Full Text Searchable PDF User Manual

Auxiliary Electric Heat
Installation, Operation &
Maintenance Instructions
97B0005N04
Revised: December 16, 2015
AG Series Electric Heaters
Table of Contents
Overview 3
Vertical Up
fl
ow or Down
fl
ow
Installation - Internal
3
Vertical Up
fl
ow Installation - External
4
Horizontal Installation - External
Wiring 6
Setup 6
Ratings 7
Electrical Data
7
Staging Options
7-8
Accessory Heater Dimensions
9
Warranty 10
Revision Log
12

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
2
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
This page was intentionally left blank.

3
E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
c l i m a t e m a s t e r. c o m
Overview
The AG Series Auxiliary Electric Heat mounts internally on
TS, TE and TT upfl ow (Figure 1b) or downfl ow units and all
TAH units. It mounts directly to the blower outlet of TS, TE
and TT horizontal units (Figure 8) and on all TZ units. Note
the model compatibility Table 1. Horizontal units are rated
for zero clearance at the unit and 1" clearance for fi rst three
feet of duct, vertical units rated for zero clearance for both
unit and duct. Downfl ow units can not be located directly
over a discharge register. The discharge plenum must be
constructed from non combustible material. The AG electric
heat contains a four stage relay control board which activates
the elements directly via an internally wired low voltage
harness. Low voltage signals (W1 and W2) are staged from
the CXM or DXM control of the unit.
TS ,TT and TE Vertical Upfl ow or Downfl ow and TAH
Installation - Internal
1. Disconnect power to the unit.
2. Remove blower access panel(s) from the unit and
control box cover from the electric heater.
3. Remove blower mounting bolts and drop blower
assembly as shown in fi gure 2. Removal of electrical
wiring should not be necessary.
4. Position the electric heater as illustrated in fi gure 3 with
its control box facing the front access panel of the unit.
Attach heater to unit using the support pins on the back
and bolts on the front.
The electric heater air inlet dimensions should match the
unit blower outlet, installer should stop and refer to the
unit/heater compatibility chart later in this instruction or
consult factory if they do not match.
5. Re-install blower assembly on to electric heater using
pins and bolts as before. Check blower electrical wiring
for proper connection and remedy any pinched wire(s) or
contact with sharp edges.
6. Route the low voltage control harness through one of the
‘pie’ bushings in the heater control box and plug on to
the P2 connector. See fi gure 6.
7. Install power conduit through the unit cabinet as shown
in fi gure 7 and attach directly to the electric heater
control box. See fi gures 9a-c.
8. Replace all covers and panels, heater installation is
complete. Proceed to wiring and setup.
5HPRYHEROWV
DQGGURSEORZHU
/RFDWHHOHFWULFKHDWDVVHPEO\
RQSLQVLQGLVFKDUJHSDQHO
DQGLQVHUWEROWV
5HORFDWHEORZHULQHOHFWULF
KHDWDVVHPEO\LQVDPH
PDQQHU
Figure 2: Blower removal
Figure 3: AG electric heat mounting and
blower re-installation
Figure 1b: Typical vertical unit installation
Overview
$LU&RLO
(OHFWULF+HDW
$VVHPEO\
)LHOGVXSSOLHG
GLVFRQQHFW
UHIHUWRORFDOFRGHV
/RZYROWDJHFRQWUROKDUQHVV
LVSUHZLUHGRQDOO
GLVWULEXWRUFODVVXQLWV
Figure 1a: Typical air handler installation

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
4
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
Vertical Installation - External
Auxiliary electric heat
power supply knockout
opposite air coil
Electric Heat Assembly
Air Coil
Low Voltage control harness
is prewired on all distributor
class units.
*
1. Disconnect power to the unit.
2.
Remove blower access panel(s) from the unit and control
box and element covers from the electric heater.
3. Locate remove and discard blower discharge fl anges
from the unit but save the screws. Flanges will be
packaged loose inside the blower compartment of
vertical upfl ow units. TZ036 and 042 units require a
transition bracket between the cabinet top and the
electric heater. This bracket is packaged inside the
blower compartment for fi eld installation.
4. Position the electric heater as illustrated herein. Heater
control box should be facing the front access panel of
vertical units.
The electric heater air inlet dimensions should match
the unit air outlet, installer should stop and refer to the
unit/heater compatibility chart later in this instruction or
consult factory if they do not match.
5. Use the saved blower fl ange screws to attach the heater
by its fl anges to the unit panel except do not fasten
fl ange on control box side.
6. Use aluminum tape (not provided) to seal all four heater
fl anges to the blower panel.
7. Locate and route the low voltage control harness through
the top panel knockout(s). Seal the penetration ‘air tight’.
This harness is factory installed on all TZ units (wire-tied
to the fan housing).
8. Route the control harness through one of the ‘pie’
bushings in the heater control box and plug on to the P2
connector. See fi gure 5.
9. Install power conduit and attach directly to the electric
heater control box. See fi gures 5a-c.
10. Replace all covers and panels, heater installation is
complete. Proceed to wiring and setup.

5
E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
c l i m a t e m a s t e r. c o m
Horizontal External Installation
1. Disconnect power to the unit.
2. Remove blower access panel from the unit and control box
and element covers from the electric heater.
3. Remove and discard blower discharge
fl
anges from the
unit but save the screws. TZ036 and 042 units require
a transition bracket between the cabinet panel and
the electric heater. This bracket is packaged inside the
blower compartment for
fi
eld installation.
4. Position the electric heater as illustrated herein. Notice
that the discharge air opening is o
ff
centered in the
blower panel. The electric heater must be positioned so
that its control box is located vertically over the wide
side of this panel.
The electric heater air inlet dimensions should match
the unit air outlet, installer should stop and refer to the
unit/heater compatibility chart later in this instruction or
consult factory if they do not match.
5. Use the saved blower
fl
ange screws to attach the heater
by its
fl
anges to the unit panel except do not fasten
fl
ange on control box side.
6. Use aluminum tape (not provided) to seal all four heater
fl
anges to the blower panel.
7. Locate and route the low voltage control harness
through one of the unit corner post or blower panel
knockout(s). Seal the penetration ‘air tight’. This harness
is factory installed and wire-tied to the fan housing.
8. Route the control harness through one of the ‘pie’
bushings in the heater control box and plug on to the P2
connector. See
fi
gure 6.
9. Install power conduit and attach directly to the electric
heater control box.
10. Replace all covers and panels, heater installation is
complete. Proceed to wiring and setup.
Figure 6: Low Voltage Harness Connection
Figure 8: Typical Horizontal Installation
Horizontal Installation - External
Locate electric heat
harness in air handler
and route through
one of the provided
bushing
Field-supplied disconnect
(refer to local codes)

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
6
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
21
2))
21
2))
3
,QDQGN:XQLWV
WZRSRZHUFLUFXLWVDUH
HPSOR\HGWRUHGXFHZLUHV
VL]HDQGFRVWRIEUHDNHUV
/
/
/
/
3
&RQGXLW
Figure 8a: Power Wiring, Dual Circuits, 15, 20kw
Figure 8b: Power Wiring, Single Circuit, 12, 15, 20kw
Wiring and Setup (all models)
1. Install power wiring and connect to power block or
circuit breakers. In 15 or 20kW models two power
circuits may be used to reduce wiring and breaker
costs as in Figure 8a. If a single circuit supply is
desired, install the optional single circuit accessory kit
(P/N 16B0002N02), as shown in Figure 8b, that can be
obtained from your distributor.
Optional for TAH: AG**C kits only. Blower power may
be supplied from T3 & T4 CB5 breaker. Refer to wiring
diagram 96B0143N01.
2. Ensure unit air
fl
ow setting is above minimum air
fl
ow rating
for the electric heat model from Table 1.
3. Check heat staging for the application. Table 4 contained
later in this IOM shows the factory default staging and
the alternate
fi
eld selectable staging where applicable.
Staging changes are made by dip switch settings. See
fi
gure 9. These are identi
fi
ed as either ER1, ER2, ER3 or
ER4 depending on the heater size.
4. Mark the appropriate box of the electric heat model
installed on the additional serial plate on the exterior of
the unit.
5. Turn on the power to the unit and the auxiliary
electric heat.
Auxiliary Electric Heat Start-up
Put thermostat in emergency heat mode (or jumper t-stat
input R to W and R to G) and setpoint to high setting. ‘Touch-
jumper' the test pins of the CXM or DXM into test mode to
reduce time delays. Unit will require 15-20 seconds before
engaging emergency heat mode stage 1 (W1) and then
another 15-20 seconds to engage stage 2 (W2) when in ‘Test
mode’. Verify proper electric heat operation.
Figure 9: Staging Dip Switches
Figure 8c: Power Wiring, 4, 5, 8, and 10kw
Wiring
In 15 and 20 kW units, optional
single power circuit is employed to
reduce the number of wires needed.
ER1
ER2
ER1
ER2
ER3
ER4
For AGM/L 4, 5, 8, 10kW.
For AGM/L 12, 15, and 20kW.

7
E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
c l i m a t e m a s t e r. c o m
Table 2: AG Electric Heat Electrical Data - TAH
Table 1: AG Electric Heat Ratings
Staging Options
Auxiliary
Electric
Heat
Model
TS, TT, TE Models
TZ Models
TAH Models
kW Rating
Btuh Rating
Minimum
CFM
Required
018
024-
030
036-
038
042-
072
024
030-
042
048-
060
Auxiliary
Electric
Heat
Model*
026
038
049-
064
240V
208V
240V
208V
AGM4A
AGM4C
3.8
2.9
13000
9900
500
AGM5A
AGM5C
4.8
3.6
16300 12300
500
AGM8A
AGM8C
7.6
5.7
25900 19400
650
AGM10A
AGM10C
9.6
7.2
32700 24600
650
AGM12A
11.4
8.6
38900 29200
750
AGL10A
AGL10C
9.6
7.2
32700 24600
1300
AGL15A
AGL15C
14.4
10.8
49100 36900
1350
AGL20A
AGL20C
19.2
14.4
65500 49200
1350
Black area denotes compatibility
Note: Horizontal units rated for zero clearance unit and 1” clearance for the fi rst three feet of duct,
Vertical units rated for zero clearance for both unit and duct.
* Can be used on corresponding TZ, TE, TS and TT models
Unit Model
Head Kit
Model
Supply
Heater
Amps
240
Heater
Amps
208
Blower
FLA
Minimum Circuit Amps
Maximum Breaker
Size
240 V
208 V
240 V
208 V
TAH026
AGM4C
SINGLE
15.8
14
4.3
25
23
25
25
AGM 5C
SINGLE
20
17.3
4.3
30
27
30
30
AGM 8C
SINGLE
31.7
27.5
4.3
45
40
45
40
AGM 10C
SINGLE
40
34.7
4.3
55
49
60
50
TAH038
AGL10C
SINGLE
40
34.7
4.3
59
52
60
60
AGL15C
DUAL L1/L2
40
34.7
0
50
43
50
45
L3/L4
20
17.3
4.3
34
30
35
30
TAH049 and
TAH060
AGL10C
SINGLE
40
34.7
7.0
59
52
60
60
AGL15C
DUAL L1/L2
40
34.7
0.0
50
43
50
45
L3/L4
20
17.3
7.0
34
30
35
30
AGL20C
DUAL L1/L2
40
34.7
0.0
50
43
50
45
L3/L4
40
34.7
7.0
59
52
60
60
All heaters rated single phase 208/240V 60Hz
All Fuses UL Class K general purpose
All models 15kW or larger feature internal circuit breakers

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
8
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
Table 4: AG Electric Heat Staging Options
Auxiliary Electric
Heat Model
Supply
Circuit
Heater Amps
Minimum Circuit Amps
Maximum Fuse
240V
208V
240V
208V
240V
208V
AGM4A
Single
15.8
14.0
19.8
17.1
20
20
AGM5A
Single
20.0
17.3
25.0
21.6
25
25
AGM8A
Single
31.7
27.5
39.6
34.4
40
35
AGM10A
Single
40.0
34.7
50.0
43.4
50
45
AGL10A
Single
40.0
34.7
50.0
43.4
50
45
AGM12A
Single
47.5
41.2
59.4
51.5
60
60
Dual-L1/L2
31.7
27.5
39.6
34.4
40
35
Dual - L3/L4
15.8
13.7
19.8
17.1
20
20
AGL15A
Single
60.0
52.0
75.0
65.0
80
70
Dual - L1/L2
40.0
34.7
50.0
43.4
50
45
Dual - L3/L4
20.0
17.3
25.0
21.6
25
25
AGL20A
Single
80.0
69.3
100.0
86.6
100
90
Dual - L1/L2
40.0
34.7
50.0
43.4
50
45
Dual - L3/L4
40.0
34.7
50.0
43.4
50
45
All heaters rated single phase 208/240V 60Hz
All Fuses UL Class K general purpose
All models 12kW or larger feature internal circuit breakers
Table 3: AG Electric Heat Electrical Data - TS/TT/TE
Staging Options
Heater Model
Staging
Factory Setting
Alternate Setting
kW
Dip Position
Stage 1 kW
Stage 2 kW
Dip Position
Stage 1 kw
Stage 2 kW
AGM4
4
ER1
4
AGM5
5
ER1
5
AGM8
4 or 8
ER1
4
4
ER2
8
AGM10, AGL10
5 or 10
ER1
5
5
ER2
10
AGM12
4, 8, or 12
ER1, ER4
4
8
ER3, ER4
8
4
AGL15
5,10 or 15
ER1, ER4
5
10
ER3, ER2
10
5
AGL20
10 or 20
ER3, ER4
10
10

9
E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
c l i m a t e m a s t e r. c o m
Accessory Heater Dimensions
The maximum recommended air velocity for a supply plenum is 900 fpm. When connecting a plenum to an external
supplemental heater, ensure that the air velocity in the plenum does not exceed 900 fpm. Noise and air distribution issues
may occur if supply plenum velocities exceed 900 fpm.
AGM4A - 12A
AGL10A - 20A
14.7
Control
box
Element
cover
10.3
15.5
15.1
12
Discharge Air Opening
Discharge Air Opening
16.1
8.1
3
13.3
13.5
2
A
I
R
F
L
O
W
Discharge Air Opening
Discharge Air Opening
A
I
R
F
L
O
W
Rev. A 13.6
Rev. B 14.9
Rev. A 10.7
Rev. B 12.0
14.6
8.8
11.7
Control box
Element
cover
13.6
10.7
6.2
5.1
Rev. A 9.4
Rev. B 10.6
10.2
1
14.6
1.4
9.4

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
10
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
&/,0$
7(0$67(5,1&
/,0,7('(;35(66
:
$55$17</,0,7
$
7,212)
5(0(',(6
$1'/,$%,/,7<
)
25
5(6,'(17,$/
&/$66352'8&76
:,7+/$%25
$//2:
$1&(
,WLVH[SUHVVO\XQGHUVWRRGWKDWXQOHVVDVWDWHPHQWLVVSHFL¿FDO
O\LGHQWL¿HGDVDZDUUDQW\
VWDWHPHQWVPDGHE\&OLPDWH0DVWHU
,QFD'HODZDUHFRUSRUDWLRQ³&0´RULWVUHSUHVHQWDWLYHVUHO
DWLQJWR&0¶
VSURGXFWVZKHWKHURUDOZULWWHQRUFRQWDLQHG
LQDQ\VDOHVOLWHUDWXUHFDWDORJRUDJUHHPHQWDUHQRWH[SUHVV
ZDUUDQWLHVDQGGRQRWIRUPDSDUWRIWKHEDVLVRIWKHEDU
JDLQ
EXWDUHPHUHO\&0¶
VRSLQLRQRUFRPPHQGDWLRQRI&0¶
VSURGXFWV
(;&(37
$663(&,),&$//
<
6(7
)25
7+
+(5(,1
7+(5(,612(;35(66
:
$55$17<
$6
7
2
$1<
2)
&0¶6352'8&76
&00$.(612
:
$55$17<
$*$,167
/$
7(17
'()(&76&00$.(612
:
$55
$17<
2)
0(5&+$17
$%,/,7<
2)
7+(
*22'6252)
7+(),71(662)
7+(*22'6)25
$1<
3
$5
7,&8/$5385326(
*5$17
2)
/,0,7('(;35(66
:
$55$17<
&0ZDUUDQWVLWV5HVLGHQWLDO&ODVVSURGXFWVSXUFKDVHGDQGUHWDL
QHGLQWKH8QLWHG6WDWHVRI
$PHULFDDQG&DQDGDWREHIUHHIURP
GHIHFWVLQPDWHULDODQGZRUNPDQVKLSXQGHUQRUPDOXVHDQGPDLQW
HQDQFHDVIROORZV
$LUFRQGLWLRQLQJKHDWLQJ
DQGRUKHDWSXPSXQLWVEXLOWRUVROGE\&0³&08QLWV´IRUWHQ
\HDUVIURPWKH
:
DUUDQW\,QFHSWLRQ'DWHDVGH¿QHGEHORZ
7KHUPRVWDWVDX[LOLDU\HOHFWULFKHDWHUVDQGJHRWKHUPDOSX
PSLQJPRGXOHVEXLOWRUVROGE\&0ZKHQLQVWDOOHG
ZLWK&08QLWVIRUWHQ\HDUVIURPWKH
:
DUUDQW\,QFHSWLRQ'
DWHDVGH¿QHGEHORZDQG2WKHUDFFHVVRULHVDQGSDUWVEXLO
WRUVROGE\&0ZKHQLQVWDOOHGZLWK&08QLWVIRURQH\HDU
IURPWKHGDWHRIVKLSPHQWIURP&0
7KH³:
DUUDQW\
,QFHSWLRQ'DWH´VKDOOEHWKHGDWHRIRULJLQDOXQLWLQVWDOODWLRQ
RUVL[PRQWKVIURPGDWHRIXQLWVKLSPHQWIURP&0ZKLFKHY
HUFRPHV¿UVW
7
RPDNHDFODLPXQGHUWKLVZDUUDQW\
SDUWVPXVWEHUHWXUQHGWR
&0LQ2NODKRPD&LW\
2NODKRPDIUHLJKWSUHSDLGQRODWHUWKDQQ
LQHW\GD\VDIWHUWKHGDWHRIWKHIDLOXUHRIWKHSDUWLI&
0GHWHUPLQHVWKHSDUWWREHGHIHFWLYHDQGZLWKLQ&0¶
V
/LPLWHG([SUHVV
:
DUUDQW\
&0VKDOOZKHQVXFKSDUWKDVEHHQHLW
KHUUHSODFHGRUUHSDLUHGUHWXUQVXFKWRDIDFWRU\UHFRJQL]HGG
LVWULEXWRU
GHDOHURUVHUYLFHRU
JDQL]DWLRQ)
2%&02NODKRPD
&LW\
2NODKRPDIUHLJKWSUHSDLG
7KHZDUUDQW\RQ
DQ\SDUWUHSDLUHGRUUHSODFHGXQGHUZDUUDQW\H[SLUHVDWWKHHQG
RIWKHRULJLQDOZDUUDQW\SHULRG
7KLV/LPLWHG([SUHVV
:
DUUDQW\VKDOOFRYHUWKHODERULQFXUUHGE\
&0DXWKRUL]HGVHUYLFHSHUVRQQHOLQFRQQHFWLRQZLWKWKHLQVWDOO
DWLRQRIDQHZRUUHSDLUHGZDUUDQW\SDUWWKDWLVFRYHUHGE\WKL
V/LPLWHG([SUHVV
:
DUUDQW\RQO\WRWKHH[WHQW
VSHFL¿FDOO\VHWIRUWKLQWKHWKHQH[LVWLQJODERUDOORZDQFHVFKH
GXOHSURYLGHGE\&0¶
V
:
DUUDQW\'HSDUWPHQWDQGRQO\DVIROORZV
&08QLWVIRU¿YH\HDUVIURPWKH
:
DUUDQW\,QFHSWLRQ'DWH
7KHUPRVWDWVDX[LOLDU\HOHFWULFKHDWHUVDQG
JHRWKHUPDOSXPSLQJPRGXOHVEXLOWRUVROGE\&0ZKHQLQVWDOOHG
ZLWK&08QLWVIRU¿YH\HDUVIURPWKH
:
DUUDQW\,QFHSWLRQ'D
WH
$FWXDO/DERUFRVWVDUHQRWFRYHUHGE\WKLV/LPLWHG([SUHVV
:
DUUDQW\WRWKHH[WHQWWKH\H[FHHGWKHDPRXQW
DOORZHGXQGHUVDLGDOORZDQFHVFKHGXOHWKH\DUHQRWVSHFL¿FDOO\
SURYLGHGIRULQVDLGDOORZDQFHVFKHGXOHWKH\DUHQRWWKHUHVX
OWRIZRUNSHUIRUPHGE\&0DXWKRUL]HGVHUYLFHSHUVRQQHOWKH\D
UHLQFXUUHGLQFRQQHFWLRQZLWKDSDUWQRWFRYHUHGE\
WKLV/LPLWHG([SUHVV
:
DUUDQW\
RUWKH\DUHLQFXUUHGPRUHWKDQW
KHWLPHSHULRGVVHWIRUWKLQWKLVSDUDJUDSKDIWHUWKH
:
DUUDQW\
,QFHSWLRQ'DWH
7KLVZDUUDQW\GRHVQRWFRYHUDQGGRHVQRWDSSO\WR
$LU¿OW
HUVIXVHVUHIULJHUDQWÀXLGVRLO3URGXFWVUHORFDWHGDIW
HULQLWLDOLQVWDOODWLRQ
$Q\SRUWLRQRUFRPSRQHQWRIDQ\V\
VWHPWKDWLVQRWVXSSOLHGE\&0UHJDUGOHVVRIWKHFDXVHRIWKH
IDLOXUHRIVXFKSRUWLRQRUFRPSRQHQW3URGXFWVRQZKLFKWKH
XQLWLGHQWL¿FDWLRQWDJVRUODEHOVKDYHEHHQUHPRYHGRUGHIDFHG
3URGXFWVRQZKLFKSD\PHQWWR&0RUWRWKHRZQHU
¶VVHOOHU
RULQVWDOOLQJFRQWUDFWRU
LVLQGHIDXOW3URGXFWV
VXEMHFWHGWRLPSURSHURULQDGHTXDWHLQVWDOODWLRQPDLQWHQDQFH
UHSDLU
ZLULQJRUYROWDJHFRQGLWLRQV3URGXFWVVXEMHFWHGWR
DFFLGHQWPLVXVHQHJOLJHQFHDEXVH¿UHÀRRGOLJKWQLQJXQD
XWKRUL]HGDOWHUDWLRQPLVDSSOLFDWLRQFRQWDPLQDWHG
RUFRUURVLYHDLURUOLTXLGVXSSO\
RSHUDWLRQDWDEQRUPDODLURU
OLTXLGWHPSHUDWXUHVRUÀRZUDWHVRURSHQLQJRIWKHUHIULJHUDQ
WFLUFXLWE\XQTXDOL¿HGSHUVRQQHO0ROGIXQJXVRUEDFWHULD
GDPDJHV&RUURVLRQRUDEUDVLRQRIWKHSURGXFW
3URGXFWVVXSSOLHGE\RWKHUV
3URGXFWVZKLFKKDYHEHHQ
RSHUDWHGLQDPDQQHUFRQWUDU\WR&0¶
VSULQWHGLQVWUXFWLRQV
3URGXFWVZKLFKKDYHLQVXI¿FLHQWSHUIRUPDQFHDVDUHVXOWRIL
PSURSHUV\VWHPGHVLJQRULPSURSHUDSSOLFDWLRQ
LQVWDOODWLRQRUXVHRI&0¶
VSURGXFWVRU(OHFWULFLW\RUI
XHOFRVWVRUDQ\LQFUHDVHVRUXQUHDOL]HGVDYLQJVLQVDPHIRU
DQ\UHDVRQZKDWVRHYHU
7KLV/LPLWHG([SUHVV
:
DUUDQW\SURYLGHVWKHOLPLWHGODERUDOORZD
QFHFRYHUDJHDVVHWIRUWKDERYH2WKHUZLVH&0LVQRWUHVSRQVL
EOHIRU
7KHFRVWVRIDQ\ÀXLGVUHIULJHUDQWRUV\VWHPFRPS
RQHQWVVXSSOLHGE\RWKHUVRUDVVRFLDWHGODERUWRUHSDLU
RUUHSODFHWKHVDPHZKLFKLVLQFXUUHGDVDUHVXOWRIDGHIHFWL
YHSDUWFRYHUHGE\&0¶
V/LPLWHG([SUHVV
:
DUUDQW\
7KHFRVWV
RIODERU
UHIULJHUDQWPDWHULDOVRUVHUYLFHLQFXUUHGLQGLDJQR
VLVDQGUHPRYDORIWKHGHIHFWLYHSDUWRULQREWDLQLQJDQG
UHSODFLQJWKHQHZRUUHSDLUHGSDUW
7
UDQVSRUWDWLRQFRVWVRI
WKHGHIHFWLYHSDUWIURPWKHLQVWDOODWLRQVLWHWR&0RURIWKH
UHWXUQRIWKDWSDUWLIQRWFRYHUHGE\&0¶
V/LPLWHG([SUHVV
:
DU
UDQW\RU
7KHFRVWVRIQRUPDOPDLQWHQDQFH
7KLV/LPLWHG([SUHVV
:
DUUDQW\DSSOLHVWR&05HVLGHQWLDO&ODVVS
URGXFWVRUGHUHGIURP&0RQRUDIWHU0D\WKLVZRXOGJHQ
HUDOO\LQFOXGH&08QLWVZLWKVHULDOQXPEHUVEHJLQQLQJZLWK³1
´DQGKLJKHUDQGLVQRWUHWURDFWLYHWRDQ\
SURGXFWVRUGHUHGIURP&0SULRUWR0D\WKLVZRXOGJHQHU
DOO\LQFOXGH&08QLWVZLWKVHULDOQXPEHUVEHJLQQLQJZLWK³1
´
DQGORZHU,I\RXDUHXQVXUHLIWKLV/LPLWHG([SUHVV
:
DUUDQW
\DSSOLHVWRWKHSURGXFW\RXKDYHSXUFKDVHG
FRQWDFW&0DWWKHSKRQHQXPEHURUDGGUHVVUHÀHFWHGEHORZ
/LPLWDWLRQ
7KLV/LPLWHG([SUHVV
:
DUUDQW\LVJLYHQLQOLHXRIDOORWKHUZD
UUDQWLHV,IQRWZLWKVWDQGLQJWKHGLVFODLPHUVFRQWDLQHGKHUHLQ
LWLVGHWHUPLQHGWKDWRWKHUZDUUDQWLHVH[LVWDQ\VXFKH[SUHVV
ZDUUDQW\
LQFOXGLQJZLWKRXWOLPLWDWLRQDQ\
H[SUHVVZDUUDQWLHVRUDQ\LPSOLHGZDUUDQWLHVRI¿WQHVVIRUSDUW
LFXODUSXUSRVHDQGPHUFKDQWDELOLW\
VKDOOEHOLPLWHGWRWKHGXU
DWLRQRIWKH/LPLWHG([SUHVV
:
DUUDQW\
/,0,7
$
7,212)
5(0(',(6
,QWKHHYHQWRIDEUHDFKRIWKH/LPLWHG([SUHVV
:
DUUDQW\
&0ZL
OORQO\EHREOLJDWHGDW&0¶
VRSWLRQWRUHSDLUWKHIDLOHGSDUWR
UXQLWRUWRIXUQLVKDQHZRUUHEXLOWSDUWRUXQLWLQH[FKDQJH
IRUWKHSDUWRUXQLWZKLFKKDVIDLOHG,IDIWHUZULWWHQQRWLFH
WR&0¶
VIDFWRU\LQ2NODKRPD&LW\
2NODKRPDRIHDFKGHIHFWPDOI
XQFWLRQRURWKHUIDLOXUHDQGDUHDVRQDEOHQXPEHURIDWWHPSWVE
\&0WRFRUUHFWWKHGHIHFWPDOIXQFWLRQRURWKHUIDLOXUHDQGW
KHUHPHG\IDLOVRILWVHVVHQWLDOSXUSRVH&0VKDOO
UHIXQGWKHSXUFKDVHSULFHSDLGWR&0LQH[FKDQJHIRUWKHUHWXUQ
RIWKHVROGJRRGV6DLGUHIXQGVKDOOEHWKHPD[LPXPOLDELOLW
\RI&0
7+,65(0('<
,6
7+(62/(
$1'(;&/86,9(5(0('<
2)
7+(%8<(52538
5&+$6(5
$*$,167
&0)25%5($&+2)
&2175$&7
)25
7+(%5($&+2)
$1<
:
$55$1
7<
25)25&0¶61(*/,*(1&(25,1675,&7
/,$%,/,7<
/,0,7
$
7,212)
/,$%,/,7<
&0VKDOOKDYHQROLDELOLW\IRUDQ\GDPDJHVLI&0¶
VSHUIRUPDQFH
LVGHOD\HGIRUDQ\UHDVRQRULVSUHYHQWHGWRDQ\H[WHQWE\DQ\
HYHQWVXFKDVEXWQRWOLPLWHGWRDQ\ZDU
FLYLOXQUHVWJRYHU
QPHQWUHVWULFWLRQVRUUHVWUDLQWVVWULNHVRU
ZRUNVWRSSDJHV¿UHÀRRGDFFLGHQWVKRUWDJHVRIWUDQVSRUWDWLR
QIXHOPDWHULDORUODERU
DFWVRI*RGRUDQ\RWKHUUHDVRQEH
\RQGWKHVROHFRQWURORI&0
&0(;35(66/
<
',6&/$,06
$1'(;&/8'(6
$1<
/,$%,/,7<
)25
&216(48(17,$/
25,1&,'(17
$/
'$0$*(,1&2175$&7
)25%5($&+2)
$
1<
(;35(6625,03/,('
:
$55$17<
25,1
7
2
5
7
:+(7+(5)25&0¶
V1(
*/,*(1&(25
$6675,&7
/,$%,/,7<
2%7
$,1,1*
:
$55$17<
3(5)250$1&(
1RUPDOO\
WKHGHDOHURUVHUYLFHRU
JDQL]DWLRQZKRLQVWDOOHGWKH
SURGXFWVZLOOSURYLGHZDUUDQW\SHUIRUPDQFHIRUWKHRZQHU
6KRX
OGWKHLQVWDOOHUEHXQDYDLODEOHFRQWDFWDQ\&0UHFRJQL]HGGLVW
ULEXWRU
GHDOHURUVHUYLFHRU
JDQL]DWLRQ,IDVVLVWDQFHLV
UHTXLUHGLQREWDLQLQJZDUUDQW\SHUIRUPDQFHZULWHRUFDOO
&OLPDWH0DVWHU
,QF&XVWRPHU6HUYLFH6:
WK6WUH
HW2NODKRPD&LW\
2NODKRPDHV
HUYLFH#FOLPDWHPDVWHU
FRP
127(6RPHVWDWHVRU&DQDGLDQSURYLQFHVGRQRWDOORZOLPLWDWLR
QVRQKRZORQJDQLPSOLHGZDUUDQW\ODVWVRUWKHOLPLWDWLRQRU
H[FOXVLRQVRIFRQVHTXHQWLDORULQFLGHQWDOGDPDJHVVRWKHIRUHJ
RLQJH[FOXVLRQVDQGOLPLWDWLRQVPD\QRWDSSO\WR\RX
7KLVZDUUDQW\JLYHV\RXVSHFL¿FOHJDOULJKWVDQG\RXPD\DOVR
KDYHRWKHUULJKWVZKLFKYDU\IURPVWDWHWRVWDWHDQGIURP&DQDG
LDQSURYLQFHWR&DQDGLDQSURYLQFH
3OHDVHUHIHUWRWKH&0,QVWDOODWLRQ2SHUDWLRQDQG0DLQWHQDQFH
0DQXDOIRURSHUDWLQJDQGPDLQWHQDQFHLQVWUXFWLRQV
5HY
3DUW1R53
Warranty

11
E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
c l i m a t e m a s t e r. c o m
Notes

E l e c t r i c H e a t - I n s t a l l a t i o n , O p e r a t i o n , a n d M a i n t e n a n c e
R e v i s e d : D e c e m b e r 1 6 , 2 0 1 5
12
C l i m a t e M a s t e r G e o t h e r m a l H e a t i n g a n d C o o l i n g
Revision History
97B0005N04
ClimateMaster works continually to improve its products. As a result, the design and speci
fi
cations of each product at the time for order may be
changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000
for speci
fi
c information on the current design and speci
fi
cations. Statements and other information contained herein are not express warran-
ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
The management system governing the manufacture of ClimateMaster’s products is ISO 9001:compliant
© ClimateMaster, Inc. 2014
*97B0005N04*
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com
Date
Page #
Description
16 Dec., 2015
8
Add AGM12 to table 3
04 Aug., 2015
9
Updated Illustration Title AGL10A - 20A
09 Feb., 2015
All
Misc Edits
22 Dec., 2014
5
External Installation Instructions Updated
29 Oct., 2014
All
First Published
Rev.:December 16, 2015T