Full Text Searchable PDF User Manual

Operation Manual
97B0106N01
Rev.: 11/3/17
ACDU03 Communicating
Service Tool
Table of Contents
Caution:
These instructions are intended to be used by the installer or service personnel. End users are NOT advised to change or
modify any of these settings. Doing so may cause the equipment to stop working properly and/or may void the warranty on
both the thermostat and the equipment.
Section Title
Page
1.0 Connection
3
2.0 Menu
Structure
4
3.0 System
Confi guration
4
3.1
Airfl ow Selection
4
3.2
Option Selection
5
3.3
Unit Confi guration
5
3.4
Pump Confi guration
6
3.5
Valve
Confi guration
6
3.6
Multi-Unit
Confi guration
7
4.0
Service Mode
8
4.1
Manual
Operation
8
4.2
Control
Diagnostics
8
4.3
Dipswitch
Confi guration
9
4.4
Fault
History
9
4.5
Clear Fault History
11
5.0 Revision
History
12

This page was intentionally left blank.

3
A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
ClimateMaster’s Communicating Service Tool (ACDU03) allows install and service technicians to confi gure and diagnose
ClimateMaster Digital Communicating Units without installing a digital communicating thermostat.
Using the Service Tool, a technician can ELECTRONICALLY:
1. Confi gure items like: airfl ow, heat pump options and confi guration, pump or modulating valve operation, unit family, unit
size, etc.
AND
2. Diagnose the unit by operating it manually, performing control diagnostics, viewing dip switch confi gurations, or by
viewing fault history and operating conditions when a fault occurred.
The Service Tool connects to the DXM2 board with a 4-Wire Connector as shown below:
P1
Alarm
O
Y1
Y2
W
G
C
R
AL1
R
C
R
NSB
AL2
JW1
P2
P5
B-
Gnd
A+
24V
Service tool
connection
DXM2
Board
DXM2
DXM2
Board
Board
1.0 Connection
WARNING!
WARNING! Connecting wire harness while unit is
powered on or connecting backward may damage
service tool.
Note: For Vertical Stack models (TSM, TSL) must
order harness for connection to service port outside
chassis. Harness part number 11B0100N27. DXM2 to
service port is factory wired.

A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
4
G e o t h e r m a l H e a t P u m p S y s t e m s
2.0 Menu Structure
System Confi guration
Airfl ow Selection
Option Selection
Unit Confi guration
Pump Confi guration
Valve
Confi guration
Service Mode
Manual
Operation
Control
Diagnostics
Dipswitch
Confi guration
Fault
History
Clear Fault History
Menu Structure
Start-up Screen
System Confi guration Menu
SERVICE TOOL MENU
SYSTEM CONFIG
SERVICE MODE
ACDU03 1.00
SELECT OPTION
3.0 System Confi guration
Use the System Confi guration option on the start-up screen
to adjust critical equipment settings.
The System Confi guration information will be automatically
obtained from each communicating control in the system.
Note 1: The Airfl ow Selection menu (section 3.1) will not be
present if the connected communicating control system has
no blower.
Note 2:
The Pump Confi guration menu (section 3.4) will
not be present if the connected communicating control is
confi gured for No Loop Confi guration (OTHER).
Note 3:
The Valve Confi guration menu (section 3.5) will
not be present if the connected communicating control is
confi gured for No Loop Confi guration (OTHER).
3.1 AIRFLOW
SELECTION
Adjust the airfl ow settings for each system operating mode
using the up/down arrow buttons. Press the center button to
select each item.
• Airfl ow Settings (defaults stored in control) -
valid range: obtained from control (in 25 CFM
increments)
• Blower Off Delay (default 60 seconds) – valid
range: 0 to 255 seconds (in 5 second increments)
NOTE 1: The Airfl ow Settings will only be present if the
connected communicating control is confi gured for ECM
blower.
NOTE 2: If multiple units are connected to one thermostat,
refer to section 3.6 for unit selection.
SYSTEM CONFIGURATION
AIRFLOW SELECTION
OPTION SELECTION
UNIT CONFIG TES026
PUMP CONFIGURATION
SELECT OPTION
PREVIOUS SELECT

5
A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
Option Selection Menu
Unit Confi guration Menu
OPTION SELECTION
MOTORIZED VALVE OFF
COMPRESSOR ASCD 0
SELECT OPTION
PREVIOUS SELECT
NOTE:
“Motorized Valve” used here refers to a two-position
motorized water valve, not to be confused with the modulating
motorized water valve found in the LOOP CONFIG.
3.2 OPTION
SELECTION
This option allows the confi guration of heat pump options to
be modifi ed.
Adjust the Option settings using the up/down arrow buttons.
Press the center button to select each item.
• Motorized Valve (defaults stored in control) – valid
range: Off, On “On” delays compressor start until
the valve is fully open.
• Compressor ASCD (Anti-Short Cycle Delay (default
stored in control) – valid range: 5 to 8 (in 1 minute
increments)
NOTE 1: The Compressor Anti-Short Cycle Delay setting
provides equipment protection by forcing the compressor to
wait a few minutes before restarting.
NOTE 2: If multiple units are connected to one thermostat,
refer to section 3.6 for unit selection.
3.3 UNIT
CONFIGURATION
Adjust the Unit Confi guration settings including Heat
Pump Family, Heat Pump Size, Blower Type, and Loop
Confi guration using the up/down arrow buttons. Press the
center button to select each item.
• Heat Pump Family (default stored in control) –
valid range: TE, TY, TES, TEP, TRT, TSM, TSL
• Heat Pump Size (default stored in control) – valid
range: depends on Heat Pump Family setting
• Blower Type (default stored in control) – valid
range: NO BLOWER, 2-SPD PSC, COM ECM-V,
1-SPD PSC, 2-SPD CTM, PWM ECM, VFD
• Loop
Confi g (default stored in control) – valid
range: Other, VS PUMP, MOD VALVE
Airfl ow, pump and valves can be confi gured from ‘System
Confi guration’ screen.
Select ‘VS PUMP PARALLEL’ when applying an internal
variable speed fl ow controller with other fl ow controllers on a
single loop in parallel.
NOTE: Refer to section 3.6.3 for multi-unit confi guration
instructions.
UNIT CONFIGURATION
CURRENT CONFIG TE026
HEAT PUMP FAMILY TE
HEAT PUMP SIZE 026
BLOWER TYPE ECM
LOOP CONFIG VS PUMP
SELECT OPTION
PREVIOUS SAVE

A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
6
G e o t h e r m a l H e a t P u m p S y s t e m s
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION SINGLE
PUMP CONTROL FIXED
HEATING STAGE 1 60%
COOLING STAGE 2 75%
COOLING STAGE 1 50%
COOLING STAGE 2 70%
PREVIOUS SELECT
3.4 PUMP
CONFIGURATION
vFlow™ vs internal fl ow control pump can be controlled either
through temperature differential (Delta T) or can be set to
specifi c speed (fi xed; % of full speed for each heat and cool
stage).
Can be confi gured for either single pumping or parallel
pumping.
Confi gure temperature differentials at the thermostat for
vFlow™ units with an internal fl ow control pump.
Adjust the Pump Confi guration settings using the up/down
arrow buttons. Press the center button to select each item.
• Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
• Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
Maximum Heat LWT (valid range based on specifi c model;
refer to model IOM). Minimum Cool LWT (valid range based
on specifi c model; refer to model IOM).
NOTE:
Refer to section 3.6.3 for multi-unit confi guration
instructions.
To control vs pump by fi xed speed, select ‘Pump Control’,
press , use down arrow to select ‘Fixed’, and press to
save.
Default stored in control. Valid range: 15% - 90% (in 1%
increments)
Heating Stage 1
Cooling Stage 1
Heating Stage 2
Cooling Stage 2
If Pump Confi guration is set to ‘VS PUMP PARALLEL’, valid
range changes to 50-90% (in 1% increments).
3.5 VALVE
CONFIGURATION
Confi gure temperature differentials at the thermostat for
vFlow™ units with a motorized modulating valve.
Adjust the Valve Confi guration settings using the up/down
arrow buttons. Press the center button to select each item.
• Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
• Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments)
NOTE 1: Minimum and Maximum degree values are shown
only when the control is confi gured with the appropriate
values.
NOTE 2: Refer to section 3.6.3 for multi-unit confi guration
instructions.
3.5.1 MODULATING VALVE OFF POSITION
For certain commercial multi-unit applications, the modulating
valve can be kept slightly open by choosing values 3.3-4.0.
MODULATING VALVE
CONFIGURATION
OFF POSITION 0.0
VALVE CONTROL DELTA T
HEATING DELTA T 7 F
COOLING DELTA T 10 F
MAXIMUM HEAT LWT 80 F
MINIMUM COOL LWT 40 F
PREVIOUS SELECT
VARIABLE SPD INTERNAL
PUMP CONFIGURATION
LOOP OPTION PARALLEL
PUMP CONTROL DELTA T
HEATING DELTA T 7 F
COOLING DELTA T 10 F
MAXIMUM HEAT LWT 80 F
MINIMUM COOL LWT 40 F
PREVIOUS SELECT

7
A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
Two
connections
on DXM2
board to allow
for multi-unit
installation
Or
AIRFLOW SELECTION
TT026 S N - - - - - 1 2 3 4
TT026 S N - - - - - 5 6 7 8
TT038 S N - - - - - 9 0 1 2
PREVIOUS SELECT
OPTION SELECTION
TT026 S N - - - - - 1 2 3 4
TT026 S N - - - - - 5 6 7 8
TT038 S N - - - - - 9 0 1 2
PREVIOUS SELECT
3.6 MULTI-UNIT
CONFIGURATION
If multiple units are connected to one ATC thermostat upon
unit start-up, the thermostat will automatically register the
serial numbers of all units connected to it.
NOTE: Multiple units may be connected directly to the ATC
thermostat or connected to one another in series, as shown
by the fi gure below.
3.6.1 MULTI-UNIT
AIRFLOW
SELECTION
In section 3.1, when an installer selects “Airfl ow Selection”
from the System Confi guration menu, the installer may
choose the unit to confi gure by the last 4 digits of its serial
number from the following screen.
3.6.2
MULTI-UNIT OPTION SELECTION
In section 3.2, when an installer selects “Option Selection”
from the System Confi guration menu, the installer may
choose the unit to confi gure by the last 4 digits of its serial
number from the following screen.
3.6.3
Multi-Unit, Unit, Pump, & Valve Confi guration
To confi gure Unit, Pump, and Valve options in sections 3.3-
3.5, the thermostat must be connected to only one unit at a
time.

A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
8
G e o t h e r m a l H e a t P u m p S y s t e m s
4.0 Service Mode
4.1 MANUAL
OPERATION
Manual Operation mode allows service personnel to manually
command operation for any of the thermostat outputs, blower
speed, as well as pump speed or valve position to help
troubleshoot specifi c components.
NOTE 1
: The ECM Airfl ow adjustment will not be present if the
connected communicating control (DXM2) is not confi gured for
ECM (section 3.1).
NOTE 2
: The Pump Speed adjustment will not be present
if the connected communicating control (DXM2) is not
confi gured for Pump (section 3.4).
NOTE 3
: The Valve Position adjustment will not be present if
the connected communicating control (DXM2) is confi gured for
Valve (section 3.5).
4.2 CONTROL
DIAGNOSTICS
Control Diagnostics mode allows service personnel to view
the status of all physical inputs, switches and temperature
sensor readings, as well as the operational status of the heat
pump at the thermostat.
Navigate between diagnostic screens using the left/right
arrow buttons.
NOTE
: The Pump Status will not be present if the connected
communicating control (DXM2) is not confi gured for Pump
(section 3.4).
SERVICE MODE
MANUAL OPERATION
CONTROL DIAGNOSTICS
DIPSWITCH CONFIG
FAULT HISTORY
CLEAR FAULT HISTORY
SELECT OPTION
PREVIOUS SELECT
MANUAL OPERATING MODE
Y1
COMM OUTPUT
OFF
Y2
COMM OUTPUT
OFF
W
COMM OUTPUT
OFF
O
COMM OUTPUT
OFF
G
COMM OUTPUT
OFF
H
COMM OUTPUT
OFF
DH
COMM OUTPUT
OFF
ECM
AIRFLOW
0
PUMP SPEED
0%
TEST
MODE
OFF
SELECT OPTION
PREVIOUS SELECT
CONTROL STATUS
TEMPERATURES
LT1 TEMP 38.1
LT2 TEMP 79.9
COMP DISCHARGE 157.7
HOT WATER EWT 121.5
LEAVING AIR 75.1
LEAVING WATER 73.3
ENTERING WATER 78.5
CONTROL VOLTAGE 26.4
ECM BLOWER RPM 550
ECM TARGET CFM 800
ECM BLWR STATIC N/A
PREVIOUS NEXT
CONTROL DIAGNOSTICS
HP SWITCH CL
LOC SWITCH CL
Y1 PHYSICAL INPUT ON
Y2 PHYSICAL INPUT OFF
W PHYSICAL INPUT OFF
O PHYSICAL INPUT ON
G PHYSICAL INPUT ON
H PHYSICAL INPUT OFF
EMERG SHUTDOWN OFF
NIGHT SETBACK OFF
OVR INPUT OFF
PREVIOUS NEXT
CONTROL DIAGNOSTICS
PUMP OPERATION
PUMP SPEED 60%
PUMP WATTS 140
FLOW RATE GPM 7.4
PREVIOUS

9
A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
4.3 DIPSWITCH
CONFIGURATION
Dipswitch Confi guration mode allows the service personnel
to view the status of all dipswitch settings for the connected
communicating control (DXM2/AXM) at the thermostat.
Navigate between confi guration screens using the left/right
arrow buttons.
NOTE
: The unit control dipswitch settings cannot be changed
from the thermostat or confi guration/diagnostics tool.
S1 Dipswitch Status
S2 Dipswitch Status
S3 Dipswitch Status
Fault History
CONTROL CONFIGURATION
DIPSWITCH S1
1 ON UPS ENABLED
2 ON DUAL COMP STG 1
3 ON HEAT PUMP TSTAT
4 ON RV O THERMOSTAT
5 ON DEHUMID OFF
6 ON EH2 AUX HEAT
7 ON BOILERLESS
8 ON SEE DXM2 AOM
PREVIOUS NEXT
CONTROL CONFIGURATION
DIPSWITCH S2
1 ON \ ACCESSORY 1
2 ON ACCESSORY 2
3 ON/
4 ON \ ACCESSORY 2
5 ON ACTIVE W/ COMP
6 ON /
7 ON H DEHUM INPUT
8 ON FACTORY SETTING
PREVIOUS NEXT
CONTROL CONFIGURATION
DIPSWITCH S3
1 ON FACTORY SETTING
2 OFF HWG TEST OFF
3 OFF HWG SP 125
4 OFF HWG DISABLED
JW3 LT1 SETTING WELL
PREVIOUS
TT038 SN - - - - - 0 1 2 3
LAST 5 FAULTS
LT1 LOW WATER TEMP
NO FAULT
NO FAULT
NO FAULT
NO FAULT
NEXT
PREVIOUS SELECT
4.4 FAULT
HISTORY
Fault History mode displays the fi ve most recent stored fault
codes for the connected communicating control (DXM2).
Navigate between control fault codes using the up/down
arrow buttons. Press the center button to view more
information about the highlighted fault code.

A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
10
G e o t h e r m a l H e a t P u m p S y s t e m s
4.4.1 Temperature Conditions
Displays detailed temperature readings that were
recorded at the time the fault occurred
4.4.0 Fault Conditions Menu
4.4.2 Flow
Conditions
Displays detailed blower and pump speed / valve posi-
tion readings that were recorded at the time the fault
occurred.
4.4.3 Input/Output
Conditions
Displays the status of all physical and communicated
inputs, switches, and control outputs that were re-
corded at the time the fault occurred.
FAULT CONDITION MENU
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
FAULT TEMP CONDITIONS
FAULT FLOW CONDITIONS
FAULT I/O CONDITIONS
FAULT CONFIG COND
FAULT POSSIBLE CAUSES
PREVIOUS SELECT
FAULT TEMPERATURE CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
LT1 TEMP 28.1
LT2 TEMP 97.3
HOT WATER EWT 121.5
COMP DISCHARGE 157.7
LEAVING AIR 92.7
LEAVING WATER 34.9
ENTERING WATER 42.1
CONTROL VOLTAGE 26.4
PREVIOUS
FAULT I / O CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
TSTAT SAFETY OUTPT
CONV COMM
HPS
Y1
Y1
LOC
CC
Y2
Y2
CO
RV
W
W
ACC1
O
O
OUTPT
ACC2
G
G
FAN
AL1
H
H
HWG
EH1
OVR
DH
PUMP
EH2
PREVIOUS
FAULT FLOW CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
ECM TARGET CFM 800
ECM BLOWER RPM 550
FLOW RATE GPM 6.5
PUMP SPEED 60%
PUMP WATTS 140
LOOP CONFIG VS PUMP
PREVIOUS SINGLE
FAULT FLOW CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
ECM TARGET CFM 800
ECM BLOWER RPM 550
VALVE POSITION 10.0V
LOOP CONFIG MOD VALVE
PREVIOUS MIN POS

11
A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
4.4.3 Confi guration Conditions
Displays the status of all dipswitch settings that were
recorded at the time the fault occurred.
4.4.4 Possible
Causes
Displays possible causes as to why the fault occurred
4.5
CLEAR FAULT HISTORY
Clear Fault History will clear all fault codes stored in the
thermostat as well as the fault history in any connected
communicating controls (DXM2/AXM).
FAULT CONFG CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
S1 S2 S3
1 ON 1 ON 1 ON
2 ON 2 ON 2 OFF
3 ON 3 ON 3 OFF
4 ON 4 ON 4 OFF
5 ON 5 ON
6 ON 6 ON LT1 WELL
7 ON 7 ON LT2 WELL
8 ON 8 ON
PREVIOUS
POSSIBLE FAULT CAUSES
LOW WATER COIL TEMP
LOW WATER TEMP - HTG
LOW WATER FLOW - HTG
LOW REFRIG CHARGE - HTG
INCORRECT LT1 SETTING
BAD LT1 THERMISTOR
PREVIOUS

A C D U 0 3 C o m m u n i c a t i n g S e r v i c e To o l
R e v. : N o v e m b e r 3 , 2 0 1 7
12
G e o t h e r m a l H e a t P u m p S y s t e m s
5.0 Revision History
97B0106N01
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be
changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000
for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warran-
ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
© ClimateMaster, Inc. 2012
*97B0106N01*
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com
Rev.:
J a n u a r y 2 3 , 2 0 1 9
Date
Page #
Description
23 Jan. 19
3,4
Update harness and service tool part number
3 Nov., 17
All
Updated tstat Part number to ATC32U03
16 October, 2017
5
Update blower types
25 Jan., 2016
12
Updated Certifi cation Logos
17 Apr., 14
3,5
Text Updated
11 Feb., 14
All
ACDU01 Updated to ACDU02
23 Oct. 12
4-7
Unit Confi g, Pump Confi g and Valve Confi g Sections Updated
8 May, 12
All
First Published