PDF User Manual

  1. Home
  2. Manuals
  3. Climacon MDV06I-018bW Installation Manual

Climacon MDV06I-018bW Installation Manual

Made by: Climacon
Type: Installation Manual
Category: Air Conditioner
Pages: 22
Size: 2.87 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

Four-way Cassette Type

INSTALLATION    MANUAL

Thank you very much for purchasing our air conditioner,  

Before using your air conditioner , please read this manual carefully and keep it for future reference.

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

Install according to this installation instructions strictly. 

If installation is defective, it will cause water leakage, 
electrical shock fire.

When installing the unit in a small room, take measures 
against to keep refrigerant concentration from exceeding 
allowable safety limits in the event of refrigerant leakage.

 

Contact the place of purchase for  information. Excessive 
refrigerant in a closed ambient can lead to oxygen deficiency.

Use the attached accessories parts and specified parts 
for installation. 

otherwise, it will cause the set to fall, water  leakage, 
electrical shock fire.

Install at a strong and firm location which is able to 
withstand the set' s weight. 

If the strength is not enough or installation is not properly 
done, the set will drop to cause injury.

The appliance must be installed 2.5m above floor.

The appliance shall not be installed in the laundry.

Before obtaining access to terminals, all supply circuits 
must be disconnected.

The appliance must be positioned so that the plug is 
accessible.

The enclosure of the appliance shall be marked by word, 
or by symbols, with the direction of the fluid flow.

For electrical work, follow the local national wiring 
standard, regulation and this installation instructions. An 
independent circuit and single outlet must be used. 

If electrical circuit capacity is not enough or defect in 
electrical work, it will cause electrical shock fire.

Use the specified cable and connect tightly and clamp 
the cable so that no external force will be acted on the 
terminal.

 

If connection or fixing is not perfect, it will cause heat-up or 
fire at the connection.

Wiring routing must be properly arranged so that control 
board cover is fixed properly. 

If control board cover is not fixed perfectly, it will cause 
heat-up at connection point of terminal, fire or electrical 
shock.

If the supply cord is damaged, it must be replaced by the 
manufacture or its sevice agent or similarly qualifued 
person in order to avoid a hazard.

An all-pole disconnection switch having a contract 
separation of at least 3mm in a  poles should be 
connected in fixed wiring.

When carrying out piping connection, take care not to let 
air substances go into refrigeration cycle. 

Otherwise, it will cause lower capacity, abnormal high 
pressure in the refrigeration cycle, explosion and injury.

Do not modify the length of the power supply cord or use 
of extension cord, and do not share the single outlet with 
other electrical appliances. 

Otherwise, it will cause fire or electrical shock.

1

installation manual

Be sure to be in conformity with the local, national and 
international laws and regulations.

Read "PRECAUTIONS" carefully before installation.

The following precautions include important safty items. 
Observe them and never forget.

Keep this manual with the owner's manual in a handy place 
for future reference.

 

1.    PRECAUTIONS

WARNING

WARNING

The safty precautions listed here are divided into two categories. In 
either case, important safty information is listed which must be read 
carefully.

After completing the installation, make sure that the unit operates 
properly during the start-up operation. Please instruct the customer 
on how to operate the unit and keep it maintained.Also, inform 
customers that they should store this installation manual along with 
the owner's manual for future reference.  

Be sure only trained and qualified service personnel to 
install, repair or service the equipment.

Improper installation, repair, and maintenance may result in 
electric shocks, short-circuit, leaks, fire or other damage to 
the equipment.

Failure to observe a warning may result in death.

CAUTION

Failure to observe a caution may result in injury or damage 
to the equipment.

CONTENTS

PAGE

PRECAUTIONS.......................................................................................1
INSTALLATION INFORMATION................................................................2
ATTACHED FITTINGS.............................................................................3
INDOOR UNIT INSTALLATION.................................................................4
OUTDOOR UNIT INSTALLATION..............................................................7
INSTALL THE CONNECTING PIPE...........................................................8
CONNECT THE DRAIN PIPE..................................................................10
WIRING................................................................................................11
TEST OPERATION.................................................................................12

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

2

installation manual

To install properly, please read this "installation manual" at 
first.

The air conditioner must be installed by qualified persons.

When installing the indoor unit or its tubing, please follow 
this manual as strictly as possible.

If the air conditioner is installed on a metal part of the 
building, it must be electrically insulated according to the 
relevant standards to electrical appliances.

When all the installation work is finished, please turn on the 
power only after a thorough check.

Regret for no further announcement if there is any change 
of this manual caused by product improvement.

2.    INSTALLATION INFORMATION

INSTALLATION ORDER

Select the location;

Install the indoor unit;

Install the outdoor unit;

Install the connecting pipe ;

Connect the drain pipe;

Wiring;

Test operation.

CAUTION

Ground the air conditioner.

Do not connect the ground wire to gas or water pipes, 
lightning rod or a telephone ground wire.Incomplete 
grounding may result in electric shocks.

Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in 
electric shocks.

Connect the outdoor unit wires , then connect the indoor 
unit wires.

 

You are not allow to connect the air conditioner with the 
power source until wiring and piping the air conditioner is 
done.

While following the instructions in this installation 
manual, install drain piping in order to ensure proper 
drainage and insulate piping in order to prevent 
condensation.

Improper drain piping may result in water leakage and 
property damage.

Install the indoor and outdoor units, power supply wiring 
and connecting wires at least 1 meter away from 
televisions or radios in order to prevent image 
interference or noise.

Depending on the radio waves, a distance of 1 meter may not 
be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children 
or infirm persons without supervision.

Young children should be supervised to ensure that they 
do not play with the appliance

.

Don't install the air conditioner in the following locations:

There is petrolatum existing.

There is salty air surrounding (near the coast).

There is caustic gas (the sulfide, for example) existing in 
the air (near a hot spring).

The Volt vibrates violently (in the factories).

In buses or cabinets.

In kitchen where it is full of oil gas.

There is strong electromagnetic wave existing.

There are inflammable materials or gas.

There is acid or alkaline liquid evaporating.

Other special conditions.

Carry out the specified installation work after taking 
into account strong winds, typhoons or earthquakes.

Improper installation work may result in the equipment 
falling and causing accidents.

If the refrigerant leaks during installation, ventilate the 
area immediately.

Toxic gas may be produced if the refrigerant comes into the 
place contacting with fire.

After completing the installation work, check that the 
refrigerant does not leak.

Toxic gas may be produced if the refrigerant leaks into the 
room and comes into contact with a source of fire, such as 
a fan heater, stove or cooker.

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

3.    ATTACHED FITTINGS

Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully. 

QUANTITY

INSTALLATION FITTINGS

Tubing & Fittings

Remote controller & Its Frame

Drainpipe Fittings

Protect Pipe Fittings

Others

SHAPE

NAME

1. Expansible hook

5. Connecting pipe group

7. Soundproof / insulation sheath

6. Binding tape

8. Out-let pipe sheath

9. Out-let pipe clasp

10. Tightening band

11. Drain joint

12. Seal ring

13. Wall conduit

14. Wall conduit cover

19. Owner's manual

20. Installation manual

15. Remote controller

16. Frame

17. Mounting screw(ST2.9

10-C-H) 

18. Alkaline dry batteries (AM4)

2. Installation hook

3. Installation paper board        

4. Bolt  M5

4

4

4

1

1

4

6

2

1

1

20

1

1

1

1

1

1

2

2

1

1

3

installation manual

21.Net work winding

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

4.    INDOOR UNIT INSTALLATION

Drain side

Tubing side

                                     (Unit: mm)

780(Hook-location)

680(Hook-location)

840(Body)

840(Body)

950(Panel)

950(Panel)

>1000mm

>1000mm

>1000mm

>1000mm

Body

L

Ceiling

10-12mm

Body

Central  hole

Bolt M6X12

Installation paper board

Ceiling

880mm (ceiling hole)

Ground

A

H

Panel

Inlet

Outlet

Outlet

>2500mm

Connecting point of drain pipe

Connecting point of 
refrigerant pipe

Connecting point of 
refrigerant pipe

(Liquid side 

C)

(Gas side 

B)

Grid switch

45 

Slit

Side plate

Inner insulation

Drain piper

Piping 

Side plate

Inner insulation

Inner insulation

Insulation (local)

Side plate

Insulation (local)

10mm

fig.2

fig.3

fig.4

fig.1

fig.8

fig.11

fig.10

fig.9

fig.6

fig.7

MODEL

A

B

C

H

18000

24000

260

260

240

240

12.7

6.35

Table 1

mm

NOTE

All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you 
purchased(depend on model).The actual shape shall prevail.

FIGURES 1

16

9.53

330

310

16

9.53

36000

48000

330

310

16

9.53

4.1

4

installation manual

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

fig.5

 


background image

installation manual

5

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

>1000mm

>1000mm

>1000mm

>1000mm

Body

L

Ceiling

10-12mm

Body

Central  hole

Bolt M6X12

Installation paper board

Grid switch

45 

fig.14

fig.15

fig.12

fig.6

fig.21

fig.20

fig.19

fig.16

fig.17

NOTE

All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you 
purchased(depend on model).The actual shape shall prevail.

the oth

er one structure for 1800

But/h

Drain side

Tubing side

                                     (Unit: mm)

3DQHO

3DQHO

3DQHO

+RRNORFDWLRQ

+RRNORFDWLRQ

%RG\

!PP

PP

2XWOHW

2XWOHW

,QOHW

Tubing side

&RQQHFWLQJSRLQWRIGUDLQSLSH

&RQQHFWLQJSRLQWRI
UHIULJHUDQWSLSH

/LTXLGVLGHž

&RQQHFWLQJSRLQWRI
UHIULJHUDQWSLSH
*DVVLGHž

3DQHO

&HLOLQJ

!PP

Drain piper

Piping 

7KHRWKHURQHVWUXFWXUHIRU%XWK

7KHRWKHURQHVWUXFWXUHIRU%XWK

fig.13

fig.18

4.2

 


background image

Cross-screwdriver

Outlet joint

Tubing joint Hook panel

Swing Motor

Hook-bolt

Water- receiver

,

Installation cover s rope

Tap Screw

Slide the four sliders
in the corresponding 
channel when installing 
the cover 

Leakage

Ceiling

Pollution

Water condensation

<200mm

1-1.5 m

<200mm

Lean over 1/50

Pump-pipe clasp

 (the fittings)

fig.22

fig.24

fig.26

fig.28

panel sponge

body

Ceiling

panel

panel foam1 

air out

Fan

panel foam 2

4

- 6m

m

outlet foam

Loosen upper nut

Adjust lower nut

Gap not allowed

1-1.5 m

a  

b

>1.5m

c  

Lean over 1/50

Fasten here

Drainpipe

Pump joint

Test mouth

Body

Water-receiver

Test cover

Stow tube

Drain plug

fig.23

fig.25

fig.27

fig.29

Connecting pipe

NOTE

All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you 
purchased(depend on model).The actual shape shall prevail.

FIGURES 2

4.3

6

installation manual

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

4.4   Install The Panel

5.1   Installation Place

Remove the air-in grill.

CAUTION

Never put the panel face down on floor or against the 
wall, or on bulgy objects.

Never crash or strike it.

Do not coil the wiring of the swing motor into the seal 
sponge.

CAUTION

Slide two grill switches toward the middle at the same time, 
and then pull them up. 

(Refer to fig.9)

Draw the grill up to an angle of about 45, and remove it. 

(Refer to fig.10)

Remove the installation covers at the four corners

Wrench off the bolts, loose the rope of the installation covers, 
and remove them. 

(Refer to fig.11)

Install the panel

Align the swing motor on the panel to the tubing joints of the 
body properly. 

( Refer to fig.22)

Fix hooks of the panel at swing motor and its opposite sides 
to the hooks of corresponding water receiver. ( Refer to  
fig.22.1) Then hang the other two panel hooks onto 
corresponding hangers of the body. 

( Refer to fig.22.2)

 

Adjust the four panel hook screws to keep the panel 
horizontal, and screw them up to the ceiling evenly. 

( Refer to  

fig.22.3)

Regulate the panel in the direction of the arrow in fig.12.4 
slightly to fit the panel's center to the center of the ceiling's 
opening. Guarantee that hooks of four corners are fixed well.

1

2

3

4

5

6

Keep fastening the screws under the panel hooks, until the 
thickness of the sponge between the body and the panel's 
outlet has been reduced to about 4~6mm. The edge of the 
panel should contact with the ceiling well.

 (Refer to fig.23)

    

Fasten the rope of installation cover on the bolt of the 
installation cover. 

(Refer to fig.26-left) 

Press the installation cover into the panel slightly. 

(Refer to 

fig.26-right)

    

Malfunction described in fig.24 can be caused by 
inappropriate tightness the screw. 

If the gap between the panel and ceiling still exists after 
fastening the screws, the height of the indoor unit should 
be modified again. 

( Refer to fig.25-left)

You can modify the height of the indoor unit through the 
openings on the panel's four corners, if the lift of the 
indoor unit and the drainpipe is not influenced 

(refer to 

fig.26-right).

Hang the air-in grill to the panel, then connect the lead 
terminator of the swing motor and that of the control box 
with corresponding terminators on the body respectively.

Relocate the air-in grill in the procedure of reversed order.

Relocate the installation cover.

5.    OUTDOOR UNIT INSTALLATION

There is enough room for installation and maintenance.

The air outlet and the air inlet are not impeded, and can 
not be reached by strong wind.

It must be a dry and well ventilating place.

The support is flat and horizontal and can stand the 
weight of the outdoor unit. And will no additional noise or 
vibration.

Your neighborhood will not feel uncomfortable with the 
noise or expelled air.

It is easy to install the connecting pipes or cables.

Determine the air outlet direction where the discharged air 
is not blocked.

There is no danger of fire due to leakage of inflammable 
gas.

The piping length between the outdoor unit and the indoor 
unit may not exceed the allowable piping length.

In the case that the installation place is exposed to strong 
wind such as a seaside, make sure the fan operating 
properly by putting the unit lengthwise along the wall or 
using a dust or shield.

(refer to fig.30)

If possible, do not install the unit where it is exposed to 
direct sunlight. 

If necessary, install a blind that does not interfere with the 
air flow.

During the heating mode, the water drained off the 
outdoor unit ,The condensate should be well drained away 
by the drain hole to an appropriate place, so as not to 
interfere other people. 

Select the position where it will not be subject to snow 
drifts, accumulation of leaves or other seasonal debris. If 
unavoidable, please cover it with a shelter.

Locate the outdoor unit as close to the indoor unit as 
possible.

If possible, please remove the obstacles nearby to prevent 
the performance from being impeded by too little of air 
circulation.

The minimum distance between the outdoor unit and 
obstacles described in the installation chart does not 
mean that the same is applicable to the  situation of an 
airtight room. Leave open two of the three directions 
(M,N,P) 

(refer to fig.33)

X

O

Strong wind

(fig.30)

The outdoor unit should be installed in the location that 
meets the following requiements:

NOTE

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail.

7

installation manual

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

A

H

(fig.31)

(fig.33)

(fig.32)

B

E

C

D

5.2   Moving and installation

>

60

c

m

Fix with bolt

(fig.34)

6.    INSTALL THE CONNECTING PIPE

Check whether the height drop between the indoor unit and 
outdoor unit, the length of refrigerant pipe, and the number of 
the bends meet the following requirements:

CAUTION

All field piping must be provided by a licensed 
refrigeration technician and must comply with the 
relevant local and national codes.

Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation.

The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already.

Keep the connecting pipe dry, and do not let moisture in 
during installation.

Execute heat insulation work completely on both sides 
of the gas piping and the liquid piping. Otherwise, this 
can sometimes result in water leakage.

   The Procedure of Connecting Pipes

6.1

MODEL

18

24

36

48

A

B

C

D

E

H

840

894

990

940

560

590

624

600

335

333

366

376

360

355

396

400

310

302

340

340

677

860

960

1245

R410A

Table 2

mm

REMARK

>30cm

>60cm

>30cm

 >200

cm

(Wall or obstacle)

Maintain channel

Air outlet

Air inlet

M

P

Air inlet

N

NOTE

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail.

NOTE

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail.

Since the gravity center of the unit is not at its physical 
center, so please be careful when lifting it with a sling.

Never hold the inlet of the outdoor unit to prevent it from 
deforming.

Do not touch the fan with hands or other objects.

Do not lean it more than 45, and do not lay it sidelong.

Make concrete foundation accoding to the sepecif-ications of 
the outdoor units.

(refer to fig.34)

Fasten the feet of this unit with bolts firmly to prevent it from 
collapsing in case of earthquake or strong wind.

(refer to 

fig.34)

 

Table 3

The max 
height 
drop (m)

 

When outdoor 
unit is top

 

When outdoor 
unit is bottom

 

The length of refrigerant pipe (m) 

The number of bends 

   

Capicity (Btu/h)

 

/HVVWKDQ

8

installation manual

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

How to Connect the pipes

Drill a hole in the wall (suitable just for the size of the wall 
conduit), then set on the fittings such as the wall conduit and 
its cover.

Bind the connecting pipe and the cables together tightly with 
binding tapes.
Pass the bound connecting pipe through the wall conduct 
from outside. Be careful of the pipe allocation to do on 
damage to the tubing.
 
Connect the pipes. Refer to "How to Connect the pipes" for 
details.

Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details.

open the stop values of the outdoor unit to make the 
refrigerant pipe connecting the indoor unit with the outdoor 
unit in fluent flow.

Check the leakage. Check all the joints with the leak detector 
or soap water.

Cover the joints of the connecting pipe with the soundproof / 
insulating sheath (fittings), and bind it well with the tapes to 
prevent leakage.

1

2

3

5

6

7

4

Be sure to with insulating materials cover all the exposed 
parts of the flare pipe joints and refrigerant pipe on the 
liquid-side and the gas-side. Ensure that there is no gap 
between them.
Incomplete insulation may cause water condensation.

Flaring

1

Cut a pipe with a pipe cutter. 

(refer to fig.22)

2

Bend the tubing in proper way. Do not harm to them.

Connect the indoor unit at first, then the outdoor 
unit.

Too large torque will harm the bellmouthing and too small 
will cause leakage. Please determine the torque 
according to Table 4.

After the connecting work is finished, be sure to check 
that there is no gas leak.

The bending angle should not exceed 90.

Bending position is preferably in the middle of the 
bendable pipe. The larger the bending radius the better it 
is.

Do not bend the pipe more than three times.

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly.

Be sure to use both a spanner and torque wrench 
together when connecting or disconnecting pipes to /from 
the unit.

Ta ble 4

PP

̚1P

̚NJIFP

̚1P

̚NJIFP

̚1P

̚NJIFP

̚1P

̚NJIFP

̚1P

̚NJIFP

5a

°±

°     

±

$

Insert a flare nut into a pipe and flare the pipe.

Refer to Table 4 for the dimension of flare nut spaces.

90

Lean     crude     burr

(refer to fig.35)

min

max

Bend the pipe with thumb

min-radius 100mm

(fig.36)

(fig.37)

(fig.38)

CAUTION

CAUTION

How to expel the air with a vacuum pump

Stop valve operation intruduction

1.          Opening stop valve

2.          Closing stop valve

1.

2.

1.

2.

3.

Remove the cap and turn the valve 
counterclock-wise with the hexagon wrench.

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may breakthe valve body, as 
the valve is not a backseat type. Always use the special 
tool.

Make sure to tighten the cap securely.

Remove the cap and turn the valve clockwise with the 
hexagon wrench.

Securely tighten the valve until the shaft contacts the 
main bodyseal.

Pipe  gauge Tightening     torque

t

Flare dimensin A

Flare     shape

9

installation manual

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

Tightening torque N  M (Turn clockwise to close)

Stop

Valve

size

Shaft

(valve body)

Cap

(Valve lid)

Ø6.4

5.4

̚

6.6

Hexagonal

wrench 4 mm

13.5

̚

16.5

11.5

̚

13.9

Ø9.5

Ø12.7

8.1

̚

9.9

18

̚

22

Ø15.9

13.5

̚

16.5

Hexagonal

wrench 6 mm

23

̚

27

Ø22.2

27

̚

33

Hexagonal

wrench

10 mm

36

̚

44

Ø25.4

Loosen and remove the maintenance nuts of stop valves A 
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A 
and B are both closed)

Connect the joint of the charge hose with the vacuum pump.

Open the Lo-lever of the manifold value completely.

Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut.

1

2

4

3

5

7

6

-76 cmHg

Lo-lever

Hi-lever

Charge hose

Charge hose

Vacuum pump

Lo-lever

Manifold valve

Multi-meter

Pressure meter

(fig.28)

Additional Refrigerant Charge

6.2

CAUTION

Refrigerant cannot be charged until field wiring has been 
completed.

Refrigerant may only be charged after performing the leak 
test  and the vacuum pumping.

W h e n  c h a r g i n g  a  s y s t e m ,  c a r e  s h a l l  b e  t a k e n  t h a t  i t s 
maximum permissible charge is never exceeded, in view of 
the danger of liquid hammer.

C h a r g i n g  w i t h  a n  u n s u i t a b l e  s u b s t a n c e  m a y  c a u s e 
e x p l o s i o n s  a n d  a c c i d e n t s ,  s o  a l w a y s  e n s u r e  t h a t  t h e 
appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes when 
charging refrigerant.

The outdoor unit is factory charged with refrigerant. Some 
systems require additional charging of refrigerant depending 
on pipe lengths. The additional refrigerant to be charged 
can be calculated from the following formule:

R = T X (L-5)m

7.    CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit

You can use a polyethylene tube as the drainpipe 
(out-dia.37-39mm, in-dia.32mm). It could be bought at local 
market or from your dealer.
 
Set the mouth of the drainpipe onto the root of the body's 
pump-pipe, and clip the drainpipe and the out-let pipe sheath 
(fittings) together firmly with the out-let pipe clasp (fitting).

Using the vacuum pump

When the pumping has finished, close the Lo-lever of the 
manifold valve completely and turn off the vacuum 
pump.Make pumping for 15 minutes or more and check that 
the compound meter indicates -76cmHg(-1X10 Pa)

Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap.

Disassemble the charge hose from the service port of stop 
valve A, and fasten the nut.

5

(fig.40)

NOTE

If a negative result is gotten for R from the formule at 
right, no refrigam needs to be added nor removed.

(fig.39)

CAUTION

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks 
arepresent.

service port

cap

maintenance nut

hexagon hole

shaft

seal

Make sure to tighten the cap securely.
For the tightening torque, refer to the table below.

Outdoor
unit

Indoor
unit

Stop valve

Gas side

Liquid side

A

C

D

B

Table 5

Maintenance 
nut

Table 3

   

&DSLFLW\%WXK

&DSLFLW\%WXK

7J

7J

7

g

7KHTXDQWLW\RIWKHFKDUJHG

R(g): Additional refrigetant to be charged
L(m): The length of the liquid pipe

UHIULJHUDQWSHUPHWHU

10

installation manual

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

Drainage test

Drainage test

Inatall the drain joint of the outdoor unit

Check whether the drainpipe is unhindered.

New built house should have this test done before paving 
the ceiling.

Remove the test cover, and stow water of about 2000ml to the 
water receiver through the stow tube. 

( Refer to fig.29 in the 

figure page)

Turn on the power, and operate the air conditioner under the 
"COOLING" mode. Listen to the sound of the drain pump. 
Check whether the water is discharger well (a lag of 1min is 
allowed before discharging, according to the length of the drain 
pipe), and check whether water leaks from the joints.

1

2

Stop the air conditioner, turn off the power, and reset the test 
cover to its original position.

3

Fit the seal into the drain joint, then insert the drain joint into the 
base pan hole of outdoor, rotate 90 to securely assemble them. 
Connect the drain joint with an extension drain hose (Locally 
purchased), in case of the condensate draining off the outdoor 
unit during the heating mode.

8.    WIRING

CAUTION

The air conditioner should use separate power supply 
with rated voltage.

The external power supply to the air conditioner should 
have ground wiring, which is linked to the ground wiring 
of the indoor and outdoor unit.

The wiring work should be done by qualified persons 
according to circuit drawing.

An all-pole disconnection switch having a cintract 
separation of at least 3mm in a  poles should be 
connected in fixed wiring.

Be sure to locate the power wiring and the signal wring 
well to avoid cross-disturbance.

Do not turn on the power until you have checked 
carefully after wiring.

NOTE

The drain plug is used to empty the water-receiver for 
maintenance of the air conditioner. Please stuff it imposition at 
all times during operation to avoid leakage.

The body's pump pipe and the drainpipe (especially the 
indoor part) should be covered evenly with the out-let pipe 
sheath (fittings) and be bound tightly with the constrictor to 
prevent condensation caused by entered air.

To prevent water from flowing backwards into the air 
conditioner while the air conditioner stops, please lean the 
drainpipe down toward outdoor (outlet-side) at a degree of 
over 1/ 50. And please avoid any bulge or water deposit. ( 
Refer to fig.27.a in the figure page)

Do not drag the drainpipe violently when connecting to 
prevent the body from being pulled. Meanwhile, one 
supportpoint should be set every 1~1.5m to prevent the 
drainpipe from yielding (Refer to fig.27.a in the figure page). 
Or you can tie the drainpipe with the connecting pipe to fix 
it.(Refer to fig.27.c in the figure page)

In the case of prolonged drainpipe, you had better tighten its 
indoor part with a protection tube to prevent it from loosing.

If the outlet of the drainpipe is higher than the body's pump 
joint, the pipe should be arranged as vertically as possible. 
And the lift distance must be less than 200mm, otherwise the 
water will overflow when the air conditioner stops.( Refer to 
fig.28 in the figure page)

The end of the drainpipe should be over 50mm higher than 
the ground or the bottom of the drainage chute, and do not 
immerse it in water. If you discharge the water directly into 
sewage, be sure to make a U-form aquaseal by bending the 
pipe up to prevent the smelly gas entering the house through 
the drain pipe.

NOTE

The power connection for the air conditioner has to be 
done at the main power distribution. The distribution has 
t o  b e  o f  a  l o w  i m p e d a n c e ,  n o r m a l l y  t h e  r e q u i r e d 
impedance reaches at a 32 A fusing point.

No other equipment has to be connected with this power 
line.

For detailed installation acceptance please refer to your 
power supplier, if restrictions do apply for products like 
washing machines, air conditioners or electrical ovens. 

For power details of the air conditioner refer to the rating 
plate of the product. 

For any question contact your local dealer.

Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the 
compressor (technical process) ,following installation 
conditions do apply.

1

2

4

3

5

Seal

The base pan hole
of outdoor unit

Drain joint

Seal

The base pan 
of outdoor unit 

Drain 
joint

(fig.42)

NOTE

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail.

11

installation manual

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

Dissemble the bolts from the cover.(If there isn't a cover on 
the outdoor unit, disassemble the bolts from the maintenance 
board, and pull it in the direction of the arrow to remove the 
protection board.)

(refer to fig.43)

Connect the connective cables to the terminals as identified 
with their respective mached numbers on the terminal block 
of indoor and outdoor units.

Re-install the cover or the protection board.

Connect the cable

8.1

The Specification of Power

8.2

Wiring figure

8.3

(refer to table6

̚

table 7

)

(refer to Fig44

̚

Fig47

)

(fig.33)

Protection board

Cover

9.  TEST OPERATION

The test operation must be carried out after the entire 
installation has been completed.

Please confirm the following points before the test operation:

2

1

According to the user's requirement, install the remote 
controller frame where the remote controller's signal can 
reach the indoor unit smoothly.

Test operation

4

3

The indoor unit and outdoor unit are installed properly.

Tubing and wiring are correctly completed.

The refrigerant pipe system is leakage-checked.

The drainage is unimpeded.

The heating insulation works well.

The ground wiring is connected correctly.

The length of the tubing and the added stow capacity of 
the refrigerant have been recorded.

The power voltage fits the rated voltage of the air 
conditioner.

There is no obstacle at the outlet and inlet of the outdoor 
and indoor units.

The gas-side and liquid-side stop valves are both opened.

The air conditioner is pre-heated by turning on the power.

Set the air conditioner under the mode of "COOLING" with the 
remote controller, and check the following points. If there is 
any malfunction, please resolve it according to the chapter 
"Troubleshooting" in the "Owner's Manual". 

1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works 
well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during 
operation.
I. Whether the air conditioner heats well in the case of the 
HEATING/COOLING type.

2) The outdoor unit
a. Whether there is vibration or abnormal noise during 
operation.
b. Whether the generated wind, noise, or condensed of by 
the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked. 

CAUTION

A protection feature prevents the air conditioner from being 
activated for approximately 3 minutes when it is restarted 
immediately after shut off.

NOTE

All the pictures in this manual are for explanation 
purpose only. They may be slightly different from the 
air conditioner you purchased(depend on model).The 
actual shape shall prevail.

12

installation manual

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

 

Table 6

13

installation manual

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

    A

( )

Cap icity(Btu/h)

(WEAK ELECTRIC SIGNAL)

INDOOR/OUTDOOR CONNECTING  WIRING

CIRCUIT BREAKER/FUSE

 POW ER WIRIN G

PH ASE

FREQUENCY 
  AND VOLT

1-PHASE

220-240V~   50Hz

30/25

3X1.0

3 X2.5

3-core  shield ed

 wire

18000

1-PHASE

220 -240V~  50H z

4 0/25

3X1.0

3 X2.5

24 000

40/25

3 X1.0

5X2.5

3600 0-60000

1-PHASE

220-240V~   50 Hz

3-core sh ielded

wire

3-core sh ielded

 wire

OU TD OOR UN IT 

POWER

IN DOOR UNIT 

POWER

PHASE

FREQUENCY 
  AND VOLT

1-PHASE

1-PHASE

3-PHASE

1-PHASE

220-240V~  50H z 220 -240V~  50H z 380-415 V~  50 Hz

 POWER W IRING

  (  m )

2  

m

  (  m )

m

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSLFLW\%WXK

14

installation manual

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH

KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\

OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\

DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH

LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

PDLQWHQDQFHSHUVRQ

15

installation manual

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

16

installation manual

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

Fig.45

Switch/Fuse

Power wiring (indoor)

Indoor
Unit

Outdoor
Unit

CAUTION

The wiring chart of cooling& heating type in  R410A series are shown as follows.When wiring, please 
choose the corresponding figure,or it may cause damage.

CENTRAL CONTROL
MONITOR(CCM)

COMPUTER

Power supply

380-415V~ 50Hz

Power supply

220-240V~ 50Hz

3-phase

1-phase

Communication Bus

Power wiring (outdoor)

Fig.44

Switch/Fuse

Power wiring (indoor)

Indoor
Unit

Outdoor
Unit

CENTRAL CONTROL
MONITOR(CCM)

COMPUTER

Power supply

Power supply

220-240V~ 50Hz

1-phase

Communication Bus

Power wiring (outdoor)

220-240V~ 50Hz

1-phase

For 18000-24000Btu/h

For 36000-48000Btu/h

17

installation manual

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

18

installation manual

Fig.46

Fig.47

For 18000-24000Btu/h

For 36000-48000Btu/h

9+]

FRUHFDEOH;PP

3RZHUVXSSO\

3KDVH

9+]

FRUHFDEOH;PP

3RZHUVXSSO\

3KDVH

FRUHFDEOH[PP

FRUHVKLHOGHGFDEOH

28

7'

22

5

81

,7

3RZHUVXSSO\

3KDVH9

̚

FRUHFDEOH[PP

3RZHUVXSSO\

3KDVH9

̚

,1'22581,7

/

1

/

/

72 &&0
&20 0%8 6

%WXK,QGRRUXQLW
HOHFWULFDOSODWHZLWK
RUWHUPLDOV

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

19

installation manual

ndenser

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

     MDV06I-018bW 

2200017216

7KHRWKHURQHVWUXFWXUHIRU%XWK

 


background image

 

&DSLFLW\%WXK

7J

&DSLFLW\%WXK

&DSDFLW\%WXK

1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ

7KHRWKHURQHVWUXFWXUHIRU%XWK