RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Application,  characteristics  and  technical  data 
have to be taken from the hardware data sheet: 

 

560CMD11 R0001 

1KGT 150 764 V0011 

560CMD11 R0011 

1KGT 150 764 V0011 

Operation 

The Communication Unit 560CMD11 is one of the 
CMU  boards  (CMU  =  communication  unit)  of  the 
remote  terminal  unit  RTU560.  The  560CMD11 
controls process events and communications with 
control  centers  and  local  MMI  systems  via  up  to 
four serial Interfaces (CP1, CP2, CPA, CPB), two 
Ethernet  10BaseT/100BaseT  LAN  Interfaces  (E1, 
E2) and an integrated GPRS modem. 

 

Fig. 1:  Block diagram 560CMD11 

To force the IP-Address to a default value at start-
up, the “Def. IP-Addr” switch on the front side (see 
Fig. 

8) 

has 

to 

be 

switched 

“ON”.  

The 560CMD11 starts with the factory settings for 
the  Ethernet  Interface  (see  Fig.  2)  which  are 
192.168.0.1 for the IP-address with the network 

setting  255.255.255.0  for  the  subnet  mask  and 
192.168.0.20 for the gateway. 

Switch

„Def. IP- Address“

position

?

OFF

E

Read IP address

from confi-

guration file

ON

Set Switch

„Def. IP-Address“

to 

„OFF“

Send Configuration

to RTU 192.168.0.1

Switch

„Def. IP- Address“

position

?

OFF

E

Read IP address

from confi-

guration file

ON

Set Switch

„Def. IP-Address“

to 

„OFF“

Send Configuration

to RTU 192.168.0.1

 

        

Fig. 2: Use Switch „Def. IP-Addr“ 

Serial Interface 

The  serial  interfaces  (CP1,  CP2,  CPA  and  CPB) 
are  available  on  the  RJ45  connector  on  the  front 
plate. It can interface RS485 (Tab. 1) or RS232C 
(Tab. 2) signals.  

 

Serial Interfaces RS485 Mode 

Pin 

Signal 

 

 

 

 

 

RJ45

1

8

Rx

Tx

RJ45

1

8

RJ45

1

8

Rx

Tx

 

 Jack 

Not used 

TA 

Data - 

TB 

Data + 

Not used 

GND 

Signal Ground 

Not used 

Table 1: Serial Interfaces RS485 Mode 

 


background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 
 

Serial Interface RS232C Mode 

Pin 

Signal 

Input / Output 

 

 

 

 

RJ45

1

8

Rx

Tx

RJ45

1

8

RJ45

1

8

Rx

Tx

 

 

    Jack 

DCD 

Input 

RxD 

Input 

TxD 

Output 

DTR 

Output 

GND 

RTS 

Output 

CTS 

Input 

 

Shield 

Connected with housing 

Table 2: Serial Interface RS232C Mode 

The interfaces are available on the RJ45 connect-
ors and designed for RS485. The bus is terminat-
ed by a 1 k

Ω resistor for the interfaces. 

CP1 and CP2 Interface 

At  the  CP1  and  CP2  interfaces  connected  to  an 
USART  (universal  synchronous/asynchronous  re-
ceiver/transmitter)  different  UART  based  protocol 
types can be used. 

CPA and CPB Interface 

The settings have to be done by the RTUtil560 
configuration tool.  
At the CPA and CPB interfaces different UART 
character based protocol types can be used. 

560CMD11 R0011 

The  communication  interface  CPB  has  two  differ-
ent functions: 

 

UART character based protocols 

 

GPRS-Modem-Interface 

Both functions are mutually exclusive. 

 

GPRS-Modem (only R0011) 

The  settings  have  to  be  done  by  the  RTUtil560 
configuration tool.  

The  560CMD11  R0011  provides  a  radio  interface 
via  an  integrated  Quad-Band  GSM/GPRS  mo-
dem. For communication via the GSM/GPRS mo-
dem a pluggable SIM-Card is necessary. 

The  SIM-Card  socket  is  placed  below  the  Com-
pactFlash socket. 

The  Quad-Band  modem  is  designed  for  following 
frequencies and GSM nets: 

 

GSM  850MHz  max.  2Watt  transmitting 
power 

 

E-GSM  900MHz  max.  2Watt  transmitting 
power 

 

DCS  1800MHz  max.  1Watt  transmitting 
power 

 

PCS  1900MHz  max.  1Watt  transmitting 
power 

 

At the housing (see Fig. 10) an antenna or anten-
na  cable  can  be  connected  via  a  50

Ω  (high  fre-

quency) SMA-RF-connector type. 

 

Note: 

Operating without a frequency tuned antenna can 
be cause damage on the GPRS modem. 

Following antennas are recommended: 

 

560ANA01 bar (dipole) antenna 
ABB number: 1KGT023600R0001 

 

560ANA02 Wall-mount antenna connect-
ed by a 5mtr long coaxial cable 
ABB number: 1KGT023700R0005 

 

560ANA02 Wall-mount antenna connect-
ed by a 20mtr long coaxial cable       ABB 
number: 1KGT023700R0020 

 

 


background image

RTU560

 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Ethernet Interface E1 and E2 

The  Ethernet  Interfaces  are  available  on  a  RJ45 
connector and supports different functions: 

 

Webserver-diagnostic  with  download  of 
configuration files and firmware 

 

TCP/IP based protocols  

 

Integrated HMI 

The signals are used according to Table 3. 

 

Ethernet Interface 

Pin 

Signal 

Input/Output 

 

 

 

 

 

RJ45

1

8

Lnk

Act

RJ45

1

8

RJ45

1

8

Lnk

Act

 

   Jack 

 

TD + 

Output 

TD - 

Output 

RD + 

Input 

 

Not used 

 

RD - 

Input 

 

Not used 

 

 

Shield 

Connected with hou-

sing 

Table 3: Ethernet Interfaces E1, E2 

IO-Bus 

The connection to the local I/O boards is done by 
a 20 pole female connector. The connection to the 
serial peripheral bus (Wired OR-Bus, (WOR)) is 
done by a 20 pole male connector (see Fig. 6). 
The order of the 23AD62 module includes one 
ribbon cable. The ribbon cable should not exceed 
a length of 50cm (20inch). 

 

     

!!

  

 

 

 

Power Supply DC- In 

The  supply  voltage  for  the  560CMD11  is  24VDC. 
The  connector  consists  of  a  3  pole  pluggable 
screw-terminal  5,08mm  (see  Tab.4  and  Fig.  8  or 
Fig. 11).The max. input power is 67 Watt. 

 

In  some  cases  an  external  potential 
isolation  for  the  DC-Input  is  neces-
sary.  This  can  be  done  e.g.  by  a 
power supply unit 560PSU40/41. 

 

Power Supply DC- Out 

The 560CMD11 provides 24VDC output power for 
max.  0.5A.The  connector  consists  of  a  3  pole 
pluggable screw-terminal 5,08mm (see Tab. 4 and 
Fig.  8  or  Fig.  11).The  output  power  can  only  be 
used for the relay output board (23BO61/62). 

 

!!

 

 

560CMD11 Earthing  

On the strength of safety and EMC protection it is 
important to make a connection as short as possi-
ble  to  a  system  earth  (may  be  DIN-rail  or  mount-
ing  plate).  An  ordinary  1.5mm

2

  multi-core  wire 

(green/yellow)  can  be  used  and  should  not  ex-
ceed a length of 100 cm (39 inch). The first pin of 
the  3  pole  DC-In  connector  is  the  earth-pin  (see 
Tab. 4 and Fig. 8 or Fig. 11). 

 

Power -Supply 

DC-Out 

DC-IN 

Pin 

earth 

earth 

-Vout  

- Vin 

2  

+Vout 

+ Vin 

Table 4: 3 Pole Power Connector 

Attention: It is not allowed to pull 
or to plug the 20 pole ribbon ca-
ble  during  the  operation  pro-
cess

 

It is not allowed to use the output 
power for the process supply! 

!!

 


background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

The  power  supply  terminal 

X38-2

  (-)  is  internal 

connected  with  the  housing  ground  by  terminal 

X43

 (see Fig. 3). 

The  protection  earth must be  connected  to screw 
terminal 

4-1

  (see  Tab.  4)  for  both  560CMD11  re-

visions. In rare cases (e.g. when grounding signal 
zero  to  Vin  (+))  the  jumper  X43  has  to  be  re-
moved,  but  it  is  only  possible  in  Version  R0001. 
Opening  of  the  housing  is  done  in  the  same  way 
as for changing the CF card. 

 

Fig. 3:  Placement of X43 at CMU PCB 

 

Additional information for R0011 

It should be noted, that the module stipulates a 
minus earthing concept conditional on the GPRS 
technologies. In system with other earth concept it 
must be used a galvanic isolated power supply for 
the CMD11 to avoid the destroying (see Fig.4). 
Depending of the system architecture may also be 
required an additional galvanic isolated RS232 
interface (see Fig.5), if the entire system is 
grounded positively. 

Signaling 

The  red  LED  of  the  560CMD11  is  controlled  by 
the RTU560 firmware. For the definition and oper-
ation of the LED “ERR" please refer to the release 
specific  function  description.  The  connector  em-
bedded LEDs “Tx” and “Rx” are directly connected 
to  the  receiver/transmitter  of  the  communication 
line.  The  LEDs  “Act"  and  “Lnk”  are  directly  con-
nected to the Ethernet-controller. 

Tab.  5  describes  the  system  LEDs  of  the 
560CMD11. 

 

LED 

Colour 

Meaning 

ERR 

(1x) red 

Warning / Error 

Tx 

(4x) green 

Grün 

Transmit data  
(CP1, 2, A, B) 

Rx 

(4x) green 

Grün 

Receive data  
(CP1, 2, A, B) 

Act 

(2x) green 

Ethernet Activity E1, E2 

Lnk 

(2x) yellow 

Ethernet Link E1, E2 

IO-Bus 

(1x) green 

Serial Peripheral Bus 

PF 

(1X) red 

One of the output voltage 
is fail 

RUN 

(1x) green 

The CMU is reachable 
via Ethernet 

RUN  

(1x) yellow 

The firmware is running 
but not reachable via 
Ethernet 

RUN 

OFF 

No firmware is running 

Def. IP-

Addr 

(1x) red 

The default IP-address is 
active 

GPRS 

(1x) green 

Transmit data (on air), 
Communication GPRS 
modem 

Table 5: Meaning of LEDs 

 


background image

RTU560

 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Fig. 4: Negative System Earthing 

 

Fig. 5: Positive System Earthing 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power 

supply 

System 

 

560CMD11 

 

GPRS 

Chip 

R

S2
32

 

 

560PSU40/41 

 

RS232 galvanic 

isolated 

power 

supply 

System 

 560CMD11 

 

GPRS 

Chip 

R

S

2

3

2

 

 

560PSU40/41 

 


background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Firmware Version 

The  current  firmware  version  will  be  delivered  on 
a  CompactFlash  memory  card.  A  new  firmware 
file can be loaded via the Web diagnostic tool into 
the removable CompactFlash

 

memory card. 

For changing the CompactFlash

 

memory card the 

right  side  of  the  housing  has  to  be  opened  (see 
Fig. 8 and Fig. 11).  

!!

 

 

1.  Disconnect  the  power-supply  of  the 

560CMD11. 

2.  Take  care  of  ESD  protection  before 

opening the 560CMD11 housing. 

3.  Open the 4 screws on the right side of 

the housing (see Fig. 8 and Fig. 11). 

4.  Pull  or  plug  only  the  CF-card. 

Don’t 

touch other components. 

5.  Close  the  housing  before  the  power- 

supply is connected to the 560CMD11 

 

 
SIM-Card (only R0011) 

For communication  via the GSM/GPRS modem a 
pluggable SIM-Card (ID-000) is necessary. 

For  changing  the  SIM-Card  the  right  side  of  the 
housing has to be opened (see Fig. 11).  

!!

 

 

1.  Disconnect  the  power-supply  of  the 

560CMD11. 

2.  Take  care  of  ESD  protection  before 

opening the 560CMD11 housing. 

3.  Open the 4 screws on the right side of 

the housing (see Fig. 11). 

4.  Pull  or  plug  only  the  SIM-Card. 

Don’t 

touch other components. 

5.  Close  the  housing  before  the  power- 

supply is connected to the 560CMD11 

 

For changing the CF - card 
follow the instructions below

For changing the SIM-Card 
follow the instructions below

 


background image

RTU560

 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Settings 

Hardware settings and operation of the communi-
cation Interfaces of the 560CMD11 are carried out 
with the RTUtil560 configuration tool. For the con-
figuration  procedure  of  the  communication  Inter-
faces  and  the  IO-Bus,  please  refer  to  the 
560RTUtil user guide. 

The  following  parameters  have  to  be  defined  for 
all protocols: 

 

Baudrate: 

 50  to 19 200 baud Mo-

dem control: 

 

Direct link (TxD/RxD only) 

 

WT  link  full  duplex  (560FSM10/11  no 
handshake)  

 

WT  link  half  duplex  (560FSM10/11  with 
RTS / DCD) 

 

Dial  up  (external  modem  without  hand-
shake, without RTS / CTS) 

 

Loop  switch  unit  (RP570/71  Host  Inter-
face only) 

 

Link  with  collision  avoidance  (TxD,  RxD, 
DCD, without handshake (DNP 3.0 only) 

 

The settings of the Ethernet Interface are: 

 

Node name 

 

IP address 

 

Subnet mask 

 

Default gateway 

 

Routing information 

 

The number of the host Interface. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6: 560ANA02 

 

 

For  the  configuration  procedure  of  the  GPRS-
Modem (only R0011),  please refer to the  function 
description part 6. 

The settings of the GPRS-Modem are: 

 

Local IP address 

 

Remote network IP address 

 

PIN number SIM-Card 

 

Username 

 

User password 

 

Provider Connectionstring (APN) 

 

RF sensitivity (only R0011) 

 

Main  parameters  for  the  transmitter 
are:  

  Max. output power: 30dBm ± 5dB  

  Min. output power:  0dBm ±5dB  

 

min.  signal  level  at  input  of  GPRS-
Chip: -108dBm 

 

cable  RG58  with  losses  of  0,546dB/m 

 10,92dB (20m) 

 

antenna with a gain of 2,2dBi 

 

Exemplary calculation: 

min. signal (receive) with 20m cable = 
-109dB + 10,92dB 

– 2,2dBr =  

-99,28dBm 

result:  the  RF  signal  at  the  point  of 
antenna shall be min. -99,28dBm 

 


background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

 
 

Fig. 7: Top side of 560CMD11 R0001 housing 

 

screws 

screws 

Fig. 8: Front and right side of 560CMD11 R0001 housing 

 

Fig. 9: Bottom side of 560CMD11 R0001 housing 

 

 


background image

RTU560

 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

Ethernet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 10: Top side of 560CMD11 R0011 housing 

 

Fig. 11: Front and right side of 560CMD11 R0011 housing 

 

screws 

screws 

Fig. 12: Bottom side of 560CMD11 R0011 housing 

 

 


background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

10 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note: 
We reserve the right to make technical changes or modify the contents 
of this document without prior notice. With regard to purchase orders, 
the agreed particulars shall prevail. ABB AG does not accept any  
responsibility whatsoever for potential errors or possible lack of  
information in this document. 
 
We reserve all rights in this document and in the subject matter and 
illustrations contained therein. Any reproduction, disclosure to third  
parties or utilization of its contents - in whole or in parts 

–is forbidden 

without prior written consent of ABB AG. 
 
Copyright© 2012 ABB 
All rights reserved