ATA11U03

Non-Programmable 

Heat Pump Thermostat

Installation Manual

97B0082N06

Revised: 16 September, 2013

FOR INSTALLER  

AND OWNER ONLY

Table of Contents

Safety Considerations 

3

General 3
Package Contents 

3

Installation Considerations 

3

Power 3
Wiring 3
Thermostat Location 

3

Installation 4
Configuration 

5-8

Entering and Exiting Configuration Mode 

5

Configuration Options 

5

Exiting Configuration Mode 

8

System Start-Up and Checkout 

8

Installer Test Mode 

8

Terminating Installer Test 

8

Checklist 

8

Operation 

9

Mode Selection 

9

Fan Selection 

9

Fan Display 

9

Set Temperature Selection 

9

Display Lighting 

9

Remote Sensor Temperature Display 

9

Timers 10
Five-Minute Compressor Timeguard 

10

Minimum On Timer 

10

Cycle Timer 

10

Troubleshooting 

10

Space Temperature Sensor Failure 

10

Memory Failure 

10

Equipment Outputs 

10

Wiring Diagrams 

10

Thermostat Configuration Record 

11

Revision History 

12

 


background image

2

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

This Page Intentionally Left Blank

 


background image

3

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

General

Safety Considerations

Read and follow manufacturer instructions carefully. 
Follow all local electrical codes during installation. All 
wiring must conform to local and national electrical 
codes. Improper wiring or installation may damage 
thermostat.

Recognize safety information. This is the safety alert 
symbol   . When the safety alert symbol is present on 
equipment or in the instruction manual, be alert to the 
potential for personal injury.

Understand the signal words 

DANGER, WARNING,

 

and 

CAUTION

. These words are used with the safety 

alert symbol. 

DANGER

 identifies the most serious 

hazards which will result in severe personal injury or 
death. 

WARNING

 signifies a hazard which could result 

in personal injury or death. 

CAUTION

 is used to identify 

unsafe practices which would result in minor personal 
injury or property damage.

General

Non-programmable heat pump thermostats are wall-
mounted, low-voltage thermostats that maintain 
room temperature by con trolling the operation of 
heat pump systems. A variety of features are provided 
including sepa rate heating and cooling set points, auto 
changeover, keypad lockout, back lighting, and built-in 
installer test.

Figure 1: Non-Programmable Heat Pump Thermostat

This Installation Instruction covers installation, 
configuration, and start up of the non-programmable heat 
pump thermostat. 

This manual is intended for installer and owner only.

Package Contents

1 - Thermostat
1 - Backplate (mounting base with terminal strips)
2 - Screws and anchors
3 - User Operating Manual (review with end user)

Installation Considerations
Power

 - 24 volt AC (50/60 Hz) power via the Rc/Rh and C 

terminals. Rc and Rh terminals are connected via factory-
installed jumper wire. 

Wiring 

-

 

Requires 6 conductor thermostat cable for 2 fan 

speed units. The wire length should be no more than 250 
ft (76 m). Use 22 AWG (American Wire Gage) for normal 
wiring applications. Continuous wire lengths over 100 ft 
(30.5 m) should use 20 AWG or larger.
Reconfigure if unit is only 1 fan speed, see option 40.

Note: This thermostat has battery compartment but is 

non-operational and must be wired.

Thermostat Location

 — 

The thermostat should be mounted: 
•  approximately 5 ft (1.5 m) from the floor
•  in the conditioned space, preferably on an inside wall 

on a section of wall without pipes or ductwork

The thermostat should NOT be mounted:
•  close to a window, on an outside wall, or next to a 

door leading to the outside

•  where exposed to direct light and heat or any other 

temperature-radi ating object which may cause a false 
reading

•  close to or in direct airflow from supply registers or 

return air grille in areas with poor air circulation.

 

 

 


background image

4

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

Installation - 

To install the thermostat, perform the 

following procedure:
1.  Turn off all power to equipment.

Installation

� 

CAUTION!

 �

ENVIRONMENTAL HAZARD!

 Failure to follow this 

caution may result in environmental damage. Mercury is a 

hazardous waste. Federal regulations require that mercury 

be disposed of properly.

2.  If an existing thermostat is being replaced:

a.  Remove existing thermostat from wall.
b.  Record the wire color and old termi nal marking.
c.  Disconnect wires from existing thermostat, one 

at a time. Be careful not to allow wires to fall back 
into the wall.

d.  Recycle old thermostats that contain Mercury.

Figure 2: Backplate Mounting

2.A   

New Installation -

 

 

a.  Optional - install 2x4 box horizontal. 

 

b.  Run new wiring, must meet all NEC and local  

 

 codes.

 

c.   Note each wire color and connection at unit.

3.  Press the thumb release at the top of the thermostat 

and pull apart carefully to separate back-plate from 

the thermostat.

4.  Pull thermostat wires through large hole in 

backplate. Level back-plate against wall (for 
appearance only, the thermostat does not need be 
leveled for proper operation) and mark wall through 
two mounting holes. See Fig. 2.

5.  For direct mounting to wall, drill two 3/16-in. 

mounting holes in the wall where marked, use 
anchors provided.

6.  Secure backplate to box or wall with two screws 

provided. Make sure all wires extend through hole in 
backplate.

7.  Adjust length and routing of each wire to reach 

proper connector block and terminal on backplate 
with 1/4-in. (6 mm) of extra wire. Strip only 1/4-in. of 

insulation from each wire to prevent adjacent wires 
from shorting together when connected.

8.  Match and connect equipment wires to proper 

terminals of the connector blocks (see Fig. 3).

9.  Push any excess wire into wall and against backplate. 

Seal hole in wall to prevent air leaks. Leaks can affect 
operation.

10.  Attach thermostat to backplate by inserting tab on 

bottom edge and hinging up until top snap secures.

11.  Turn ON power to unit.

When power is applied, all display icons are lit for 2 
seconds to test the display. Following this, the equipment 
type for which the thermostat is configured is displayed 
for an additional 2 seconds.

� 

CAUTION!

 �

Failure to follow this caution may result in equipment 

damage or improper operation. Improper wiring or 

installation may damage the thermostat. Check to make 

sure wiring is correct before proceeding with installation or 

turning on unit.

Figure 3: Terminal Strip (wiring diagram - see figure 7)

� 

WARNING!

 �

WARNING!

 Electrical shock can cause personal injury and 

death. Before installing thermostat, shut off all power to 

this equipment during installation. There may be more than 

one power disconnect. Tag all disconnect loca tions to alert 

others not to restore power until work is completed.

 


background image

5

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

Configuration

Configuration

Configuration options enable the installer to configure 
the thermostat for a particular installation. These 
configuration options are stored to the internal 
memory so they are retained through a power outage. 
The availability of some configuration options will be 
dependent upon other conditions in the thermostat. 

Table 1: Configuration Options Summary

Entering and Exiting Configuration Mode

 - Press and 

hold the fan button for about 10 seconds. After the 10 
second period the Option number “02” will appear 
flashing in the space temperature location. The value of 
the configuration setting will be displayed in the set point 
location.

The parameter that is changeable will be determined by 
the flashing area. The up or down buttons can be used 

to select a new value. The mode button can be used to 
toggle/move the selection between the configuration 
option number and the configuration value. To exit the 
installer configuration screen, press the fan button. If 
no button is pressed for three minutes, the installer 
configuration screen will time out and the thermostat will 
return to normal operation.

All changes to the installer configuration are saved as 
they are made. There is no provision to exit the installer 
configuration and cancel the change. The installer will 
have to manually change a configuration back to its 
original value to “undo” a change.

Configuration Options

OPTION 02 — REMOTE SENSOR SELECTION

 — A 

remote sensor 17B0008N05 (for inside duet), or ASW06 
(for wall) can be connected to the S1 and S2 screw 
terminals to sense either remote space, return air, 
outdoor air, or supply air temperature.

Selection: rA, Od, SA, rS
rA* — Sense return air temperature
 

* Display only, not used for temperature control.

Od*— Sense outdoor air temperature 
SA*— Sense supply air temperature 
rS — Sense remote space temperature
Default: rS

Note: Option 02 cannot be changed from the rS setting 

if Option 05 is set to either r or Lr.

OPTION 03 — ENGLISH/METRIC

 — This configuration 

selects be-tween Fahrenheit (F) and Celsius (C) operation.

Selection: F, C
Default: F

OPTION 05 — SPACE TEMPERATURE SENSING 

— 

This selection determines which sensor the control 
will use for measuring space temperature. Space 
temperature can be sensed in one of three ways: the 
local sensor (L) located on the thermostat, the remote 
sensor (r), or the average of local and remote sensors (Lr).

Selection: L, r, Lr (Do not use)
L — Local sensor: The onboard thermistor is the 
control point for the temperature control algorithm.
r — Remote space sensor: The remote space 
temperature is the control point for the temperature 
control algorithm.

NOTE: This selection is only available if Option 02 

indicates that the S1, S2 terminals are sensing a 

remote space temperature.

 

Default: r 

� 

WARNING!

 �

WARNING!

 User should not reconfigure installer set up. 

Equipment damage could occur.

� 

NOTICE

 �

Wall thermostat requires configurating for on board sensing.  

Installer must configure 05 to L unless remote sensor  

is used.

Option 

Number

Configuration

Default

02

Remote Sensor Selection

rS

03

English/Metric

F

05

Space Temperature Sensing

r

07

Equipment DDC Controller

OF

11

Deadband between Heating and Cooling Set Points

5

13

Space Temperature Display Adjustment (Offset)

0

15

Auto Mode Availability

ON

16 

Maximum Cycles Per Hour

4

18

Backlight Configuration

OF

20

Outdoor Air Temperature Adjustment (Offset)

0

21

Keypad Lockout

OF

26

Minimum Cooling Set Point

60

27 

Maximum Heating Set Point

85

39

Temperature Display

St

40

Fan Speeds Selection

2

 


background image

6

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

OPTION 07 — EQUIPMENT DDC CONTROLLER

 — 

This selection should be set to ON when control is to be 
used with ClimateMaster heat pump units, the DXM or 
CXM will take care of the timeguard and cycle timers. The 
minimum on time is still controlled by the thermostat. Off 
setting could delay compressor start by 12 minutes.

Selection: OF(F), ON
OF — Timeguard and cycle timers are enabled 
ON — Timeguard and cycle timers are disabled 
Default: OF (off)

OPTION 11 — DEADBAND BETWEEN HEATING 

AND COOLING SET POINTS 

— This selection allows 

the installer to choose how much differential will exist 
between the heating and cooling set points.

Selection: 1 to 10 (F or C)
Default: 5

OPTION 13 — SPACE TEMPERATURE DISPLAY 

ADJUSTMENT (OFFSET) 

— This configuration is 

the number of degrees to be added to the displayed 
temperature to calibrate or deliberately miscalibrate 
the measured space temperature. This selection is not 
available to the installer if Option 39 is set to SP (set 
point display).

Selection: –5 to 5 F (always in F) Default: 0

OPTION 15 — AUTO MODE AVAILABILITY 

— The 

ON selection will allow automatic changeover between 
heating and cooling as demand requires a mode 
selection. OF maintains either heating or cooling mode 
selection only.

Selection: ON, OF(F)
ON — Auto mode 
OF — Manual mode
Default: ON

OPTION 16 — MAX CYCLES PER HOUR

 — The 

maximum cycle rate is limited by internal timers to the 
selected number of cycles per hour. Selection of a higher 
number causes faster cycling resulting in more constant 
room temperature.

Selection: 4, 6, 8
4 — The Y1 output will be energized at most twice 
per hour. When an output is energized, it will not be 
energized again for 15 minutes.
6 — The Y1 output will be energized at most four 
times per hour. When an output is energized, it will 
not be energized again for 10 minutes.
8 — The Y1 output will be energized at most six times 
per hour. When an output is energized, it will not be 

energized again for 8 minutes.
Default: 4

OPTION 18 — BACKLIGHT CONFIGURATION

 —

When set to OF (off), the backlight will be lit for 10 
seconds after a button is pressed. After 10 seconds of no 
button presses, the backlight turns off.

When ON is enabled, the backlight will normally be 
on and dim in appearance. The backlight brightness 
becomes brighter when a button is pressed. After 10 
seconds of no button presses, the backlight will return to 
the dimmer level until another button press occurs.

Selection: OF(F), ON
Default: ON with 24 vac power; for batteries only, 
default is OFF.

OPTION 20 — OUTDOOR AIR TEMPERATURE 

DISPLAY ADJUSTMENT (OFFSET)

 — This selection 

is not available unless Option 02 is set to Od (outdoor 
air temperature) and a valid sensor is connected to S1 
and S2 terminals. It allows the calibration, or deliberate 
mis-calibration of the outdoor air temperature sensor 
reading.

Selection: –5 to 5 (number of degrees F added to the 
outdoor air temperature reading to “calibrate” the 
temperature sensor)
Default: 0

OPTION 21 — KEYPAD LOCKOUT WITH PASSCODE

 

— The thermostat is shipped with the keypad fully 
accessible. This option allows the installer to limit access 
to the keypad.

Selection: OF(F), 1, cd
OF — When set to OF, the user has full access to the 
keypad
1 — The user will only have access to modify the set 
points (within the set point limits of Option 26 and 
Option 27). The padlock icon will be displayed until 
the user presses and holds the up and down buttons 
simultaneously for five seconds to unlock the keypad. 
Once the keypad is unlocked, the user has full access 
to the thermostat functionality. The keypad returns 
to the locked condition after no buttons have been 
pressed for two minutes.
cd — The entire keypad is locked and the padlock 
icon is displayed. When the user presses a button 
the backlight turns on to maximum brightness for 10 
seconds and a “--” is displayed in the temperature 
setting. The user must enter the unlock code and 
press the mode button to unlock the thermostat. 
The padlock icon will then turn off and the user will 

Configuration

 


background image

7

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

have full access to the thermostat functionality. The 
thermostat will lock after no buttons have been 
pressed for two minutes.

If the option value is set to “cd”, the mode, up and 
down buttons will work as follows:
1.  Pressing the mode button once will display the 

flashing Option number (21).

2.  Pressing the mode button again and the option 

value will flash OF, 1 or cd.

3.  Pressing the mode button a third time will display 

the keypad lock icon and the code entry values 
(see Fig. 4). The up and down buttons will allow 
the selection of a code value between 00 to 199.

4.  Pressing the mode key again will return the focus 

to the Option number (21) .

Default: OF (off)

 

OPTION 26 — MINIMUM COOLING SET POINT

 

— This parameter establishes the minimum cooling 
set point that the user is allowed to set. Otherwise, 
the equipment type allows both heating and cooling 
operation, so the minimum is 60 F plus Option 11 
(deadband) and the maximum is 90 F.

Selection: minimum = 60 F + deadband, maximum 
= 90 F 
Default: 60 F (based on the adjustable deadband 
default = 5)

OPTION 27 — MAXIMUM HEATING SET POINT

 — 

This parameter establishes the maximum heating set 
point that the user is allowed to set. The equipment 

type allows both heating and cooling operations, so the 
minimum is 50 F plus Option 11 (deadband) and the 
maximum is 90 F.

Selection: minimum = 50 F, maximum = 90 F – 
deadband
Default: 85 F (based on adjustable deadband default = 5)

OPTION 39 — TEMPERATURE DISPLAY

 — This 

configuration allows the installer to select either the 
set point temperature or the space temperature to be 
displayed on the large temperature display digits.

When the option St is chosen, the space temperature, as 
defined by Option 05, is displayed using the traditional 
space temperature digits on the LCD display. The current 
set temperature is displayed using the normal set-point 
display digits.

When SP is chosen, the current set point temperature is 
displayed using the traditional space temperature digits 
on the LCD display. The normal set point display digits 
remain blank. Space temperature is not be displayed, but 
if a problem occurs with the actual space temperature 
sensor, the characters “- -” will be displayed instead of 
the set temperature to indicate that the temperature 
sensor has an error.

NOTE: The “Actual Temp” icon is not to be 

displayed when the sensor type is set to Set Point 

display (SP).

Selection: St, SP
Default: St (Space Temperature)

OPTION 40 — FAN SPEEDS

 — This configuration 

allows the installer to select the number of fan speeds 
the system with operate with. When set to 1, the single 
speed fan only will be available (LO). When set to 2, both 
fan speeds will be available (LO & HI).

Selection: 1, 2
Default: 2
Check unit submittal for fan speeds available. Set 
accordingly.

OPTION 99 — RESET TO FACTORY DEFAULTS

 — This 

configuration allows the installer to return the thermostat 
to its “out of the box” settings. Not recommended  
to use.

IMPORTANT:

 All configuration settings, mode, fan and 

set point settings which have been manually entered will 
be lost and will require resetting.

When this setting is first selected, 99 will be displayed in 
the space temperature location and an initial value of 10 

Configuration

Figure 4: Selection of Code Value

 


background image

8

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

will be displayed in the set-point location.
To initiate factory defaults, the installer then presses the 
mode button until the 10 is flashing. The installer then 
presses and holds the down button. While the down 
button is held, the 10 will count down from 10 to zero at 
a rate of 2 counts per second (5 seconds total). When the 
value reaches zero, all display segments are turned on for 
five seconds and the factory defaults are restored. If at 
any time during the countdown the installer releases the 
down button, the countdown terminates and the display 
returns to the starting value of 10.

Exiting Configuration Mode

 - To exit the configuration 

mode, press the fan button.

SYSTEM START-UP AND CHECKOUT
Installer Test Mode

 — This thermostat has a built-

in installer test capability. It allows easy operation of 
equipment without delays or set point adjustments to 
force heating or cooling. To enter installer test mode, 
press and hold the fan button for 15 seconds (after 10 
seconds installer configuration is entered; a continuous 
15 seconds and installer test is entered). At the start of 
installer test, the mode is Off, the fan is “fan auto” and 
the set point display displays “InS.”

NOTE: Unit must be powered up and CXM/DXM 

in test mode to disable unit timers or compressor 

not energized for more than 5 minutes.

The mode button is used to change the system operating 
mode to test the heating and cooling equipment. Auto 
mode is not available during installer test.

When the mode is set to heat, “H” is displayed, heating 
is energized for 180 seconds. During the installer test 
operation, the “on” icon is displayed.

At the end of the equipment test cycle the mode returns to 
OFF.

The LCD display counts down the time remaining 
(in seconds, from 180 to 0) for each stage when the 
equipment is energized. See Fig. 5.

The same procedure is repeated for the cool mode. “C” 
is displayed when cooling is active.

The test of a heating or cooling cycle can be terminated 
before the timer counts down to zero by pressing the 
mode button.

Pressing the fan button alternates the fan selection 
between fan auto and fan on and the fan output follows 
accordingly. There is no timer associated with the installer 
testing of the fan operation.

Terminating Installer Test

 — After 15 minutes of no 

button presses by the installer, installer test is terminated.

Pressing the up button, down button, or cycling 
thermostat power at any time during installer test 
terminates the installer test and returns the thermostat to 
normal operation.

Figure 5: Installer Test Mode

Checklist

 — The following installer checklist should be 

performed after completing installation:
1.  Run equipment through several heating and cooling 

cycles to ensure proper operation. To operate the 
thermostat in its normal operating mode, consult the 
User Operating Manual.

2.  If the equipment is to be left in operation, the 

set points and operating mode must be properly 
selected.

3.  Put away tools and instruments and clean up debris.
4.  Review and leave this manual and User Operating 

Manual with owner.

 

 

 


background image

9

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

OPERATION

Mode Selection

 — The mode button allows the user to 

display the off, heat, cool, auto icons. Pressing the mode 
button cycles through the available modes based on the 
equipment selection from Option 15. Available choices 
are listed in Table 2.

Table 2: Mode Selection

Fan Selection 

— The thermostat offers two continuous 

(ON) or two cycling (AUTO) and two fan speeds high (HI) 
or low (LO). Pressing the fan button cycles through the 
following displays fan on LO, fan on HI, auto fan LO, auto 
fan HI.

Fan Display

 — If Option 39 is set to display set point 

(SP), then the two-speed fan setting remains on the 
display. If the current fan speed is not shown on the 
display, the first press of the fan button will display the 
current selection. The fan selection can only be changed 
by a fan button press when the current selection is shown 
on the display. See Fig. 6.

If Option 39 is set to display the space temperature (St), 
then the two-speed fan setting (LO or HI) remains on the 
display for three seconds after the last press of the fan 
button.

Figure 6: Current Fan Selection Display

Set Temperature Selection

 — If auto mode is not 

active and off mode is not active, pressing the up or 
down button causes the set point corresponding to the 
current system mode to be updated. If the up or down 
button is held, the set point value will be scrolled. The 
set point change also takes into account that Option 11 
(deadband) is preserved along with ensuring that Option 
26 (minimum cooling set point) and Option 27 (maximum 
heating set point) are taken into account to enforce set 
point limits.

If auto mode is active, pressing the up or down button 
causes the set point corresponding to the current 
operating mode to be updated. To move between the 
heat and cool set points, press the mode button to 
toggle between set points. Once the desired set point 
has been adjusted, press the mode button to return to 
auto mode.

If off mode is active, the up and down buttons are 
ignored for changing set point(s).

When changing the set points, the following restrictions 
are in place. The cool set point cannot be increased 
above 90 degrees F (32 C) or decreased below Option 
26, the minimum cooling set point. The heat set point 
cannot be decreased below 50 F (10 C) or increased 
above Option 27, the maximum heating set point.

When Option 39 is set to SP (set point), the set point 
adjustment is displayed in the large space temperature 
digits.

Display Lighting

 — The display has two levels of 

lighting, high level and low level. High level lighting 
comes on for 10 seconds when buttons are being 
pressed. The low level can be selected (see Option 18) 
for continuous backlight.

Remote Sensor Temperature Display 

— Pressing 

the up and down buttons simultaneously displays the 
temperature of the sensor connected to the S1 and S2 
terminals for five seconds, then the thermostat returns to 
normal operation.

If the sensor is invalid, then the display shows “--” in the 
large temperature display digits.

 

 

OPTION 15

AVAILABLE MODES

On

Off, Heat Cool, Auto

Off

Off, Heat, Cool

 


background image

10

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

Timers

 — There are several timers which influence the 

thermostat’s operation that are listed below. If any of the 
timers is preventing the equipment from turning on, the 
“on” icon will flash.

Five-Minute Compressor Timeguard

 — This timer 

prevents the Y1 output from turning on unless it has been 
off for 5 minutes. (Option 07 set to OF)

After a power cycle, a randomized delay will be added 
to end of the timeguard timer to prevent multiple units 
from hitting the power grid all at the same time. The 
randomization timer will be between zero and five 
minutes. If a demand exists, compressor outputs will 
energize between 5 and 10 minutes after the power 
cycle. It can be defeated by simultaneously pressing the 
fan and up keys.

Minimum On Timer 

— Once the equipment has been 

turned on, it must remain on for 3 minutes. A change in 
mode or set point will cancel this timer.

Cycle Timer

 — The number of equipment cycles per hour 

is determined by configuration Option 16. Based on the 
selection of 4, 6 or 8 cycles per hour, this timer is set to 
15, 10 or 8 minutes. This much time must elapse from the 
start of one cycle before another cycle can start, imposing 
the cycles per hour limits. It can be defeated for one cycle 
by simultaneously pressing the fan and up keys.

TROUBLESHOOTING

There are three system error messages that may appear 
on the thermostat screen indicating a problem with 
the thermostat’s operation. See text below for possible 
system error messages and their meaning.

Space Temperature Sensor Failure

 — If the room 

temperature sensor fails, the temperature display will 
show “--” (two dashes). If the space temperature is 
the average of both the local and remote sensors (as 
configured in Option 5), and one of the sensors fails, the 
thermostat provides control to the valid sensor only. The 
display will alternate every 10 seconds between “--” for 
the invalid sensor and the reading from the valid sensor.

Memory Failure 

— If there is an internal memory failure, 

the temperature display will show “E4,” the thermostat 
needs to be replaced.

WIRING DIAGRAMS

System wiring diagram is shown for typical ClimateMaster 
heat pump unit. See Fig. 7.
   

O is Energized for cooling
G is low speed fan
G2 is hi speed fan

Figure 7: Typical Wiring Diagram - Heat Pump

Rc

Rh

W

C

G

G2

R

W OR W1
C
G
H (DXM ONLY)

O
Y or Y1

NOTE 1

NOTE 2

S2
S1

O

Y1

THERMOSTAT

HEAT PUMP

CXM/DXM

HEAT PUMP

REMOTE 

SENSOR 

(Optional)

 


background image

11

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

THERMOSTAT CONFIGURATION RECORD

INSTALLER:                                                                                                                                                                                            

PART NUMBER:                                                                                                                                                                                     

DATE:                                                                                                                                                                                                      

HOLE IN WALL SEALED:                                                                                                                                                                       

MODE SETTINGS:                                                                                                                                                                                 

MODE (Off, Heat, Cool, Auto):                                                                                                                                                                   

HEATING SET POINT:                                                                                                                                                                            

COOLING SET POINT:                                                                                                                                                                           

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring 

obligations.

Thermostat Configuration Record

 

CONFIGURATION DESCRIPTION

 

USER OPTIONS 

SETTING

 

Option 02 

_____  Remote Sensor Selection

 

Option 03 

_____  English/Metric

 

Option 05 

_____  Space Temperature Sensing

 

Option 07 

_____  Equipment DDC Controller

 

 

_____  Deadband between Heating and Cooling Set

 

Option 11 

 

Points

 

 

_____  Space Temperature Display Adjustment

 

Option 13 

 

(Offset)

 

Option 15 

_____  Auto Mode Availability

 

Option 16 

_____  Maximum Cycles Per Hour

 

Option 18 

_____  Backlight Configuration

 

 

_____  Outdoor Air Temperature Display Adjustment

 

Option 20 

 

(Offset)

 

Option 21 

_____  Keypad Lockout

 

Option 26 

_____  Minimum Cooling Set Point

 

Option 27 

_____  Maximum Heating Set Point

 

Option 39 

_____  Temperature Display

 

Option 40 

_____  Fan Speeds Available (1 or 2)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring 

obligations.

 


background image

12

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

Revision History

Date:

Item:

Action:

09/16/13

Warning and Table, page 5 

Updated

08/27/13

First Published

We work continually to improve our products. As a result, the design and specifications of each product at the time of order may be changed without 

notice and may not be as described herein. Please contact our Customer Service Department at 1-405-745-6000 for specific information on the 

current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any 

bargain between the parties, but are merely our opinion or commendation of its products. 
We are a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org

 

© LSB, Inc. 2013 

Rev.: 16 September, 2013

*97B0082N06*

97B0082N06