Before You Start   

1.1 

 

1.1  Before You Start 

Product Completeness Check 

Please check the contents of your 2N

®

 Helios IP Uni delivery: 

1 2N

®

 Helios IP Uni (selected model) 

1 Torx 10 / Torx 20 double-ended wrench 

1 2N

®

 Helios IP Uni Installation Manual 

1 mounting template 

1 CD 

1 A5 transparent name plate foil 

1 spare name plate 

1 brick flush mounting box 

4 4x12 stainless steel, torx screws for plastics 

2 cable ties 

 

 


background image

Mechanical Installation   

1.2 

 

1.2  Mechanical Installation 

Mountiong Type Overview 

Refer to the table below for a list of mounting types and necessary components. 

Flush mounting – classic bricks  

(also hollow bricks, thermally insulated 
walls, etc.) 

What you need:

  

A properly cut hole 

Plaster, mounting glue, mounting foam or 
mortar as necessary 

 

 

Flush mounting – plasterboard

 

What you need:

  

Just a properly curt hole 

 

Wall mounting 

(concrete and steel 

structures, entry barrier columns, etc.) 

What you need:

  

Wall mounting box   

Part No.

 9153003 

 

 

 


background image

Mechanical Installation   

1.2 

 

Caution 

 

The warranty does not apply to the product defects and failures arisen as 
a  result  of  improper  mounting  (in  contradiction  herewith).  The 
manufacturer is neither liable for damage caused by theft within an area 
that is accessible after the attached electric lock is switched. The product 
is  not  designed  as  a  burglar  protection  device  except  when  used  in 
combination with a standard lock, which has the security function. 

 

When  the  proper  mounting  instructions  are  not  met,  water  might  get  in 
and destroy the electronics. It is because the  intercom circuits are under 
continuous  voltage  and  water  infiltration  causes  an  electro-chemical 
reaction. The manufacturer’s warranty shall be void for products damaged 
in this way! 

Common Mounting Principles 

Tip 

 

Select flush mounting where possible to make your product elegant 
looking, more vandal resistant and more secure. 

Caution 

 

Stainless steel screws are used for the 2N

®

 

Helios IP Uni assembly. Other 

screws than stainless steel ones corrode soon and may aesthetically 
deteriorate the surrounding environment! 

 

Having removed the front panel, make sure that no dirt gets inside the 
product (especially onto the sealing surface).  

 


background image

Mechanical Installation   

1.2 

 

Flush Mounting 

– Classic Bricks 

1.

 

Cut a wall hole using the template enclosed. Make sure 
that all the required cables are available in the hole.  

2.

 

Unpack the plastic mounting box. Break out the cable 
holes as necessary and make sure that the wall hole is 
big enough for the box. 

3.

 

Wall up the mounting box making sure that the box is 
aligned with the wall surface. Wait until the plaster 
(mortar, mounting foam, etc.) sets. 

4.

 

Unscrew the front panel from the door intercom.  

5.

 

Connect the cables to the terminals or RJ connector as 
described in the 

Electric Connection

 subsection. 

6.

 

You can use the cable tie for connection as shown: 

  

 

Suggested cable fixation 

Mounting completion – after electric installation! 

7.

 

Insert the intercom in the mounting box in the wall. 

8.

 

Tighten the intercom with the stainless steel screws included in the delivery. As the 
screw holes are oval, you can perfect the vertical position before tightening. 

9.

 

We do not recommend you to insert the button tags now.  

10.

 

Replace the stainless steel front panel fixing it with the stainless steel screws you 
unscrewed in step 4 above. 

 

 

 


background image

Mechanical Installation   

1.2 

 

Flush Mounting 

– Plasterboard 

Tip 

 

If this is your first plasterboard installation, check the 
function of the intercom side clamps. Loosen and then 
re-tighten the clamp screw to see how it turns 
automatically and starts moving forwards in its slot. 
Remember to return the clamp into the original position 
after the check!  

Caution 

 

Check the plasterboard wall and room interior pressure 
values (caused, e.g., by overpressure ventilation). If the 
difference between the values is too great, separate the 
intercom using, for example, the mounting box enclosed 
and seal the cable passage to avoid loudspeaker 
damage. 

 

1.

 

Cut a hole using the template enclosed (165 x 95 mm).  

2.

 

Unscrew the front panel from the door intercom.  

3.

 

Connect the cables in the hole to the terminals or RJ 
connector as described in the 

Electric Connection

 

subsection

.

 

4.

 

You can use the cable tie for connection as shown on 
previous page. 

Mounting completion – after electric installation!

 

5.

 

Insert the intercom in the hole keeping it in the vertical 
position. 

6.

 

Loosen the four clamp screws one after another and then 
retighten them slowly. They will turn aside automatically and 
start moving forwards in their slots. You need about 

10 

turns

 to tighten the clamps completely. You can perfect the 

vertical position before final tightening of the screws.  

7.

 

We do not recommend you to insert the button tags now.  

8.

 

Replace the stainless steel front panel fixing it with the 
stainless steel screws you unscrewed in step 2. 

 

 

 

Wall Mounting 

Use the wall (surface) mounting box, part No.

 9153003

, and follow the instructions 

enclosed. 

 


background image

Electric Installation   

1.3 

 

1.3  Electric Installation 

This subsection describes how to connect 2N

®

 Helios IP Uni into your Local Area 

Network (LAN) and how to connect supply voltage and the electric lock.  

PCB Connectors 

 

 

 

 

 

 

Description of Connectors  

LAN 

LAN connector  

OUT1 

12V/700 mA switched 
output 

RELAY1  Relay NO/NC contacts 

TAMPER   Tamper switch 

POWER  12V/1A DC power input 

RESET 

RESET button 

 

 

 


background image

Electric Installation   

1.3 

 

LAN Connection 

2N

®

 Helios IP Uni is connected to the LAN via a RJ-45 terminated (connector X11) 

UTP/STP cable (of category Cat 5e or higher). The system is equipped with the Auto-
MDIX function and so both the straight and crossed cable versions can be used 

External Power Supply Connection 

2N

®

 Helios IP Uni can be fed either from an external 12V/1A DC power supply or from 

the LAN equipped with the PoE 802.3af supporting network elements.  

External Power Supply 

An external 12V power supply is connected to terminal block X19. Use a 12V +- 15% 
DC power source dimensioned to current intake of 1A at least (Part No. 91341481E) to 
ensure a reliable function of your device. 

PoE Supply 

2N

®

 Helios IP Uni is compatible with the PoE 802.3af (Class 0 – 12.95W) technology 

and can be supplied directly from the LAN via compatible network elements. If your 
LAN in incompatible, insert the PoE injector, Part No. 91758100E, between 
2N

®

 Helios IP Uni and the nearest network element. 

Electric Lock Connection 

2N

®

 Helios IP Uni is equipped with an electrically isolated relay switch with NO and NC 

contacts (terminal block X17) and 12V/700mA switched output (terminal block X18), 
to which a standard electric lock or another compatible electrical appliance can be 
connected. 

Tamper Switch Connection 

2N

®

 Helios IP Uni is equipped with a tamper switch for detection of unauthorized 

penetration into the device. After correct and complete installation of the device the 
tamper switch is closed. Tamper switch opens immediately when the front panel is 
removed. Tamper switch contacts are available on terminal block X18. 

Device Resetting 

2N

®

 Helios IP Uni is equipped with a RESET button. Push the button for more than 10s 

to reset the factory default values, deleting all the data stored in the device. Push the 
button shortly (< 1s) to restart the device without changing its configuration. 

 


background image

Button Tags 

– Insertion and Replacement   

1.4 

 

1.4  Button Tags 

– Insertion and 

Replacement 

Tag Printing 

1.

 

Every name plate includes a piece of foil, which can be written over manually, 

using a waterproof permanent marker.  

Note 

 

Always  use  waterproof  foil  (enclosed  or  other)  for  the  tags.  Never  use 
paper or ink jet printing to avoid damage due to water leakage! 

Tag Inserting / Replacing 

 

2N

®

 Helios IP Uni provides an intuitive, easy 

access to the name plates. The tags are easy 
to insert and replace even without a manual. 
You need not remove the front panel and 
thus are not exposed to the risk of loss of 
components while replacing the tags. 

1.

 

Loosen the name plate screw using 

the wrench enclosed, for example. 
You can open the name plate window 
like a door without losing the 
tightened screw.  

2.

 

Remove the used or blank name tag 

and insert a new tag. 

3.

 

Close the name plate window and 

tighten the screw appropriately.  

4.

 

Check the click effect of the buttons: 

if the button fails to click properly 
when pressed (when moved by 
approx. 0.5 mm), the tag is too thick 
or thin. Make sure that the button 
clicks when you press it on either 
end. 

 

 
 

 

 

 

 


background image

2N® Helios IP Uni Configuration   

1.5 

 

1.5  2N

®

 Helios IP Uni Configuration 

2N

®

 Helios IP Uni 

Use a PC equipped with any web browser to configure: 

 

Launch your web browser (Internet Explorer, Firefox, etc.). 

 

Enter the IP address of your intercom (

http://192.168.1.100/

, e.g.). 

 

Log in using the 

Admin

 user name and 

2n 

password. 

You have to know the IP address of your device to log in to the integrated web server. 
By default, 2N

®

 Helios IP Uni is switched into the dynamic IP address mode, i.e. it 

obtains the IP address automatically if a properly set DHCP server is available in your 
LAN. If no such DHCP server is available, you can operate 2N

®

 Helios IP Uni in the 

static IP address mode. Refer to the 

2N

® 

Helios IP Configuration Manual 

for 

configuration details.  

If your device remains inaccessible (you have forgotten the IP address, or the LAN 
configuration has changed, for example), change the LAN settings using the buttons 
on the device.  

Static/Dynamic Address Setting Mode Switching 

In case your 2N

®

 Helios IP Uni device is equipped with 1 or 2 buttons, you can switch 

the modes using one button only. 

 

 

Connect 2N

®

 Helios IP Uni

 

to the power supply (or, disconnect and reconnect 

it if already connected). 

 

Wait for the first acoustic signal  . 

 

Press button 1 fifteen times. 

 

The acoustic signal 

 indicates mode switching. 

 

Wait until the device is restarted automatically. 

 

Note: The 15-times-1 sequence must be entered within 30 seconds after the first 
sound signal for security reasons. The inter-digit delay may be 2s at most  

The static IP address mode will be switched into the dynamic IP address mode and 
vice versa upon restart.  

 


background image

Maintenance   

1.6 

 

1.6  Maintenance 

Cleaning 

If used frequently, 2N® Helios IP Uni gets dirty. To clean it, use a piece of soft cloth 
moistened with clean water. We recommend you to obey the following principles while 
cleaning: 

 

Never use aggressive detergents (such as abrasives or strong disinfectants). 

 

Alcohol-based cleaners may be applied. 

 

Clean the device in dry weather in order to make waste water evaporate 

quickly.  

 

Future Tag Replacement, Programming Changes 

For necessary steps refer to the preceding subsections. Keep the following for future 
changes: 

 

This manual 

 

Unused transparent foil strips for button tags 

 

Always use the product for the purpose it was designed and manufactured for, in 
compliance herewith. 

The manufacturer reserves the right to modify the product in order to improve its 
qualities. 

2N®

 Helios

 contains no environmentally harmful components. When the product‘s 

service life is exhausted and you would like to dispose of it please do so in accordance 

with applicable legal regulations. 

 


background image

Technical Parameters   

1.7 

 

1.7  Technical Parameters 

Signalling protocol 

SIP (UDP) 

 

 

 

Buttons 

 

 

Button design 

Transparent, white backlit buttons with easily 
replaceable name tags 

 

Button count 

1 or 2 

 

 

 

Audio

 

 

 

Microphone 

1 integrated microphone 

 

Amplifier 

1W (class D) 

 

Loudspeaker 

1W  

 

Volume control 

Adjustable with automatic adaptive mode 

 

Full duplex 

Yes (AEC) 

 

 

 

Audio stream 

 

 

Protocols 

RTP/RTSP 

 

Codecs 

G.711 

 

 

 

Interfaces 

 

 

Power supply 

12V+-15%/1A DC or PoE 

 

PoE 

PoE 802.3af (Class 0 - 12.95W) 

 

LAN 

10/100BASE-TX s Auto-MDIX, RJ-45 

 

Recommended cabling  Cat-5e or higher 

 

Passive switch 

NO and NC contacts, up to 30V/1A AC/DC 

 

Active switch output 

12V/700mA DC 

 

 

 

Mechanical properties 

 

 

Cover 

ABS plastic, high-quality stainless steel 

 

Working temperature  -40°C to 55°C 

 

Working relative 
humidity 

10% to 95% (non-condensing) 

 

Storing temperature 

-40°C to 70°C 

 

Dimensions 

193 x 115 x 39 mm 
197 x 119 x 47 mm with flush mounting box 
193 x 115 x 57 mm for wall mounting 

 

Weight 

Product net weight....... 500 g 
Mounting box ....... 135 g 
Total weight incl. package ... 800 g 

 

Covering level 

IP54 

 

 


background image

 

 

 

 