DESHUMIDIFIER 

CONSOLES 

Models DH-60 / DH-90 / DH-120

INSTALLATION AND OPERATING INSTRUCTIONS

 (to be read carefully and kept for future reference)

 


background image

16/28

2015/12 - Indice de révision : B - Code : 33491

 

„

SAFETY INSTRUCTIONS AND RECOMMENDATIONS  ..............................17

Children and physically or mentally impaired persons: ........................................................17
Electrical safety: ...................................................................................................................17
Fire safety: ............................................................................................................................17

OPERATING PRINCIPLE ...............................................................................18

 

„

DIMENSIONS AND TECHNICAL DATA  ........................................................19

 

„

INSTALLATION  ..............................................................................................20

 

„

WIRING ...........................................................................................................21

 

„

COMMISSIONING AND USE .........................................................................22

Connection of the device to the mains: ................................................................................22
Start up: ................................................................................................................................22
Selection of the operating mode: ..........................................................................................22
Setting the humidity set point: ..............................................................................................22
Setting the temperature set point (if the heating option is installed and active): ..................23
Programming a postponed start and a postponed stop:  ......................................................23
Selecting the fan operating speed:  ......................................................................................24
Automatic defrosting: ............................................................................................................24
Shutting down the device: ....................................................................................................24
Locking/ unlocking the control pad: ......................................................................................24
Verifying and setting and the operating parameters: ............................................................24

 

„

INSTALLATION OF THE HEATING ELEMENT (OPTION)  ...........................25

 

„

MAINTENANCE - UPKEEP ............................................................................27

 

„

ERROR CODES AND TROUBLESHOOTING: ..............................................28

Error codes:   ........................................................................................................................28
Trouble shooting: ..................................................................................................................28

 


background image

17/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Safety instructions and recommendations 

TO BE READ CAREFULLY

 

ƒ

Children and physically or mentally impaired persons:

These dehumidifiers may be operated by children at least 8 years old and physically or mentally impaired 

persons if:

• 

they are adequately supervised.

• 

they have been provided with instructions concerning safe operation of the device.

• 

they understand the associated risks.

Neither cleaning nor maintenance may be entrusted to children or physically or mentally impaired persons.
Place the control panel out of the reach of children to prevent them from operating the device.

 

ƒ

Electrical safety:

• 

Install the machine in compliance with the regulations in effect in the country of installation (notably 

electrical regulations), notably, respect safety distances from water.

• 

DH dehumidifiers are not electrically protected against the intrusion of water (rain, splashing).

In France, regulations (standard C 15-100) stipulate the following:

• 

The dehumidifier should be installed at a distance of more than 3 m from a bath, private above-

ground spa or shower stall. 

• 

The dehumidifier should be installed at a distance of more than 3.5 m from an in-ground spa or 

pool.

• 

A means to instantly cut power to the device must be installed at the head of the line (circuit 

breaker or switch).

• 

A thermal magnetic circuit breaker or fuse holder+fuse with a breaking current rated for the 

amperage of the device must be installed at the head of the line. 

• 

We strongly recommend installation of a 30mA (trip current) residual current device upstream from 

their power supply.

• 

Have the device wired in by a qualified professional.

• 

At least once a year, check that electrical wire contacts are correctly tightened. 

• 

Check regularly that the power cable is in good condition, in the event of damage to the cable (cut, 

crushed ,wear, etc.), have it replaced immediately by a qualified professional. 

• 

Always cut the power to the device upstream prior to any technical intervention on the device 

(repair, maintenance).

• 

The heating element (optional) must be installed by a qualified professional. 

 

ƒ

Fire prevention:

• 

Do not use the dehumidifier to extract solvent vapours from the air, more generally, never use the 

device in a inflammable or explosive atmosphere.   

• 

Do not  store inflammable liquids or materials close to the device. 

• 

Do not splash liquids onto the device.

• 

Do not insert objects through the slots in the grate, teach children not to do this either.

• 

Do not obstruct air flow at the intake or exhaust grates by covering the machine with material, or 

a box or by positioning the machine with the front face too close to a partition. 

• 

In the event of abnormal noise, odour or smoke, shut the dehumidifier down immediately and cut 

the power supply. Never attempt to the repair the device yourself, contact your sales agent. 

• 

Leave a gap of at least 80 cm in front of the machine and 30 cm on either side of the machine in 

order to facilitate technical interventions.  

 


background image

18/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Operating principle

FAIRLAND console dehumidifiers are used to limit the relative humidity in an enclosed space containing a 

pool or spa to a value selected by the user (between 30% and 99%). They should be installed inside the 

room to be dehumidified. 

This dehumidifier is designed to operate with an ambient temperature between 10°C and 38°C. Performance 

data is not guaranteed outside this range. 

If the dehumidifier is fitted with the heating option, it may be used to increase the room temperature to a 

value selected by the user (between 18°C and 32°C). As soon as the room temperature drops below this 

value, the heating system will be activated to raise the temperature to the set point. Should the temperature 

spontaneously rise above the set point, heating will remain stopped. 

This paragraph will help explain how a FAIRLAND dehumidifier works and provide a better understanding 

of the importance of the provisions concerning installation, use and maintenance set out in this document. 

• 

A heat transfer fluid travels in a loop in a copper circuit, as it travels it experiences  the following 

cycle:

• 

Step 1: warm, humid ambient air from the room to be dehumidified is drawn at a high flow rate over 

a fin-type radiator in which cold fluid is circulating, this is the evaporator. Upon contact with the 

evaporator, the air temperature falls until it reaches the condensation point of water vapour, which 

causes the water to condense in fine droplets. At the same time, the heat transfer fluid recovers 

the calories given up by the ambient air. 

• 

Step 2: the fluid enters the compressor where it experiences a high increase in pressure and an 

increase in temperature.  

• 

Step  3:  the  cold,  dehumidified  air  then  passes  over  a  second  fin-type  radiator  located  behind 

the evaporator, the condenser, through which the hot heat transfer fluid from the compressor is 

circulating, this heats the cold, dehumidified air before it is returned to the pool room. 

• 

Step 4: the heat transfer fluid passes into the expansion chamber where it is returned to its initial 

temperature and pressure, before returning to step 1 to restart the cycle.

Thus, the compressor and the expansion chamber is composed of two half-loops:

• 

the half-loop on the condenser side is called the HP (High Pressure) loop.

• 

the half-loop on the evaporator side is called the LP (Low Pressure) loop.

Start up of the compressor is slaved to the dehumidification demand. 

The  user  may  choose  to  allow  the  fan  to  run  continuously  or  for  the  fan  to  stop  when  there  is  no 

dehumidification or heating demand (refer to setting of parameter C8 in paragraph VI.11). Running the fan 

at low speed in the absence of a dehumidification or heating demand creates continuous movement that 

homogenises the air in the room and allows more precise control of these two parameters. 

 


background image

19/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Dimensions and technical data 

(1) : the dehumidification capacity refers to the volume of condensates recovered in one day at a constant 

temperature of 30°C and relative humidity of 70%.
(2) : ambient temperature 30°C, relative humidity 70%.

Technical data is susceptible to modification to reflect product upgrades.

Dimension 

(mm)

Ref

Model

A

B

C

D

E

F

G

H

DH60

286

886 

200

126

613

718

36

860

DH90

286

1186 200

126

913

718

36

860

DH120

286

1186 200

126

913

718

36

860

Technical data

DH60

DH90

DH120

Dehumidification capacity (1)            litres/24h

60

93

120

Nominal input power (dehumidification mode)  W

990

1690

2000

Maximum input power (dehumidification mode) W 

1200

2000

2450

Heating power output in dehumidification mode (2) W

2200

4200

5500

Power of the auxiliary heating element (option)  W

2000

3000

3000

Air flow rate, fan at full speed       m3/h

800

1000

1200

Power supply

monophasé 230 V~50Hz

Nominal/ maximum current (without auxiliary element)   A

4,58 / 5,20

7,83 / 9,15

9,15 / 

10,8

Accoustic pressure at 5 metres (dB(A))

39,5

40,8

40,8

Net weight/ gross weight  (without auxiliary heating)       kg

53 / 68

70 / 86

75 / 91

Quantity of refrigerant R 410 A      g

800

1050

1300

Overall dimensions (length*width*height)

855x242x848

1155x280x848

 


background image

20/28

2015/12 - Indice de révision : B - Code : 33491

The machine is fitted with HP and LP safety mechanisms controlled by a pressure switch. 

The LP pressure switch stops the compressor if the pressure drops below 0.05 MPa and automatically 

resets when the pressure rises above 0.15 MPa.
OFF : 0.05 MPa
ON : 0.15 MPa

The HP pressure switch stops the compressor when the pressure rises above 4.2 MPa, and automatically 

resets when the pressure drops below 3.6 MPa.
OFF : 4.2 MPa
ON : 3.6 MPa

The machine is fitted with a n air circulation defrosting function.

 

„

Installation 

Take into account the minimum distance limitations between the dehumidifier and the water body, 

specified in the regulations in effect, when selecting the installation site.

If the machine is free-standing, it must be set on solid, stable and horizontal surface. 

The dehumidifier is delivered with 4 height adjustable, vibration damping pads to be 

screwed into place beneath the machine. 

A  flexible,  translucent  condensate  drainage  tube  (length  2  m)  is 

also supplied. This should be connected to the machine under the 

power cable connection.

The dehumidifier may also be mounted on 

a wall using the two slots located on the 

rear panel. Before mounting the device on 

a wall, verify that the wall, and the means 

of anchoring it to the wall, will support the 

weight of the machine.

The remote installed control pad is fitted with a 10 m cable attached by a 

quick disconnect fitting. The control pad is not watertight so it should be 

protected from the elements

.

Control pad cable

Power cable

Condensate drainage tube (to be 

installed)

 


background image

21/28

2015/12 - Indice de révision : B - Code : 33491

The control panel is delivered with a wall mounting bracket.

1. 

Remove the 2 screws from the mounting bracket.

2. 

Mount the bracket on the wall in the desired position (out of the reach of children) using the 2 central 

slots or the 4 peripheral slots (screws and bushings are not supplied).

3. 

The cut out for the cable should face down

 (to avoid streaming of condensates inside the control 

panel).

4. 

Unclip the rear casing of the control panel.

5. 

Fix the rear casing of the control panel to the bracket using the 2 screws previously removed from 

the mounting bracket.  

6. 

Clip the control panel onto its rear face.

 

„

Electrical wiring

The power cable is comprised of three strands (live =  brown ; neutral = 

blue ; earth = green and yellow), it is 1.5 m long. 
To extend the power cable, use a cable with strands of the same cross section 

if the total length of the cable will not exceed 10 m. If the cable in longer than 

10 m, use an extension cable with strands that have a wider cross section.
Solder the wires together, use heat shrink tubing to insulate the soldered 

connections. 

The power cable must be connected to a thermal 

magnetic protection device or a fuse holder + fuse, 

rated fro the machine’s power consumption. 

We strongly recommend that the machine’s power 

line be protected by a 30 mA RCD. 

Even with an extension, the control cable may not be longer than 50 meters. To extend the cable, use 

cable with the same cross sections and connect the wires as described previously. 

Type

DH 60

DH 90

DH 120

Residual current 

device

Nominal current  ( Amps)

20

30

40

Trip current mA

30

30

30

d curve thermal magnetic circuit breaker - 

Nominal trip current in (A)

DH without 

heater 

7 (8 if not 

adjustable)

11 (16 if not 

adjustable)

12 (16 if not 

adjustable)

DH with 

heater

16

25

26 (32 if not 

adjustable)

Power cable  (mm2)

3 x 2,5

3 × 4

3 × 4

Remote installed control pad cable (mm2)

3 × 0.5

3 × 0.5

3 × 0.5

Support de fixation

Panneau arrière  

commande

 


background image

22/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Commissioning and operation

Important:

 The dehumidifier is designed to operate at an ambient temperature of between 5°C and 35°C. 

Correct operation is not guaranteed outside this range. 

The device has 4 operating modes:

• 

Dehumidification only 

• 

Fan only (air circulation) 

 

• 

Dehumidification + heating (if the heating option is installed) 

  

• 

Heating only (if the heating option is installed) 

 

ƒ

Plugging the device into the mains:

The default display appears on the control pad screen:

• 

on the left, the relative humidity (%) in the room as measured by the machine 

(humidity sensor)

• 

 on the right, the temperature (°C) in the room as measured by the machine 

(temperature sensor)

 

ƒ

Starting up the device:

Press the On/ Off button

The active operation symbol appears on the screen.

 

ƒ

Selection of the operating mode, by successive presses on the M button:

In dehumidification mode, if there is a dehumidification demand, the compressor will start one minute 

after the fan (time delay).

 

ƒ

Selecting the humidity set point:

(Dehumidification mode - with or without heating):

It is possible to select the relative humidity that should not be exceeded in the room, the allowed range is 

between 30% and 99%. Note that the dehumidifier cannot increase the relative humidity in the room if it 

falls below the set point.
To display the current set point value on screen, press one of the arrow keys (

or

) once.

While the set point flashes on screen, use the arrow keys (

 and

) to increase or decrease this value in 

increments of 1% until the desired set point is displayed.  
The screen will automatically revert to the default display after 8 seconds of inactivity. 

Nota 

bene 

 

:

 The relative humidity control differential is +/-5%: 

As soon as the relative humidity rises at least 5% above the set point, the compressor and the fan will start 

if the machine is in dehumidification mode or in dehumidification + heating mode (option). 

Inversely, as soon as the relative humidity falls at least 5% below the set point, the machine will stop 

dehumidifying the air. 

 

ƒ

Selecting the temperature set point (if the heating option is installed and active):

If the optional heating element is installed, the parameter C1 will need to be configured, see paragraph 

VI.11.
 It is possible to select the minimum air temperature to be maintained in the room. If the temperature in the 

room rises above the set point, the dehumidifier will not be able to cool it. 

 


background image

23/28

2015/12 - Indice de révision : B - Code : 33491

• 

In heating only mode: 

To display the temperature set point, press one of the arrow keys  (

or 

) once. While the set point is 

flashing,  press the arrow keys (

 and

) to increase or decrease the set point temperature in increments 

of 1°C. The screen will automatically revert to the default display after 8 seconds of inactivity.

• 

In dehumidification + heating mode: 

 

Press one of the arrow keys  (

or 

) once, and then press the  

 button to display  the temperature set 

point. Select the desired set point as described above. 
As soon as the ambient temperature measured by the machine drops at least 1°C below  the set point, the 

element will start to heat. Heating will stop as soon as the ambient temperature measured by the machine 

rises at least 1°C above the set point. 

 

ƒ

 Programming a delayed start or a delayed stop: 

A delayed stop can only be programmed while the machine is running. 

Press the 

 button.

Using the arrow keys 

 or 

, select a shut down delay of between 

1

 and 

12

 hours maximum (one hour 

increments).
Allow the screen to return to the default display.

The 

OFF

  symbol  appears  in  the  bottom  of  the  screen,  confirming  that  the

OFF

 operation has been 

registered and that the machine will shut down after the programmed delay. 
A delayed start can only be programmed while the machine is off. 

Press the 

 button.

Using the arrow keys 

 or 

, select a start up delay of between 

1

 and 

12

 hours maximum (one hour 

increments).
Allow the screen to return to the default display.

The 

ON

 symbol appears in the bottom of the screen, confirming that the

ON

 operation has been registered 

and that the machine will start after the programmed delay. 
To cancel a delayed start or strop, press the 

 button to display the delay (it will begin to flash), now press 

the On/Off button (the machine will either start or stop depending on its current status).

 

ƒ

Setting the fan speed: 

While the machine is running, press the 

SET

 button to select the fan speed: High or Low

 


background image

24/28

2015/12 - Indice de révision : B - Code : 33491

 

ƒ

Automatic defrosting:

When the ambient temperature is low (around 10°C), the surface temperature of the fins and 

evaporator tubes could be below 0°C while the machine is running in dehumidification mode. 

This can lead to freezing of the condensates on the evaporator.  
Accumulated frost will obstruct the air flow and hinder the refrigeration cycle. Before this phenomenon 

becomes too pronounced, the machine is programmed to automatically trigger a defrosting cycle by 

stopping the compressor and the circulation of air.

The symbol 

 will appear on the control panel screen. 

The air will gradually melt the frost, the compressor will restart automatically once the frost is completely 

melted.

Nota bene:

 For the defrosting function to be effective, it is important not to run the machine at ambient 

temperatures below 10°C. 

 

ƒ

Shutting down the device:

Press the On/ Off button.
The compressor will stop, approximately 30 seconds later, the fan will also stop.

Nota bene 

 There is a minimum time delay before the fan and compressor can be restarted (approximately 

30 seconds for the fan and approximately 2 minutes for the compressor). 

 

ƒ

Locking/ unlocking the key pad:

To deactivate the key pad, press the two arrow keys (

 and 

) simultaneously and hold them down for 

three seconds.  

The following symbol will appear on screen: 
To reactivate the key pad, repeat this operation.

 

ƒ

Verifying and setting the operating parameters:

This menu is reserved to qualified maintenance professionals.

To enter the parameter setting menu, hold the SET key down for at least 3 seconds. Use the arrow keys 

 and 

to scroll through the parameters until the parameter that you wish to verify or modify is displayed 

on screen.  

While the dehumidifier is running, it is possible to view the parameters but not to modify them. 
While the machine is stopped, parameters may be both viewed and modified.

 


background image

25/28

2015/12 - Indice de révision : B - Code : 33491

To modify the value of the parameter displayed, press the SET key. The value of the parameter will begin 

to flash, use the arrow keys (

 and 

) to modify the parameter. Press the SET key to validate the modi-

fication.  

 Press    or   .

 

„

Installation of the heating element (option) 

The heating element should only be installed by a qualified professional

.  

Parameter 

code

Parameter title

Allowed values

Default value

1

C1

With or without heating

0 without / 1 with

0

2

C2

Heating element temperature

From -20°C to +99°C

Value measured

3

C3

Humidity compensation to calibrate 

the humidity sensor

 From -5%  to  +5%

0%

4

C4

Minimum time lapse between two 

defrosting cycles

From 15Min to 90Min

20Min

5

C5

Defrosting cycle start temperature

From -10°C to 10°C

-1°C

6

C6

Defrosting cycle end temperature

From 0°C to 15°C

8°C

7

C7

Maximum duration of the defrosting 

cycle

From 2Min to 12Min

8Min

8

C8

Fan operation once the set point is 

reached

0 the fan stops at the set point  

/ 1 the fan switches to low speed at 

the set point

1

9

C9

Exhaust air temperature

-20°C~99°C

Measured value

10

CA

Refrigerant temperature at the 

evaporator inlet

-20°C~99°C

Measured value

11

Cb

EXV step no.

100~500P

Measured value

12

CC

Overheating target value

Between -20°C and +20°C

5°C

Stop the machine and cut the power supply to the dehumidifier.

1. 

Remove the plastic casing: extract the 2 Phillips head screws located 

midway up each side, and the 3 Phillips head screws on the bottom of 

the machine on each side. Also, to facilitate removal,  take the metallic 

strip off the back of the machine. Free the casing by pulling it forward. 

2. 

Place  the  element  flat  over  the  fins  and 

tube condenser with the black grating 

facing upwards and the connections 

oriented towards the electrical box. Feed 

the electrical wires through the opening 

located on the right hand side. 

 

Align the holes in the heating element plate 

with those of the base and insert the 4 

screws to attach the heating element 

to the machine. 

3. 

Open the lid of the electrical box 

 


background image

26/28

2015/12 - Indice de révision : B - Code : 33491

Electrical 

box

Extract the 4 screws from 

the lid of the box

4. 

Feed the wire into the box through one of the openings located at the bottom of the box.

5. 

Connect the white signal wire to the circuit board at the yellow 

bridge on port P4 

 

 

 

6. 

Connect the earth lug to the earth terminal on the 

connector block, over the one already in place. 

 

 

 

 

 

 

 

Connect the neutral lug to the rear neutral pin on the 

white terminal. First remove the neutral double lug 

already in place. Connect the neutral cable of the 

heating element to the rear pin, then reconnect the 

double lug to the front pin using one of the two lugs.   

  

 

7. 

Connect the female live lug to the 

free male lug of one of the two black 

components.

8. 

Put the lid of the electrical box back in 

position. 

9. 

Replace the dehumidifier casing and the 

screws.

10. 

Modify the parameter C1: change the value to 1.

 


background image

27/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Upkeep – maintenance 

The casing may be cleaned with a damp cloth, if necessary wetted with some neutral domestic cleaning 

agent.
Never use solvants.
Never spray the machine with a water jet.
Check regularly that the power cable connections, heating element connections (if this option is installed), 

and the connections inside the electrical box are correctly tightened.   

Check regularly that the air intake filter, located behind the air intake grate at the bottom of the front casing,  

is clean. If necessary, clean it with a cloth or soft bristle brush. 

 


background image

28/28

2015/12 - Indice de révision : B - Code : 33491

 

„

Error codes and trouble-shooting 

 

ƒ

Error codes:  

 

ƒ

Troubleshooting:

Symptom

Probable cause

Possible solution

The dehumidifer will 

not switch on

Circuit breaker(s) or fuse tripped 

Identify the reason for the fault, correct it 

and reset the circuit breaker or replace the 

fuse

On/ Off button set to off

Switch the machine on

Loose electrical connection

Verify that the remote installed control pad 

cable and the power cable are correctly 

tightened

In heating mode, the 

air is circulating but 

the air temperature 

at the inlet is the 

same as the air 

temperature at the 

outlet

T°C set point set to a temperature lower 

than the ambient T°C 

Modify the set point

3 minute time delay

Wait at least 5 minutes for the heating 

element to reach temperature

Bad contact

Check that the heating element connections 

are correctly tightened

If the problem is not resolved, contact the Procopi agent

Code

Meaning

Safety measure triggered

E1 

Faulty ambient air T° sensor (sensor or connection cable)

Shuts down the machine

E2 

Faulty defrosting sensor (sensor or connection cable)

The machine continues to run

E3 

Faulty humidity sensor (sensor or connection cable)

Shuts down the machine

EF 

Faulty exhaust air T° sensor (sensor or connection cable)

Turns off the heating element

EH 

Refrigerant T° sensor at the evaporator inlet is faulty (sensor or 

connection cable)

The machine continues to run

E4 

HP safety mechanism tripped

Stops the compressor

E5 

LP safety mechanism tripped

Stops the compressor

E7 

Exhaust air thermal protection tripped 

Turns off the heating element

EE 

Communication error

Shuts down the machine

EC 

Heating element thermal protection tripped 

Turns off the heating element