PDF User Manual

  1. Home
  2. Manuals
  3. 2GIS 2GIG-SDS1-345 User Manual

2GIS 2GIG-SDS1-345 User Manual

Made by: 2GIS
Type: User Manual
Category: Accessories
Pages: 4
Size: 1.00 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

 

Copyright ©

 

2016 Nortek Security & Control 

1

 2GIG-SDS1-345

SMOKE DETECTOR SENSOR

GENERAL INFORMATION

The 2GIG Smoke Detector Sensor, part number 2GIG-SDS1-345, is a 110V AC 
powered sensor. It monitors the interconnect line on interconnected hardwired 
smoke detector systems and sends out a transmission when smoke is detected 
at any of the smoke alarm units connected on the same circuit. The device has 

LEDs to visually indicate the status of the sensor. A single CR2032 ba  ery provides 
backup power in the event that AC power is lost on the smoke detector system 
circuit. The smoke detector sensor communicates with a compa  ble 2GIG control 

panel and can send alarm, low ba  ery, AC power loss, and supervisory messages 
to the system's receiver.

Contents of Carton:

• 1-Smoke Detector Sensor
• 2-2" long 10-32 Screws
• 1-CR 2032 3 Volt Coin Ba  ery

Figure 1. 

2GIG-SDS1 Kit

IMPORTANT: 

This device must be tested and maintained regularly. This device 

is intended for use with compa  ble smoke detectors, but will not detect the 

presence of smoke, heat, or 

fi

 re directly.

 

Note: 

Each of the smoke alarms part of interconnected smoke alarms must be:

• Present in every required loca  on per NFPA 72,11.5.1
• Con

fi

 rmed as less than ten years from date of installa  on (or manufacture). 

Please check label on the device or original smoke detector device manual.

• Hardwired to a single, common 120V AC circuit designated for interconnected 

smoke alarms.

• Pass the manufacturer's stated tes  ng regimen to con

fi

 rm proper interconnect 

opera  on.

• Have fresh back-up ba  eries.
• On the list of compa  ble models (any model not listed may work but has not 

been compa  bility tested.

• This device shall not be installed in loca  ons where the normal ambient 

temperature is below 40F(4.4C) or exceeds 100F (37.8C), unless the alarm has 
been determined capable of being used at installa  on points with higher or 
lower ambient temperatures.

• Please see sec  on at the end regarding informa  on on the proper installa  on 

of smoke detectors that are intended to work with the Smoke Detector Sensor.

• This device is not intended to work with smoke alarms paired with smoke alarm 

guards, unless the combina  on has been evaluated and found suitable for this 
purpose.

Compatible Smoke Alarm Models

• BRK Brands Model 7010B: AC Powered Photoelectric Smoke Alarm with Ba  ery Backup
• Firex Kidde Model i4618: Hardwire Ioniza  on Smoke Detector with Ba  ery Backup
• First Alert BRK Model 9120B: Hardwired Smoke Alarm with Ba  ery Backup
• Kidde Model i12040: 120V AC Wire-in Smoke Alarm with Ba  ery Backup
• USI Electric Model 5304: Hardwired Ioniza  on Smoke and Fire Alarm with 

Ba  ery Backup

CAUTION: 

Before a  emp  ng  installa  on, locate the primary electrical circuit 

that powers the interconnected hardwired smoke detector system and shut o

  

or disconnect power to this circuit. An electrical shock hazard is present if this 
electrical circuit is not temporarily disabled during installa  on.

WARNING: 

Remember to turn on or reconnect power to the primary electrical 

circuit that powers the interconnected hardwired smoke detector system. The 

fi

 re 

warning system may be disabled if electrical power is not restored to the system

Install Sensor

Select a smoke detector that will be used to provide power and communicate to 
the smoke detector sensor. Any smoke detector that is within range of a wireless 
2GIG receiver can be selected if the smoke detector is part of an interconnected 

hardwired system.
Remove the exis  ng smoke detector from the exis  ng moun  ng bracket. This is 
usually done by twis  ng the detector counter clockwise or clockwise from where 

it is mounted.

Figure 2. 

Remove Exis  ng Smoke Detector from Smoke Detector Moun  ng Bracket

Figure 3. 

Unplug Pigtail of Exis  ng Smoke Detector

Unplug the exis  ng smoke detector from the smoke detector pigtail. Loosen the 
two screws used to hold the exis  ng moun  ng bracket and remove it from the 
wall or ceiling.

Figure 4. 

Remove Exis  ng Smoke Detector Moun  ng Bracket from Wall or Ceiling

PRINTER’S INSTRUCTIONS:

INSTR,INSTL,2GIG-SDS1-345 - P/N: 10010592 X8- INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 8.500” X 11.000” - TOL. +/- 0.020”- SCALE: 1-1 - PAGE 1 OF 2- FOLDING: FOLD 1X TO FINAL SIZE: 8.500" X 5.500"- FINISH WITH LOGO SHOWING

+

CR2032

3V

SMOKE DETECTOR
SENSOR

WIRETAPS

CR2032
COIN BATTERY

10-32 X 2” 
SCREWS

SMOKE

EXISTING 
SMOKE
DETECTOR
MOUNTING 
BASE 

EXISTING 
SMOKE
DETECTOR

ROTATE
COUNTER
CLOCKWISE
TO REMOVE

EXISTING SMOKE
DETECTOR

EXISTING SMOKE DETECTOR
MOUNTING BRACKET

UNPLUG
SMOKE DETECTOR
FROM EXISTING 
POWER PIGTAIL

REMOVE

 EXISTING SMOKE

DETECTOR MOUNTING 
BRACKET FROM WALL OR
CEILING

EXISTING
SMOKE
DETECTOR
POWER
PIGTAIL

ACCESS HOLE
IN WALL OR 
CEILING

REMOVE
EXISTING
SCREWS

 


background image

2 Copyright

 

© 2016 Nortek Security & Contro

l

Figure 5. 

Install Smoke Detector Sensor between Wall and Moun  ng Bracket

Place the smoke detector sensor where the exis  ng  moun  ng bracket was 
located. Make sure the wire/wiretaps are inserted through the center opening of 
the smoke detector moun  ng bracket.

Place the exis  ng smoke detector moun  ng bracket on top of smoke detector 
sensor.  Align the smoke detector sensor and the smoke detector moun  ng 
bracket and replace the two screws used to hold the bracket in place. Tighten all 
screws down.

 

NOTE: 

It is suggested that the smoke detector sensor LEDs be oriented towards 

the bo  om or in a manner that allows the LEDs on the unit to be visible.

Figure 6. 

Wiretaps/Wires, & Pigtail through Center 

Figure 7. 

Crimping Wiretaps onto Wires 

Figure 8. 

Wiretap Connec  ons 

Wiring the Connections

Before connec  ng the wires from the smoke detector sensor, iden  fy the (+) line 
(hot) 120VAC wire and the neutral wire. Usually the (+) line (hot) 120VAC wire 
will be 

black

 and the 

neutral

 wire white. Use a voltmeter or voltage sensor to 

verify that the proper wires are selected. You may need to reconnect power to the 
electrical circuit powering the interconnected hardwired smoke detectors in order 
to do this (Figure 8).

WARNING: 

Remember to disconnect or shut o

  electrical power to the 

interconnected hardwired smoke detector if it was powered on in the previous 
step to iden  fy the  120VAC wires.
Use an electrician’s linesman plier or equivalent tool (See Figure 8) and using the 

installed wiretaps on the device, crimp the wiretap with the black wire onto the  
120VAC line (hot) wire.

 

NOTE: 

Wiretaps must be used on a sec  on of stranded wire. This is typically 

located between the connector to the smoke detector and the wire nut.

The wiretap with the yellow wire should be a  ached to the wire lead connected 
to the interconnect wire of the smoke detector. This wire is typically yellow or 
orange.

Once all  (3) three wiretaps have been installed (Figure 8), rea  ach the electrical 
wire pigtail to the back of the smoke detector unit and mount the smoke detector 
on the moun  ng base (Refer to Figure 3).

Installing the Back-Up Battery

Figure 9. 

Installing Back-up Ba  ery

WARNING: 

Ensure that the smoke detector sensor has been wired correctly. 

Damage to the smoke detector sensor may occur if the  120 VAC line (hot) wire 

neutral wire are reversed. The unit may fail to func  on properly if incorrectly 
wired.

Turn on or reconnect power to the primary electrical circuit that powers the 
interconnected hardwired smoke detector system. The device should now power 
on.
Use a 

fl

 at bladed tool, slide out the ba  ery tray that holds the backup ba  ery. 

Insert a CR2032A ba  ery (included) into the ba  ery slot. Slide the ba  ery tray 

back into the device (Figure 9). 

 

NOTE: 

Orient the (+) ba  ery terminal up so that it is visible when facing the unit.

Programming the Sensor

Follow the instruc  ons on how to program a sensor into a compa  ble 2GIG control 
panel. See the 2GIG control panel’s Installa  on & Programming Guide for more 
informa  on on how to learn a sensor into the control panel.

The device should learn in as a Loop 1 sensor device. Use a small paper clip or other 
sharp object and carefully insert into the learn/test bu  on hole. This will send 

out an alarm transmission ID so the the sensor can be learned into a compa  ble 
control panel or can be used to test that the transmi  er is working properly.

Replacing the Battery

If the compa  ble control panel shows that this sensor has a low ba  ery, the 

backup ba  ery may need to be replaced.
Use a 

fl

 at headed screw driver or other tool to slide the ba  ery tray out of the 

device. Remove the ba  ery from the tray and replace with a new CR2032A 
ba  ery. Slide the ba  ery tray back into the unit, making sure that the tray is fully 
inserted into the unit.

 

NOTE: 

Use Panasonic CR2032A ba  eries or equivalent. Use of another ba  ery 

may damage or nega  vely a

 ect the opera  on of the device.

End-of-Life

The Smoke Detector Sensor does not have an End-of-Life (EOL), however the 

smoke detector(s) that this device monitors may have an EOL condi  on. Follow 
the owner's manual for the smoke detector regarding instruc  ons on proper 
smoke detector EOL condi  ons.

SMOKE 
DETECTOR 
SENSOR

EXISTING 
SMOKE 
DETECTOR 
MOUNTING
BRACKET

EXISTING 
POWER
PIGTAIL

WIRETAPS (3)
(NOT CONNECTED)

MOUNT BRACKET
WITH LED’S AT BOTTOM

EXISTING 
POWER
 PIGTAIL

WIRETAPS (3)
CRIMPED 
TO PRIMARY
CIRCUIT WIRES

WIRING CODE:

• BLACK TO BLACK

 (120 VAC)

• WHITE TO WHITE

 (NEUTRAL)

• YELLOW TO YELLOW

 OR

  ORANGE

 (INTERCONNECT)

PRIMARY POWER
WIRING

WHT/WHT (NEUTRAL)

BLK/BLK (110VAC)

YEL/YEL OR
YEL/ORANGE

+

CR2032

3V

First Alert

First Alert

SMOKE AND CARBON

MONOXIDE ALARM

CO

MOVE TO

FRESH AIR

SMOKE

+

CR2032

3V

STEP 1

PULL OUT
BATTERY TRAY
WITH FLATHEAD
SCREWDRIVER

STEP 2

INSERT 
BATTERY 

+ POLARITY

FACING UP

SMOKE DETECTOR 
SENSOR

SMOKE DETECTOR 

1. PLACE WIRE 
INTO
WIRETAP.

2. HINGE WIRETAP
UP AND OVER 
WIRE STRAND

3. CRIMP
WIRETAP WITH
PLIERS

SMOKE 
DETECTOR
SENSOR

EXISTING SMOKE DETECTOR
MOUNTING BRACKET

EXISTING
POWER
PIGTAIL

WALL ACCESS HOLE

WIRETAPS (3)
(NOT CONNECTED)

 


background image

 

Copyright ©

 

2016 Nortek Security & Control 

3

LED Status

Status

LEDs

Radio Signaling

2GIG 

Control Panel 

Display

PowerOn

Sequential green, orange, 
red fl ashes

N/A

N/A

Normal

Green LED fl ash every 48s

N/A

N/A

Alarm

Red fl ash every 1s

Alarm (Loop 1)

On screen and 
audible alarm (Use 
code to silence)

Loss of AC Power 
Fault

Orange fl ash every 20s

Tamper

On screen alert 
shown "Device 
name- Battery Low" 
or "AC Loss"

Low Battery Fault

Orange fl ash every 4s

Low Battery

On Screen alert 
shown "Device 
name- Battery Low

Learn Button

Sequential green, orange, 
red fl ashes

Alarm (Loop1)

On screen and 
audible alarm (use 
code to silence)

Testing the Smoke Detector System

Figure 10. Loca  on of LEDs and Learn/Test Bu  on Hole

The device should be tested in accordance with NFPA 72 guidelines. The following
instruc  ons are intended to provide a general guideline on how to test the smoke 
detector system, smoke detector sensor, and communica  ons to an alarm panel.

Follow the smoke alarm instruc  on manual on tes  ng the smoke alarm and any 

interconnected units. There usually is a test bu   on on the smoke detector that can 
be pressed to ini  ate a test mode. This should cause the sounder to alarm and also 

any smoke detectors that are interconnected to also alarm.
The smoke detector sensor should send out a transmission to a compa  ble alarm 

panel. 
If this transmission is not received, 

fi

 rst check if the Smoke Detector Sensor is 

properly programmed into a compa  ble alarm panel. Please follow the alarm 
panel instruc  ons on learning in a sensor.
Also, check that the interconnect wire on the smoke detector is properly connected 

to the Smoke Detector Sensor. The LEDs on the Smoke Detector Sensor should 

fl

 ash red indica  ng that it has received the alarm signal from the smoke detector.

Testing the Smoke Detector Sensor Radio Transmission Only

The Smoke Detector Sensor incorporates a small test bu  on. This test bu  on can 
be ac  vated by inser  ng a straightened paper clip or sharp object into the Learn/

Test hole. The Smoke Detector Sensor will then send an alarm signal transmission 
to a compa  ble alarm panel. This can be used to test that the Smoke Detector 

Sensor will send a proper transmission to an alarm panel. This DOES NOT test if 
the wiring between the smoke detector and the smoke detector sensor is correct.

Troubleshooting Installation Chart

When tes  ng the installa  on of a smoke detector sensor, check for these common 

issues.

Condi

Ɵ

 on

Smoke Detector

Result

Resolution

Smoke Detector 
Sensor LED

Alarm Panel

Smoke detector is in 
alarm mode

LED on smoke 
detector sensor do not 
work properly

Alarm panel does not 
receive alarm signals

Check to make sure 
interconnect wire from 
the smoke detector is 
properly connected 
to the smoke detector 
sensor.

Smoke detector is in 
alarm mode

LED on smoke 
detector sensor works 
properly

Alarm panel does not 
receive alarm signals

Check to make 
sure the smoke 
detector sensor is 
properly learned or 
programmed into a 
compatible alarm 
panel

Specifi cations

Input Power

120VAC 50/60Hz 12W

Backup Power

3-Volt CR2032 Battery or Equivalent

Backup Battery Life

>8 years

Operating Temperature

32°F to 122°F (0°C to 50°C)

Operating Humidity

5–95% RH non-condensing

Compatibility

2GIG receivers

Wireless Signal Range

350ft (110m)

Supervisory Interval

70 minutes

Certifi cation

FCC/IC and ETL

Selecting a Location

Selec  ng a suitable loca  on  is  cri  cal to the opera  on of smoke alarms. This 
equipment should be installed in accordance with Na  onal Fire Protec  on 
Associa  on’s (NFPA) Standard 72 (see Figure 11).

A-11-8.3a  Where to Locate the Required Smoke Alarms in 
Existing Construction.

The major threat from 

fi

 re in a family living unit occurs at night when everyone is 

asleep. The principal threat to persons in sleeping areas comes from 

fi

 res in the 

remainder of the unit. Therefore, a smoke alarm(s) is best located between the 
bedroom areas and the rest of the unit. In units with only one bedroom area on 

one 

fl

 oor, the smoke alarm(s) should be located as shown in Figure 11A.

In family living units with more than one bedroom area or with more than one 

fl

 oor, more than one smoke alarm is required, as shown in Figure 11C.

In addi  on to smoke alarms outside of the sleeping areas, the installa  on of a 

smoke alarm on each addi  onal story of the family living unit, including the 
basement, is required. These installa  ons are shown in Figure 11B. The living area 
smoke alarm should be installed in the living room or near the stairway to the 

upper level, or in both loca  ons. The basement smoke alarm should be installed 
in close proximity to the stairway leading to the 

fl

 oor above. Where installed on 

an open-joisted ceiling, the alarm should be placed on the bo  om of the joists. 
The alarm should be posi  oned rela  ve to the stairway to intercept smoke coming 

from a 

fi

 re in the basement before smoke enters the stairway (Figure 11D).

Figure 11. 

Smoke Alarm Placement

Where to Locate the Required Smoke Alarms in New Construction.

All of the smoke alarms speci

fi

 ed for exis  ng construc  on are required and, in 

addi  on, a smoke alarm is required in each bedroom.

Are More Smoke Alarms Desirable?

The required number of smoke alarms might not provide reliable early warning 
protection for those areas separated by a door from the areas protected by the 
required smoke alarms. For this reason, it is recommended that the householder 
consider the use of additional smoke alarms for those areas for increased protection. 
The additional areas include the basement, bedrooms, dining room, furnace 
room, utility room, and hallways not protected by the required smoke alarms. The 
installation of smoke alarms in kitchens, attics (fi nished or unfi nished), or garages is 
not normally recommended, as these locations occasionally experience conditions 
that can result in improper operation.
Since regulations pertaining to smoke alarm/detector installation vary from state 
to state, contact the authority having jurisdiction (AHJ). Where public safety is 
primary, the AHJ may be federal, state, local, or other regional department or 
individual such as a fi re chief, fi re marshal, chief of a fi re prevention bureau, 

LEDS ON SMOKE
DETECTOR SENSOR

LEARN/TEST BUTTON
HOLE

First Alert

A smoke alarm should be located 

between the sleeping area and 

the rest of the family living unit.

BEDROOM

BEDROOM

BEDROOM

TV

ROOM

DINING

KITCHEN

SMOKE

ALARMS LIVING

ROOM

In family living units with more 

than one (1) sleeping area, a 

smoke alarm should be provid-

ed to protect each sleeping 

area.

Indicates a required 

smoke alarm

Indicates an optional 

smoke alarm if door 

is not provided be-

tween living and rec-

reation rooms
Indicates addition-

al smoke alarms 

required for new 

construction

BED

ROOM

BED

ROOM

LIVING 
ROOM

HALL

BASEMENT

DINING

ROOM

A smoke alarm 

should be located 

on each story.

DINING

KITCHEN

BEDROOM

BEDROOM

BEDROOM

LIVING 
ROOM

SMOKE
ALARM

IMPORTANT

: Regulations pertaining to smoke alarm installations vary. For 

more information, contact your local fire department or local authority having 
jurisdiction.

LIVING

ROOM

BASEMENT

BED

ROOM

HALL

BED

ROOM

RECREATION ROOM

A

B

C

D

In split-level configu-

rations, smoke 

alarms are optional 

where a door is not 

provided between a 

living and recreation 

room.

 


background image

4 Copyright

 

© 2016 Nortek Security & Contro

l

labor or health department, building offi cial, electrical inspector, or others having 
statutory authority. For insurance purposes, an insurance inspection department, 
rating bureau, or other insurance company representative may be the AHJ. In 
some cases, the property owner or their designated agent assumes the role of the 
AHJ. At government installations, the commanding offi cer or department offi cial 
may be the AHJ.
In addition to NFPA 72, use the following location guidelines to optimize 
performance and reduce the chance of false alarms from the alarm:

•  Locate ceiling-mounted smoke alarms in the center of a room or hallway at 

least 4 inches (10cm) from any walls or partitions.

•  Locate wall-mounted smoke alarms so the top of the alarm is 4 to 12 inches 

(10 to 31cm) below the ceiling.

•  Locate in a suitable environment as follows:

•  Temperature between 40°F (4.4°C) and 100°F (37.8°C)
•  Humidity between 0 and 95% non-condensing

•  Locate away from air conditioners, heating registers, and any other ventilation 

source that may interfere with smoke entering the alarm.

•  Mount smoke alarms on a fi rm permanent surface.
•  Locate away from large metallic objects to reduce shielding of the wireless 

transmitter’s signal.

Smoke alarms are not to be used with detector guards unless the 
combination has been evaluated and found suitable for that purpose.

WARNING! LIMITATIONS OF SMOKE ALARMS

Wireless smoke alarms are very reliable, but may not work under all conditions. 
No fi re alarm provides total protection of life or property. Smoke alarms are not a 
substitute for life insurance.

Smoke alarms require a source of power to work. 

This smoke alarm will not 

operate and the alarm will not sound if batteries are dead or not installed properly. 

Smoke alarms may not be heard.

  A sound sleeper or someone who has taken 

drugs or alcohol may not awaken if the alarm is installed outside a bedroom. 
Closed or partially closed doors and distance can block sound. This alarm is not 
designed for the hearing impaired.

Smoke alarms may not always activate and provide warning early enough.

 

Smoke alarms only activate when enough smoke reaches the alarm. If a fi re starts 
in a chimney, wall, roof, on the other side of closed doors, or on a different level of 
the property, enough smoke may not reach the alarm for it to be activated.
Smoke alarms are a signifi cant help in reducing loss, injury and even death. 
However, no matter how good a detection device is, nothing works perfectly under 
every circumstance and we must warn you that you cannot expect a smoke alarm 
to ensure that you will never suffer any damage or injury. 
Current studies have shown smoke alarms may not awaken all sleeping individuals. 
It is the responsibility of individuals in the household that are capable of assisting 
others to provide assistance to those who may not be awakened by the alarm 
sound, or to those who may be incapable of safely evacuating the area unassisted.

FIRE PREVENTION AND ESCAPE

The purpose of an early warning smoke alarm is to detect the presence of fi re in 
its early stages and sound an alarm giving the occupants time to exit the premises 
safely.

AVOID FIRE HAZARDS

No detec  on device can protect life in all situa  ons. Therefore, safeguards should 
be taken to avoid poten  ally dangerous situa  ons as follows:

•  Do not smoke in bed.
•  Do not leave children home alone.
•  Never clean with fl ammable liquids such as gasoline.
•  Properly store materials. Use general good housekeeping techniques to 

keep your home neat and tidy.  A cluttered basement, attic, or other storage 
area is an open invitation to fi re.

•  Use combustible materials and electrical appliances carefully and only for 

their intended uses. Do not overload electrical outlets.

•  Do not store explosive and/or fast burning materials in your home.
•  Even after proper precautions have been taken, fi res can start. Be prepared.

IN CASE OF FIRE

In the event of a 

fi

 re:

•  Leave immediately. Don’t stop to pack or search for valuables. 
•  In heavy smoke, hold your breath and stay low, crawl if necessary. The 

clearest air is usually near the fl oor.  

•  If you have to go through a closed door, carefully feel the door and door knob 

to see if undue heat is present. If they seem cool, brace your foot against the 
bottom of the door with your hip against the door and one hand against the 
top edge. Open it slightly. If a rush of hot air is felt, slam the door quickly and 
latch it. Unvented fi re tends to build up considerable pressure. Be sure all 
members of the household realize and understand this danger.

•  Use your neighbor’s phone or a street fi re alarm box to call the fi re department. 

The job of extinguishing the fi re should be left to the professionals.

BE PREPARED

Prac  ce the following steps to prepare you and your family in the event of a 

fi

 re:

•  Perform fi re drills regularly. Use them to assure recognition of an alarm 

signal. 

•  Draw a fl oor plan and show two exits from each room. It is important that 

children be instructed carefully, because they tend to hide in times of crisis.

•  Establish one meeting place outside the home. Insist that everyone meet 

there during an alarm. This will eliminate the tragedy of someone reentering 
the house for a missing member who is actually safe.

•  If you have children and/or physically challenged people residing in your 

household, use window decals to help emergency personnel identify the 
sleeping quarters of these individuals.

FCC COMPLIANCE STATEMENT

This device complies with Part 15 of the FCC Rules and Industry Canada license exempt standard(s). 

Opera  on is subject to the following two condi  ons:

(1) This device may not cause harmful interference, and

(2) This device must accept any interference received, including interference received that may 

cause undesired opera  on.

Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio 

exempts de licence. L’exploita  on est autorisée aux deux condi  ons suivantes:

(1) l’appareil ne doit pas produire de brouillage, et

(2) l’u  lisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le 

brouillage est suscep  ble d’en comprome  re le fonc  onnement.

This equipment has been tested and found to comply with the limits for a Class B digital device, 

pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protec  on 

against harmful interference in a residen  al installa  on.

This Class B digital apparatus complies with Canadian ICES-003

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

This equipment generates, uses, and can radiate radio frequency energy and, if not installed and 

used in accordance with the instruc   ons may cause harmful interference to radio communica  ons. 

However, there is no guarantee that interference will not occur in a par  cular  installa  on.  If 

this equipment does cause harmful interference to radio or television recep  on, which can be 

determined by turning the equipment o

  and on, the user is encouraged to try to correct the 

interference by one or more of the following measures:

• Reorient or relocate the receiving antenna.

• Increase the separa  on between the equipment and receiver

• Connect the equipment into an outlet on a circuit di

 erent from that to which the receiver is 

connected

• Consult the dealer or an experienced radio/TV technician to help.

WARNING: Changes or modi

fi

 ca  ons not expressly approved by the manufacturer could void the 

user’s authority to operate the equipment.

LIMITED WARRANTY

This Nortek Security & Control LLC product is warranted against defects in material and 

workmanship for two (2) years. This warranty extends only to wholesale customers who buy direct 

from Nortek Security & Control LLC or through Nortek Security & Control normal distribu  on 

channels. Nortek Security & Control does not warrant this product to consumers. Consumers 

should inquire from their selling dealer as to the nature of the dealer’s warranty, if any.

There are no obliga  ons or liabili  es on the part of Nortek Security & Control for consequen  al 

damages arising out of or in connec  on with use or performance of this product or other indirect 

damages with respect to loss of property, revenue, or pro

fi

 t, or cost of removal, installa  on, or 

reinstalla  on. All implied warran  es for func  onality, are valid only un  l the warranty expires. This 

Nortek Security &Control Warranty is in lieu of all other warran  es express or implied.

Nortek Security & Control LLC

2GIG

1950 Camino Vida Roble, Suite 150 
Carlsbad, CA 92008-6517 USA

For technical support in the USA and Canada:

855-2GIG-TECH (855-244-4832)
Email: 2gigtechsupport@nortek.com

Visit www.nortekcontrol.com for technical support hours of opera  on

For technical support outside of the USA and Canada:

Contact your regional distributor

Visit dealer.2gig.com for a list of distributors in your region 

10010592X8