DESHUMIDIFIER
CONSOLES
Models DH-60 / DH-90 / DH-120
INSTALLATION AND OPERATING INSTRUCTIONS
(to be read carefully and kept for future reference)

16/28
2015/12 - Indice de révision : B - Code : 33491
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ..............................17
Children and physically or mentally impaired persons: ........................................................17
Electrical safety: ...................................................................................................................17
Fire safety: ............................................................................................................................17
OPERATING PRINCIPLE ...............................................................................18
DIMENSIONS AND TECHNICAL DATA ........................................................19
INSTALLATION ..............................................................................................20
WIRING ...........................................................................................................21
COMMISSIONING AND USE .........................................................................22
Connection of the device to the mains: ................................................................................22
Start up: ................................................................................................................................22
Selection of the operating mode: ..........................................................................................22
Setting the humidity set point: ..............................................................................................22
Setting the temperature set point (if the heating option is installed and active): ..................23
Programming a postponed start and a postponed stop: ......................................................23
Selecting the fan operating speed: ......................................................................................24
Automatic defrosting: ............................................................................................................24
Shutting down the device: ....................................................................................................24
Locking/ unlocking the control pad: ......................................................................................24
Verifying and setting and the operating parameters: ............................................................24
INSTALLATION OF THE HEATING ELEMENT (OPTION) ...........................25
MAINTENANCE - UPKEEP ............................................................................27
ERROR CODES AND TROUBLESHOOTING: ..............................................28
Error codes: ........................................................................................................................28
Trouble shooting: ..................................................................................................................28

17/28
2015/12 - Indice de révision : B - Code : 33491
Safety instructions and recommendations
TO BE READ CAREFULLY
Children and physically or mentally impaired persons:
These dehumidifiers may be operated by children at least 8 years old and physically or mentally impaired
persons if:
•
they are adequately supervised.
•
they have been provided with instructions concerning safe operation of the device.
•
they understand the associated risks.
Neither cleaning nor maintenance may be entrusted to children or physically or mentally impaired persons.
Place the control panel out of the reach of children to prevent them from operating the device.
Electrical safety:
•
Install the machine in compliance with the regulations in effect in the country of installation (notably
electrical regulations), notably, respect safety distances from water.
•
DH dehumidifiers are not electrically protected against the intrusion of water (rain, splashing).
In France, regulations (standard C 15-100) stipulate the following:
•
The dehumidifier should be installed at a distance of more than 3 m from a bath, private above-
ground spa or shower stall.
•
The dehumidifier should be installed at a distance of more than 3.5 m from an in-ground spa or
pool.
•
A means to instantly cut power to the device must be installed at the head of the line (circuit
breaker or switch).
•
A thermal magnetic circuit breaker or fuse holder+fuse with a breaking current rated for the
amperage of the device must be installed at the head of the line.
•
We strongly recommend installation of a 30mA (trip current) residual current device upstream from
their power supply.
•
Have the device wired in by a qualified professional.
•
At least once a year, check that electrical wire contacts are correctly tightened.
•
Check regularly that the power cable is in good condition, in the event of damage to the cable (cut,
crushed ,wear, etc.), have it replaced immediately by a qualified professional.
•
Always cut the power to the device upstream prior to any technical intervention on the device
(repair, maintenance).
•
The heating element (optional) must be installed by a qualified professional.
Fire prevention:
•
Do not use the dehumidifier to extract solvent vapours from the air, more generally, never use the
device in a inflammable or explosive atmosphere.
•
Do not store inflammable liquids or materials close to the device.
•
Do not splash liquids onto the device.
•
Do not insert objects through the slots in the grate, teach children not to do this either.
•
Do not obstruct air flow at the intake or exhaust grates by covering the machine with material, or
a box or by positioning the machine with the front face too close to a partition.
•
In the event of abnormal noise, odour or smoke, shut the dehumidifier down immediately and cut
the power supply. Never attempt to the repair the device yourself, contact your sales agent.
•
Leave a gap of at least 80 cm in front of the machine and 30 cm on either side of the machine in
order to facilitate technical interventions.

18/28
2015/12 - Indice de révision : B - Code : 33491
Operating principle
FAIRLAND console dehumidifiers are used to limit the relative humidity in an enclosed space containing a
pool or spa to a value selected by the user (between 30% and 99%). They should be installed inside the
room to be dehumidified.
This dehumidifier is designed to operate with an ambient temperature between 10°C and 38°C. Performance
data is not guaranteed outside this range.
If the dehumidifier is fitted with the heating option, it may be used to increase the room temperature to a
value selected by the user (between 18°C and 32°C). As soon as the room temperature drops below this
value, the heating system will be activated to raise the temperature to the set point. Should the temperature
spontaneously rise above the set point, heating will remain stopped.
This paragraph will help explain how a FAIRLAND dehumidifier works and provide a better understanding
of the importance of the provisions concerning installation, use and maintenance set out in this document.
•
A heat transfer fluid travels in a loop in a copper circuit, as it travels it experiences the following
cycle:
•
Step 1: warm, humid ambient air from the room to be dehumidified is drawn at a high flow rate over
a fin-type radiator in which cold fluid is circulating, this is the evaporator. Upon contact with the
evaporator, the air temperature falls until it reaches the condensation point of water vapour, which
causes the water to condense in fine droplets. At the same time, the heat transfer fluid recovers
the calories given up by the ambient air.
•
Step 2: the fluid enters the compressor where it experiences a high increase in pressure and an
increase in temperature.
•
Step 3: the cold, dehumidified air then passes over a second fin-type radiator located behind
the evaporator, the condenser, through which the hot heat transfer fluid from the compressor is
circulating, this heats the cold, dehumidified air before it is returned to the pool room.
•
Step 4: the heat transfer fluid passes into the expansion chamber where it is returned to its initial
temperature and pressure, before returning to step 1 to restart the cycle.
Thus, the compressor and the expansion chamber is composed of two half-loops:
•
the half-loop on the condenser side is called the HP (High Pressure) loop.
•
the half-loop on the evaporator side is called the LP (Low Pressure) loop.
Start up of the compressor is slaved to the dehumidification demand.
The user may choose to allow the fan to run continuously or for the fan to stop when there is no
dehumidification or heating demand (refer to setting of parameter C8 in paragraph VI.11). Running the fan
at low speed in the absence of a dehumidification or heating demand creates continuous movement that
homogenises the air in the room and allows more precise control of these two parameters.

19/28
2015/12 - Indice de révision : B - Code : 33491
Dimensions and technical data
(1) : the dehumidification capacity refers to the volume of condensates recovered in one day at a constant
temperature of 30°C and relative humidity of 70%.
(2) : ambient temperature 30°C, relative humidity 70%.
Technical data is susceptible to modification to reflect product upgrades.
Dimension
(mm)
Ref
Model
A
B
C
D
E
F
G
H
DH60
286
886
200
126
613
718
36
860
DH90
286
1186 200
126
913
718
36
860
DH120
286
1186 200
126
913
718
36
860
Technical data
DH60
DH90
DH120
Dehumidification capacity (1) litres/24h
60
93
120
Nominal input power (dehumidification mode) W
990
1690
2000
Maximum input power (dehumidification mode) W
1200
2000
2450
Heating power output in dehumidification mode (2) W
2200
4200
5500
Power of the auxiliary heating element (option) W
2000
3000
3000
Air flow rate, fan at full speed m3/h
800
1000
1200
Power supply
monophasé 230 V~50Hz
Nominal/ maximum current (without auxiliary element) A
4,58 / 5,20
7,83 / 9,15
9,15 /
10,8
Accoustic pressure at 5 metres (dB(A))
39,5
40,8
40,8
Net weight/ gross weight (without auxiliary heating) kg
53 / 68
70 / 86
75 / 91
Quantity of refrigerant R 410 A g
800
1050
1300
Overall dimensions (length*width*height)
855x242x848
1155x280x848

20/28
2015/12 - Indice de révision : B - Code : 33491
The machine is fitted with HP and LP safety mechanisms controlled by a pressure switch.
The LP pressure switch stops the compressor if the pressure drops below 0.05 MPa and automatically
resets when the pressure rises above 0.15 MPa.
OFF : 0.05 MPa
ON : 0.15 MPa
The HP pressure switch stops the compressor when the pressure rises above 4.2 MPa, and automatically
resets when the pressure drops below 3.6 MPa.
OFF : 4.2 MPa
ON : 3.6 MPa
The machine is fitted with a n air circulation defrosting function.
Installation
Take into account the minimum distance limitations between the dehumidifier and the water body,
specified in the regulations in effect, when selecting the installation site.
If the machine is free-standing, it must be set on solid, stable and horizontal surface.
The dehumidifier is delivered with 4 height adjustable, vibration damping pads to be
screwed into place beneath the machine.
A flexible, translucent condensate drainage tube (length 2 m) is
also supplied. This should be connected to the machine under the
power cable connection.
The dehumidifier may also be mounted on
a wall using the two slots located on the
rear panel. Before mounting the device on
a wall, verify that the wall, and the means
of anchoring it to the wall, will support the
weight of the machine.
The remote installed control pad is fitted with a 10 m cable attached by a
quick disconnect fitting. The control pad is not watertight so it should be
protected from the elements
.
Control pad cable
Power cable
Condensate drainage tube (to be
installed)

21/28
2015/12 - Indice de révision : B - Code : 33491
The control panel is delivered with a wall mounting bracket.
1.
Remove the 2 screws from the mounting bracket.
2.
Mount the bracket on the wall in the desired position (out of the reach of children) using the 2 central
slots or the 4 peripheral slots (screws and bushings are not supplied).
3.
The cut out for the cable should face down
(to avoid streaming of condensates inside the control
panel).
4.
Unclip the rear casing of the control panel.
5.
Fix the rear casing of the control panel to the bracket using the 2 screws previously removed from
the mounting bracket.
6.
Clip the control panel onto its rear face.
Electrical wiring
The power cable is comprised of three strands (live = brown ; neutral =
blue ; earth = green and yellow), it is 1.5 m long.
To extend the power cable, use a cable with strands of the same cross section
if the total length of the cable will not exceed 10 m. If the cable in longer than
10 m, use an extension cable with strands that have a wider cross section.
Solder the wires together, use heat shrink tubing to insulate the soldered
connections.
The power cable must be connected to a thermal
magnetic protection device or a fuse holder + fuse,
rated fro the machine’s power consumption.
We strongly recommend that the machine’s power
line be protected by a 30 mA RCD.
Even with an extension, the control cable may not be longer than 50 meters. To extend the cable, use
cable with the same cross sections and connect the wires as described previously.
Type
DH 60
DH 90
DH 120
Residual current
device
Nominal current ( Amps)
20
30
40
Trip current mA
30
30
30
d curve thermal magnetic circuit breaker -
Nominal trip current in (A)
DH without
heater
7 (8 if not
adjustable)
11 (16 if not
adjustable)
12 (16 if not
adjustable)
DH with
heater
16
25
26 (32 if not
adjustable)
Power cable (mm2)
3 x 2,5
3 × 4
3 × 4
Remote installed control pad cable (mm2)
3 × 0.5
3 × 0.5
3 × 0.5
Support de fixation
Panneau arrière
commande

22/28
2015/12 - Indice de révision : B - Code : 33491
Commissioning and operation
Important:
The dehumidifier is designed to operate at an ambient temperature of between 5°C and 35°C.
Correct operation is not guaranteed outside this range.
The device has 4 operating modes:
•
Dehumidification only
•
Fan only (air circulation)
•
Dehumidification + heating (if the heating option is installed)
•
Heating only (if the heating option is installed)
Plugging the device into the mains:
The default display appears on the control pad screen:
•
on the left, the relative humidity (%) in the room as measured by the machine
(humidity sensor)
•
on the right, the temperature (°C) in the room as measured by the machine
(temperature sensor)
Starting up the device:
Press the On/ Off button
:
The active operation symbol appears on the screen.
Selection of the operating mode, by successive presses on the M button:
In dehumidification mode, if there is a dehumidification demand, the compressor will start one minute
after the fan (time delay).
Selecting the humidity set point:
(Dehumidification mode - with or without heating):
It is possible to select the relative humidity that should not be exceeded in the room, the allowed range is
between 30% and 99%. Note that the dehumidifier cannot increase the relative humidity in the room if it
falls below the set point.
To display the current set point value on screen, press one of the arrow keys (
or
) once.
While the set point flashes on screen, use the arrow keys (
and
) to increase or decrease this value in
increments of 1% until the desired set point is displayed.
The screen will automatically revert to the default display after 8 seconds of inactivity.
Nota
bene
:
The relative humidity control differential is +/-5%:
As soon as the relative humidity rises at least 5% above the set point, the compressor and the fan will start
if the machine is in dehumidification mode or in dehumidification + heating mode (option).
Inversely, as soon as the relative humidity falls at least 5% below the set point, the machine will stop
dehumidifying the air.
Selecting the temperature set point (if the heating option is installed and active):
If the optional heating element is installed, the parameter C1 will need to be configured, see paragraph
VI.11.
It is possible to select the minimum air temperature to be maintained in the room. If the temperature in the
room rises above the set point, the dehumidifier will not be able to cool it.

23/28
2015/12 - Indice de révision : B - Code : 33491
•
In heating only mode:
To display the temperature set point, press one of the arrow keys (
or
) once. While the set point is
flashing, press the arrow keys (
and
) to increase or decrease the set point temperature in increments
of 1°C. The screen will automatically revert to the default display after 8 seconds of inactivity.
•
In dehumidification + heating mode:
Press one of the arrow keys (
or
) once, and then press the
button to display the temperature set
point. Select the desired set point as described above.
As soon as the ambient temperature measured by the machine drops at least 1°C below the set point, the
element will start to heat. Heating will stop as soon as the ambient temperature measured by the machine
rises at least 1°C above the set point.
Programming a delayed start or a delayed stop:
A delayed stop can only be programmed while the machine is running.
Press the
button.
Using the arrow keys
or
, select a shut down delay of between
1
and
12
hours maximum (one hour
increments).
Allow the screen to return to the default display.
The
OFF
symbol appears in the bottom of the screen, confirming that the
OFF
operation has been
registered and that the machine will shut down after the programmed delay.
A delayed start can only be programmed while the machine is off.
Press the
button.
Using the arrow keys
or
, select a start up delay of between
1
and
12
hours maximum (one hour
increments).
Allow the screen to return to the default display.
The
ON
symbol appears in the bottom of the screen, confirming that the
ON
operation has been registered
and that the machine will start after the programmed delay.
To cancel a delayed start or strop, press the
button to display the delay (it will begin to flash), now press
the On/Off button (the machine will either start or stop depending on its current status).
Setting the fan speed:
While the machine is running, press the
SET
button to select the fan speed: High or Low

24/28
2015/12 - Indice de révision : B - Code : 33491
Automatic defrosting:
When the ambient temperature is low (around 10°C), the surface temperature of the fins and
evaporator tubes could be below 0°C while the machine is running in dehumidification mode.
This can lead to freezing of the condensates on the evaporator.
Accumulated frost will obstruct the air flow and hinder the refrigeration cycle. Before this phenomenon
becomes too pronounced, the machine is programmed to automatically trigger a defrosting cycle by
stopping the compressor and the circulation of air.
The symbol
will appear on the control panel screen.
The air will gradually melt the frost, the compressor will restart automatically once the frost is completely
melted.
Nota bene:
For the defrosting function to be effective, it is important not to run the machine at ambient
temperatures below 10°C.
Shutting down the device:
Press the On/ Off button.
The compressor will stop, approximately 30 seconds later, the fan will also stop.
Nota bene
There is a minimum time delay before the fan and compressor can be restarted (approximately
30 seconds for the fan and approximately 2 minutes for the compressor).
Locking/ unlocking the key pad:
To deactivate the key pad, press the two arrow keys (
and
) simultaneously and hold them down for
three seconds.
The following symbol will appear on screen:
To reactivate the key pad, repeat this operation.
Verifying and setting the operating parameters:
This menu is reserved to qualified maintenance professionals.
To enter the parameter setting menu, hold the SET key down for at least 3 seconds. Use the arrow keys
and
to scroll through the parameters until the parameter that you wish to verify or modify is displayed
on screen.
While the dehumidifier is running, it is possible to view the parameters but not to modify them.
While the machine is stopped, parameters may be both viewed and modified.

25/28
2015/12 - Indice de révision : B - Code : 33491
To modify the value of the parameter displayed, press the SET key. The value of the parameter will begin
to flash, use the arrow keys (
and
) to modify the parameter. Press the SET key to validate the modi-
fication.
Press or .
Installation of the heating element (option)
The heating element should only be installed by a qualified professional
.
N°
Parameter
code
Parameter title
Allowed values
Default value
1
C1
With or without heating
0 without / 1 with
0
2
C2
Heating element temperature
From -20°C to +99°C
Value measured
3
C3
Humidity compensation to calibrate
the humidity sensor
From -5% to +5%
0%
4
C4
Minimum time lapse between two
defrosting cycles
From 15Min to 90Min
20Min
5
C5
Defrosting cycle start temperature
From -10°C to 10°C
-1°C
6
C6
Defrosting cycle end temperature
From 0°C to 15°C
8°C
7
C7
Maximum duration of the defrosting
cycle
From 2Min to 12Min
8Min
8
C8
Fan operation once the set point is
reached
0 the fan stops at the set point
/ 1 the fan switches to low speed at
the set point
1
9
C9
Exhaust air temperature
-20°C~99°C
Measured value
10
CA
Refrigerant temperature at the
evaporator inlet
-20°C~99°C
Measured value
11
Cb
EXV step no.
100~500P
Measured value
12
CC
Overheating target value
Between -20°C and +20°C
5°C
Stop the machine and cut the power supply to the dehumidifier.
1.
Remove the plastic casing: extract the 2 Phillips head screws located
midway up each side, and the 3 Phillips head screws on the bottom of
the machine on each side. Also, to facilitate removal, take the metallic
strip off the back of the machine. Free the casing by pulling it forward.
2.
Place the element flat over the fins and
tube condenser with the black grating
facing upwards and the connections
oriented towards the electrical box. Feed
the electrical wires through the opening
located on the right hand side.
Align the holes in the heating element plate
with those of the base and insert the 4
screws to attach the heating element
to the machine.
3.
Open the lid of the electrical box

26/28
2015/12 - Indice de révision : B - Code : 33491
Electrical
box
Extract the 4 screws from
the lid of the box
4.
Feed the wire into the box through one of the openings located at the bottom of the box.
5.
Connect the white signal wire to the circuit board at the yellow
bridge on port P4
6.
Connect the earth lug to the earth terminal on the
connector block, over the one already in place.
Connect the neutral lug to the rear neutral pin on the
white terminal. First remove the neutral double lug
already in place. Connect the neutral cable of the
heating element to the rear pin, then reconnect the
double lug to the front pin using one of the two lugs.
7.
Connect the female live lug to the
free male lug of one of the two black
components.
8.
Put the lid of the electrical box back in
position.
9.
Replace the dehumidifier casing and the
screws.
10.
Modify the parameter C1: change the value to 1.

27/28
2015/12 - Indice de révision : B - Code : 33491
Upkeep – maintenance
The casing may be cleaned with a damp cloth, if necessary wetted with some neutral domestic cleaning
agent.
Never use solvants.
Never spray the machine with a water jet.
Check regularly that the power cable connections, heating element connections (if this option is installed),
and the connections inside the electrical box are correctly tightened.
Check regularly that the air intake filter, located behind the air intake grate at the bottom of the front casing,
is clean. If necessary, clean it with a cloth or soft bristle brush.

28/28
2015/12 - Indice de révision : B - Code : 33491
Error codes and trouble-shooting
Error codes:
Troubleshooting:
Symptom
Probable cause
Possible solution
The dehumidifer will
not switch on
Circuit breaker(s) or fuse tripped
Identify the reason for the fault, correct it
and reset the circuit breaker or replace the
fuse
On/ Off button set to off
Switch the machine on
Loose electrical connection
Verify that the remote installed control pad
cable and the power cable are correctly
tightened
In heating mode, the
air is circulating but
the air temperature
at the inlet is the
same as the air
temperature at the
outlet
T°C set point set to a temperature lower
than the ambient T°C
Modify the set point
3 minute time delay
Wait at least 5 minutes for the heating
element to reach temperature
Bad contact
Check that the heating element connections
are correctly tightened
If the problem is not resolved, contact the Procopi agent
Code
Meaning
Safety measure triggered
E1
Faulty ambient air T° sensor (sensor or connection cable)
Shuts down the machine
E2
Faulty defrosting sensor (sensor or connection cable)
The machine continues to run
E3
Faulty humidity sensor (sensor or connection cable)
Shuts down the machine
EF
Faulty exhaust air T° sensor (sensor or connection cable)
Turns off the heating element
EH
Refrigerant T° sensor at the evaporator inlet is faulty (sensor or
connection cable)
The machine continues to run
E4
HP safety mechanism tripped
Stops the compressor
E5
LP safety mechanism tripped
Stops the compressor
E7
Exhaust air thermal protection tripped
Turns off the heating element
EE
Communication error
Shuts down the machine
EC
Heating element thermal protection tripped
Turns off the heating element