PDF User Manual

  1. Home
  2. Manuals
  3. CleanSweep AREC144FG User Manual

CleanSweep AREC144FG User Manual

Made by: CleanSweep
Type: User Guide
Category: Power distribution unit
Pages: 4
Size: 1.29 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

CleanSweep

®

  

Power Distribution Unit (PDU)  

with EMI Filtering and  

Advanced Transient Surge Protection

 

AREC144FG 

User’s Guide

 

PDU Care 

Normally,  PDU  requires  no  maintenance  and  no  calibration.    It  is  recommended, 
though, to periodically inspect PDU for overheating.

 

During its normal  operation PDU may have elevated temperature which  would feel 

warm

” 

to the touch, but not what is considered 

hot.

”  

If the PDU does feels 

hot

” 

to the touch (more than 70

0

C or 158

0

F), turn off PDU and disconnect equipment that 

is  powered  by  PDU  immediately.    First,  verify  that  the  total  current  load  does  not 
exceed PDU

s maximum rating.  Keep in mind that sometimes stated power rating of 

equipment is 

typical

” 

rather than 

maximum

” 

-

 

it is prudent to load PDU to no more 

than 75% of its capacity to accommodate for such situations. Then, check if the heat 
dissipation of the PDU is obstructed by improper installations such as objects placed 
on its top or lack of space around it for proper ventilation, or its placement in a small 
confined space.  If such problem is identified, correct it, let the PDU cool down and 
turn it back on.  Check within 30 minutes and then within an hour the temperature of 
the  PDU.    If  the  PDU  still  feels 

hot

” 

to  the  touch,  turn  PDU  off,  disconnect  your 

equipment, and discontinue using PDU.  For warranty or other repair contact factory 
or its authorized distributors.

 

Life Critical Applications 

OnFILTER products shall not be used in life

-

critical or mission

-

critical applications.

   

While OnFILTER believes it designs and manufactures very reliable products, many of 
the vendors that OnFILTER sources components from do not recommend or endorse 
the  use  of  their  products  in  life–

 

or  mission

-

critical  applications.  By  extension, 

 

OnFILTER must adhere to the same business policy.  

 

Disclaimer

 

OnFILTER products are not designed, intended, authorized, tested, or listed for use in 
systems intended to support or sustain life, or for any other application in which the 
failure  of  an  OnFILTER  product  could  create  a  situation  where  personal  injury  or 
death  may  occur.  Should  Buyer  purchase  or  use  OnFILTER  products  for  any  such 

 

unintended  or  unauthorized  application,  Buyer  shall  indemnify  and  hold  OnFILTER 
and  its  officers,  employees,  subsidiaries,  affiliates,  agents  and  distributors  harmless 
against all claims, costs, damages and expenses, and  reasonable attorney fees aris-
ing out of, directly or indirectly, any claim or personal injury or death associated with 
such unintended or unauthorized use, even if such claim alleges that OnFILTER was 
negligent regarding the design or manufacture of the part.

 

 

OnFILTER, Inc.

 

730 Mission Dr. Ste. 102 

 

Santa Cruz, CA 95060 U.S.A.

 

Tel. +1.831.824.4052 

FAX +1.206.350.7458 

www.onfilter.com

 

info@onfilter.com

 

 

©

 2017

 On

FI

LTE

R, I

nc

.  Al

l ri

gh

ts res

erved

. C

lean

Swe

ep is

 a

 reg

ist

ere

d t

ra

dem

ark

 o

f On

FI

LTE

R, I

nc

. PU

B03701

 

All specifications are subject to change without notice. Patents Pending. Made in U.S.A. 

8

 

w

w

w

.on

fil

te

r.c

om

 

 


background image

2

 

Thank you for buying CleanSweep

®

 rack

-

mounted PDU (power distribution unit)! 

 

Your  new  CleanSweep

®

  PDU  will  provide  your  sensitive  equipment  with  AC  power 

free  from  electromagnetic  interference  (EMI)  and  power  line  transients.    Such 

 

artifacts  on  power  lines  and  ground  cause  numerous  equipment  malfunctions,  in-
cluding  lock

-

up,  erratic  response,  software  errors,  and  other  often 

unexplained

” 

behavior.    Excessive  transients  and  noise  can  also  cause    damage  to  sensitive 

 

components via induced electrical overstress (EOS).  For more details on this subject 
please visit 

Library

 section on our web site 

www.onfilter.com

.

 

Safety First! 

CleanSweep

®

 PDUs operate with high voltage that, improperly installed or used, may 

cause  property  damage,  injury  and  death.    Always  observe  safety  measures  when 
using  power  line  filters.    Here  are  some  of  the  key  safety  precautions  you  should 
take:

 

WARNING 

 

• 

Do not exceed PDU

s maximum rating 

-

 it may cause overheating 

 

• 

Use PDU after the fuse or circuit breaker of no more than specified max. rating 

 

• 

Use only with the power cord supplied by manufacturer 

 

• 

This PDU is not for household use 

 

• 

PDU must be plugged into a properly wired grounding type outlet 

 

• 

No serviceable parts inside 

-

 do not open.  High voltage is present inside.

 

Introduction 

CleanSweep

®

 EMI PDUs reduce noise on power lines providing clean power to your 

equipment.    High  levels  of  noise  (also  called  conducted 

El

ectro 

M

agnetic 

 

I

nterference 

-

  EMI)  interferes  with  normal  operation  of  electronic  equipment  and 

can cause physical component damage inside the equipment.  Noise on power lines 
is  common  in  industrial  and  office  environment  and  the  only  practical  way  to  deal 
with it  is by using properly

-

designed filter which  is a  part  of CleanSweep® PDU.  In 

addition  to  effectively  suppressing  EMI,  OnFILTER

’ 

CleanSweep

®

  PDU    provides 

 

advanced  transient  surge  protection  by  reducing  power  line  transients  down  to 

 

insignificant levels surpassing conventional surge protection. 

 

Installation  

Proper installation of PDU helps to assure its continuous operation for a long time.  
Please follow these requirements for installation: 

 

• 

Use PDU in a dry location away from debris and from the possibility of spillage, 
including from cleaning 

 

• 

Ambient temperature at the place of installation should not exceed the range of 
5

0

…40

0

C

 

• 

Firmly fasten PDU in a 

19” 

rack using all four screw (supplied)

 

• 

Install filter close to your equipment

 

• 

Do not install PDU in small confined spaces with restricted air circulation in or-
der to avoid overheating.  Allow some space on each side for proper ventilation

 

7

 

w

w

w

.on

fil

te

r.c

om

 

w

w

w

.onf

ilte

r.com

 

Mechanical Specification

 

Material

   

 

 

 

Powder

-

coated aluminum

 

Dimensions

 

 

 

 

See drawing below

 

Mounting

  

 

 

 

19” 

rack, 2

-

Up

 

 

Included

 

AREC144FG PDU

 

 

 

 

1 ea.

 

Power cable NEMA5

-

15 to C13, AWG14

 

1 ea.

 

Mounting screws 10

-

32

 

 

 

4 ea.

 

This User

s Guide

   

 

 

1 ea.

 

 


background image

6

 

3

 

Connections 

 WARNING

 

• 

Before attempting any electrical connection, verify that your power source, such 
as electrical outlet or junction box, is correctly wired and properly grounded. 

 

• 

Do not use PDU without proper grounding!  Failure to properly ground the PDU 
may  result  in  failure  to  ground  your  equipment,  in  unsafe  situation  that  can 
cause property damage and injury, as well as failure of PDU to perform. 

 

• 

Use  only  the  power  cable  supplied  with  the  PDU.    Other  cables  that  may  look 
very similar to the one supplied may not have the same voltage/current ratings.

 

 

To connect PDU follow the steps below:

 

• 

Install  PDU  in  a  rack  and  firmly  fasten  its  front  panel  to  the  rack

s  rails  using 

 

supplied screws

 

• 

Power down and unplug your equipment that will be powered by PDU

 

• 

Connect supplied power cable to the inlet on the back of PDU

 

• 

Plug the PDU

s cable into the power outlet 

 

• 

Turn  power  switch  on  PDU  on 

(“

RESET

” 

position).  The  red  light  in  the  power 

switch should light up indicating that it receives power

 

• 

Plug your equipment into the outlet of PDU and turn it on

 

w

w

w

.on

fil

te

r.c

om

 

w

w

w

.onf

ilte

r.com

 

Specification

 

Below  are  typical  performance  data  for  CleanSweep

®

  PDU  AREC144FG.  For  more 

 

specifics and technical information please visit our 

web site

 www.onfilter.com 

 

Absolute Maximum  Ratings

 

Voltage

   

 

 

250VAC 50/60Hz

 

Current

   

 

 

15A RMS total for all outlets

 

 

 

 

 

It is recommended to use no more than 75% of

 

 

 

 

 

the max. current in order not to trip circuit breaker

 

Ambient temperature

 

 

+5

0

 C to +40

0

 C

 

 

 

 

 

AREC144FG should be used only in indoor non

-

hazardous 

 

 

 

 

 

applications

 

Connectivity

 

Inlet

 

 

 

 

IEC320  C14

 

Outlets 

   

 

 

IEC320  C13 (four outlets)

 

Electrical Parameters

 

Circuit breaker

 

 

 

15A slow action with power indication

 

Leakage current

 

 

 

3.5mA max.

 

EMI Filtering

 

Types

 

 

 

 

Differential mode; common mode; ground

 

Pulse Attenuation (typical or better): 

 

Differential mode 

 

 

24dB 

 

Common mode 

   

 

20dB 

 

Continuous emission

 

 

See graphs of typical performance on page 4

 

 

 

 

 

All performance parameters are measured in 

 

 

 

 

 

1/100 Ohms setup as it closely resembles real

-

life 

 

 

 

 

 

environment. 

 

Transient Surge Suppression

 

Stage 1 (MOV)

 

High peak surge current rating 

 

22kA, single 8/20

μ

s pulse

 

Clamping voltage at 1mA

 

 

430V max.

 

Clamping voltage at 100A

 

 

640V

 

Voltage protection rating

 

 

800V

 

Stage 2 (EMI Filter)

 

Transient voltage spike 

 

 

10V max. (typ.)

 

 


background image

4

 

5

 

Advanced Transient Surge Suppression

 

Power line surge is a sudden high energy disturbance in line voltage typically lasting 
less  than  one  cycle  which  causes  short  high  voltage  increases  (up  to  3kV  or  even 
higher).    This  may  cause  data  corruption,  equipment  malfunction,  equipment 

 

damage and process interruption.

 

CleanSweep®  PDU  AREC144FG  has  two  stages  of  transient  surge  protection.    First 
stage protects your equipment from long

-

lasting surges (typically lasting less than a 

second).    Special  high  energy  absorbing  MOV  (Metal  Oxide  Varistors)  installed 

 

between  Live

-

Neutral,  Live

-

Ground  and  Neutral

-

Ground  absorb  surges  with  peak  

current up to 22kA.  

 

The  second  stage  is  most  important.  While 
conventional 

surge 

protection 

limits 

 

transients by amplitude, this may leave your 
equipment  exposed  to  spikes  up  to  600V.  
CleanSweep®  PDU  utilizes  special  unique 
short  transient  suppressor  circuit  as  a  part 
of its EMI filtering to limit power line transi-
ents to no more than 10V (typ.).   The graph 
on  the  right  shows  how  CleanSweep®  PDU 
suppresses  transient  surge  spike  which 
would  go  unnoticed  by  conventional  surge 
protection.  

 

With these two transient suppression stages 
working together your equipment is well

-

protected

Note that MOV may lose some effectiveness if there are many very strong surges; 
however EMI filter protection (second stage) does not wear out.

 

Multiple Loads and EMI Filtering

 

When using more than one equipment plugged into CleanSweep® PDU output, keep 
in mind that: 

 

• 

Total current consumption shall never exceed maximum current rating, and 

 

• 

There is no filtering or surge protection between the loads at the output 

 

EMI filtering and surge protection are provided only between the inlet on the back of 
PDU 

-

  and  output  connectors  on  the  front  panel.    There  is  no  filtering  or  other 

 

protection between the outlets on the front of the PDU—they are simply connected 
in  parallel.  If  you  have  a  known  piece  of  equipment  which  is 

noisy

” 

it  would  be 

better to power it up separately so that it won

t pollute the rest of equipment. 

 

 
 
 

w

w

w

.on

fil

te

r.c

om

 

w

w

w

.onf

ilte

r.com

 

PDU Operation and Performance 

CleanSweep

®

 PDU provides several functions:

 

• 

Distributes power to four loads

 

• 

Serves as overcurrent protection (circuit breaker)

 

• 

Blocks EMI from AC power lines and ground providing your equipment with clean 

AC power

 

• 

Uses advanced transient surge protection to protect your equipment from harm-

ful power line spikes

 

Overload Protection

 

CleanSweep® PDU AREC144FG is equipped with a built

-

in 15A circuit breaker on its 

front  panel.  It is prudent  to have typical load current  of no more than 75% of the 
circuit breaker

’ 

rating to avoid shutdown during occasional excessive current peaks 

which  may  not  be  specified  in  your  equipment

’ 

specification.  Should  the  current 

through the PDU exceed its maximum rated current, this circuit breaker will trigger 
and disconnect power to PDU and to the equipment plugged into it.  In this case do 
not reset the circuit breaker until you unplug equipment that may contribute to  ex-
cessive current consumption and wait a few minutes to let circuit breaker 

cool off.

” 

Circuit breaker can be reset by simply toggling switch on the front panel into Reset 
(upper) position.

 

The red light in the circuit breaker is 

On

” 

when power is on.  When power is off and 

if circuit breaker cuts off power, the light will be off.

 

EMI Filtering

 

EMI filter incorporated into CleanSweep® PDU AREC144FG provides significant noise 
suppression  in  several  modes—differential  (between  live  and  neutral),  common 
mode  (live  and  neutral  to  ground)  and,  uniquely,  in  ground  line  itself.    Unlike 

 

conventional EMI filters, CleanSweep® PDU offers effective noise suppression for real

-

life  situations  in  real

-

life  use.    For  technical  details  on  this  please  see 

 

OnFILTER Advantage App. Note

 on our 

web site

 www.onfilter.com. 

 

The charts below show typical EMI suppression performance of AREC144FG PDU.

 

Transient surge response of AREC144FG PDU

 

Attenuation of EMI in Frequency Domain

 

Attenuation of EMI in Time Domain