Full Text Searchable PDF User Manual

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
1
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
GENERAL
Climate Wizard is an “Indirect Evaporative Air Cooler” that is capable of delivering cooled air, with no
added moisture at temperatures that are very similar to those produced by refrigerated air
conditioners. The Climate Wizard comprises of one (1) backward curved, high pressure,
centrifugal fan directly connected to an electronically commutated motor (ECM), a multi-patented
heat exchanger core, a water reservoir and water distribution system including circulating centrifugal
pump(s), automatic chlorination device and an auto water management feature.
Climate Wizard cannot remove moisture, but it does not add any moisture.
Climate Wizard is manufactured in two configurations - HORIZONTAL and VERTICAL. This
Application Guide refers to the HORIZONTAL configuration only.
The heat exchanger core may comprise of 2 or 3 sections.
The 2-section model is the CW-H10, with nominal cooling capacity of 10 KW*
The 3-section model is the CW-H15, with nominal cooling capacity of 15 KW*.
* [Cooling capacity is calculated at inlet conditions of 38
0
C dry-bulb and 10
0
C dewpoint temperatures, in accordance with Australian Standard AS2913-
2000. For other conditions refer tables on page 5. This capacity applies only when the Climate Wizard is being used in Stand Alone Cooling
applications. For Cold Front Cooling higher capacities apply - refer table on page 9.]
Not all the inlet air is delivered into the building. Inside the Climate Wizard the air is divided into
two streams..One stream is supercooled and delivered into the building, and the second stream is
used to intensify the wet-bulb depression, is supersaturated and discharged to atmosphere along
with all the heat that has been removed from the dry fresh air stream.
External Static pressure affects the behaviour of the two air streams inside the machine. A means
of compensating for the external static pressure will be provided on the Climate Wizard depending
on the application - see later information in this Guide.
INLET
(AMBIENT)
AIR
EXHAUST
AIR (WARM
& MOIST)
SUPPLY
AIR (COOL
& DRY)

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
2
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
GENERAL ….cont’d
Being a water based machine Climate Wizard incorporates features that recognise the necessity of
managing water quality and of complying with Codes that address regulations for health protection.
Inside the cooler there is an electrolytic Chlorinator that generates free Chlorine in the water
reservoir and behaves as a permanent biocide to annul any bacterial activity in the water. It is fail-
safe because if it ceases to function, the Climate Wizard will also shut down.
A water management system measures the salinity of the water and drains a percentage of the
water from the reservoir while admitting fresh water to dilute the salt concentration in the reservoir.
A 3-probe detector is located in the reservoir. This feature can be field set to either measure the
salinity via the probes, or to drain water out and admit fresh water after the level has reached the top
probe eight (8) times. [This is a measure of how much water has been evaporated in the machine.]
In Salinity measuring mode it maximises water usage before purging, thereby eliminating water
wastage.
SERVICES - water & electricity & drain
Climate Wizard requires a permanent water supply to be connected. 1/2 inch BSP male connection
point provided on the cooler (see diagram). Pressure range required - 100 kPa - 800kPa at flow
rate of 20 L/min.
Climate Wizard requires 3-phase electrical power to be supplied. Minimum 10 amp, 4-wire+
ground conductors supplied from independent circuit breaker. If required, main isolation switch to
be furnished by contractor adjacent to the cooler. Main power terminals provided inside electrical
cabinet with glands provided for cable entry.
A built-in Drain Valve is controlled by the water management system. The valve has 40mm BSP
male connection and is provided with a reducing fitting for connection if desired to a flexible hose for
running water to waste. See diagram for location. Recommended minimum drain hose internal
diameter 20mm.
TOP VIEW
121
120
DRAIN IN
FLOOR OF TANK
806
ACCESS COVER FOR
DRAIN CONNECTION
WATER CONNECTION
1
/2” BSP NIPPLE
806
AIR
INLET
END VIEW

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
3
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
Climate Wizard is designed to be used in 3 different types of applications:
1.
STAND ALONE COOLING - in cases where the Climate Wizard is the primary source of Air
Conditioning for the building.
2. SUPPLEMENTARY COOLING - in cases where the Climate Wizard is used to augment the
capacity of the existing air conditioning system, or to extend its reach into the building, or to
greatly reduce the energy consumption of the Air Conditioning plant.
3.
COLD FRONT COOLING - in cases where the Climate Wizard is used to pre-cool the fresh air
supply to new or existing refrigerated air conditioning plants in order to prolong the life of the
plants, to save significant energy, and to greatly reduce demand on existing infrastructure
which becomes over-stressed in heat-wave conditions.
In each application type, remarkable energy savings can be achieved compared with conventional
Refrigerated Air Conditioning. THE HOTTER THE CLIMATE THE MORE SAVINGS WILL BE
MADE.
See following pages for details of each application type.
CW
CW
STAND ALONE COOLING
CW
CW
COLD FRONT COOLING
AC
AC
CW
SUPPLEMENTARY COOLING
AC

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
4
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
STAND ALONE COOLING:
Climate Wizard can be used to supply the entire air conditioning demand of a building.
The Climate Wizard is intended to be installed external to any building, but may also be installed
indoors, for example in an air conditioning plant room provided that fresh outside air can be supplied
to the cooler and that the exhaust air is discharged directly to the exterior of the building.
The supply air temperature delivered by the Climate Wizard, and its airflow, is similar to the tempera-
ture and airflow of a refrigerated Air Conditioner. Therefore the air distribution design should follow
similar parameters of design and installation. Essentially that means similar duct sizes, similar
outlet design and attention given to the avoidance of cold air drafts. The use of Zones is acceptable
provided that used air can exit the building satisfactorily.
IT IS ESSENTIAL THAT THE PLANT BE SO ARRANGED THAT THE CLIMATE WIZARD EX-
HAUST AIR CANNOT BE RECIRCULATED INTO THE AIR INLET OF THE COOLER.
Sizing:
It should be understood that the Climate Wizard performance is similar to a refrigerated Air Condi-
tioner in regard to the supply air temperature and the ‘no added moisture’ feature. Since refriger-
ated Air Conditioners are sized on the basis of a heatload calculation, Climate Wizard must be
treated in the same way. Contractors should therefore continue to use their regular method for de-
termining the heatload of a building and apply the Climate Wizard to that heatload. The ‘Air Change
Rate’ method that is often used for Direct Evaporative Air Coolers is NOT to be used.
However, the rated capacity of the Climate Wizard will vary according to the local climate conditions,
and the indoor temperature setting. Thus a second calculation must be made before the final siz-
ing of the cooler can be made.
For the CW-H10: Cooling capacity = K1 x
T watts
[
K1 = specific heat x density x airflow = 1.23 x 800 L/sec = 984)
T = (Tset room - Tsupply)] [Tsupply is found in table 1.]
For the CW-H15: Cooling capacity = K2 x
T watts
[
K2 = specific heat x density x airflow = 1.23 x 1100 L/sec = 1353)
T = (Tset room - Tsupply)] [Tsupply is found in table 1.]
Table 1.
SHOWS SUPPLY AIR TEMPERATURE FOR
GIVEN INLET DRY-BULB AND DEWPOINT
TEMPERATURES
Inlet dry-bulb temperature - deg C
26 32 38 44 50
0
9.4 10.7 12.2 13.6 15.0
5
11.1 12.2 13.5 14.8 16.0
10
13.4 14.2 15.4 16.3 17.3
15
16.4 17.0 17.6 18.4 19.0
20
20.5 20.6 20.8 21.0 21.2
Inlet Tdew
deg C
FOR CONTROL SCHEMES
SEE SECTION HEADED
“CONTROL SCHEMES”

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
5
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
STAND ALONE COOLING:
Tables of Nominal Cooling Effect for Climate Wizard in various locations and various jurisdictions.
Tdb
Twb
Tdew
Trm
Ts
CW H
1
0 CW H
1
5
deg C
deg C
deg C
deg C
deg C
KW
KW
Beijing
34.5 20.9
1
3.9
27
1
7
1
0
1
4
Birm'ghm
27
1
8.3
1
3.3
24
1
5
9
1
2
Cairo
37.6 22
1
4.3
27
1
7.5
9
1
3
Chicago
32.4 22.5
1
8.
1
26.7
1
9
8
1
0
Dubai
42.8 23.8
1
4.5
27
1
7
1
0
1
4
Jo'berg
28.9
1
7.9
11
.3
24
1
5
9
1
2
Madrid
35.9
1
8.7 7.5
27
1
4
1
3
1
8
Milan
33.9 22.8
1
7.9
24
1
9.5
4
6
Paris
32.3 20.6
1
4.6
24
1
6
8
11
Phoenix
43.4 20.4 5.5
26.7
1
5
1
2
1
6
NOMINAL COOLING EFFECT FOR NAMED CITIES KW
Tdb
Twb
Tdew
Trm
Ts
CW H
1
0 CW H
1
5
deg C
deg C
deg C
deg C
deg C
KW
KW
AS29
1
3
38 2
1
11
.8
27.4
1
7
1
0
1
4
Eurovent
35
1
9 9.
1
27
1
5
1
2
1
6
UK (Cosaf)
30
1
6 5.6
22
1
7.5
4
6
CEC (USA)
32.8 20.5
1
4.
1
26.7
1
9
8
1
0
ARI (USA)
35 23.9
1
9.3
26.7
1
7
1
0
1
3
NOMINAL COOLING EFFECT FOR NAMED STANDARDS/NORMS KW
Tdb
ambient dry bulb temperature
Twb
ambient wet bulb temperature
Tdew
ambient dewpoint temperature
Trm
selected room temperature
Ts
supply air temperature from Climate Wizard

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
6
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
SUPPLEMENTARY COOLING:
Climate Wizard can be used to boost or supplement the existing air conditioning capacity of a build-
ing. In this application the Climate Wizard will be installed in a similar way to the Stand Alone ap-
plication, but will be sized to provide added cooling capacity to the building. It can also be used to
supply all the fresh air requirement of a building and in this case it will be sized according to the
fresh air quantity requirement.
The Climate Wizard is intended to be installed external to any building, but may also be installed
indoors, for example in an air conditioning plant room provided that fresh outside air can be supplied
to the cooler and that the exhaust air is discharged directly to the exterior of the building.
The supply air temperature delivered by the Climate Wizard, and its airflow, is similar to the tempera-
ture and airflow of a refrigerated Air Conditioner. Therefore the air distribution design should follow
similar parameters of design and installation. Essentially that means similar duct sizes, similar
outlet design and attention given to the avoidance of cold air drafts. The use of Zones is acceptable
provided that used air can exit the building satisfactorily.
IT IS ESSENTIAL THAT THE PLANT BE SO ARRANGED THAT THE CLIMATE WIZARD EX-
HAUST AIR CANNOT BE RECIRCULATED INTO THE AIR INLET OF THE COOLER.
Sizing:
The decision to install supplementary cooling equipment will arise from a number of causes:
1.
Existing plant is overloaded
2.
Existing plant is nearing end of life
3.
Energy consumption of building must be reduced but ‘Cold Front Cooling’ (see later heading)
option is either not possible or not economical
4.
Building has been extended but existing plant is at full capacity
In addressing points 1,2,3 above, since the Climate Wizard delivers 100% fresh air and with no
added moisture, the fresh air intake of the existing Air Conditioning plant should be closed in order
for the Climate Wizard to provide all the fresh air required for the building. This will have the imme-
diate effect of reducing the load on the existing plant and saving energy. The decision about the
quantity of Climate Wizard coolers depends entirely on matching the Climate Wizard airflow with the
quantity of fresh air that was being delivered by the existing plant. The amount of energy that was
being consumed by the existing plant will be greatly decreased because the Climate Wizard can
cool the same quantity of fresh air for much less consumed energy. See table under Cold Front
Cooling. The maximum supply airflow of the 2 Climate Wizard models is:
CW-H10
approx. 800 L/sec at 80 Pa
CW-H15
approx. 1100 L/sec at 80 Pa

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
7
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
SUPPLEMENTARY COOLING (cont’d):
Sizing (cont’d):
Addressing point 4 above, the foregoing procedure may be adequate to cope with the increased
load, but if not, additional Climate Wizard coolers may be installed. In this case the cooling capac-
ity of the Climate Wizard should be calculated in the same way as for Stand Alone cooling, using
local climate data and the desired indoor room temperature required by the Owners.
For the CW-H10: Cooling capacity = K1 x
T watts
[
K1 = specific heat x density x airflow = 1.23 x 800 L/sec = 984)
T = (Tset room - Tsupply)] [Tsupply is found in table 1.]
For the CW-H15: Cooling capacity = K2 x
T watts
[
K2 = specific heat x density x airflow = 1.23 x 1100 L/sec = 1353)
T = (Tset room - Tsupply)] [Tsupply is found in table 1.]
Table 1.
SHOWS SUPPLY TEMPERATURE FOR GIVEN
INLET
DRY-
BULB
AND
DEWPOINT
TEMPERA
TURES
Inlet Tdew
Inlet dry-bulb temperature
26 32 38 44 50
0
9.4 10.7 12.2 13.6 15.0
5
11.1 12.2 13.5 14.8 16.0
10
13.4 14.2 15.4 16.3 17.3
15
16.4 17.0 17.6 18.4 19.0
20
20.5 20.6 20.8 21.0 21.2
FOR CONTROL SCHEMES
SEE SECTION HEADED
“CONTROL SCHEMES”

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
8
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
COLD FRONT COOLING:
Cold Front Cooling describes the case in which Climate Wizard is used to pre-cool the fresh air com-
ponent of a refrigerated air conditioning plant. In most countries and jurisdictions around the world
a mandatory quantity of fresh air is required to be delivered into the building as a percentage of the
total air quantity of the air conditioning system. This quantity is often up to 25% of the total air re-
quirement of the application. Climate Wizard will completely cool this air at very low cost.
It is therefore extremely cost effective to use Climate Wizard to perform this function and thereby
reduce the load on the refrigeration plant, and its wear and tear while greatly reducing the cost of
running the plant.
The Climate Wizard is intended to be installed external to any building, but may also be installed
indoors, for example in an air conditioning plant room provided that fresh outside air can be supplied
to the cooler and that the exhaust air is discharged directly to the exterior of the building.
IT IS ESSENTIAL THAT THE PLANT BE SO ARRANGED THAT THE CLIMATE WIZARD EX-
HAUST AIR CANNOT BE RECIRCULATED INTO THE AIR INLET OF THE COOLER.
Examples of typical designs:
1. Climate Wizard installed on roof and ducted into Air Conditioning plant room below.
CW
A-C UNIT
Fresh air
intake
Return air
Supply air
to building
CW
Alternative
site for CW
Fresh air louvres to be
closed when Climate
Wizard installed on roof

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
9
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
COLD FRONT COOLING (cont’d):
Examples of typical designs (cont’d):
2.
Climate Wizard installed on roof and ducted directly into fresh air intake of Air Conditioner in
plant room below.
Two examples of Climate Wizard Cold Front Cooling installations in Australia
A-C UNIT
Fresh air
intake
Return air
CW
Supply air
to building
CW
Alternative
site for CW
Barometric
damper

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
10
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
COLD FRONT COOLING (cont’d):
The Barometric Damper may be controlled by natural pressure variations or, if motorised, by the
control system, depending on whether the Climate Wizard is required to function or not.
Sizing:
Cold Front Cooling means pre-cooling warm (hot) fresh air that is required by a refrigerated
Air Conditioning plant. Since Climate Wizard cools fresh air down to almost the dewpoint and does
not add any moisture, it is the ideal product to pre-cool the fresh air. This low-cost pre-cooled air
creates immediate energy savings for the building and it reduces the load on the refrigeration equip-
ment, thereby extending the life of the plant and saving capital outlay. It also enables load to be
removed from the existing over-stressed electrical power infrastructure, and especially so in heat-
wave conditions.
First ascertain the quantity of fresh air of which the refrigerated Air Conditioning plant is capable.
Match this quantity to the quantity of air of the Climate Wizard will deliver. The maximum supply
airflow of the 2 Climate Wizard models is:
CW-H10
approx. 800 L/sec at 80 Pa
CW-H15
approx. 1100 L/sec at 80 Pa
For customers who need to know the energy saving, the following table provides the Cooling Effect
in KW of each model at various ambient conditions.
Further reductions in energy consumption can be achieved when a portion of the return air is ducted
via the Climate Wizard.
Maximising the use of return air can also open up further very viable possibilities for Climate Wizard
in localities with extremely high dewpoint temperatures.
These are special cases and lie outside the scope of this Guide.
INLET DRY-BULB TEMPERATURE -
0
C
Tdew
20 26 32 38 44 50
0
CW-H10
12.0 16.3 21.0 25.4 29.9 34.4
CW-H15
16.5 22.5 28.8 34.9 41.1 47.4
5
CW-H10
10.0 14.7 19.5 24.1 28.7 33.5
CW-H15
13.8 20.2 26.8 33.1 39.5 46.0
10
CW-H10
7.6 12.4 17.5 22.2 27.3 32.2
CW-H15
10.4 17.0 24.1 30.6 37.5 44.2
15
CW-H10 4.3
9.4 14.8 20.1 25.2 30.5
CW-H15
6.0 13.0 20.3 27.6 34.6 41.9
20
CW-H10
5.4 11.2 16.9 22.6 28.3
CW-H15
7.4 15.4 23.3 31.1 39.0
Table of Cooling Effect for Climate Wizard - KW
COLD FRONT COOLING

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
11
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
1
2
3
4
5
6
L1 L2 L3
N
MAIN SUPPLY
3 POWER IN
MAIN P.C.B.
6 SALINITY PROBE
7 MOTOR CONTROL SIGNAL
9 WATER INLET SOLENOID
10 CHLORINATOR LINK
8 WALL CONTROL
1 MOTOR CONTACTOR COIL
4 PUMP LINK
2 FUSE T15A
1
2
3
4
5 6
7
8
9
10
5 DRAIN VALVE
FAN CONT
ACTOR
INTERFACE P.C.B.
11
4
14 15 16 17
10
11
11 INTERFACE BOARD LINK
E
1
3
5 A1
2
4
6 A2
bl
br
FAN
12 12
13 13
12 PUMP X 2
13 CHLORINATOR X 2
14 COOL/VENT INPUT
15 ERROR SIGNAL OUTPUT
16 REMOTE ON/OFF INPUT
17 FAN SPEED INPUT 0-10Vdc
br
bl
7
ELECTRICAL WIRING DIAGRAM FOR CLIMATE WIZARD

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
12
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
BAR
O
M
ET
RI
C PRE
SSUR
E
: 101.325 k
P
a
PSYCHRO
MET
R
IC
CHA
RT
No
rm
a
l Temper
atur
e
S
I Un
its
SE
A
LE
VEL
-2
0
-1
5
-1
0
-5
0
5
101
52
02
53
03
54
04
55
0
DRY
BUL
B
TE
M
P
ER
ATUR
E -
°
C
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
-1
0
-5
0
5
10
15
20
25
30
DEW
PO
IN
T T
EM
PE
RA
TURE
- °
C
Ch
ar
t by
: H
A
NDS
DO
W
N
S
O
F
T
W
A
R
E
, www.
ha
nd
sd
o
w
n
sof
tw
ar
e.
co
m
15
%
25
%
2%
4%
6%
8%
R
E
LA
T
IV
E
H
U
M
ID
IT
Y
10
%
R
E
LA
T
IV
E
H
U
M
ID
IT
Y
20
%
30
%
40
%
50
%
60
%
70%
80
%
90
%
-1
5
-15
-1
0
-10
-5
-5
0
5
5
10
10
15
15
20
20
25
25
30
W
ET
BU
LB
TE
M
PE
R
ATU
R
E
- °
C
30
HUMID
IT
Y RAT
IO
- GRAM
S M
OIS
TURE PE
R KILO
GR
AM
DRY AIR
BAR
O
M
ET
RI
C PRE
SSUR
E
: 101.325 k
P
a
PSYCHRO
MET
R
IC
CHA
RT
No
rm
a
l Temper
atur
e
S
I Un
its
SE
A
LE
VEL
Ch
ar
t by
: H
A
NDS
DO
W
N
S
O
F
T
W
A
R
E
, www.
ha
nd
sd
o
w
n
sof
tw
ar
e.
co
m
20 26
32
38
44
50
INLET
DR
Y
BU
LB T
E
M
P
E
R
AT
URE
CL
IM
A
T
E WI
Z
A
RD -
A
d
e
la
id
e
DI
RE
CT
EVA
P -
A
d
e
la
id
e
S
u
ppl
y te
m
p
- 2
3
.5
de
g
Lin
es of sup
pl
y temperature for
co
ns
ta
nt inlet
tem
pe
ra
tures
. F
or
intermedia
te supply
tempera
tures,
ap
pr
oximate the sup
pl
y temp
erature
between a
dja
cent
lin
es
.
PROVISIONAL
LINES OF SUPPL
Y
A
IR TEMPER
A
T
URE
Cl
im
ate
W
iz
ard
- sup
p
ly
ai
r temp - 15
.6
de
g C

This Guide is subject to change without notice.
REVISED AND PUBLISHED - 13 OCTOBER 2009
13
APPLICATION GUIDE
Models CW-H10, CW-H15
Indirect Evaporative Air Conditioner
CONTROL SCHEMES:
Climate Wizard coolers are supplied from the factory with one (1) Wall Control and a 20m control
cable. This makes it possible for the Cooler to be controlled independently and automatically from
the zone to which it is delivering cool air. No additional equipment is required. The Wall Control
incorporates a thermostat that regulates fan speed to maintain indoor temperature within + 0.5
0
C of
the set temperature. See table of Parameters and values
Climate Wizard Coolers are also supplied with an ‘Interface PCB’ that can be connected to a remote
BMS control system.
When either control option is being used, the inbuilt Climate Wizard water management and fault
monitoring features are fully operational. See table of monitored variables and fault values
The Climate Wizard control scheme incorporates some Parameters that can be altered to other set-
tings if the default settings are not suitable.
[