PDF User Manual

  1. Home
  2. Manuals
  3. Prolon PL-RS Quick Start Manual

Prolon PL-RS Quick Start Manual

PL-T500\ PL-T200\ PL-T1000\ PL-VC2000\ PL-C1000-VAV

Made by: Prolon
Type: Quick Start Guide
Category: Control Systems
Pages: 10
Size: 0.94 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

QUICK START 

GUIDE

VAV CONTROLLERS & WALL SENSORS

www.proloncontrols.com  |   info@proloncontrols.com

17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9

REV 1.0

PL-QCK-WSENSOR/VC2000-EN


background image

© Copyright 2018 Prolon. All rights reserved.

No part of this document may be photocopied or reproduced by any means, or translated to 

another language without prior written consent of Prolon. All specifications are nominal and 

may change as design improvements are introduced. Prolon shall not be liable for damages 

resulting from misapplication or misuse of its products. All trademarks are the property of their 

respective owners.

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

3

Analog Sensor 

(PL-RS)

 .................................................................................................4

  Dimensions and Wiring .....................................................................................4
Digital Sensor 

(PL-T200)

 ...............................................................................................6

  Dimensions and Wiring .....................................................................................6
Digital Sensor 

(PL-T500)

 ...............................................................................................8 

  Dimensions and Wiring .....................................................................................8
Digital Sensor 

(PL-T1000)

 ........................................................................................... 10 

  Installation .......................................................................................................... 10
  Auxiliary Analog Input .................................................................................... 12
  Operation ............................................................................................................ 12
  Changing the Setpoint ................................................................................... 13
  Schedule Override ........................................................................................... 13
VAV Zone Controller 

(PL-C1000-VAV)

 ....................................................................... 14

VAV Zone Controller 

(PL-VC2000)

 ............................................................................ 16

Compliance............................................................................................................... 18
Technical Specifications ....................................................................................... 18

Table of Contents


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

4

Analog Sensor 

(PL-RS)

COM
THERM
COM
POT

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Schedule override

Room temperature

Setpoint (10K)

Dimensions and Wiring

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

5

COM
THERM
COM
POT

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Schedule override

Room temperature

Setpoint (10K)

Temperature table (thermistor: 10K Type 3)

Fahrenheit

41

50

59

68

77

86

95

104

Celsius

5

10

15

20

25

30

35

40

Ohms

25395

19903

15714

12493

10000

8056

6530

5324


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

6

Digital Sensor 

(PL-T200)

Dimensions and Wiring

INT A (+)
INT B (-)
24VAC
COM

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Schedule override

(hold for 3 second)

Communication (RS485)

Power (2 VA max)

RJ45 connection

(to C1000)

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

7

INT A (+)
INT B (-)
24VAC
COM

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Schedule override

(hold for 3 second)

Communication (RS485)

Power (2 VA max)

RJ45 connection

(to C1000)


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

8

Digital Sensor 

(PL-T500)

Dimensions and Wiring

INT A (+)
INT B (-)
24VAC
COM

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Communication (RS485)

Power (2 VA max)

RJ45 connection

(to C1000)

Schedule override:

Hold 3 seconds

Change unit °F/°C:

Double-click

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

9

INT A (+)
INT B (-)
24VAC
COM

4.96”

(126 mm)

1.30”

(33 mm)

3.23”

(82 mm)

Communication (RS485)

Power (2 VA max)

RJ45 connection

(to C1000)

Schedule override:

Hold 3 seconds

Change unit °F/°C:

Double-click


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

10

Digital Sensor 

(PL-T1000)

Installation
  1. Open casing to remove back cover by pushing on the tab located 

  underneath the thermostat. (See Figure 1)
  2. Pull wire(s) throught central hole of back cover.
  3. Screw in the back cover to the wall.
  4. Connect wires:
  • If using twisted pair wires:

    

- Pull out screw terminal block.

    

- Remove 1 cm insulation from each wire.

    

- Connect the wires to the terminal blocks and reconnect

    

   the terminal blocks. (See Figure 2)

   If using CAT5 cable:

    

- Plug the cable into the RJ45 jack of the T1000 (if CAT5 cable 

    

  is opened at the controller, refer to Figure 3 for pinout of the 

    

  T1000’s RJ45 jack).

  5. Reconnect top cover.

IMPORTANT! Do not install the thermostat under the following

conditions:
    Any location exposed to direct sunlight.
    On an outside wall.
    Near an air dischatge grill.
    In a location where vertical sir circulation is retricted.
    Near a dimmer switch.

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

11

Figure 1

Figure 2

Figure 3

INT A 

INT B

24 VAC

COM

24V

RJ45 (Female)


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

12

Digital Sensor 

(PL-T1000)

Auxiliary Analog Input
The T1000 has auxiliary analog input which can be used to connect 

another thermistor. The T1000 can be configured to use this alternate 

temperature reading for a variety of functions, including temperature 

averaging or radiant floor slab temperature. The alternate thermistor 

(10KΩ type 3) can be connected to the auxiliary input using the “AUX 

IN“ and “COM“ pins. (See figure below)

Analog Input

Operation
The T1000 is controlled using the circular touch pad on the bottom half 

of the thermostat. The touch pad uses capacitive sensing technology 

to detect finger proximity. There are no moving parts to push or rotate. 

The T1000 is controlled using simple scrolling, tapping or holding

motions, performed around the circle of the touch pad. The center of 

the circle is unused.

Scroll clockwise or

counterclockwise

to adjust or navigate

Tap here to

ENTER

Tap here to

go BACK

5

6

7

8

9

10

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

13

Changing the Setpoint

Schedule Override
The First, go to the Setpoint screen.

Scroll or tap

(any direction)

Heat SP

Cool SP

Adjust your setpoint

by scrolling clockwise

or counterckwise

View current zone

temperature

Home Screen

Setpoint Screen

Tap anywhere

(or simply wait)

return to

Home Screen

The sun icon is

displayed when

overridden

OVERRIDE ACTIVE

(Occupied mode)

The moon icon

indicates

unoccupied mode

Scroll clockwise

to override

67.5

79.5

67.5

79.5


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

14

VAV Zone Controller 

(PL-C1000-VAV)

INT Port: Incoming Modbus RS485 communication from digital

sensor 

-OR-

 Remote computer with Prolon Focus software

Digital Input for night setback / Standby mode

Multi-function analog input

Common for all the inputs

Temperature setpoint (0-10K potentiometer)

Room temperature sensor (10K thermistor)

Output 5 (analog 0-10VDC) (Max Current: 40 mA)

Output 4 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 3 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 2 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 1 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Power source of the controller (24 VAC - Class 2)

NET Port: Incoming Modbus RS485 communication

- OR -

 BACnet MS/TP

32-122 °F (0-50 °C) Non-condensing

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

15

INT Port: Incoming Modbus RS485 communication from digital

sensor 

-OR-

 Remote computer with Prolon Focus software

Digital Input for night setback / Standby mode

Multi-function analog input

Common for all the inputs

Temperature setpoint (0-10K potentiometer)

Room temperature sensor (10K thermistor)

Output 5 (analog 0-10VDC) (Max Current: 40 mA)

Output 4 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 3 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 2 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Output 1 - Isolated or source, TRIAC 24 VAC

(max current: 300 mA)

Power source of the controller (24 VAC - Class 2)

NET Port: Incoming Modbus RS485 communication

- OR -

 BACnet MS/TP

cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

16

VAV Zone Controller 

(PL-VC2000)

Service pin

General purpose analog input

(0-5 VDC, 4-20mA, 10K thermistor)

Supply / Radiant / Zone / Occupancy / Discharge

Digital sensor (T1000, T500 or T200) /

Remote computer with Focus

Analog output (0-10 VDC) (max current: 40 mA)

Network communication

Digital output - Isolated Triac

Dry contact (24 VAC) (max current: 750 mA)

Power source of the controller

(24 VAC - Class 2)

Airflow Sensor (PL-VC2000-PI)

Airflow sensors are only included in the PL-VC2000-PI

models only. Adding an airflow sensor to the Prolon VC2000

lets it regulate the airflow as well as temperature in a zone, 

independently of the static pressure variations of the system.

The default flow sensor has a range of 0 to 2 in H20

(0 to 500 Pa). Depending on the flow cross used, this

translates to roughly 0-3500 ft/min.

32-122 °F (0-50 °C) Non-condensing

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

17

Service pin

General purpose analog input

(0-5 VDC, 4-20mA, 10K thermistor)

Supply / Radiant / Zone / Occupancy / Discharge

Digital sensor (T1000, T500 or T200) /

Remote computer with Focus

Analog output (0-10 VDC) (max current: 40 mA)

Network communication

Digital output - Isolated Triac

Dry contact (24 VAC) (max current: 750 mA)

Power source of the controller

(24 VAC - Class 2)

Airflow Sensor (PL-VC2000-PI)

Airflow sensors are only included in the PL-VC2000-PI

models only. Adding an airflow sensor to the Prolon VC2000

lets it regulate the airflow as well as temperature in a zone, 

independently of the static pressure variations of the system.

The default flow sensor has a range of 0 to 2 in H20

(0 to 500 Pa). Depending on the flow cross used, this

translates to roughly 0-3500 ft/min.

cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1


background image

REV 1.0  /   PL-QCK-WSENSOR/VC2000-EN

18

Compliance

Technical Specifications

Digital Sensor (PL-T1000)
  FCC Compliant to CFR47, Part 15, Subpart B, Class B
  Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B) / NMB-3(B)
  RoHS Directive (2002/95/EC)

VAV Zone Controller (PL-C1000-VAV / PL-VC2000)
  cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
  CAN/CSA-C22.2 No. 2015-12, Signal Equipment
  FCC Compliant to CFR47, Part 15, Subpart B, Class B
  Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B)/NMB-3(B)
  RoHS Directive (2002/95/EC) 

FCC User Information

This device complies with Part 15 of the FCC Rules. Operation is subject to the 

following two conditions: (1) this device may not cause harmful interference, and 

(2) this device must accept any interference received, including interference that 

may cause undesired operation. 

Industry Canada 

This Class (B) digital apparatus meets all the requirements of the Canadian

Interference-Causing Equipment regulations.

Cet appareil numérique de la Classe (B) respecte toutes les exigences du

Réglement sur le matériel brouilleur du Canada.

PL-RS / PL-T200

Supply: 24 VAC ±10%, 50/60 Hz

Consumption: 2 VA max

PL-T500 / PL-T1000

Supply: 24 VAC ±10%, 50/60 Hz

Consumption: 5 VA max

PL-C1000-VAV

Supply: 24 VAC ±10%, 50/60 Hz

Consumption: 2 VA (Typ), 32 VA (Input)

PL-VC2000

Supply: 24 VAC ±10%, 50/60 Hz, Class 2

Consumption: 3 VA (Typ), 5 VA (Max),

24 VA (Input)