdoor temperature sensor must be
installed for this feature to work.
5.6.5.5 PROGRAMMED DEMAND REDUCTION
Programmed Demand Reduction is a feature
designed to reduce your electric load during
preselected time periods in which peak utility rates
are high. You can program your thermostat to
reduce the electric load by limiting operation or
capacity during the high utility rate time period that
you specify for each day of the week.
While the Programmed Demand Reduction mode
is active, the thermostat outputs will be limited

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
10
G e o t h e r m a l H e a t P u m p S y s t e m s
by the Programmed Demand Reduction option
selected below.
NOTE
: The thermostat must be confi gured for
programmable mode by installer to access the
Programmed Demand Reduction settings.
5.6.5.5.1 PROGRAMMED DEMAND
REDUCTION MODE
Through Programmed Demand Reduction
Mode, you can set the unit’s limited operation
during the Programmed Demand Reduction
schedule.
Adjust the Programmed Demand Reduction
Mode settings using the up/down arrow buttons.
Press the center button to save changes.
•
No Demand Reduction (default):
During
the scheduled Programmed Demand
Reduction time (section 5.6.5.5.4), the
system operates normally based on the
setpoints.
• No
Auxiliary
Heat:
During the scheduled
Programmed Demand Reduction time
(section 5.6.5.5.4), auxiliary heat will not
be activated, regardless of the heating
demand.
•
No 2nd Stage Compressor:
During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), the compressor
is limited to only part load (1st stage)
operation and auxiliary heat is turned off,
regardless of system demand.
NOTE 1
: The thermostat must be confi gured for
auxiliary heat by installer to access the Demand
Reduction NO AUXILIARY HEAT option.
NOTE 2
: The thermostat must be confi gured
for Multistage by installer to access the Demand
Reduction NO 2nd STAGE COMP option.
5.6.5.5.2 Climadry™ - PROGRAMMED
DEMAND REDUCTION
This option allows for the customization
of Climadry™ (Dehumidifi cation, optional)
operation during the Programmed Demand
Reduction schedule.
Adjust the Programmed Demand Reduction
Climadry™ settings using the up/down arrow
buttons. Press the center button to save
changes.
•
Suspend Climadry™ (default):
During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), Climadry™ is
turned off, regardless of the dehumidifi cation
demand.
• Allow
Climadry:
During the scheduled
Programmed Demand Reduction time
(section 5.6.5.5.4), Climadry™ will operate
normally.
NOTE
: The thermostat must be confi gured
for humidity control by installer and the DXM2
must be confi gured for Climadry™ operation to
access Demand Reduction Climadry™ settings.
5.6.5.5.3 FAN - PROGRAMMED DEMAND
REDUCTION
This option allows for the customization of
fan settings during the Programmed Demand
Reduction schedule.
Adjust the Programmed Demand Reduction
Fan settings using the up/down arrow buttons.
Press the center button to save changes.
•
Auto Fan Only (default):
During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), only auto fan mode
is allowed.
•
Allow Continuous Fan:
During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), the fan will operate
normally.
5.6.5.5.4 SCHEDULE - PROGRAMMED
DEMAND REDUCTION
This option allows setting a 7-day time schedule
for Programmed Demand Reduction.
Adjust the Programmed Demand Reduction
Schedule start and end time settings using
the up/down arrow buttons in increments of
10 minutes. Press the center button to save
changes.
NOTE
: To disable Programmed Demand
Reduction, set the Start time equal to the End
time for that day.
5.6.6 INTERMITTENT FAN
Intermittent Fan function allows the fan to run
periodically when the heating/cooling equipment is
off. Many times this functionality is used to improve
the performance of air cleaning or special fi ltration
systems.
When the Intermittent Fan function is active, the fan
output will be activated for the currently selected
Intermittent Fan On Time, and then operate using
the selected Intermittent Fan Off and On times until a
heating or cooling operation is activated again.
After the heating or cooling operation is complete,
the intermittent fan operation will resume with the
beginning of a new Intermittent Fan On Time on the ¼
hour.
• On Time (default Off):
options: Off, 5 to 20
minutes (in 5 minute increments)

11
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
• Off
Time:
options: 5 to 90 minutes (in 5 minute
increments)
NOTE
: This intermittent fan operation can also
improve the performance of air cleaning or special
fi ltration systems that locate the cleaning or fi ltration
media at the return air side of the fan.
5.6.7 SERVICE INFORMATION (System Status and
Fault Information)
These additional screens help the service personnel
to have a better understanding of what problems
might be occurring before arriving for service.
5.6.7.1 FAULT STATUS
Fault Status mode displays the active fault code as
well as the fi ve most recent stored fault codes that
occurred on the system.
Navigate between system fault codes using the up/
down arrow buttons. Press the center button to
view more information about potential reasons why
the highlighted fault may have occurred.
5.6.7.2 TEMPERATURE STATUS
Temperature Status mode allows the user to view
the status of all temperature sensor readings
including onboard and remote sensors.
NOTE
: If a temperature sensor is not connected
or a temperature reading is out of the valid range,
N/A will be displayed.
5.6.7.3 CLEAR FAULT HISTORY
Clear Fault History will clear all fault codes stored
in the thermostat.
5.6.7.4 SYSTEM STATUS
System Status mode allows the user to view the
status of all temperature sensor readings as well
as the operational status of the blower and pump.
NOTE 1
: If any temperature reading is out of the
valid range, N/A will be displayed.
NOTE 2
: If the connected communicating control
is not confi gured for Pump by installer or no
valid pump information is communicated by the
connected control, N/A will be displayed.
5.6.8 SETPOINT LIMITS
Use this option to limit the heating and cooling
setpoints. This function is used to avoid setting
the cooling temperature too low or the heating
temperature too high.
Adjust the maximum heating and minimum cooling
Setpoint Limits settings using the up/down arrow
buttons. Navigate between Setpoint Limits using the
left/right arrow buttons. Press the center button to
save changes.
• Maximum Heating (default 95
°
F):
valid range:
60 to 95°F (in 1°F increments)
• Minimum Cooling (default 55
°
F):
valid range:
55 to 80°F (in 1°F increments)
NOTE
: The thermostat will operate with a fi xed
Minimum Heating Setpoint value of 55°F and a
Maximum Cooling Setpoint value of 95°F.
5.6.9 DEMAND REDUCTION - External Sensor Input
Demand Reduction is used to reduce the electric
load while peak utility rates are high. While the
Demand Reduction mode is active, the thermostat
will implement load reduction by limiting operation or
capacity. The thermostat outputs will be limited by
the Demand Reduction option selected below (section
5.6.9.1).
NOTE
: The thermostat must be confi gured for
Demand Reduction by installer to access Demand
Reduction settings.
5.6.9.1 DEMAND REDUCTION MODE
Through Demand Reduction Mode, you can set the
unit’s limited operation while Demand Reduction is
active.
Adjust the Demand Reduction Mode settings using
the up/down arrow buttons. Press the center
button to save changes.
•
No Auxiliary Heat (default):
While the
assigned Demand Reduction input is active,
auxiliary heat will not be activated regardless of
the heating demand.
•
No 2nd Stage Compressor:
While the
assigned Demand Reduction input is active,
the compressor is limited to only part load (1st
stage) operation and auxiliary heat is turned off
regardless of system demand.
•
No Operation (default – if either setting is
not present):
While the assigned Demand
Reduction input is active, the thermostat
outputs will not be activated for heating or
cooling regardless of the heating or cooling
demand.
NOTE 1
: The thermostat must be confi gured for
auxiliary heat by installer to access the Demand
Reduction NO AUXILIARY HEAT option.
NOTE 2
: The thermostat must be confi gured
for Multistage by installer to access the Demand
Reduction NO 2nd STAGE COMP option.
5.6.9.2 Climadry™ - DEMAND REDUCTION
This option allows for the customization of
Climadry™ (Dehumidifi cation, optional) operation
while Demand Reduction is active.

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
12
G e o t h e r m a l H e a t P u m p S y s t e m s
Adjust the Demand Reduction Climadry™ settings
using the up/down arrow buttons. Press the center
button to save changes.
•
Suspend Climadry™ (default):
While the
assigned Demand Reduction input is active,
Climadry™ is turned off, regardless of the
dehumidifi caiton demand.
• Allow
Climadry:
While the assigned Demand
Reduction input is active, Climadry™ will
operate normally.
NOTE
: The thermostat must be confi gured for
humidity control by installer and the DXM2 must
be confi gured for Climadry™ operation to access
Demand Reduction Climadry™ settings.
5.6.9.3 FAN - DEMAND REDUCTION
This option allows for the customization of fan
settings while Demand Reduction is active.
Adjust the Demand Reduction Fan settings using
the up/down arrow buttons. Press the center
button to save changes.
•
Auto Fan Only (default):
While the assigned
Demand Reduction input is active, the fan
output will not be activated unless the heat
pump is in 1st or 2nd stage operation or
auxiliary heat mode is active.
•
Allow Continuous Fan:
While the assigned
Demand Reduction input is active, the fan
output will operate normally.
5.7 SECURITY LOCKOUT
The Security Lockout function allows you to lockout
thermostat display, requiring a password to make changes.
Adjust the four-digit Security Pin using the up/down arrow
buttons. Navigate between digits using the left/right arrow
buttons. Press the center button to save changes.
• Temp
Adjust
Only:
while locked, thermostat will still
allow temperature adjustment
• Total Keypad Lockout:
while locked, thermostat will not
allow any changes
5.8 NIGHT
SETBACK
Under Night Setback mode, the thermostat will operate using
alternate Night Setback heating and cooling setpoints, fan
mode, and humidifi cation and dehumidifi cation setpoints.
Night Setback is activated by an input signal at the unit
control board to reduce the electric load while the building is
unoccupied.
NOTE
: While the Night Setback mode is active, the screen
backlight will be red when ON.
5.8.1 NIGHT SETBACK SETPOINTS
Adjust the Night Setback setpoints using the up/down
arrow buttons. Navigate between Night Setback
setpoints using the left/right arrow buttons. Press the
center button to save changes.
• Heat Setpoint (default 60
°
F):
options: 55°F to
Maximum Heating Setpoint Limit (section 5.6.8)
• Cool Setpoint (default 80
°
F):
options: Minimum
Cooling Setpoint Limit (section 5.6.8) to 95°F
NOTE
: The thermostat forces a 2°F “dead-band”
between the Night Setback Heating and Cooling
setpoints. While adjusting the Night Setback Heating
setpoint, the Night Setback Cooling setpoint may be
automatically increased to enforce a 2°F “dead-band”.
Likewise, while adjusting the Night Setback Cooling
setpoint, the Night Setback Heating setpoint may be
automatically reduced to enforce a 2°F “dead-band”.
5.8.2 NIGHT SETBACK OVERRIDE
While the Night Setback mode is active, the
alternate Night Setback setpoints can be temporarily
overridden, by using the normal temperature
adjustment screen. If the heating and cooling
setpoints are adjusted while Night Setback is active,
these temporary setpoints will remain active for the
current Night Setback Override time, unless they are
adjusted again, or the Night Setback mode is de-
activated.
Adjust the Night Setback Override setting using the
up/down arrow buttons. Press the center button to
save changes.
SECURITY LOCKOUT
SAVE
TOTAL KEYPAD LOCKOUT
PREVIOUS
SELECT OPTION
TEMP ADJUST ONLY
MAIN MENU
SET DATE AND TIME
HOLD
SECURITY LOCKOUT
PROGRAM
FAN
MODE
SETTINGS

13
AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
• Night Setback Override (default 2 hours):
options: 1 to 8 hours (in 15 minute increments)
5.8.3 NIGHT SETBACK DEMAND REDUCTION
Through Night Setback Demand Reduction Mode,
you can set the unit’s limited operation while Night
Setback is active.
Adjust the Night Setback Demand Reduction Mode
settings using the up/down arrow buttons. Press the
center button to save changes.
• No Demand Reduction (default):
While the
Night Setback input and the assigned Demand
Reduction input is active, the thermostat outputs
will operate normally based on the night setback
setpoints.
• No Auxiliary Heat:
While the Night Setback
input and the assigned Demand Reduction input
is active, auxiliary heat will not be activated,
regardless of the heating demand.
• No 2nd Stage Compressor:
While the Night
Setback input and the assigned Demand
Reduction input is active, the second stage heat
pump output will not be activated regardless of
the heating or cooling demand, and auxiliary heat
will not be activated, regardless of the heating
demand.
NOTE 1
: The thermostat must be confi gured for
auxiliary heat to access the Demand Reduction NO
AUXILIARY HEAT option.
NOTE 2
: The thermostat must be confi gured for
Multistage to access the Demand Reduction NO 2nd
STAGE COMP option.
5.8.4 NIGHT SETBACK FAN OPERATION
This option allows for the customization of fan settings
while Night Setback is active.
Adjust the Night Setback Fan settings using the up/
down arrow buttons. Press the center button to save
changes.
• Auto Operation Only (default):
While the Night
Setback input is active, the fan output will not be
activated unless Y1 or W is active.
• Fan Same As Occupied:
While the Night Setback
input is active, the fan output will operate normally.
5.8.5 NIGHT SETBACK DEHUMIDIFICATION
This option allows for the customization of humidity
control while Night Setback is active.
Adjust the Night Setback Dehumidifi cation settings
using the up/down arrow buttons. Press the center
button to save changes.
• On:
While the Night Setback input is active, the
dehumidifi cation output will operate normally.
• Off
(default):
While the Night Setback input is
active, the dehumidifi cation output will not be
activated, regardless of the dehumidifi cation
demand.
5.8.5.1 NIGHT SETBACK HUMIDITY CONTROL
If the Night Setback Dehumidifi cation Mode is set
to ON, the thermostat will prompt for Night Setback
Humidity Setpoints. Adjust the Night Setback
Humidity setpoints using the up/down arrow
buttons. Press the center button to save changes.
• Humidifi cation Setpoint (default 40%):
options: 10% to 45% (in 5% increments)
• Dehumidifi cation Setpoint (default 60%):
options: 45% to 80% (in 5% increments)
6.0 Service Needed
If the unit is not operating or not operating optimally, the
thermostat will display ‘Service Needed’ screen.
The next screen will display the model and serial number of
your ClimateMaster unit, the phone number of your installing
contractor, and the fault code and a description of the fault
that triggered the Service Needed screen
PRESS ANY BUTTON FOR
MORE INFORMATION
SERVICE
NEEDED
PHONE CONTRACTOR
SERVICE
NEEDED
BRAND NAME
MODEL NUMBER
SERIAL NUMBER
E7 = OVER/UNDER VOLTAGE

AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - U s e r M a n u a l
C r e a t e d : 8 M a y, 2 0 1 2
14
G e o t h e r m a l H e a t P u m p S y s t e m s
7.0 Revision History
R
M
A
N
U
F
A
C
T
U
R
E
R
CE
RT
IFIED
TO ARI
AS
C
O
M
P
LY
IN
G
W
IT
H
IS
O
STA
NDARD 13
25
6-
1
HEA
T PUMP
S
W
A
T
E
R
TO
AI
R
BR
IN
E
T
O
A
IR
97B0055N02
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be
changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000
for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warran-
ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
The management system governing the manufacture of ClimateMaster’s products is ISO 9001:2000 certifi ed.
© ClimateMaster, Inc. 2012
*97B0055N02*
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com
Created: 8 May, 2012
ISO 9001:2000
Certified
Quality: First & Always
Date
Page #
Description
8 May, 12
All
First Published