PDF User Manual

  1. Home
  2. Manuals
  3. Cleveland SteamerGard WT-300 Installation, Operation And Maintanance Manual

Cleveland SteamerGard WT-300 Installation, Operation And Maintanance Manual

SteamerGard WT-600 SteamerGard WT-900

Made by: Cleveland
Type: Installation, Operation And Maintanance Manual
Category: Water Filtration Systems
Pages: 18
Size: 0.78 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

SteamerGard

 

WT-300, WT-600 and WT-900  
WATER TREATMENT SYSTEM 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 

 
 
 
 
 

Pan Number 98-0800

 

WTS-04

 

INSTALLATION, 
OPERATION AND 
MAINTENANCE 
MANUAL 

 


background image

Contents 

 
 

Installation 

 
 

Installation Requirements 

Space Requirements 

Operating Parameters  

Feedwater Chemistry  

Electrical  

Installation Drawings 

 
 

Space Requirements, Figure 1.  

Typical Installation, Figure 2 

4-5 

SteamerGard Detail, Figure 3  

6-7 

Installation Procedure  

 
 

Positioning equipment. 

Wall Mounting RO. 

Wall Mounting Filter Assy. 

Feedwater Connection. 

Drain Connection  

10 

Product Water Connection  

10 

Electrical Connection 

10 

Storage Tank Installation Procedure  

11 

Contol-Bypass Panel Installation Procedure  

12 

Final Connection to Steamer  

12 

Start-UP Procedure 

 
 

Start-up Procedure 

13 

Final Inspection. 

13 

Routine Maintenance 

 
 

Depressurization Procedure 

14 

Sediment Filter Replacement 

14 

Carbon Filter Replacement 

15 

Post Treatment Filter Replacement 

15 

Final Inspection 

15 

Restarting and Purging the RO 

15 

Wiring Diagram 

16 

 

 


background image

Installation Requirements 

Before beginning the installation, review the criteria below to make sure that the requirements have been or will be met when the 
installation is complete.  Also,confirm that the feed water falls within the limits shown below.  If you're not sure if this has been done, 

check with your SteamerGard distributor or the factory before installing the system.  This is important because failures caused by 

water related problems are not covered under the system warranty. 

 

Operating parameters: 

Model 

 

Operating pressure 

175 psi 

Typical TDS rejection 

>96% 

Feed Temperature 

40- 100° F (4-38° C) 

Feed pressure  

25 - 85 psi (1.4 - 5.9 bar) at 3 gpm 

Production* 

WT-300, WT-600, WT-900 

 

*Model number equals nominal production in gallons per day @ 77°F (25°C) @ 500 ppm based on 24 hr day. Actual output may vary 

according to local water conditions and membrane variations. 

 

1

 

 


background image

Installation Requirements, Cont'd 

Feedwater chemistry: 

Parameter

 

 

 

 

Feed TDS

 

Up to 2000 ppm

 

Feed pH

 

5-11

 

Hardness

 

20 grains or less

 

Free chlorine

 

<2mg/l

 

Iron (Fe)

 

. 1 mg/I maximum

 

Manganese

 

.05 mg/1 maximum

 

Hydrogen sulfide

 

none allowable

 

Turbidity

 

<5NTU

 

 
If your water analysis indicates that any of these parameters are not in range, additional pretreatment or higher frequency 
of maintenance may be required. Contact your SteamerGard distributor or the factory for assistance. NOTE: The presence 
of silica or flocculants (e.g. alum or cationic polymers) in the feedwater can cause membrane fouling and may require 
special chemical pretreatment or periodic membrane cleaning. 

Electrical requirements: 

Model

 

WT-300, WT-600

 

WT-900

 

Electrical

 

115 VAC, 60 Hz, 6.2 Amp.

 

115 VAC, 60 Hz, 7.5 Amp.

 

Motor

 

1/3 HP

 

1/2 HP

 

Pump

 

Rotary vane type

 

Rotary vane type

 

 

Drain 

Drain must allow a minimum flow of 5 gallons per minute. 
Follow local plumbing codes for connection of drain line. Most plumbing codes require the installation of an 
approved air gap in the drain line. 

 

2

 

 


background image

Getting to Know the SteamerGard System 

Before beginning the installation, take a few minutes to familiarize yourself with the SteamerGard system by studying the 
drawings on the following pages.  Figure 2 shows a typical SteamerGard installation. Figure 3 shows a detailed view of the 

SteamerGard RO, pretreatment and post treatment system. 

3

 

 


background image

 

 


background image

 

SteamerGard WT-600 RO, Pretreatment and Postreatment Assembly 

(Shown with cover removed)

 

 


background image

  

 


background image

Figure 3.

    SteamerGard WT-300/600/900 Detail 

 

 

 

 

 

 

 

 

 

Item# 

Part # 

Description 

Item# 

Part # 

Description 

47-121261 

20", 5 micron sediment prefilter 

20 

53-5107 

Reject flo

w

 control (WT-300) 

47-212314 

20", carbon prefilter 

20 

53-5109 

Reject now control (WT-600) 

47-45171 

10", pH adjusting filter 

20 

 

Reject now control (WT-900) 

11 

60-633232 

Pressure control valve 

21 

60-1242301 

Feedwater inlet solenoid 

12 

24-1117 

Storage tank pressure switch 

22 

89-1210501 

Pump, Procon 1504 (WT-300) 

14 

24-1112 

Feedwater pressure swtich 

22 

89-1611101 

Pump, GR1 88000-004 (WT-600) 

15 

95-123327 

Gauge, 0-300 psi, 2 1/2", 1/4" 

22 

89-1211301 

Pump, Procon 2504 (WT-900) 

18 

95-123325 

Gauge. 0-160 psi, 2 1/2", 1/4" 

23 

45-1222211 

20" Blue filter housing 

19 

66-4311 

RO Module (WT-300/600) 

24 

45-1111231 

10" Clear filter housing 

19 

66-4315 

RO Module (WT-900) 

25 

89-2213111 

Motor, 1/3 HP (WT-300/600) 

 

 

 

25 

89-2913912 

Motor, 1/2 HP (WT-900) 

 

 


background image

Installation Procedure, RO system 

Position the storage tank in the desired location. (See storage tank installation procedures for more information). The RO 
should be installed within 15 feet of the storage tanks. We recommend that you allow at least 6 inches of clearance on all 
sides of the RO to facilitate service. Feedwater, drain and electrical connections are also required. Small enclosed and 
unventilated spaces (e.g. cabinets) must be avoided or the motor may overheat. 

Wall mounting the RO. 

1.   Position the wall mount bracket in the desired position. The holes 

in the bracket (16" centers)

 must line up with wood studs in the 

wall.

 (See Figure 5.) Use all six of the #12 x 1 1/2" phillips 

screws provided. 

2.   If wood studs are not available, a 3/4" sheet of plywood (20" x 

20" x 3/4" or larger) should be mounted to the wall (See Figure 
6.) using appropriate hardware for the type of wall and the weight 
(100 Ibs) to be supported. (This hardware is not included with the 
SteamerGard System). The wall mount bracket can then be 
mounted to the plywood using the six, #12 x 1 1/2" phillips 
screws provided. 

3.   Inspect the back of the vertical panel of the RO. There will be a 

black circular rubber "well nut" pressed into a hole near the 
center of the panel with a 1/4" x 3/4" phillips head machine screw 
and washer screwed into it. Next, tip the RO up and look 
underneath it. There will be two "well nuts" in the bottom. 
Remove the 1/4" x 3/4" phillips head machine screws from the 
well nuts. Leave the well nuts in the frame. 

4.   With the wall mount bracket securely installed, lift the RO into 

position on the bracket. Note that the tabs on the upper shelf of 
the wall mount bracket must engage the rectangular cut outs in 
the vertical panel of the RO frame. 

5.   From behind the frame, locate the tab bent down from the upper 

shelf. Align the "well nut" in the center of the frame with the hole 
in this tab and insert a 1/4" x 3/4" phillips head machine screw 
through the hole in the tab and screw it into the well nut in the 
frame. (See Figure 7.) 

5.   From below the lower shelf, locate the two holes that correspond 

with rubber mounted nuts in the bottom of the RO frame. Insert a 
1/4" x 3/4" phillips head machine screw into each of these nuts 
and tighten. (See Figure 7.) 

 

8

 

 

 


background image

Wall mounting the filter assembly, installing the filters. 

1.   With the filter bowls removed, position the filter bracket over the 1/4" studs at the bottom of the wall mount 

bracket. Secure

 the

 filter bracket to the wall mount bracket using 1/4" nuts and lock washers. 

2.   Remove the filters from their packaging. Locate the 5 micron sediment prefilter. This is the 20" long all-white 

filler with grooves cut into its surface (Fig. 3, Item 3). Place it into one of the blue sumps (Fig. 3, Item 23). Make 
sure there is an "O" ring in the groove in the top

 of

 the sump. Install the sump onto the filter head on the far right 

side labeled "Prefilter" by engaging the grooves and turning the sump until hand tight. 

3.   Locate the two carbon filters. These are the remaining 20" long filters (Fig. 3, Item 4). Insert them into the 

remaining 20" blue sumps (Fig. 3, Item 23). Check to see that the "0" ring is in place and install the sumps onto 
the next two positions labeled "Carbon filter". 

4.   Insert the remaining filter into the 10" clear filter housing (Fig- 3, Item 24). This filter is the 

SteamerGard posttreatment filter (Fig. 3, Item 7). Check that the "0" ring is in place and install the sump onto the 
remaining filter head on the far left of the filter bracket. This head is labeled "Postfilter". 

Feedwater connection 

The feedwater supply line must be at least 1/2" O.D. (Outside diameter) tubing and should not exceed 20 feet from 
the main feedwater connection to the RO system. The installation package includes 25 feet of 1/2" 

O.D.

 polybutylene 

tubing for making this connection. For longer runs, 1/2" pipe or larger should be brought to within 20 feet of the RO 
system. 

1.   Connect to an adequate water supply with a ball or gate valve (valve not included with SteamerGard system) to 

provide a 1/2" connection for feed water. Supply must be able to flow at least 4 gpm. Under 

no

 circumstances 

should a needle valve or self piercing valve be used. 

2. Run the 1/2" O.D- line from the feedwater connection at the main 

water line to the inlet feedwater valve on the prefilter assembly. 
Remove the compression nut from this valve (Fig 3, Item 2) and 
slide it onto the tubing followed by a Delrin (white plastic) sleeve. 
(See Fig. 9) Note that there may be a brass sleeve inside the 
compression nut Discard the brass sleeve. Connect the tubing to the 
valve by inserting the tubing all the way into the fitting and 
tightening the compression nut. 

3.   Install the purge valve assembly by threading it into the female 

threads on the feed water solenoid. (Fig. 9-1) 

4. Remove the compression nut from the prefilter assembly outlet 

connection (Fig. 3, Item 5). Slide the compression nut and a Delrin 
sleeve onto one end of a piece of 1/2" O.D. tubing Connect this end 
of the tubing to the prefilter assembly outlet connection. Route the 
tubing in a gradual arc down and to the left, behind the post 
treatment filter, and up to the feedwater inlet connection on the 
purge valve assembly (Fig.3, Item 9). Avoid sharp bends.

 Do not kink

 the

 tubing.

 Cut the tubing using a plastic 

tubing cutter or razor knife. Make a smooth, clean, 90° cut or leaks may result. Slip a compression nut and Delrin 
sleeve over the end and connect the tubing to the feedwater solenoid. 

9

 

 

 


background image

Cleveland Range                           Installation, Operation and Maintenance Manual 
 
Drain connection

 

1.   Run 3/8" O.D. (1/4" nominal) tubing from the reject drain connection (Fig. 3, Item 17) to the drain. Use the 3/8" 

Delrin (white plastic) sleeve provided on the connection to the brass compression fitting at the drain connection. 

2.   The drain is pressurized and may be run up to 10 feet above the RO or up to 25 feet from the RO to the drain. Care 

must be taken not to crimp or block the drain line. 

3.   Run a line from the purge valve on the inlet to the RO (Fig. 3, Item 26) to the drain or leave the end accessible for 

purging the filters into a bucket. 

Important:

 An approved air gap should exist between the RO unit and the drain opening to meet local plumbing 

codes. 

Product water connection

 

1.   Remove the plastic compression nut from the 

product water outlet connection on the RO. (Fig. 3, 
Item 10) Slide the nut, me stainless steel grip ring, 
the plastic washer and the''O" ring, (Fig. 10) about 
1/4" past the end of a piece of 3/8" O.D. (1/4" 
nominal) tubing. Insert the assembly into the product 
water outlet connection and tighten me compression 
nut 

2. Run this line down to the inlet side of the post 

treatment filter (Fig. 3, Item 8) and connect it 

3.   For connection of the post treatment filter to the 

storage tank, see the storage installation instructions. 

Electrical connection

 

    Be certain the red handled "ON/OFF'' switch on the RO (Fig 3, Item 13) is in the "OFF'' position.

 DOWN IS 

"ON" — UP IS "OFF".

 

1.  Connect the power cord from the RO to a 115 VAC, 15 AMP grounded receptacle. 

2.  Refer to the Start -Up section for further instructions. 

 

 

10 

 


background image

Storage Tank Installation Procedure 

The SteamerGard storage tanks are 10, 20 and 40 gallon, self pressurized storage tanks. As water from the RO fills the 
tank, the pressure in the tank increases until it reaches 60 psi, at which point the RO will automatically turn off. As water is 
drawn from the tank, the pressure in the tank drops. When the pressure in 
the tank drops to 40 psi, the RO will automatically mm on. 

1.   Install the ball valve kit onto the tank. (Fig 4.) Use approximately 4 

wraps of Teflon tape (provided) to seal each of the connections. 
Tighten the fittings approximately one mm past hand tight.

 Do not 

over tighten.

 Over-tightening may crack the fittings. 

2.   We recommend the use of the elbow fitting included to direct the ball 

valve up along the tank instead of connecting the ball valve directly 
to the nipple. Using the elbow will result in a more compact 
installation that is less vulnerable to breakage. 

3.   Check the air pressure in the tank- With no water in the tank, it 

should be 15 psi. Add or remove air as required. 

4.   Place the tank in the desired location. It should be placed in an area 

where it will not be frequently bumped or jarred. 

5.   Run a 3/8" O.D. polybutylene line from one side of the Tee to the 

product water outlet on the post treatment assembly on the RO (Fig. 
3, Item 6). 

6.  Open the ball valve on the tank by turning the handle until it's 

parallel with the body of the valve. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 


background image

Control Panel Installation, Connection to Steamer

 

The control panel provides a water quality monitor (Fig. 5, Item 6), bypass valve (Fig. 5, Item 4) and storage tank pressure 
gauge (Fig. 5, Item 5). The water quality monitor measures the quality of water provided by the SieamerGard. If a red light is 
noted, service is required. The bypass valve allows operation of the steamer on tap water in the event of failure of the 
SteamerGard system. 

1.   Position the control panel on a wall in the vicinity of the 

steamer (See Figure 2). You will also need access to a 
cold water supply. 

2.   Mount the control panel to the wall using the four 

#10x1 1/2" screws and wall anchors provided. 

3.   Tap into a cold water supply line near the control panel. 

We recommend the installation of a ball valve at the 
point you tap into the cold water supply. Run a line 
from the cold water supply to the control panel. If the 
distance is 25' or less, use 3/8" O.D. polybutylene 
tubing. For longer runs, use 1/2' O.D. tubing and reduce 
down at the control panel. Connect this line to the 
"Bypass" fitting (Fig. 5, Item 2) on the control panel. 

4.   Connect a 3/8" O.D. polybutylene line to the open end 

of the Tee on the storage tank. Run this line from the 
tank to the SteamerGard connection on the control 
panel. (Fig. 5, Item 1) 

5.   Connect a 3/8" O.D. polybutylene line to the outlet on the control panel (Fig. 5, Item 3). Connect me other end of this 

line to the steam generator (boiler) connection on the steamer. Install a check valve as directed in the steamer manual 
at the inlet connection to the steam generator. The fitting and check valve required to make this connection are not 
included in the SteamerGard system. 

NOTE: Do not connect the purified water to the condenser. The condenser must be connected to a separate 
cold water supply.

 

The SteamerGard installation is now complete. You can now start-up the steamer 
by following the start-up instructions for the steamer. 

12

 

 

 


background image

Start-Up Procedures, 

1.   With all connections completed and checked and the ON/OFF switch (Fig 3. Item 13) still in the "OFF'' (up) position, 

open the main feed water supply valve and the prefilter assy. shut-off valve (Fig 3, Item 1) 

2.   Turn the pressure control valve (Fig 3, Item 11) several turns counterclockwise until the handle feels loose. The lock-

nut on the threaded shaft may have to be loosened. 

3.   Open the purge valve at the inlet to the RO system.(Fig. 3, Item 26). Allow the water to drain until all of the air is 

purged. Close the drain valve. 

4.   Turn the power switch to the "ON'' (down) position. The motor should start running and the operating pressure gauge 

should read less than 150 PSI. Gradually open the flush valve (Fig 3, Item 16) to help expel air from the system. The 
system may temporarily cycle on and off. If this occurs, slowly turn the flush valve toward the closed position until 
cycling stops. When air is purged and water flow stabilizes (30 to 60 seconds), close the flush valve. 

5.   Slowly mm the pressure control valve knob clockwise until the pressure gauge (Fig 3, Item 15) reads 175  psi.

 

Maximum operating pressure is 175 psi.

 When set, tighten the lock-nut on the control valve shaft. 

DO NOT set the operating pressure as read by this gauge at anything higher than 175 psi. Operating at higher 
pressures will subject the system to pressures greater than it is designed for. 

6.   While the storage tank is filling, inspect the pretreatment assembly, RO system and all connections for leaks and make 

necessary adjustments. 

7.   When the storage tank is full, the RO will automatically shut off. It is important to verify that the RO shuts off when 

the storage tank is full. To verify proper operation, check the pressure gauge on the control panel (Fig. 5, Item 5) and 
observe that the system shuts off at 60 psi. Use the chart below to determine the time necessary for the RO to fill the 
tank. 

Model

 

Fill Time, 10 gal. tank

 

Fill Time, 20 gal. tank

 

Fill Time, 40 gal. tank

 

WT-300

 

45 to 90 minutes

 

1.5 to 3 hours

 

3 to 6 hours

 

WT-600

 

23 to 45 minutes

 

45 to 90 minutes

 

1.5 to 3 hours

 

WT-900

 

20 to 30 minutes

 

30 to 60 minutes

 

1 to 2 hours

 

 

The RO will resume operation when the tank pressure drops to approximately 40 psi. 

NOTE:

 The feedwater and storage tank  pressure switches are factory calibrated and should not be altered. If you feel 

pressure switch adjustment is required, consult with your dealer and refer to the instructions for adjustment on 
the inside of the pressure switch cap. 

8.  Check for leaks in the fittings on the tank, the RO the control panel and steamer. Correct leaks as necessary. 

9.  Check the control panel to make sure that it is in the "SteamerGard" position (Fig. 5, Item 4). 

13

 

 


background image

Routine Maintenance 

Routine maintenance is essential for consistent performance and long system life. The required routine maintenance consists 
of changing the sediment and carbon prefilters. Since maintenance frequency will range from 3 to 6 months depending on 
the properties of your feedwater, it's important that you consult with your distributor or the factory for recommended 
maintenance frequency for your system. 

De-pressurization Procedure

 

Prior to changing any prefilters, the feedwater must be shut off and the system must be depressurized. To do this: 

1.   If the steamer is running, switch the steamer to the "Bypass" position at the control panel. 

2.   If the RO is running, turn it off by switching the ON/OFF switch to the OFF (up) position. 

3.   Close the feedwater shut-off valve on the prefilter assembly by turning its handle until it is perpendicular to the 

valve body. 

4.   Open the purge valve at the inlet to the RO system (Fig. 3, Item 26). This will relieve the pressure from prefilter. 

Although the system is de-pressurized, the filter bowls will still be full of water when removed. 

Sediment Prefilter Replacement Procedure

 

1.   De-pressurize the system. 

2.   Locate the sediment prefilter (Fig. 3, Item 3). To remove the sediment prefilter, unscrew the filter bowl to the left 

(counterclockwise as viewed from the bottom), using a filter bowl wrench or by hand. Empty the water and remove 
the filter from the bowl and discard it. 

3.   Inspect the O-ring seals for damage. The O-rings should be replaced if they are damaged or distorted. Clean the 

filter bowls with warm water and soap. Chemically disinfect the filter bowl if desired (household bleach can be 
used, 1/2 teaspoon in a filter bowl of water). 

4.  Insert the new prefilter into the filter

 bowl.

 Screw the filter bowl onto the filter head by hand or use the filter 

wrench. Be careful not to over tighten if you are using the filter wrench. 

 

14

 

 


background image

 

Routine Maintenance Cont'd 

Carbon Filter Replacement Procedure 

1.   De-pressurize

 

the system.

 

2.   Locate the carbon prefilters (Fig. 3, Item 4). To remove the carbon prefilters, unscrew the filter bowls to the left 

(counterclockwise as viewed from the bottom), using a filter bowl wrench or by hand. Remove the filters from the 
bowls and discard them. 

3.   Inspect the O-ring seals for damage. The O-rings should be replaced if they are damaged or distorted. Clean the 

filter bowls with warm water and soap. 

4.   Insert the new carbon prefilters into the filter bowls. Screw the filter bowls onto the filter heads by hand or use the 

filter wrench. Be careful not to over-tighten if you are using the filter wrench. 

Post Treatment Filter Replacement Procedure 

1.   De-pressurize the system.

 

2.   Close the ball valve on the storage tank.

 

3.   Locate the posttreatment filter (Fig. 3, Item 7). Loosen the black plasic nut on the inlet fitting to relieve pressure. 

Use a small container to catch any spillage. Carefully open the housing. Remove the filter from the bowls and 
discard it. 

4.   Inspect the O-ring seals for damage. The O-rings should be replaced if they are damaged or distorted. Insert the 

new posttreatment filter into me filter bowl. Screw the filter bowl onto the filter head by hand or use the filter 
wrench. Be careful not to over-tighten if you are using the filter wrench. 

Final Inspection

 

Check to see that the; 

s

   Prefilter bowl(s) have been tightened. 

s

   RO power switch is in the OFF position. 

s

   Rush valve is open. 

s

   Valves are closed on hydropnuematic storage tanks - left open on atmospheric tanks. 

s

    Point of use is open with hydropnuematic storage - closed with atmospheric storage. 

Restarting and Purging the RO system 

1.   Open the feedwater valve on the prefilter assembly. The drain valve on the final carbon filter should still be open. 

Purge air from the prefilters by allowing water to flow out of the drain valve until you see a steady, air free stream 
of water. Close the drain valve. 

3.   Inspect prefilter bowl(s) for leaks and make adjustments if necessary. 

4.   Turn the power switch to the

 "ON"

 (down) position. 

5.   Open the ball valve on the storage tank if it had been closed. 

6.   Switch the control panel from "Bypass" back to "SteamerGard". 

Your SteamerGard system routine maintenance is now complete. 

15

 

 


background image

 

16