PDF User Manual

  1. Home
  2. Manuals
  3. ClimateMaster ATC32U01 iGate Installation Manual

ClimateMaster ATC32U01 iGate Installation Manual

Made by: ClimateMaster
Type: Installation Manual
Category: Thermostat
Pages: 16
Size: 0.18 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

Installation Manual 

97B0055N03

Rev.: 2/4/13

ATC32U01 iGate

 Communicating, 

Programmable Thermostat

Table of Contents

Section Title 

Page

  

Safety/Installation 

Considerations  3

1.0 

User Menu Settings 

  4

2.0 

Installer Menu Settings 

  6

 

2.1 

Installer Menu Settings Access 

  6

 2.2 

Thermostat 

Confi guration 

  6

3.0 System 

Confi guration 

  7

 3.1 

Airfl ow Selection 

  7

 3.2 

Option 

Selection 

 7

 3.3 

Unit 

Confi guration 

  8

 

3.4  

Pump Confi guration 

  8

 3.5 

Valve 

Confi guration 

  9

 3.6 

Multi-Unit 

Confi guration 

  9

4.0 Accessory 

Confi guration 

  10

 

4.1  

Air Filter 

  10

 4.2 

 

Humidifi er 

  10

 

4.3  

UV Lamp 

  10

Caution:

These instructions are intended to be used by the installer or service personnel.  End users are NOT advised to change or 
modify any of these settings.  Doing so may cause the equipment to stop working properly and/or may void the warranty on 
both the thermostat and the equipment.

Section Title 

Page

 

4.4  

Air Cleaner 

  10

5.0 

Input Dealer Information 

  11

6.0 Humidity 

Confi guration 

  11

7.0 Temperature 

Algorithm 

 

11

8.0 

Demand Reduction Confi guration    11

9.0 Service 

Mode 

 

12

 9.1 

Manual 

Operation 

 12

 9.2 

Control 

Diagnostics 

 12

 9.3 

Dipswitch 

Confi guration 

  13

 9.4 

Fault 

History 

 13

 

9.5 

Clear Fault History 

  14

 9.6 

Multi-Unit 

Diagnostics 

 14

 

9.7 

Multi-Unit Fault Information 

  15

10.0 Restore 

Defaults 

 

15

11.0 Revision 

History 

16

 


background image

This page was intentionally left blank.

 


background image

3

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

ClimateMaster’s ATC32U** Communicating, Programmable 
Thermostat is the perfect compliment to a ClimateMaster 
Geothermal Heat Pump System and represents a signifi cant 
advancement in thermostat communicating technology.  For 
homeowners, the ATC32U** provides highly customizable cli-
mate control features designed to maximize comfort and re-
duce the amount of energy consumed by the ClimateMaster 
Geothermal Heat Pump System.  For dealers, it represents 
a signifi cant, industry leading advancement in confi guration, 
monitoring and diagnostics from the thermostat. Please read 
the following instructions carefully to maximize the comfort 
and cost-saving potential of your ClimateMaster Geothermal 
Heat Pump System.

SAFETY CONSIDERATIONS

Improper wiring or installation may damage thermostat. Wir-
ing must conform to local and national electrical codes

 

WARNING! 

WARNING!  Before installing thermostat, turn off all 
power to unit.  There may be more than one power 
disconnect.  Electrical shock can cause personal 
injury or death.

INSTALLATION CONSIDERATIONS

The thermostat requires no batteries.  The thermostat is not 
a power stealing device and MUST have both R and C termi-
nals connected. See Diagram 1.

INSTALLATION
I. THERMOSTAT 

LOCATION

Thermostat should be mounted:

 • 

Approximately 5 ft. (1.5m) above fl oor.

 • 

Close to or in a frequently used room, preferably on an 
inside partitioning wall.

 • 

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

 • 

Close to a window, on an outside wall, or next to a 
door leading to the outside.

 • 

Exposed to direct light and heat from a lamp, sun, 
fi replace, or other temperature-radiating object which 
may cause a false reading.

 • 

Close to or in direct airfl ow from supply registers.

 • 

In areas with poor air circulation, such as behind a 
door or in an alcove.

II. THERMOSTAT INSTALLATION

 1.  Turn off all power to unit. 
 2.  If an existing thermostat is being replaced: 
 A.  Remove existing thermostat from wall.

B.  Disconnect wires from existing thermostat, one at 

a time.  Be careful not to allow wires to fall back 
into the wall.

C.  As each wire is disconnected, record wire color 

and terminal marking.

D.  Discard or recycle old thermostat.

 

NOTE

:  Mercury is a hazardous waste and MUST be dis-

posed of properly.

 

 3.  Separate the thermostat from base.
 4.  Route thermostat wires through hole in base.  Level 

base against wall (for aesthetic value only - thermo-
stat need not be leveled for proper operation) and 
mark wall through 2 mounting holes.

 5.  Drill two 3/16-in. mounting holes in wall where 

marked.  (Note: Mounting holes on thermostat are 
designed to fi t on a horizontal J-box).

 6.  Secure base to wall with 2 anchors and screws 

provided making sure all wires extend through hole in 
base.

 7.  Connect wires to proper terminal of the connector 

block in the thermostat.

 8.  Push any excess wire back into wall.  Excess wire 

inside the thermostat case can interfere with proper 
air fl ow across the temperature sensor.  Seal hole in 
wall to prevent air leaks.  Leaks can affect operation.

 9.  Install thermostat on base.
 10. Turn on power to the unit.

 

 

III. WIRING DIAGRAMS

All excess wire should be pushed back into the wall as far as 
possible.  Excess wire inside the thermostat plastic case may 
interfere with the air fl ow across the temperature sensor. 

ATC32U** Thermostat

24Vac Hot

DXM2

Control

24V

Comm +

A+

A+

Comm -

B-

B-

OD

ID

GND

Outdoor

Sensor

(Optional)

Remote Indoor

Sensor

(Optional)

24Vac Common

Gnd

R

C

Diagram 1: Thermostat Connections

Thermostat Connections

24V Common for Control Circuit

24V Supply for Control Circuit

A+ Communications 

(Positive)

B – 

Communications (Negative)

GND Ground
OD Outdoor 

Temperature 

Sensor 

ID Indoor 

Temperature 

Sensor

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

4

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

1.0  User Menu Settings

 

1.1  OFFSETS

 If 

you 

fi nd that the temperature displayed on the 

thermostat does not accurately represent the room 
temperature where the thermostat is located, this 
offset function compensates for the difference.  
The thermostat will apply an offset between what 
temperature the thermostat is measuring versus the 
temperature that is displayed.

 1.1.1 

TEMPERATURE 

OFFSET

 

The Temperature Offset function allows for 
calibration of the temperature sensor.

 

Adjust the Temperature Offset settings using the 
up/down arrow buttons.  Press the center button to 
save changes.

• 

Indoor Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)

• 

Remote Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)  

• 

Outdoor Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)

 1.1.2 

ANTICPATOR

 If 

you 

fi nd that the thermostat is overshooting or 

undershooting the temperature setpoint value, the 
Anticipator setting allows for adjustment to correct 
the temperature algorithm.  When the Anticipator 
value is set to a lower number, the thermostat 
becomes more sensitive and when the Anticipator 
value is raised, the thermostat becomes less 
sensitive.  If the thermostat is overshooting the 
temperature setpoint, adjust the Anticipator 
value up to reduce thermostat sensitivity.  If the 
thermostat is undershooting the temperature 
setpoint, adjust the Anticipator value down to 
increase thermostat sensitivity.

 

Adjust the Anticipator setting using the up/down 
arrow buttons.  Press the center button to save 
changes.

• 

Anticipator (default 3):  valid range:  1 to 9

 1.1.3 

DIFFERENTIAL

 

The Differential adjustment will vary the number of 
degrees from the setpoint before a call for heating 
or cooling is made.  Use this function if you fi nd 
that the thermostat is starting a call too soon/late 
or staging equipment up/down too quickly/slowly.  
For example, with a 1 ˚F 1st stage differential and 
a heating setpoint of 70˚F, your thermostat will not 
call for heating until the temperature is 69˚F.

 
 

Adjust the Differential setting using the up/down 
arrow buttons.  Navigate between Differentials 
using the left/right arrow buttons.  Press the center 
button to save changes.

• 

1st  Stage (default 1°F): 

 options:  1°F to 4°F 

(in 1°F increments)

• 

2nd Stage (default 1°F):

  options:  1°F to 4°F 

(in 1°F increments)

• 

Aux Heat (default 1°F)

:  options:  1°F to 4°F 

(in 1°F increments)

 

NOTE 1:  

The thermostat must be confi gured for 

Multistage by installer to access the 2nd Stage 
Differential setting.  The thermostat must be 
confi gured for Auxiliary Heat by installer to access 
the Auxiliary Heat Differential setting.

 

 NOTE 

2:

  The temperature control algorithm must 

be confi gured for Differential control to access the 
Differential settings by installer.

 1.1.4 

HUMIDITY 

OFFSET

 If 

you 

fi nd that the Humidity level displayed on 

the thermostat does not accurately represent the 
Humidity level of the room in which the thermostat 
is located, use the Humidity Offset function to 
calibrate the humidity sensor.

 

Adjust the Humidity Offset setting using the up/
down arrow buttons.  Press the center button to 
save changes.

 

• 

Indoor Humidity (default 0%): 

 options:  

 

 

-10% to +10% (in 1% increments)

 

1.2  CYCLES PER HOUR

 

The thermostat allows the user to adjust the maximum 

number of on/off cycles per hour to maintain the 
desired indoor temperature.

 

Adjust the Cycles per Hour setting using the up/

down arrow buttons.  Press the center button to save 
changes.

•  4 (default):  

operation will start no sooner than 15 

minutes after the previous call was initiated

• 6: 

 

operation will start no sooner than 10 minutes 

after the previous call was initiated (can provide 
tighter temperature control)

 

1.3  AUTO CHANGEOVER TIME

 

When the thermostat is confi gured for AUTO mode, 

the thermostat automatically selects heating or 
cooling mode depending on the indoor temperature.  
The Auto Changeover Time is the amount of time that 
elapses before operation switches from heating to 
cooling mode or from cooling to heating mode.

 

Adjust the Auto Changeover Time using the up/

down arrow buttons.  Press the center button to save 
changes.

•  Auto Change Over Time (default 15 minutes):  

options:  0 to 120 minutes (in 15 minute 
increments)

 


background image

5

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

SERVICE INFORMATION

FAULT STATUS

TEMPERATURE STATUS

CLEAR FAULT HISTORY

SYSTEM STATUS

SELECT OPTION   

 PREVIOUS                                           

 

1.4  DEMO MODE

 

Demo mode is designed to showcase heat pump 

operation when the unit is connected to an above 
ground water loop with the supply air being blown 
directly over the water loop.  

 

1.4.1 

ENTER DEMO MODE

 

To enter Demo Mode, navigate to the Service 
Information screen (Menu>Settings>Service  
Information) then press and hold the right arrow for 
5 seconds

 

1.4.2 

DEMO MODE OPERATION

 

Control Demo Mode operation parameters from the 
Demo Operation screen shown below.

DEMO  OPERATION

OUTDOOR

FAN  AUTO

78%

HEATING

RH     36%

HUMID  ON

72%

AUTO

SETPOINT

HEAT  70

COOL  74

RH

TEMP

MODE

FAN

MENU

 

The starting mode (heating or cooling) depends 
on the loop temperature at the time when Demo 
Mode is entered. The unit will operate in heating or 
cooling based upon the following algorithm.

 

1.4.3 

EXITING DEMO MODE

 

To exit demo mode, remove power to the 
thermostat.

Start in Cooling Mode

Start in Heating Mode

90°F

70°F

50°F

Solid lines represent heating operation. Dashed lines represent 
cooling operation.

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

6

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

2.2.2 AUXILIARY 

HEAT

Adjust the Auxiliary Heat options using the up/down arrow 
buttons.  Press the center button to save changes.
 

• Electric 

(default)

 – for control of a system with  

 

 

electric auxiliary heat

 

• Multi-Fuel

 – for control of a system with furnace  

 

 

for auxiliary heat

 

• No 

Auxiliary 

Heat

 – for control of a system with no 

  

auxiliary 

heat

 

2.2.2.1  AUXILIARY HEAT CONFIGURATION

 

Select Electric Auxiliary Heat mode

• 

Auxiliary Heat to Supplement Pump

• 

Auxiliary Heat for Emergency Heat Only 

2.2 THERMOSTAT 

CONFIGURATION

Upon initial power up, the communicating thermostat will 
prompt the installer for the thermostat confi guration settings.

Model number and software version of thermostat and 
software version of connected DXM2 are also displayed on 
this screen.

2.2.1 STAGING

Adjust the staging option using the up/down arrow buttons.  
Press the center button to save changes.
 

• Single 

Stage

 – for control of a single stage   

  

compressor 

applications

 

• Multi-Stage 

(default)

 – for control of multi-   

 

 

stage compressor applications

2.0  Installer Menu Settings

2.1 

INSTALLER MENU SETTINGS ACCESS

The Installer Settings can be accessed at any time from the 
Main Operating screen by holding the up/down arrows simul-
taneously for 5 seconds while the thermostat is in OFF Mode.

Thermostat Confi guration
System Confi guration
 Airfl ow Selection 

 

 Option 

Selection 

 

 Unit 

Confi guration 

 

 Pump 

Confi guration

 Valve 

Confi guration 

Accessory Confi guration
 Air 

Filter  

 Humidifi er   
 UV 

Lamp 

 

 Air 

Cleaner 

 

Input Dealer Information
Humidity Confi guration
Temperature Algorithm
Demand Reduction Confi guration
Service Mode
 Manual 

Operation

 Control 

Diagnostics

 Dipswitch 

Confi guration

 Fault 

History

 

Clear Fault History

Restore Defaults

Installer Menu Settings Overview

THERMOSTAT

CONFIGURATION

SINGLE STAGE

MULTI STAGE

SELECT OPTION   

 PREVIOUS                                          SAVE 

THERMOSTAT

CONFIGURATION

ELECTRIC

MULTI FUEL

NO AUXILIARY HEAT

SELECT OPTION   

 PREVIOUS                                          SAVE 

THERMOSTAT

CONFIGURATION

AUXILIARY HEAT  TO

SUPPLEMENT  HEAT  PUMP

AUXILIARY  HEAT  FOR

EMERGENCY  HEAT  ONLY

SELECT OPTION   

 PREVIOUS                                          SAVE 

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE CONTROL

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

DXM2                                                               1.0

ATC32U01                                                    C 2.1

SELECT OPTION   

 PREVIOUS

 


background image

7

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

THERMOSTAT

CONFIGURATION

PROGRAMMABLE

NON PROGRAMMABLE

NIGHT SETBACK

SELECT OPTION   

 PREVIOUS                                          SAVE 

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION   

 PREVIOUS

SYSTEM CONFIGURATION

AIRFLOW SELECTION

OPTION SELECTION

UNIT CONFIG                                           TE026

PUMP CONFIGURATION

SELECT OPTION   

 PREVIOUS                                          SAVE 

AIRFLOW SELECTION

                                                                      CFM

HEAT STAGE 1                                              600

HEAT STAGE 2                                              750 

AUXILIARY HEAT                                          850

EMERGENCY HEAT                                      850

COOL STAGE 1                                             525

COOL STAGE 2                                             700

COOL DEHUMID 1                                        425

COOL DEHUMID 2                                        550

CONTINUOUS FAN                                       350

HEAT OFF DELAY                                           60

COOL OFF DELAY                                          30

 PREVIOUS                                             NEXT 

3.0  System Confi guration

Use the System Confi guration option on the start-up screen 
to adjust critical equipment settings.

The System Confi guration information will be automatically 
obtained from each communicating control in the system.

Note 1: 

The Airfl ow Selection menu (section 3.1) will not be 

present if the connected communicating control is confi gured 
for No Blower.

Note 2: 

The Pump Confi guration menu (section 3.4) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER).

Note 3: 

The Valve Confi guration menu (section 3.5) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER). 

3.1 AIRFLOW 

SELECTION

Adjust the airfl ow settings for each system operating mode 
using the up/down arrow buttons.  Press the center button to 
select each item.

• Airfl ow Settings (defaults stored in control) 

valid range:  obtained from control (in 25 CFM 

increments)

•  Blower Off Delay (default 60 seconds) 

– valid 

range:  0 to 255 seconds (in 5 second increments)

NOTE 1: 

 The Airfl ow Settings will only be present if the 

connected communicating control is confi gured for ECM 
blower.

NOTE 2:

  If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

3.2 OPTION 

SELECTION

This option allows the confi guration of heat pump options to 
be modifi ed.

Adjust the Option settings using the up/down arrow buttons.  
Press the center button to select each item.

•  Motorized Valve (defaults stored in control)

 – 

valid range:  Off, On “On” delays compressor start 
until the valve is fully open. 

NOTE:

  “Motorized Valve” used here refers to a two-position 

motorized water valve, not to be confused with the modulating 
motorized water valve found in the LOOP CONFIG.

2.2.3 PROGRAMMING

Adjust the Programming options using the up/down arrow 
buttons.  Press the center button to save changes.
 

• Programmable 

(default)

 – enables 7-day    

  

programming

 

• Non-Programmable

 – disables 7-day programming

 

• Night 

Setback

 – enables night setback 

  

programming

NOTE

:  When the thermostat is confi gured for non-

programmable mode, the Display Date and Time setting 
defaults to NO.

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

8

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

UNIT CONFIGURATION

CURRENT CONFIG                                    TE026

HEAT PUMP FAMILY                                     TE

HEAT PUMP SIZE                                         026

BLOWER TYPE                                           ECM

LOOP CONFIG                                      VS PUMP

PARALLEL

SELECT OPTION   

 PREVIOUS                                          SAVE 

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

PUMP CONTROL                                   DELTA T

HEATING DELTA T                                             7

COOLING DELTA T                                          10

MAXIMUM HEAT LWT                                      80

MINIMUM COOL LWT                                      40

 PREVIOUS                                        SELECT 

•  Compressor ASCD (Anti-Short Cycle Delay 

(default stored in control)

 – valid range:  5 to 8 

(in 1 minute increments)

NOTE 1: 

 The Compressor Anti-Short Cycle Delay setting 

provides equipment protection by forcing the compressor to 
wait a few minutes before restarting.

NOTE 2: 

 If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

3.4 PUMP 

CONFIGURATION

vFlow™ vs internal flow control pump can be controlled either 
through temperature differential (Delta T) or can be set to 
specific speed (fixed; % of full speed for each heat and cool 
stage).

Configure temperature differentials at the thermostat for 
vFlow™ units with an internal flow control pump.

Adjust the Pump Configuration settings using the up/down 
arrow buttons.  Press the center button to select each item.

 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

Maximum Heat LWT (valid range based on specifi c model; 
refer to model IOM). Minimum Cool LWT (valid range based 
on specifi c model; refer to model IOM).

NOTE:

 Refer to section 3.6.3 for multi-unit confi guration 

instructions.

To control vs pump by fi xed speed, select ‘Pump Control’, 
press  , use down arrow to select ‘Fixed’, and press   to 
save.

Default stored in control. Valid range: 15% - 90% (in 1% 
increments)
Heating Stage 1   

Cooling Stage 1

Heating Stage 2   

Cooling Stage 2

If Pump Confi guration is set to ‘VS PUMP PARALLEL’, valid 
range changes to 50-90% (in 1% increments).

OPTION SELECTION

MOTORIZED VALVE                                      OFF

COMPRESSOR ASCD                                        5

 PREVIOUS                                             NEXT 

3.3 UNIT 

CONFIGURATION

Adjust the Unit Confi guration settings including Heat 
Pump Family, Heat Pump Size, Blower Type, and Loop 
Confi guration using the up/down arrow buttons.  Press the 
center button to select each item.

•  Heat Pump Family (default stored in control) – 

valid range:  TE, TY, TES, TEP, TRT, TSM

•  Heat Pump Size (default stored in control) 

– valid 

range:  depends on Heat Pump Family setting

•  Blower Type (default stored in control)

 – valid 

 

range:  NONE, PSC–2SPD, ECM, PSC–1SPD

• Loop 

Confi g (default stored in control)

 – valid 

range:  Other, VS PUMP SINGLE, VS PUMP 

 

PARALLEL, MOD VALVE, MOD VALVE MIN POS

Airfl ow, pump and valves can be confi gured from ‘System 
Confi guration’ screen.

Select ‘VS PUMP PARALLEL’ when applying an internal 
variable speed fl ow controller with other fl ow controllers on a 
single loop in parallel.

NOTE: 

Refer to section 3.6.3 for multi-unit confi guration 

instructions.

 

CAUTION! 

CAUTION! 

This is a Commercial option only and does not 

alter Residential unit operation.

 


background image

9

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

MODULATING VALVE

CONFIGURATION

DEG

HEATING DELTA T                                            8

COOLING DELTA T                                          15

 PREVIOUS                                            NEXT 

3.5 VALVE 

CONFIGURATION

Confi gure temperature differentials at the thermostat for 
vFlow™ units with a motorized modulating valve.

Adjust the Valve Confi guration settings using the up/down 
arrow buttons.  Press the center button to select each item.

 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

NOTE 1:

 Minimum and Maximum degree values are shown 

only when the control is confi gured with the appropriate values.

NOTE 2: 

Refer to section 3.6.3 for multi-unit confi guration 

instructions.

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

PUMP CONTROL                                       FIXED

HEATING STAGE 1                                        60%

COOLING STAGE 2                                        75%

COOLING STAGE 1                                       50%

COOLING STAGE 2                                       70%

 PREVIOUS                                        SELECT 

 

3.5.1 

MODULATING VALVE OFF POSITION

 

Click Next from section 3.5 to select the off position 
value for the modulating valve.

 
 NOTE: 

For certain commercial multi-unit 

applications, the modulating valve can be kept 
slightly  open by choosing values 3.3-4.0.

MODULATING VALVE

CONFIGURATION

OFF POSITION                                               3.8

 PREVIOUS                                        SELECT 

3.6 MULTI-UNIT 

CONFIGURATION

If multiple units are connected to one ATC thermostat upon 
unit start-up, the thermostat will automatically register the 
serial numbers of all units connected to it.

NOTE: 

Multiple units may be connected directly to the ATC 

thermostat or connected to one another in series, as shown by 
the fi gure below.

Two 
connections 
on DXM2 
board to allow 
for multi-unit 
installation

Or

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

10

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

 

3.6.2 

MULTI-UNIT OPTION SELECTION

 

In section 3.2, when an installer selects “Option 
Selection” from the System Confi guration menu, 
the installer may choose the unit to confi gure 
by the last 4 digits of its serial number from the 
following screen.

AIRFLOW SELECTION

TT026                                       S N - - - - - 1 2 3 4

TT026                                       S N - - - - - 5 6 7 8

TT038                                       S N - - - - - 9 0 1 2

 PREVIOUS                                        SELECT 

OPTION SELECTION

TT026                                       S N - - - - - 1 2 3 4

TT026                                       S N - - - - - 5 6 7 8

TT038                                       S N - - - - - 9 0 1 2

 PREVIOUS                                        SELECT 

 

3.6.3 

MULTI-UNIT, UNIT, PUMP, & VALVE 

CONFIGURATION

 To 

confi gure Unit, Pump, and Valve options in 

sections 3.3-3.5, the thermostat must be  
connected to only one unit at a time.

 3.6.1 

MULTI-UNIT 

AIRFLOW 

SELECTION

 

In section 3.1, when an installer selects “Airfl ow 
Selection” from the System Confi guration menu, 
the installer may choose the unit to confi gure 
by the last 4 digits of its serial number from the 
following screen.

4.0  Accessory Confi guration

A service message will fl ash at the top of the Main screen 
when a service timer expires to alert the user that it is time to 
service these options. Refer to DXM2 AOM for instructions on 
confi guring DIP switches to confi gure accessories. Follow the 
instructions below to set service timers.

4.1 AIR 

FILTER

This feature displays an alert to remind the user to change 
the air fi lter after the selected time has passed.

Adjust the Air Filter Reminder settings using the up/down 
arrow buttons.  Press the center button to save changes.
 

•  Cumulative Run Time (default Off) – 

valid range:  

 

 

Off, 400 to 3600 hours (in 100 hour increments

)

 

•  Calendar Time (default Off) – 

valid range:  Off, 3 

 

 

to 48 months (in 3 month increments)

4.2 HUMIDIFIER

This feature displays an alert to remind the user to change 
the humidifi er pad after the selected time has passed.

Adjust the Humidifi er Reminder settings using the up/down 
arrow buttons.  Press the center button to save changes.

 

•  Cumulative Run Time (default Off) 

– valid range:  

 

 

Off, 400 to 3600 hours (in 100 hour increments)

 

•  Calendar Time (default Off) 

– valid range:  Off, 3 

 

 

to 24 months (in 3 month increments)

 

4.3 UV 

LAMP

This feature displays an alert to remind the user to change 
the UV lamps after the selected time has passed.

Adjust the UV Lamp Reminder settings using the up/down 
arrow buttons.  Press the center button to save changes.
 

•  Cumulative Run Time (default Off) 

– valid range:  

 

 

Off, 400 to 3600 hours (in 100 hour increments)

 

•  Calendar Time (default Off)

 – valid range:  Off, 3 

 

 

to 48 months (in 3 month increments)

4.4 AIR 

CLEANER

This feature displays an alert to remind the user to clean the 
fi lter(s) after the selected time has passed.

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION   

 PREVIOUS

 


background image

11

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

5.0  Input Dealer Information

Enter/edit the Dealer Information settings, including Brand 
Name, Model Number, Serial Number, Contractor Name, and 
Contractor Phone number, using the up/down arrow buttons.  
Press the center button to save changes.

Adjust the Air Cleaner Reminder settings using the up/down 
arrow buttons.  Press the center button to save changes.
 

•  Cumulative Run Time (default Off)

 – valid range:  

 

 

Off, 400 to 3600 hours (in 100 hour increments)

 

•  Calendar Time (default Off) – 

valid range:  Off, 3 

 

 

to 24 months (in 3 month increments)

6.0  Humidity Confi guration

Confi gure humidity control settings (dehumidifi cation/
humidifi cation).

Adjust the Humidity Control settings using the up/down arrow 
buttons.  Press the center button to save changes.

• Dehumidifi cation

 – This logic will communicate 

a Dehumidifi cation output when the humidity is 
greater than the setpoint (acts as a dehumidistat).  
The Dehumidifi cation output will not be 
communicated when the humidity is below the 
setpoint.

• Humidifi cation

 – This logic will communicate a 

Humidifi cation output when the humidity is less 
than the setpoint (acts as a humidistat).  When the 
Humidifi cation output is active, the fan output will 
also be active. The Humidifi cation output will not 
be communicated when the humidity is above the 
setpoint.

• Both

 – Incorporates both Dehumidifi cation and 

Humidifi cation logic.

• None 

(default)

 – Dehumidifi cation 

and Humidifi cation outputs will not be 
communicated. 

7.0  Temperature Algorithm

Confi gure the logic the thermostat uses to meet the 
temperature setpoints.

 

 

•  Proportional Integral (default)

 – This logic will 

use a combination of temperature differential and 
operating time to determine the appropriate heating 
or cooling stages for operation (see NOTE 1).

•  Proportional Integral (No Down Staging)

 – This 

logic includes the Proportional Integral logic, but 
in addition the logic keeps all active heating or 
cooling stages energized until the demand is fully 
satisfi ed (see NOTE 1).

• Differential 

– This logic will only use temperature 

differential to determine the appropriate heating or 

cooling stages for operation.  This logic will keep 
all active heating or cooling stages energized until 
the demand is fully satisfi ed (see NOTE 2).

NOTE 1

:  The Proportional Integral options require fi rst stage 

heating or cooling to be active for a minimum of 5 minutes, 
before energizing second stage when confi gured for multi 
stage operation.

NOTE 2

:  The Differential option will activate fi rst stage heating 

or cooling when the temperature is more than the fi rst stage 
differential value (User Manual section 5.6.2.3), below or 
above the setpoint.  Second stage heating or cooling will be 
activated when the temperature is more than the fi rst and 
second stage differential values combined (User Manual 
section 5.6.2.3), below or above the setpoint.  Third stage 
heating will be activated when the temperature is more than 
the fi rst, second, and third stage differential values combined 
(User Manual section 5.6.2.3), below the setpoint.

8.0  Demand Reduction 
Confi guration

Demand Reduction is activated by an input signal at the unit 
control board to reduce the electric load while peak utility 
rates are high.  The Demand Reduction Confi guration mode 
selects which of the available unit control inputs is to be 
used as the activation signal. While a physical input signal is 
present at the selected input, the thermostat will implement 
load reduction by limiting operation or capacity. Refer to 
section 5.6.9 in the user manual (part number 97B0055N02) 
for more details on Demand Reduction.

Adjust the Demand Reduction Confi guration setting using 
the up/down arrow buttons.  Press the center button to save 
changes.

•  No Demand Reduction (default)

 – Demand 

Reduction operating mode will not be activated by 
a DXM2 input.  

• DXM2 

Inputs

 – Assigns a DXM2 input to activate 

Demand Reduction operating mode.

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION   

 PREVIOUS

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

12

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

9.0  Service Mode

9.1 MANUAL 

OPERATION

Manual Operation mode allows the service personnel to 
manually command operation for any of the thermostat 
outputs, blower speed, as well as pump speed or valve 
position to help troubleshoot specifi c components.

NOTE 1

:  The ECM Airfl ow adjustment will not be present if the 

connected communicating control (DXM2) is not confi gured for 
ECM (section 3.3).

NOTE 2

:  The Pump Speed adjustment will not be present 

if the connected communicating control (DXM2) is not 
confi gured for Pump (section 3.3).

NOTE 3

:  The Valve Position adjustment will not be present if 

the connected communicating control (DXM2) is confi gured for 
Valve (section 3.1).

NOTE 4

:  If multiple units are connected to one thermostat, 

refer to section 9.6

SERVICE MODE

MANUAL OPERATION

CONTROL DIAGNOSTICS

DIPSWITCH CONFIG

FAULT  HISTORY

CLEAR FAULT HISTORY

SELECT OPTION   

 PREVIOUS                                        SELECT 

MANUAL OPERATING MODE

Y1

COMM   OUTPUT

OFF

Y2

COMM   OUTPUT

OFF

W

COMM   OUTPUT

OFF

O

COMM   OUTPUT

OFF

G

COMM   OUTPUT

OFF

H

COMM   OUTPUT

OFF

DH

COMM   OUTPUT

OFF

ECM

AIRFLOW

0

PUMP SPEED

0%

TEST

MODE

OFF

SELECT OPTION   

 PREVIOUS                                        SELECT 

9.2 CONTROL 

DIAGNOSTICS

Control Diagnostics mode allows the service personnel to 
view the status of all physical inputs, switches, temperature 
sensor readings, as well as the operational status of the 
pump at the thermostat.

Navigate between diagnostic screens using the left/right 
arrow buttons.  

NOTE 1

:  The Pump Status will not be present if the connected 

communicating control (DXM2) is not confi gured for Pump 
(section 3.3).

NOTE 2

:  If multiple units are connected to one thermostat, 

refer to section 9.6.

CONTROL DIAGNOSTICS

PUMP OPERATION

PUMP SPEED                                               60%

PUMP WATTS                                               140

FLOW RATE GPM                                         7.4

 PREVIOUS                                        

CONTROL STATUS

TEMPERATURES

LT1    TEMP                                                    38.1

LT2    TEMP                                                    79.9

COMP   DISCHARGE                                   157.7

HOT   WATER   EWT                                    121.5

LEAVING AIR                                                  75.1

LEAVING WATER                                           73.3

ENTERING WATER                                        78.5

CONTROL VOLTAGE                                     26.4

ECM    BLOWER   RPM                                  550

ECM    TARGET    CFM                                  800

ECM    BLWR    STATIC                                  N/A

 PREVIOUS                                             NEXT 

CONTROL DIAGNOSTICS

HP SWITCH                                                     CL

LOC SWITCH                                                   CL

Y1 PHYSICAL INPUT                                      ON

Y2 PHYSICAL INPUT                                     OFF

W PHYSICAL INPUT                                      OFF

O PHYSICAL INPUT                                       ON

G PHYSICAL INPUT                                       ON

H PHYSICAL INPUT                                       OFF

EMERG SHUTDOWN                                     OFF

NIGHT SETBACK                                           OFF

OVR INPUT                                                     OFF

 PREVIOUS                                             NEXT 

 


background image

13

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

9.3 DIPSWITCH 

CONFIGURATION

Dipswitch Confi guration mode allows the service personnel 
to view the status of all dipswitch settings for the connected 
communicating control (DXM2/AXM) at the thermostat. 

Navigate between confi guration screens using the left/right 
arrow buttons.  
  

NOTE 1

:  The unit control dipswitch settings cannot be 

changed from the thermostat.

NOTE 2

:  If multiple units are connected to one thermostat, 

refer to section 9.6.

CONTROL CONFIGURATION

DIPSWITCH S1

1     ON   UPS   ENABLED

2     ON   DUAL   COMP   STG   1

3     ON   HEAT   PUMP   TSTAT

4     ON   RV  O   THERMOSTAT

5     ON   DEHUMID   OFF

6     ON   EH2   AUX   HEAT

7     ON   BOILERLESS

8     ON   SEE   DXM2   AOM

 PREVIOUS                                             NEXT 

CONTROL CONFIGURATION

DIPSWITCH S2

1    ON \  ACCESSORY 1

2    ON   ACCESSORY 2

3    ON/

4    ON \ ACCESSORY 2

5    ON ACTIVE W/ COMP

6    ON /

7    ON   H    DEHUM   INPUT

8    ON   FACTORY    SETTING

 PREVIOUS                                             NEXT 

CONTROL CONFIGURATION

DIPSWITCH S3

1    ON    FACTORY    SETTING

2    OFF   HWG   TEST   OFF

3    OFF   HWG   SP   125

4    OFF   HWG   DISABLED

JW3 LT1 SETTING WELL

 PREVIOUS                                        

9.4 FAULT 

HISTORY

Fault History mode displays the fi ve most recent stored fault 
codes for the connected communicating control (DXM2).

Navigate between control fault codes using the up/down 
arrow buttons.  Press the center button to view more 
information about the highlighted fault code.

NOTE

:  If multiple units are connected to one thermostat, refer 

to section 9.7.

9.4.1 Temperature 

Conditions

Displays detailed temperature readings that were 
recorded at the time the fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.6.

TT038    SN - - - - - 0 1 2 3

LAST 5 FAULTS

LT1   LOW   WATER   TEMP

NO   FAULT

NO   FAULT

NO   FAULT

NO   FAULT

                                                                  NEXT 

 PREVIOUS                                        SELECT 

FAULT CONDITION MENU

LT1   LOW   WATER   TEMP

HEAT   1   11:11 AM   11/14

FAULT   TEMP   CONDITIONS

FAULT   FLOW   CONDITIONS

FAULT   I/O   CONDITIONS

FAULT CONFIG COND

FAULT POSSIBLE CAUSES

 PREVIOUS                                        SELECT 

FAULT TEMPERATURE CONDITIONS

LT1   LOW   WATER   TEMP

HEAT   1   11:11 AM   11/14

LT1    TEMP                                                    28.1

LT2    TEMP                                                    97.3

HOT   WATER   EWT                                    121.5

COMP   DISCHARGE                                   157.7

LEAVING AIR                                                  92.7

LEAVING WATER                                           34.9

ENTERING WATER                                        42.1

CONTROL VOLTAGE                                     26.4

 PREVIOUS                                        

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

14

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

9.4.2 Flow 

Conditions

Displays detailed blower and pump speed / valve 
position readings that were recorded at the time the 
fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

9.4.3 Input/Output 

Conditions

Displays the status of all physical and communicated 
inputs, switches, and control outputs that were 
recorded at the time the fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

9.4.4 Confi guration Conditions

Displays the status of all dipswitch settings that were 
recorded at the time the fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

FAULT FLOW CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

ECM   TARGET   CFM                                     800

ECM   BLOWER   RPM                                   550

FLOW   RATE   GPM                                       6.5

PUMP   SPEED                                              60%

VALVE POSITION                                            0%

 PREVIOUS                                        

FAULT I / O CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

       TSTAT           SAFETY           OUTPT

CONV COMM

HPS

Y1

Y1

LOC

CC

Y2

Y2

CO

RV

W

W

ACC1

O

O

OUTPT

ACC2

G

G

FAN

AL1

H

H

HWG

EH1

OVR

DH

PUMP

EH2

 PREVIOUS                                        

FAULT   CONFG   CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

        S1           S2              S3

1      ON      1    ON       1    ON

2      ON      2    ON       2    OFF

3      ON      3    ON       3    OFF

4      ON      4    ON       4    OFF

5      ON      5    ON

6      ON      6    ON       LT1    WELL

7      ON      7    ON       LT2    WELL

8      ON      8    ON

 PREVIOUS                                        

9.5 

CLEAR FAULT HISTORY

Clear Fault History will clear all fault codes stored in the 
thermostat as well as the fault history in any connected 
communicating controls (DXM2/AXM).

9.6 MULT-UNIT 

DIAGNOSTICS

If multiple units are connected to one thermostat when 
Manual Operation, Control Diagnostics, or Dipstick 
Confi guration is selected, the service personnel will see a 
screen to select a specifi c unit by the last 4 digits of its serial 
number.

NOTE:

 Multiple units may be connected directly to the ATC 

thermostat or connected to one another in series, as shown by 
the fi gure below.

9.4.5 Possible 

Causes

 

Possible causes as to why the fault occurred

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

POSSIBLE FAULT CAUSES

LOW  WATER  COIL  TEMP

LOW  WATER  TEMP - HTG

LOW  WATER  FLOW - HTG

LOW  REFRIG  CHARGE - HTG

INCORRECT  LT1  SETTING

BAD  LT1  THERMISTOR

 PREVIOUS                                        

Two 
connections 
on DXM2 
board to allow 
for multi-unit 
installation

Or

 


background image

15

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

CONTROL DIAGNOSTICS

TT026                                       S N - - - - - 1 2 3 4

TT026                                       S N - - - - - 5 6 7 8

TT038                                       S N - - - - - 9 0 1 2

 PREVIOUS                                        SELECT 

9.7 

MULT-UNIT FAULT INFO

When multiple units are connected to one thermostat, 
UNLIKE Mult-Unit Diagnostics, the service personnel views 
each units’ fault information by selecting the next option.

10.0  Restore Defaults

The thermostat will reset all settings, excluding the 
thermostat confi guration settings (section 2), to their factory 
defaults.

TT038              S N - - - - - 0 1 2 3

LAST  5  FAULTS

LT1  LOW  WATER  TEMP

NO FAULT

NO FAULT

NO FAULT

NO FAULT

                                                                  NEXT 

 PREVIOUS                                        SELECT 

 


background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

16

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

R

M

A

N

U

F

A

C

T

U

R

E

R

CE

RT

IFIED

TO ARI

AS

C

O

M

P

LY

IN

G

W
IT

H

IS

O

STA

NDARD 13

25

6-

1

HEA

T PUMP

S

W

A

T

E

R

TO

AI

R

BR

IN

E

T

O

A

IR

97B0055N03

ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be 

changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 

for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warran-

ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
The management system governing the manufacture of ClimateMaster’s products is ISO 9001:2008 certifi ed.
 

 

 

 

   

               © ClimateMaster, Inc. 2012 

*97B0055N03*

7300 S.W. 44th Street

Oklahoma City, OK 73179

Phone: 405-745-6000

Fax: 405-745-6058

climatemaster.com

Rev.: 4 Feb., 2013

ISO 9001:2008
Certified

Quality: First & Always

Date

Page #

Description

4 Feb. 13

8

Unit Confi g Section Updated

1 Oct., 12

8-9

Unit Confi g, Pump Confi g and Valve Confi g Sections Updated

1 Oct., 12

6

Tstat Confi g Section and Installer Setting Screen Updated

2 July, 12

Various

Demo Mode, Auxiliary Heat Confi guration and Multiple Unit 
Information and Screen Shots Added

8 May, 12

All

First Published

11.0  Revision History