background image

 

ClimaCheck Sweden AB, Box 46, SE-131 06 Nacka, Sweden 

 

Visiting/delivery address: Gamla Värmdövägen 6, SE-131 37 Nacka Sweden 

 

Tel.: +46 (0)8-50 255 250, E-mail: 

info@climacheck.com

 

 

Web: 

www.climacheck.com 

 

 

  

 
 
  
 
 

 

 

 

 

 
 

 

GSM Modem Manual 

 

BGS2 GPRS Modem 

ER75i Router 

ETM450 Router  

 
 
 

2016-05-04 

 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 2(22) 

 

 

 

Table of contents 

Table of contents ........................................................................................................................ 2

 

1

 

Selection of Operator - SIM card for Data transfer ............................................................ 3

 

1.1

 

Setting up M2M communication ............................................................................ 3

 

2

 

Choosing the best way to connect ...................................................................................... 4

 

2.1

 

Sending by GPRS to the ClimaCheck Server ........................................................ 4

 

2.2

 

Temporary Connection by Modem Call-Up .......................................................... 4

 

2.3

 

Sending Data by E-mail ......................................................................................... 5

 

3

 

Configuring the PA Pro for sending by GPRS ................................................................... 5

 

3.1

 

Connecting to the configuration interface .............................................................. 5

 

3.2

 

Entering APN and ISP phone number .................................................................... 5

 

3.3

 

Changing the Database Sample Interval ................................................................ 6

 

3.4

 

Changing Database UDP settings .......................................................................... 6

 

3.5

 

Setting Gateway ..................................................................................................... 7

 

4

 

Connecting and starting the modem ................................................................................... 8

 

4.1

 

Changing the Database Sample Interval ................................................................ 8

 

4.2

 

LED status on Cinterion terminal ........................................................................... 9

 

4.3

 

Trouble shooting of data communication over GPRS modem .............................. 9

 

5

 

Router Modems ................................................................................................................ 11

 

5.1

 

Signal Strength ..................................................................................................... 11

 

6

 

ER75i Router-modem ...................................................................................................... 11

 

6.1

 

Connecting to the configuration interface ............................................................ 11

 

6.2

 

Configure GPRS-connection ................................................................................ 11

 

6.3

 

Configure DHCP and IP settings ......................................................................... 12

 

6.4

 

Configure NAT-settings ....................................................................................... 13

 

7

 

ETM 450 Router modem .................................................................................................. 15

 

7.1

 

Connecting to the configuration interface ............................................................ 15

 

7.2

 

Configure WAN connection ................................................................................. 15

 

7.3

 

Configure LAN settings ....................................................................................... 16

 

7.4

 

Configure Port forwarding ................................................................................... 18

 

7.5

 

LED status on the ETM450 .................................................................................. 19

 

7.6

 

Signal Strength ..................................................................................................... 20

 

7.7

 

SMS Commands ................................................................................................... 20

 

8

 

Connecting to the PA Pro by modem call-up ................................................................... 21

 

8.1

 

Creating a remote dial-up connection .................................................................. 21

 

8.2

 

Establishing connection in ClimaCheck .............................................................. 21

 

8.3

 

Downloading the database ................................................................................... 22

 

8.4

 

Trouble shooting of dial up = modem does not answer incoming call. ............... 22

 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 3(22) 

 

 

 

1

 

Selection of Operator - SIM card for Data 
transfer 

ClimaCheck and/or ClimaCheck distributors can supply SIM cards for most markets but due to the 
operators pricing policies the roaming fees are often resulting in significantly higher rates so local 
contracts can be cost-effective in some cases. 
 

Requirement on SIM: 
It must be configured and activated for GSM data communication which often require 
some kind of “activation” by the operator even if the contract as such is including data 
capability. 

 
Typical amount of data for a standard system is 5-10 Mb of data per month depending on number 
of channels and interval between data scans. Default is 1 minute when compressor is operating 
and 5 minutes when compressor is off. To select operator with experience of data transfer Machine 
to Machine (M2M) is recommended. Operators are using different settings in their network and it is 
recommended to whenever possible use networks that offers 

public IPs

 to the connected devices 

(many networks has a firewall disabling access from the outside). A Public IP means that the 
ClimaCheck PA Pro can be contacted for configuration via Internet. The IP does not need to be a 
fixed IP as the ClimaCheck on-line server monitors incoming traffics IP number. The sending IP is 
displayed on the “Home page” for each system. If a SIM is set up to be behind the operators 
firewall data can be sent out but configuration would have to be done with a locally connected PC 
or through dial up connection, which is quite slow.         

 

1.1

 

Setting up M2M communication 

Experience shows that Machine to Machine (M2M) communication can be challenging to set up the 
first time with a new operator. 
 
Most operators are totally focused on the mobile telephone market. Even though smart phones use 
data communication of the same type as in the M2M communication used by the ClimaCheck 
Performance Analyser, it has proven that it’s difficult to get the correct configuration and 
information required. 
 

We therefor strongly advice first time set up with SIM from a new operator to 
be done prior to going on-site to ensure functionality and avoid loss of time and 
unnecessary travels. 

 
Tests should preferably be done with the equipment to be used on site but the functionality of a 
SIM and correct configuration can be tested with any ClimaCheck PA Pro and modem. By checking 
that data is actually received on the ClimaCheck on-line server functionality can be validated 
minimizing wasted time on site and return trips.  
 
The information requested and how to enter it is described in 

3.2 Entering APN and ISP phone 

number

 that should be required. Typically this is the “APN” address unique for each operator (this 

is included in the configurations a mobile phone get when you first connect it to your operator). 
 
This said the communication will not work if: 

1.

 

The SIM card is not properly activated for data communication 

2.

 

The PIN code is not removed from the SIM card before it is entered into the modem 

3.

 

The Init string for modem is not sent from the PA Pro when UDP communication is 
activated (only required with standard modem e.g. when router modem is not used). 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 4(22) 

 

 

 

Connections: 

 

 

Figure 1, ClimaCheck standard modem when one Performance Analyser PA Pro II is used 

or master slave operation with two.  

2

 

Choosing the best way to connect 

There are several ways to use the modem to transfer data and you should choose one or several 
that corresponds to your need. This section presents an overview of each method and where to 
find the relevant configuration instructions. After having made the relevant configurations, refer to 
section 4 for how to connect the modem hardware. 
 
All methods require you to have a working SIM card with the PIN code disabled.  

2.1

 

Sending by GPRS to the ClimaCheck Server 

This is the recommended mode of operation.

  

For a wide range of applications the most convenient way to transfer data is by sending them to 
the ClimaCheck server. You can then log on to 

online.climacheck.com

 from anywhere to have 

instant access to your measurements. Tools for displaying the data in tables and graphs are 
available and you can also download it for further processing. 
 
You will need a subscription for our web service to make use of this method. 
 

Read more in section 3. 

2.2

 

Temporary Connection by Modem Call-Up 

An alternate way to retrieve data is by calling the wireless modem from a normal modem 
connected to your computer. You can then start logging data as if you were connected locally or 
download the contents of the PA Pro internal database. A dialled up connection is comparably slow 
and downloading the database takes a considerable time. 
 
Even when sending data to the ClimaCheck server it is useful to use the call-up function if you 
need to change a setting on the PA Pro. 
 

Read more in section 8. 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 5(22) 

 

 

 

2.3

 

Sending Data by E-mail 

This method is listed when accessing the web interface of the ClimaCheck unit, but is currently not 
supported. 

3

 

Configuring the PA Pro for sending by GPRS 

This section explains how to configure your PA Pro unit to send data by GPRS connection to our 
server. You can then log in from any location to access your data. This requires a subscription from 
ClimaCheck or one of our partners. 

3.1

 

Connecting to the configuration interface 

In order to configure the PA Pro you must open its web based interface: 
 

 

Connect your computer to the PA Pro with a “crossed” network cable. 

 

Wait for the PA Pro to establish a connection with your computer. 

 

Open a web browser and enter the units IP-address (default 

169.254.1.1

). 

 

Enter the user name and password (default “

config

” and “

ef56

”). 

3.2

 

Entering APN and ISP phone number 

To enable the PA Pro to send data by GPRS you need to enter the APN provided by the supplier of 
your SIM card. 
 

 

Choose 

Settings -> Communication -> Modem/PPP

 

 

In the 

Modem setup string

 find the text 

“APN for used operator” 

last in the string. 

Citation mark should remain around the APN. See table below.

 

 

If a username and password is required this should be entered under 

Login -> Modem

.

 

 

Replace this text with the provided APN, leaving the quotation marks in place. 

 

In some cases your PA Pro unit comes with a preconfigured APN. If you need to change it 
just replace what is inside the quotation marks at the end of the string. 

 

Click 

Update

 to confirm your changes. 

 

 

Figure 2 

 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 6(22) 

 

 

 

In older versions of the PA Pro standard configuration the 

Phone number to ISP

 field is blank. If 

that is the case enter 

*99***1# 

and click 

Update

 
You will need to press 

Restart

 to enable the new settings, but you only need to do this once after 

finishing all configuration. You can also restart your PA Pro by turning on and off the power. 
 

APN for a number of operators: 

 
NextM2M 

 

fixedipaccess (Standard for ClimaCheck SIM) 

Telia 

 

online.telia.se 

Maingate 

 

maingate.telia.se 

Maingate VPN  

maingatelan.telia.se 

Maingate Roaming 

apn.maingate.se 

Telenor 

 

internet.telenor.se 

O2 UK 

 

mobile.o2.co.uk 

3.3

 

Changing the Database Sample Interval 

When using your PA Pro connected directly to a laptop five seconds between each sampling of data 
is the standard value. When connecting by GPRS the sample rate is set in the logger and usually to 
a lower value not to cause an unnecessary high data traffic cost. The settings for the internal 
logger and data transfer are independent. 
 

 

Choose 

Settings -> Advanced -> Databases -> DB1 Short Time

 

Set 

Time base 1

 to the sample interval you want when the compressor is not running. We 

recommend 

5 minutes

 for most situations. 

 

Set 

Time base 2

 to the sample interval you want when the compressor is running. We 

recommend 

1 minute

 for most situations. 

 

Click 

Update

 to confirm your changes. 

 
 

 

Figure 3 

 

In older versions of the PA Pro standard configuration there is no option to set a different sample 
interval for when the compressor is not running. In this case just use the standard 

Time base

 

setting. 

3.4

 

Changing Database UDP settings 

The 

Database UDP 

section contains information that allows the PA Pro to connect to our server. 

 

 

Choose 

Settings -> Advanced -> Database UDP

 

Set 

ID

 to the identifier for your account. It is provided to you by ClimaCheck or one of our 

partners and always contains 

six letters or digits

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 7(22) 

 

 

 

 

Check the 

UDP send active

 box to start sending data. Uncheck the box if you want to 

disable the sending of data. 

 

Click 

Update

 to confirm your changes. 

 

 

Figure 4 

3.5

 

Setting Gateway 

The last step to enable sending of data is to set the Gateway in the Modem/PPP section. 
 

 

Choose 

Settings -> Connection -> Modem/PPP

 

Copy the number from the 

IP-address

 field to the 

Gateway

 field. The default IP-

address/Gateway is 

192.168.48.95

.

 

 

If you want to disable sending change 

Gateway

 back to 

0.0.0.0 

 

Click 

Update

 to confirm your changes. 

 

Click 

Restart

 to restart with the new settings enabled. 

 
The PA Pro will now use the connected modem to send data to the server using GPRS and UDP. 

 

 

Figure 5

 

Important! 

If the PA Pro has been configured with a Gateway setting other than 0.0.0.0 on the 
LAN/DNS tab to communicate over a local network, the Modem connection will not work 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 8(22) 

 

 

 

despite being setup on the Modem/PPP tab. To restore connectivity over GPRS-modem 
set the Gateway to 0.0.0.0  
When Gateway is enabled (set to something other than 0.0.0.0), you can in many cases 
only connect to the PA Pro with a direct cable connection while not being connected to 
any other networks.  It will not work connecting via a router or while simultaneously 
being connected to a wireless network. In this case to restore the standard connectivity 
you need to disable Gateway by setting it to 0.0.0.0, clicking Update and Restart.

 

4

 

Connecting and starting the modem 

You should make all the required setting changes before starting the modem. When ready to 
connecting it follow these steps: 
 

 

Make sure your SIM card do not have a PIN code locking it. 

 

Insert the SIM card in the modem. Eject holder by pushing the small round button with a 
pointy object like a pencil or small screw driver. 

 

Connect the antenna to the modem and the modem to the PA Pro using a serial cable. 

 

Turn off the PA Pro. 

 

Turn on the modem by connecting it to the mains. 

 

Wait 30 seconds for the modem to go trough its start sequence. It should now display a 
short blink every three seconds. 

 

Turn on the PA Pro and wait for it to start as normal. 

 

PA Pro and the modem should now be ready. If connected by GPRS you will see double 
blinks and a longer steady blink when it is sending, but if the time between samples is long 
they can be hard to spot. If the modem is waiting for a call there will only be single blinks. 

 

4.1

 

Changing the Database Sample Interval 

When using your PA Pro connected directly to a laptop five seconds between each sampling of data 
is the standard value. When connecting by GPRS the sample rate is set in the logger and usually to 
a lower value not to cause an unnecessary high data traffic cost. The settings for the internal 
logger and data transfer are independent. 
 
Read section 3.1 and 3.3 to learn how to connect to the PA Pro and change the sampling interval. 
 
The set-up of modem configuration includes interaction of several different systems requiring a 
systematic approach to set-up and trouble shooting. 
 
The ClimaCheck PA Pro will initiate modem first time it has data to send - default 5 minutes if no 
compressor power is measured – 1 minute if power is measured - this time can be shortened by 
setting a shorter time in the settings (see 3.3 Changing the Database Sample Interval). 
 
After connection of Modem to ClimaCheck PA Pro and initiating communication as described in this 
manual data should be coming to the server.  

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 9(22) 

 

 

 

4.2

 

LED status on Cinterion terminal 

 
LED mode 

Operating status of ClimaCheck standard modem  
(Cinterion GPRS Terminal) 

Permanently off

 

The Terminal is in one of the following modes: 

• POWER DOWN mode 
• ALARM mode 
• NON-CYCLIC SLEEP mode 
• CYCLIC SLEEP mode with no temporary wake-up event1 in 

progress.

 

600 ms on / 600 ms 
off

 

Limited Network Service: No SIM card inserted or no PIN 
entered, or network search in progress, or ongoing user 
authentication, or network login in progress. 

Check – Simcard and that PIN is not activated  

75 ms on / 3 s off

 

IDLE mode: The mobile is logged on to the network (monitoring control 
channels and user interactions). No call in progress. 

Data sending not correctly activated from ClimaCheck PA Pro  
No available GPRS network – SIM not activated for data traffic 

 

Double blink e.g.  
75 ms on / 75 ms off / 
75 ms on / 3 s off

 

One or more GPRS contexts activated.  
Required status to send data. 

500 ms on / 25 ms off

 

Packet switched data transfer in progress.

 

Permanently on

 

Depending on type of call: 

Voice call: 

Connected to remote party. 

CSD call: 

Connected to remote party or exchange of parameters while 

setting up or disconnecting a call. 

Figure 6

 

Unless there is steady blink every three seconds after the modem has been connected 
ClimaCheck PA Pro will not be able to initiate data communication e.g. there is a general 
problem with the connection to the operators network this must be fixed before data 
communication over GPRS can be initiated. 
 
Check that PIN is not used by inserting SIM in a mobile.  
 
If there is single blink there is a connection to the operator but data sending is not active. 
Insert SIM in a mobile and test if you can “surf” on internet. If so - Check APN under settings 
for Mobile Network to ensure the right APN is used. 
 
Log in and check if PA Pro has an active UDP send alarm. 
 

4.3

 

Trouble shooting of data communication over GPRS modem 

If the modem does not send data or behaves unexpected, try the following: 
 

1.

 

As modem and logger are dependent on the correct initiation sequence it is worth to restart 
modem and logger before trouble shooting start. Modem must be ready when PA Pro send 
initiation string. As modem start faster than PA pro they can be started at the same time 
i.e. by shutting down the power to both units. 

2.

 

Check LED status of modem (see Figure 4) unless this is in steady blink or double blink 
mode modem/SIM is not ready. This needs to be fixed before proceeding with further 
trouble shooting. 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 10(22) 

 

 

 

o

 

Check reception, this can be checked with a phone with the same operators SIM or 
by placing the modems SIM in a mobile phone.  

 

If poor GSM coverage in the area. Try relocating the antenna. Extensions 
can be used both on the RS232 communication cable between modem to 
ClimaCheck PA Pro (up to 25 m is tested with good result) and between 
Modem and antenna (10 m good quality antenna extensions has been 
tested and do not give unacceptable reduction of signal).  

o

 

Check SIM if PIN code is required, one way of doing this is to place SIM in a mobile 
to check that there is no PIN and if so remove it. 

o

 

Check if APN and password are correct, one way is to put the SIM in a mobile 
phone and download settings that can be read in mobile phones settings for the 
network. 

o

 

Ensure that SIM is activated. 

If SIM is not activated properly the modem will not connect. 

 

If the modem is connected to the network with steady flash or double flash every 3 sec, but no 
data is transmitted it means that the modem is connected to the network but is not in data 
transmission mode. This can be caused by SIM contract not properly activated for data or that the 
PA Pro has not initiated the data send mode. Many operators require activation of SIM-cards that 
are intended for data communication. 
 

3.

 

Check LED on the ClimaCheck PA Pro for communication with modem on RS232 flashing. 
If this is not flashing while modem is connected to a network. 

o

 

Check cable (standard serial cable). 

If Led on RS232 communication is flashing but no data is received on server or PA Pro indicate data 
send error check set-up in PA Pro. 

4.

 

Check configuration step by step as described in chapter 3. 

 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 11(22) 

 

 

 

5

 

Router Modems 

ClimaCheck work with several router modems and they present signal strength as -dBm 

5.1

 

Signal Strength 

The signal strength is indicated by a LED on the front of the modem, as a dBm value on the Home 
page of the web interface or as a RSSI value (0-31) in the NETINFO SMS sent from the unit. 
 

Description 

RSSI (Sig in SMS) 

dBm 

Poor or no signal 

Signal<10 

Signal<-93 

Low 

10<Signal<15 

-93<Signal<-83 

Medium 

15<Signal<20 

-83<Signal<-73 

High 

20<Signal<25 

-73<Signal<-63 

Excellent 

25<Signal 

-63<SIgnal 

   
For reliable data transmission a signal strength above 10 (-93 dBm) is required. SMS commands 
can usually be delivered at the lowest signal strength.  
 
 

6

 

ER75i Router-modem 

The ER75i router-modem is used, together with a switch, in installations with more than one PA Pro 
on the same site. The router creates a local area network to witch the PA Pro is connected. This 
section explains how to setup the ER75i with one or more PA Pro. 
 

Note! Examples and instructions for the ER75i will be for the v2 version but are also valid 
for the v1 version.  

 

6.1

 

 Connecting to the configuration interface 

The configuration of the ER75i router-modem is done in its web based interface. 
 

 

Connect directly to its Ethernet port or via a switch with a network cable. 

 

Open a web browser and enter the units IP-address (default 

192.168.1.1 

and then 

changed to 

192.168.33.1

)  

 

Enter the user name and password (default “

root

” and “

root

”).  

 

6.2

 

Configure GPRS-connection 

To enable communication over the ER75i it needs to be configured for the specific SIM-card 
supplier that is used.  
 

 

In the menu to the left choose 

GPRS

 under 

Configuration. 

 

 

Enter APN, Climacheck supplied SIM-card in example below.  

 

Tick the box for “Check PPP connection” 

 

Enter 

online.climacheck.com

 in the “Ping IP address” field.  

 

Set “Ping Intervall” to 

600

 

 

Store settings with the “Apply” button at the bottom of the page. A window will appear 
saying “Configuration successfully updated”. Press “Back”.    

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 12(22) 

 

 

 

 

 

  

Figure 7 

Note! If the SIM-card has PIN-code activated or if the SIM-card supplier requires a username and 
password for the data-connection this is also entered on the GPRS Configuration page.  
 

6.3

 

Configure DHCP and IP settings 

The PA Pro connected to the ER75i will have static IP-addresses. To avoid computers that are 
connected to the ER75i network to get the same IP-address as a PA Pro the DHCP-settings are 
changed as follows. The IP address of the router modem is also changed not to interfere with 
existing networks.  
 

 

Choose LAN under Configuration 

 

Change IP Address to 192.168.33.1 

 

Set the IP Pool start to 192.168.33.50 

 

Set the IP Pool end to 192.168.33.254 

 

Store settings with the “Apply” button at the bottom of the page.  

 
Note! The router will now change IP number and you may have to deactivate and 
activate your network card to be able access it on the new IP, 192.168.33.1  

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 13(22) 

 

 

 

 

Figure 8 

6.4

 

Configure NAT-settings 

A SIM-card used in the ER75i will only have one IP-address connected to it. To be able to connect 
to several different PA Pro behind the ER75i a connection between different public ports accessible 
from the outside and IP numbers on the ER75i LAN is added.    
 

 

Choose NAT under Configuration 

 

Set “Public Port” to 

81

 

 

Set “Private Port” to 

80

 

 

Set “Server IP Address” to 

192.168.33.2 

 

 

Store settings with the “Apply” button at the bottom of the page. A window will appear 
saying “Configuration successfully updated”. Press “Back”. 

 

Communication that is requested on port 81 on the public IP number will now be routed to the PA 
Pro with IP number 192.168.33.2.  
 
The LAN IP used must be entered as a fixed IP in each PA Pro.  
If more PA Pro units are connected each PA Pro needs a public port routed to its IP number in the 
same way as shown above. In the figure below 2 PA Pro units are connected to the ER75i LAN.  
 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 14(22) 

 

 

 

 

Figure 9   

 
The configuration of the ER75i is now complete. The PA Pro units now need to be configured to 
send their data over the ER75i LAN according to the table below. For instructions on how to 
configure the PA Pro, see the Hardware Manual. 
 

 

IP Address 

Netmask 

Gateway 

DNS Server 3 

PA Pro 1 

192.168.33.2  255.255.255.0  192.168.33.1 

192.168.33.1 

PA Pro 2 

192.168.33.3  255.255.255.0  192.168.33.1 

192.168.33.1 

   
 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 15(22) 

 

 

 

7

 

ETM 450 Router modem  

The ETM 450 router-modem is used, together with a switch, in installations with more than one PA 
Pro on the same site. The router creates a local area network to witch the PA Pro is connected. This 
section explains how to setup the ER75i with one or more PA Pro. 

7.1

 

Connecting to the configuration interface 

The configuration of the ETM450 router-modem is done in its web based interface. 
 

 

Connect directly to its Ethernet port or via a switch with a network cable. 

 

Open a web browser and enter https:// followed by the units IP-address (default 

https://192.168.0.1 

and then changed to 

https://192.168.33.1

)  

 

Enter the user name and password (default “

admin

” and “

admin

”).  

 

Note! When accessing the router modem you may get a warning saying “There is a 
problem with this website´s security certificate”. Choose “Continue to this website” 
 

7.2

 

Configure WAN connection 

To enable communication over the ETM450 it needs to be configured for the specific SIM-card 
supplier that is used.  

 

In the Menu go to 

Network 

and 

WAN

 

 

Enter APN, ClimaCheck supplied SIM-card in example below.  

 

If your SIM-card use a PIN-code choose enable and enter it. 

 

 

Figure 10 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 16(22) 

 

 

 

 

At the bottom of the page, make sure the “Check LAN Cable” is disabled. 

 

Choose 24 hours for the “Periodic Reset” function. 

 

Choose enable for the “Keep Alive” function.  

 

Enter 299 seconds as interval and 2 as fail count.  

 

Enter 

212.85.69.58 

as 1

st

 server and leave 2

nd

 server empty.  

 

Now press Apply Changes to save and the system will reboot.  

 

    

 Figure 11 

 

7.3

 

Configure LAN settings 

 

Got to 

Network 

and 

LAN

 

 

Set IP Address to 192.168.33.1 

 

Set Default Gateway to 192.168.33.1 

 

Set DHCP Client Range to 192.168.33.50 – 192.168.33.250 

 

Set 1

st

 DNS to 208.67.222.222 

 

Set 2

nd

 DNS to 208.67.220.220 

 

Press Apply Changes to save settings.  

 

Note! The router will now change IP number and you may have to deactivate and 
activate your network card to be able access it on the new IP, 192.168.33.1  
 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 17(22) 

 

 

 

 

Figure 12 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 18(22) 

 

 

 

7.4

 

Configure Port forwarding  

A SIM-card used in the ETM450 will only have one IP-address connected to it. To be able to 
connect to several different PA Pro behind the ETM450 a connection between different public ports 
accessible from the outside and IP numbers on the ETM450 LAN is added.    
 

 

Go to 

Advanced

 and 

Port Forwarding

  

 

Set IP Address 192.168.33.2  

 

Set WAN Port 81 - 81 

 

Set LAN Port 80 – 80 

 

 

 

Save settings by pressing Apply Changes 

 

Communication that is requested on port 81 on the public IP number will now be routed to the PA 
Pro with IP number 192.168.33.2.  
 

 

Figure 13 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 19(22) 

 

 

 

The LAN IP used must be entered as a fixed IP in each PA Pro.  
If more PA Pro units are connected each PA Pro needs a public port routed to its IP number in the 
same way as shown above. In the figure below 2 PA Pro units are connected to the ETM450 LAN.  
 

 

Figure 14 

 
The configuration of the ETM450 is now complete. The PA Pro units need to be configured to send 
their data over the ETM450 LAN according to the table below. For instructions on how to configure 
the PA Pro, see the PA Pro Manual. 
 

 

IP Address 

Netmask 

Gateway 

DNS Server 3 

PA Pro 1 

192.168.33.2  255.255.255.0  192.168.33.1 

192.168.33.1 

PA Pro 2 

192.168.33.3  255.255.255.0  192.168.33.1 

192.168.33.1 

 

7.5

 

LED status on the ETM450 

 

Figure 15 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 20(22) 

 

 

 

7.6

 

Signal Strength 

The signal strength is indicated by a LED on the front of the modem, as a dBm value on the Home 
page of the web interface or as a RSSI value (0-31) in the NETINFO SMS sent from the unit. 
 

Description 

RSSI (Sig in SMS) 

dBm 

Poor or no signal 

Signal<10 

Signal<-93 

Low 

10<Signal<15 

-93<Signal<-83 

Medium 

15<Signal<20 

-83<Signal<-73 

High 

20<Signal<25 

-73<Signal<-63 

Excellent 

25<Signal 

-63<SIgnal 

   
For reliable data transmission a signal strength above 10 (-93 dBm) is required. SMS commands 
can usually be delivered at the lowest signal strength.  
 

7.7

 

SMS Commands 

  The ETM450 modem can be controlled by different SMS commands. The modem will only respond 
to SMS from numbers that are in the units phonebook, Administrator -> System. 
 

 

 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 21(22) 

 

 

 

The following SMS commands can be used: 
 

 

 

8

 

Connecting to the PA Pro by modem call-up 

This section explains how to call a modem equipped PA Pro unit with your own computers modem. 
You can then start logging as if directly connected or download collected data. This is 

only needed

 

if the data communication is not functioning whereas the Phone = dial up connection works.  
Data communication is slower over the dial-up line.  

 

Establish a connection using the remote connection created in section 8.1 

 

If the logger is activated to send UDP it can be necessary to redial as the first time will set 
the system in a mode to respond for dial up. 

8.1

 

Creating a remote dial-up connection 

You first need to make a new network connection on your PC. This guide is based on Windows XP 
but it functions in a similar way on Windows Vista and Windows 7. 
 

 

Select 

Start menu -> Connect to -> Show all connections

 

 

Select 

Create new connection

 

Choose 

Connect to a Network at my Workplace

 and 

Remote Connection

 

Give the connection a suitable name. 

 

Enter the supplied telephone number to the SIM card in your modem. Make sure it is a 
number that can connect to a calling modem. 

 

Decide if all users should have this connection or not and if you want a shortcut. 

 

Your connection is now ready. 

 
Before dialling make sure your computer is set to receive an IP number automatically. If it got a 
pre-set IP you will need to change that setting before connecting to the PA Pro modem. 
 
You should not enter a user name or password. 

8.2

 

Establishing connection in ClimaCheck 

 

Start the ClimaCheck software. 

 

Select the network interface named 

“WAN (PPP/SLIP) Interface

” or similar. 

 


background image

 

ClimaCheck GSM Modem Manual – 2015-02-26 22(22) 

 

 

 

 

Ignore the error message 

“PA Pro not found at 169.254.1.1”

 

The first time you connect: Choose 

Settings->Preferences->Perf. Analys. Pro

 and add 

the IP number 

192.168.48.95

 under 

PA Pros to connect to

 

Select 

Performance Analyser Pro -> No quick check if PA Pro is available

 

Select 

Performance Analyser Pro -> 192.168.48.95

 

Click 

Contact -> Direct

 to start using the PA Pro as usual. 

8.3

 

Downloading the database 

If you want to download the database choose 

Performance Analyser Pro -> Download and 

Save Logged Data

 and select how much data to save. Note that downloading the entire database 

by modem 

may take up to 30 minutes

, not five minutes as stated by ClimaCheck. During this 

time ClimaCheck will be unresponsive. 
 
To do ClimaCheck calculations on downloaded data go to connect and select PA Pro log file and 
select your file. Start scanning as if doing a live measurement. 
 
 

8.4

 

Trouble shooting of dial up = modem does not answer 
incoming call. 

 

Ensure you are using the correct number. Many operators supply SIMS with up to 3 
different phone numbers (data, Fax and phone). Dial-up modem to modem can be set. 

 

 

If you want to call a modem set up to send by GPRS you may need to first call it and hang 
up after 2-4 and before it responds to the call. This will make the modem temporarily turn 
off the GPRS connection and be ready for your connection. Immediately call it again to 
connect. 
 

 

Try disabling all other network connections on your computer. They may interfere with the 
modem connection.