Full Text Searchable PDF User Manual

Four-way Cassette Type
INSTALLATION MANUAL
Thank you very much for purchasing our air conditioner,
Before using your air conditioner , please read this manual carefully and keep it for future reference.
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

Install according to this installation instructions strictly.
If installation is defective, it will cause water leakage,
electrical shock fire.
When installing the unit in a small room, take measures
against to keep refrigerant concentration from exceeding
allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for information. Excessive
refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts
for installation.
otherwise, it will cause the set to fall, water leakage,
electrical shock fire.
Install at a strong and firm location which is able to
withstand the set' s weight.
If the strength is not enough or installation is not properly
done, the set will drop to cause injury.
The appliance must be installed 2.5m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits
must be disconnected.
The appliance must be positioned so that the plug is
accessible.
The enclosure of the appliance shall be marked by word,
or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring
standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in
electrical work, it will cause electrical shock fire.
Use the specified cable and connect tightly and clamp
the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or
fire at the connection.
Wiring routing must be properly arranged so that control
board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause
heat-up at connection point of terminal, fire or electrical
shock.
If the supply cord is damaged, it must be replaced by the
manufacture or its sevice agent or similarly qualifued
person in order to avoid a hazard.
An all-pole disconnection switch having a contract
separation of at least 3mm in a poles should be
connected in fixed wiring.
When carrying out piping connection, take care not to let
air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high
pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use
of extension cord, and do not share the single outlet with
other electrical appliances.
Otherwise, it will cause fire or electrical shock.
1
installation manual
Be sure to be in conformity with the local, national and
international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safty items.
Observe them and never forget.
Keep this manual with the owner's manual in a handy place
for future reference.
1. PRECAUTIONS
WARNING
WARNING
The safty precautions listed here are divided into two categories. In
either case, important safty information is listed which must be read
carefully.
After completing the installation, make sure that the unit operates
properly during the start-up operation. Please instruct the customer
on how to operate the unit and keep it maintained.Also, inform
customers that they should store this installation manual along with
the owner's manual for future reference.
Be sure only trained and qualified service personnel to
install, repair or service the equipment.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to
the equipment.
Failure to observe a warning may result in death.
CAUTION
Failure to observe a caution may result in injury or damage
to the equipment.
CONTENTS
PAGE
PRECAUTIONS.......................................................................................1
INSTALLATION INFORMATION................................................................2
ATTACHED FITTINGS.............................................................................3
INDOOR UNIT INSTALLATION.................................................................4
OUTDOOR UNIT INSTALLATION..............................................................7
INSTALL THE CONNECTING PIPE...........................................................8
CONNECT THE DRAIN PIPE..................................................................10
WIRING................................................................................................11
TEST OPERATION.................................................................................12
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

2
installation manual
To install properly, please read this "installation manual" at
first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow
this manual as strictly as possible.
If the air conditioner is installed on a metal part of the
building, it must be electrically insulated according to the
relevant standards to electrical appliances.
When all the installation work is finished, please turn on the
power only after a thorough check.
Regret for no further announcement if there is any change
of this manual caused by product improvement.
2. INSTALLATION INFORMATION
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes,
lightning rod or a telephone ground wire.Incomplete
grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in
electric shocks.
Connect the outdoor unit wires , then connect the indoor
unit wires.
You are not allow to connect the air conditioner with the
power source until wiring and piping the air conditioner is
done.
While following the instructions in this installation
manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent
condensation.
Improper drain piping may result in water leakage and
property damage.
Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 meter away from
televisions or radios in order to prevent image
interference or noise.
Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children
or infirm persons without supervision.
Young children should be supervised to ensure that they
do not play with the appliance
.
Don't install the air conditioner in the following locations:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in
the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
Carry out the specified installation work after taking
into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment
falling and causing accidents.
If the refrigerant leaks during installation, ventilate the
area immediately.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire.
After completing the installation work, check that the
refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the
room and comes into contact with a source of fire, such as
a fan heater, stove or cooker.
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
QUANTITY
INSTALLATION FITTINGS
Tubing & Fittings
Remote controller & Its Frame
Drainpipe Fittings
Protect Pipe Fittings
Others
SHAPE
NAME
1. Expansible hook
5. Connecting pipe group
7. Soundproof / insulation sheath
6. Binding tape
8. Out-let pipe sheath
9. Out-let pipe clasp
10. Tightening band
11. Drain joint
12. Seal ring
13. Wall conduit
14. Wall conduit cover
19. Owner's manual
20. Installation manual
15. Remote controller
16. Frame
17. Mounting screw(ST2.9
10-C-H)
18. Alkaline dry batteries (AM4)
2. Installation hook
3. Installation paper board
4. Bolt M5
4
4
4
1
1
4
6
2
1
1
20
1
1
1
1
1
1
2
2
1
1
3
installation manual
21.Net work winding
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

4. INDOOR UNIT INSTALLATION
Drain side
Tubing side
(Unit: mm)
780(Hook-location)
680(Hook-location)
840(Body)
840(Body)
950(Panel)
950(Panel)
>1000mm
>1000mm
>1000mm
>1000mm
Body
L
Ceiling
10-12mm
Body
Central hole
Bolt M6X12
Installation paper board
Ceiling
880mm (ceiling hole)
Ground
A
H
Panel
Inlet
Outlet
Outlet
>2500mm
Connecting point of drain pipe
Connecting point of
refrigerant pipe
Connecting point of
refrigerant pipe
(Liquid side
C)
(Gas side
B)
Grid switch
45
Slit
Side plate
Inner insulation
Drain piper
Piping
Side plate
Inner insulation
Inner insulation
Insulation (local)
Side plate
Insulation (local)
10mm
fig.2
fig.3
fig.4
fig.1
fig.8
fig.11
fig.10
fig.9
fig.6
fig.7
MODEL
A
B
C
H
18000
24000
260
260
240
240
12.7
6.35
Table 1
mm
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you
purchased(depend on model).The actual shape shall prevail.
FIGURES 1
16
9.53
330
310
16
9.53
36000
48000
330
310
16
9.53
4.1
4
installation manual
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK
fig.5

installation manual
5
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
>1000mm
>1000mm
>1000mm
>1000mm
Body
L
Ceiling
10-12mm
Body
Central hole
Bolt M6X12
Installation paper board
Grid switch
45
fig.14
fig.15
fig.12
fig.6
fig.21
fig.20
fig.19
fig.16
fig.17
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you
purchased(depend on model).The actual shape shall prevail.
the oth
er one structure for 1800
But/h
Drain side
Tubing side
(Unit: mm)
3DQHO
3DQHO
3DQHO
+RRNORFDWLRQ
+RRNORFDWLRQ
%RG\
!PP
PP
2XWOHW
2XWOHW
,QOHW
Tubing side
&RQQHFWLQJSRLQWRIGUDLQSLSH
&RQQHFWLQJSRLQWRI
UHIULJHUDQWSLSH
/LTXLGVLGH
&RQQHFWLQJSRLQWRI
UHIULJHUDQWSLSH
*DVVLGH
3DQHO
&HLOLQJ
!PP
Drain piper
Piping
7KHRWKHURQHVWUXFWXUHIRU%XWK
7KHRWKHURQHVWUXFWXUHIRU%XWK
fig.13
fig.18
4.2

Cross-screwdriver
Outlet joint
Tubing joint Hook panel
Swing Motor
Hook-bolt
Water- receiver
,
Installation cover s rope
Tap Screw
Slide the four sliders
in the corresponding
channel when installing
the cover
Leakage
Ceiling
Pollution
Water condensation
<200mm
1-1.5 m
<200mm
Lean over 1/50
Pump-pipe clasp
(the fittings)
fig.22
fig.24
fig.26
fig.28
panel sponge
body
Ceiling
panel
panel foam1
air out
Fan
panel foam 2
4
- 6m
m
outlet foam
Loosen upper nut
Adjust lower nut
Gap not allowed
1-1.5 m
a
b
>1.5m
c
Lean over 1/50
Fasten here
Drainpipe
Pump joint
Test mouth
Body
Water-receiver
Test cover
Stow tube
Drain plug
fig.23
fig.25
fig.27
fig.29
Connecting pipe
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you
purchased(depend on model).The actual shape shall prevail.
FIGURES 2
4.3
6
installation manual
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

4.4 Install The Panel
5.1 Installation Place
Remove the air-in grill.
CAUTION
Never put the panel face down on floor or against the
wall, or on bulgy objects.
Never crash or strike it.
Do not coil the wiring of the swing motor into the seal
sponge.
CAUTION
Slide two grill switches toward the middle at the same time,
and then pull them up.
(Refer to fig.9)
Draw the grill up to an angle of about 45, and remove it.
(Refer to fig.10)
Remove the installation covers at the four corners
Wrench off the bolts, loose the rope of the installation covers,
and remove them.
(Refer to fig.11)
Install the panel
Align the swing motor on the panel to the tubing joints of the
body properly.
( Refer to fig.22)
Fix hooks of the panel at swing motor and its opposite sides
to the hooks of corresponding water receiver. ( Refer to
fig.22.1) Then hang the other two panel hooks onto
corresponding hangers of the body.
( Refer to fig.22.2)
Adjust the four panel hook screws to keep the panel
horizontal, and screw them up to the ceiling evenly.
( Refer to
fig.22.3)
Regulate the panel in the direction of the arrow in fig.12.4
slightly to fit the panel's center to the center of the ceiling's
opening. Guarantee that hooks of four corners are fixed well.
1
2
3
4
5
6
Keep fastening the screws under the panel hooks, until the
thickness of the sponge between the body and the panel's
outlet has been reduced to about 4~6mm. The edge of the
panel should contact with the ceiling well.
(Refer to fig.23)
Fasten the rope of installation cover on the bolt of the
installation cover.
(Refer to fig.26-left)
Press the installation cover into the panel slightly.
(Refer to
fig.26-right)
Malfunction described in fig.24 can be caused by
inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after
fastening the screws, the height of the indoor unit should
be modified again.
( Refer to fig.25-left)
You can modify the height of the indoor unit through the
openings on the panel's four corners, if the lift of the
indoor unit and the drainpipe is not influenced
(refer to
fig.26-right).
Hang the air-in grill to the panel, then connect the lead
terminator of the swing motor and that of the control box
with corresponding terminators on the body respectively.
Relocate the air-in grill in the procedure of reversed order.
Relocate the installation cover.
5. OUTDOOR UNIT INSTALLATION
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and can
not be reached by strong wind.
It must be a dry and well ventilating place.
The support is flat and horizontal and can stand the
weight of the outdoor unit. And will no additional noise or
vibration.
Your neighborhood will not feel uncomfortable with the
noise or expelled air.
It is easy to install the connecting pipes or cables.
Determine the air outlet direction where the discharged air
is not blocked.
There is no danger of fire due to leakage of inflammable
gas.
The piping length between the outdoor unit and the indoor
unit may not exceed the allowable piping length.
In the case that the installation place is exposed to strong
wind such as a seaside, make sure the fan operating
properly by putting the unit lengthwise along the wall or
using a dust or shield.
(refer to fig.30)
If possible, do not install the unit where it is exposed to
direct sunlight.
If necessary, install a blind that does not interfere with the
air flow.
During the heating mode, the water drained off the
outdoor unit ,The condensate should be well drained away
by the drain hole to an appropriate place, so as not to
interfere other people.
Select the position where it will not be subject to snow
drifts, accumulation of leaves or other seasonal debris. If
unavoidable, please cover it with a shelter.
Locate the outdoor unit as close to the indoor unit as
possible.
If possible, please remove the obstacles nearby to prevent
the performance from being impeded by too little of air
circulation.
The minimum distance between the outdoor unit and
obstacles described in the installation chart does not
mean that the same is applicable to the situation of an
airtight room. Leave open two of the three directions
(M,N,P)
(refer to fig.33)
X
O
Strong wind
(fig.30)
The outdoor unit should be installed in the location that
meets the following requiements:
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
7
installation manual
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

A
H
(fig.31)
(fig.33)
(fig.32)
B
E
C
D
5.2 Moving and installation
>
60
c
m
Fix with bolt
(fig.34)
6. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of
the bends meet the following requirements:
CAUTION
All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.
Do not let air, dust, or other impurities fall in the pipe
system during the time of installation.
The connecting pipe should not be installed until the
indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in
during installation.
Execute heat insulation work completely on both sides
of the gas piping and the liquid piping. Otherwise, this
can sometimes result in water leakage.
The Procedure of Connecting Pipes
6.1
MODEL
18
24
36
48
A
B
C
D
E
H
840
894
990
940
560
590
624
600
335
333
366
376
360
355
396
400
310
302
340
340
677
860
960
1245
R410A
Table 2
mm
REMARK
>30cm
>60cm
>30cm
>200
cm
(Wall or obstacle)
Maintain channel
Air outlet
Air inlet
M
P
Air inlet
N
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of
the outdoor units.
(refer to fig.34)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.
(refer to
fig.34)
Table 3
The max
height
drop (m)
When outdoor
unit is top
When outdoor
unit is bottom
The length of refrigerant pipe (m)
The number of bends
Capicity (Btu/h)
/HVVWKDQ
8
installation manual
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

How to Connect the pipes
Drill a hole in the wall (suitable just for the size of the wall
conduit), then set on the fittings such as the wall conduit and
its cover.
Bind the connecting pipe and the cables together tightly with
binding tapes.
Pass the bound connecting pipe through the wall conduct
from outside. Be careful of the pipe allocation to do on
damage to the tubing.
Connect the pipes. Refer to "How to Connect the pipes" for
details.
Expel the air with a vacuum pump. Refer to "How to expel the
air with a vacuum pump" for details.
open the stop values of the outdoor unit to make the
refrigerant pipe connecting the indoor unit with the outdoor
unit in fluent flow.
Check the leakage. Check all the joints with the leak detector
or soap water.
Cover the joints of the connecting pipe with the soundproof /
insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
1
2
3
5
6
7
4
Be sure to with insulating materials cover all the exposed
parts of the flare pipe joints and refrigerant pipe on the
liquid-side and the gas-side. Ensure that there is no gap
between them.
Incomplete insulation may cause water condensation.
Flaring
1
Cut a pipe with a pipe cutter.
(refer to fig.22)
2
Bend the tubing in proper way. Do not harm to them.
Connect the indoor unit at first, then the outdoor
unit.
Too large torque will harm the bellmouthing and too small
will cause leakage. Please determine the torque
according to Table 4.
After the connecting work is finished, be sure to check
that there is no gas leak.
The bending angle should not exceed 90.
Bending position is preferably in the middle of the
bendable pipe. The larger the bending radius the better it
is.
Do not bend the pipe more than three times.
When connecting the flare nut, coat the flare both inside
and outside with either oil or ester oil and initially tighten
by hand 3 or 4 turns before tighting firmly.
Be sure to use both a spanner and torque wrench
together when connecting or disconnecting pipes to /from
the unit.
Ta ble 4
PP
̚1P
̚NJIFP
̚1P
̚NJIFP
̚1P
̚NJIFP
̚1P
̚NJIFP
̚1P
̚NJIFP
5a
°±
°
±
$
Insert a flare nut into a pipe and flare the pipe.
Refer to Table 4 for the dimension of flare nut spaces.
90
Lean crude burr
(refer to fig.35)
min
max
Bend the pipe with thumb
min-radius 100mm
(fig.36)
(fig.37)
(fig.38)
CAUTION
CAUTION
How to expel the air with a vacuum pump
Stop valve operation intruduction
1. Opening stop valve
2. Closing stop valve
1.
2.
1.
2.
3.
Remove the cap and turn the valve
counterclock-wise with the hexagon wrench.
Turn it until the shaft stops.Do not apply excessive force
to the stop valve. Doing so may breakthe valve body, as
the valve is not a backseat type. Always use the special
tool.
Make sure to tighten the cap securely.
Remove the cap and turn the valve clockwise with the
hexagon wrench.
Securely tighten the valve until the shaft contacts the
main bodyseal.
Pipe gauge Tightening torque
t
Flare dimensin A
Flare shape
9
installation manual
&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

Tightening torque N M (Turn clockwise to close)
Stop
Valve
size
Shaft
(valve body)
Cap
(Valve lid)
Ø6.4
5.4
̚
6.6
Hexagonal
wrench 4 mm
13.5
̚
16.5
11.5
̚
13.9
Ø9.5
Ø12.7
8.1
̚
9.9
18
̚
22
Ø15.9
13.5
̚
16.5
Hexagonal
wrench 6 mm
23
̚
27
Ø22.2
27
̚
33
Hexagonal
wrench
10 mm
36
̚
44
Ø25.4
Loosen and remove the maintenance nuts of stop valves A
and B, and connect the charge hose of the manifold valve to
the service port of stop valve A. (Be sure that stop valves A
and B are both closed)
Connect the joint of the charge hose with the vacuum pump.
Open the Lo-lever of the manifold value completely.
Turn on the vacuum pump. At the beginning of pumping,
loosen the maintenance nut of stop valve B a little to check
whether the air comes in (the sound of the pump changes,
and the indicator of compound meter turns below zero). Then
fasten the maintenace nut.
1
2
4
3
5
7
6
-76 cmHg
Lo-lever
Hi-lever
Charge hose
Charge hose
Vacuum pump
Lo-lever
Manifold valve
Multi-meter
Pressure meter
(fig.28)
Additional Refrigerant Charge
6.2
CAUTION
Refrigerant cannot be charged until field wiring has been
completed.
Refrigerant may only be charged after performing the leak
test and the vacuum pumping.
W h e n c h a r g i n g a s y s t e m , c a r e s h a l l b e t a k e n t h a t i t s
maximum permissible charge is never exceeded, in view of
the danger of liquid hammer.
C h a r g i n g w i t h a n u n s u i t a b l e s u b s t a n c e m a y c a u s e
e x p l o s i o n s a n d a c c i d e n t s , s o a l w a y s e n s u r e t h a t t h e
appropriate refrigerant is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when
charging refrigerant.
The outdoor unit is factory charged with refrigerant. Some
systems require additional charging of refrigerant depending
on pipe lengths. The additional refrigerant to be charged
can be calculated from the following formule:
R = T X (L-5)m
7. CONNECT THE DRAIN PIPE
Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe
(out-dia.37-39mm, in-dia.32mm). It could be bought at local
market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's
pump-pipe, and clip the drainpipe and the out-let pipe sheath
(fittings) together firmly with the out-let pipe clasp (fitting).
Using the vacuum pump
When the pumping has finished, close the Lo-lever of the
manifold valve completely and turn off the vacuum
pump.Make pumping for 15 minutes or more and check that
the compound meter indicates -76cmHg(-1X10 Pa)
Loosen and remove the cap of stop valves A and B to open
stop valve A and B completely, then fasten the cap.
Disassemble the charge hose from the service port of stop
valve A, and fasten the nut.
5
(fig.40)
NOTE
If a negative result is gotten for R from the formule at
right, no refrigam needs to be added nor removed.
(fig.39)
CAUTION
Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks
arepresent.
service port
cap
maintenance nut
hexagon hole
shaft
seal
Make sure to tighten the cap securely.
For the tightening torque, refer to the table below.
Outdoor
unit
Indoor
unit
Stop valve
Gas side
Liquid side
A
C
D
B
Table 5
Maintenance
nut
Table 3
&DSLFLW\%WXK
&DSLFLW\%WXK
7J
7J
7
g
7KHTXDQWLW\RIWKHFKDUJHG
R(g): Additional refrigetant to be charged
L(m): The length of the liquid pipe
UHIULJHUDQWSHUPHWHU
10
installation manual
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
Drainage test
Drainage test
Inatall the drain joint of the outdoor unit
Check whether the drainpipe is unhindered.
New built house should have this test done before paving
the ceiling.
Remove the test cover, and stow water of about 2000ml to the
water receiver through the stow tube.
( Refer to fig.29 in the
figure page)
Turn on the power, and operate the air conditioner under the
"COOLING" mode. Listen to the sound of the drain pump.
Check whether the water is discharger well (a lag of 1min is
allowed before discharging, according to the length of the drain
pipe), and check whether water leaks from the joints.
1
2
Stop the air conditioner, turn off the power, and reset the test
cover to its original position.
3
Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of outdoor, rotate 90 to securely assemble them.
Connect the drain joint with an extension drain hose (Locally
purchased), in case of the condensate draining off the outdoor
unit during the heating mode.
8. WIRING
CAUTION
The air conditioner should use separate power supply
with rated voltage.
The external power supply to the air conditioner should
have ground wiring, which is linked to the ground wiring
of the indoor and outdoor unit.
The wiring work should be done by qualified persons
according to circuit drawing.
An all-pole disconnection switch having a cintract
separation of at least 3mm in a poles should be
connected in fixed wiring.
Be sure to locate the power wiring and the signal wring
well to avoid cross-disturbance.
Do not turn on the power until you have checked
carefully after wiring.
NOTE
The drain plug is used to empty the water-receiver for
maintenance of the air conditioner. Please stuff it imposition at
all times during operation to avoid leakage.
The body's pump pipe and the drainpipe (especially the
indoor part) should be covered evenly with the out-let pipe
sheath (fittings) and be bound tightly with the constrictor to
prevent condensation caused by entered air.
To prevent water from flowing backwards into the air
conditioner while the air conditioner stops, please lean the
drainpipe down toward outdoor (outlet-side) at a degree of
over 1/ 50. And please avoid any bulge or water deposit. (
Refer to fig.27.a in the figure page)
Do not drag the drainpipe violently when connecting to
prevent the body from being pulled. Meanwhile, one
supportpoint should be set every 1~1.5m to prevent the
drainpipe from yielding (Refer to fig.27.a in the figure page).
Or you can tie the drainpipe with the connecting pipe to fix
it.(Refer to fig.27.c in the figure page)
In the case of prolonged drainpipe, you had better tighten its
indoor part with a protection tube to prevent it from loosing.
If the outlet of the drainpipe is higher than the body's pump
joint, the pipe should be arranged as vertically as possible.
And the lift distance must be less than 200mm, otherwise the
water will overflow when the air conditioner stops.( Refer to
fig.28 in the figure page)
The end of the drainpipe should be over 50mm higher than
the ground or the bottom of the drainage chute, and do not
immerse it in water. If you discharge the water directly into
sewage, be sure to make a U-form aquaseal by bending the
pipe up to prevent the smelly gas entering the house through
the drain pipe.
NOTE
The power connection for the air conditioner has to be
done at the main power distribution. The distribution has
t o b e o f a l o w i m p e d a n c e , n o r m a l l y t h e r e q u i r e d
impedance reaches at a 32 A fusing point.
No other equipment has to be connected with this power
line.
For detailed installation acceptance please refer to your
power supplier, if restrictions do apply for products like
washing machines, air conditioners or electrical ovens.
For power details of the air conditioner refer to the rating
plate of the product.
For any question contact your local dealer.
Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the
compressor (technical process) ,following installation
conditions do apply.
1
2
4
3
5
Seal
The base pan hole
of outdoor unit
Drain joint
Seal
The base pan
of outdoor unit
Drain
joint
(fig.42)
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
11
installation manual
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
Dissemble the bolts from the cover.(If there isn't a cover on
the outdoor unit, disassemble the bolts from the maintenance
board, and pull it in the direction of the arrow to remove the
protection board.)
(refer to fig.43)
Connect the connective cables to the terminals as identified
with their respective mached numbers on the terminal block
of indoor and outdoor units.
Re-install the cover or the protection board.
Connect the cable
8.1
The Specification of Power
8.2
Wiring figure
8.3
(refer to table6
̚
table 7
)
(refer to Fig44
̚
Fig47
)
(fig.33)
Protection board
Cover
9. TEST OPERATION
The test operation must be carried out after the entire
installation has been completed.
Please confirm the following points before the test operation:
2
1
According to the user's requirement, install the remote
controller frame where the remote controller's signal can
reach the indoor unit smoothly.
Test operation
4
3
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of
the refrigerant have been recorded.
The power voltage fits the rated voltage of the air
conditioner.
There is no obstacle at the outlet and inlet of the outdoor
and indoor units.
The gas-side and liquid-side stop valves are both opened.
The air conditioner is pre-heated by turning on the power.
Set the air conditioner under the mode of "COOLING" with the
remote controller, and check the following points. If there is
any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works
well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
operation.
I. Whether the air conditioner heats well in the case of the
HEATING/COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during
operation.
b. Whether the generated wind, noise, or condensed of by
the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked.
CAUTION
A protection feature prevents the air conditioner from being
activated for approximately 3 minutes when it is restarted
immediately after shut off.
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
12
installation manual
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
Table 6
13
installation manual
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
A
( )
Cap icity(Btu/h)
(WEAK ELECTRIC SIGNAL)
INDOOR/OUTDOOR CONNECTING WIRING
CIRCUIT BREAKER/FUSE
POW ER WIRIN G
PH ASE
FREQUENCY
AND VOLT
1-PHASE
220-240V~ 50Hz
30/25
3X1.0
3 X2.5
3-core shield ed
wire
18000
1-PHASE
220 -240V~ 50H z
4 0/25
3X1.0
3 X2.5
24 000
40/25
3 X1.0
5X2.5
3600 0-60000
1-PHASE
220-240V~ 50 Hz
3-core sh ielded
wire
3-core sh ielded
wire
OU TD OOR UN IT
POWER
IN DOOR UNIT
POWER
PHASE
FREQUENCY
AND VOLT
1-PHASE
1-PHASE
3-PHASE
1-PHASE
220-240V~ 50H z 220 -240V~ 50H z 380-415 V~ 50 Hz
POWER W IRING
( m )
2
m
( m )
2
m
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSLFLW\%WXK
¶
¶
¶
¶
14
installation manual
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
PDLQWHQDQFHSHUVRQ
15
installation manual
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
16
installation manual
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
Fig.45
Switch/Fuse
Power wiring (indoor)
Indoor
Unit
Outdoor
Unit
CAUTION
The wiring chart of cooling& heating type in R410A series are shown as follows.When wiring, please
choose the corresponding figure,or it may cause damage.
CENTRAL CONTROL
MONITOR(CCM)
COMPUTER
Power supply
380-415V~ 50Hz
Power supply
220-240V~ 50Hz
3-phase
1-phase
Communication Bus
Power wiring (outdoor)
Fig.44
Switch/Fuse
Power wiring (indoor)
Indoor
Unit
Outdoor
Unit
CENTRAL CONTROL
MONITOR(CCM)
COMPUTER
Power supply
Power supply
220-240V~ 50Hz
1-phase
Communication Bus
Power wiring (outdoor)
220-240V~ 50Hz
1-phase
For 18000-24000Btu/h
For 36000-48000Btu/h
17
installation manual
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
18
installation manual
Fig.46
Fig.47
For 18000-24000Btu/h
For 36000-48000Btu/h
9+]
FRUHFDEOH;PP
3RZHUVXSSO\
3KDVH
9+]
FRUHFDEOH;PP
3RZHUVXSSO\
3KDVH
FRUHFDEOH[PP
FRUHVKLHOGHGFDEOH
28
7'
22
5
81
,7
3RZHUVXSSO\
3KDVH9
̚
FRUHFDEOH[PP
3RZHUVXSSO\
3KDVH9
̚
,1'22581,7
/
1
/
/
72 &&0
&20 0%8 6
%WXK,QGRRUXQLW
HOHFWULFDOSODWHZLWK
RUWHUPLDOV
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
19
installation manual
ndenser
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
MDV06I-018bW
2200017216
7KHRWKHURQHVWUXFWXUHIRU%XWK

&DSLFLW\%WXK
7J
&DSLFLW\%WXK
&DSDFLW\%WXK
1RWH7KHFDSDFLW\
KDVEHHQVHWEHIRUH
OHDYLQJWKHIDFWRU\
DQ\RQHFDQÿWPRGLI\
LWH[FHSWWKH
PDLQWHQDQFHSHUVRQ
7KHRWKHURQHVWUXFWXUHIRU%XWK