CC1N7153en
14.10.2002

Siemens Building Technologies

HVAC Products

ISO 9001

7

153

Oil Burner Controls

LAL...

Oil burner controls

·

 

With or without air pressure supervision for checked air damper control

·

 

Flame supervision with
– photoresistive detector QRB1..., or
– blue-flame detector QRC1..., or
– selenium photocell detector RAR...

The LAL... and this Data Sheet are intended for OEMs which integrate the oil
burner controls in their products!

Use

-

 

For the control and supervision of oil atomization burners

-

 

For burners of medium to high capacity

-

 

For intermittent operation (at least one controlled shutdown every 24 hours)

-

 

Can be universally used with multistage or modulating burners

-

 

Suited for use with stationary air heaters

LAL1...

- Yellow- and blue-flame burners without air pressure supervision

LAL2...

- Yellow-flame burners with air pressure supervision

LAL3.25

- For special applications, e.g. burners of incinerator plants
  (for details, refer to «Type summary» and «Notes»)

LAL4...

- Yellow- and blue-flame burners with air pressure supervision

For burner controls used in connection with burners for continuous operation, refer to
Data Sheet 7785 (LOK16...).

 


background image

2/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Warning notes

To avoid injury to persons, damage to property or the environment, the following
warning notes should be observed!

Do not open, interfere with or modify the unit!

·

  Before performing any wiring changes in the connection area of the LAL…, com-

pletely isolate the burner control from the mains supply (all-polar disconnection)

·

  Ensure protection against electric shock hazard by providing adequate protection

for the burner control’s connection terminals

·

 

Check to ensure that wiring is in an orderly state and that the wires are firmly con-
nected

·

 

Press the lockout reset button / operation button only manually (applying a force of
no more than 10 N), without using any tools or pointed objects

·

 

Do not press the lockout reset button on the unit or the remote reset button
for more than 10 seconds since this damages the lockout relay in the unit

·

  Fall or shock can adversely affect the safety functions. Such units may not be put

into operation, even if they do not exhibit any damage

 


background image

3/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Engineering notes

·

 

Install switches, fuses, earthing, etc., in compliance with local regulations

·

  Connect valves and other plant components as specified in the burner manufac-

turer’s documentation

H

N

L

EK2

AL

21

1 2

1(3)

3

M1

M2

R

4

5

6

7

BV2

BV1

Z

SA

15

16 17 18

a

z

M

20

19

9

LR

7153a03/0302

24

m

LK

11 10

8

22

B

v

LP

14

12

13

23

LAL2

1 2

3

4

5

6

7

8

9

10

QRB1...

22

24

+

RAR...

SB

W



Connect safety limit thermostats (manual reset) in the line (e.g. «SB»)

‚

Remote reset
When connecting lockout reset button «EK2» between terminals 21 and
- 3: For remote reset only
- 1: For remote reset and remote emergency shutdown
With LAL…: Required switching capacity of
- switching devices connected between terminals 4 and 5 (refer to «Technical data»)

ƒ

With LAL2... / LAL3... / LAL4...: Required switching capacity of
- switching devices connected between terminal 12 and «LP» (refer to «Technical data»)
- «LP»  (refer to «Technical data»)
When using series connection, the control contacts of other devices contained in the burner plant must be con-
nected as follows:
To terminal 4 or 5 

®

 contacts that must be closed from startup to controlled shutdown 

®

 otherwise no startup

or shutdown
To terminal 12 (not with LAL1...) 

®

 contacts that must only be closed on startup 

®

 otherwise no startup

„

To terminal 14 (not with LAL1...) 

®

 contacts that must be closed no later than at the beginning of «t3» or «t3´»

and that must remain closed until controlled shutdown occurs 

®

 otherwise lockout

…

Maximum current draw, refer to «Technical data»

†

«Z» connected to terminal 15 

®

 «t3´» and «t3n»

‡

Connection of «BV...» to terminal 20, refer to «Connection examples»

ˆ

When using burners without air damper, or with an air damper not controlled and monitored by the LAL…, ter-
minal 8 must be connected to terminal 6

‰

Wire link «B» clearly marked on the underside of the LAL…
When wire link «B» is fitted, the LAL... initiates lockout if loss of flame occurs during operation. For repetition of
the startup sequence, wire link «B» on the plug-in section of the LAL... must be cut away. Just cutting is not
permitted!

Š

For the permissible lengths and laying of detector cables, refer to «Flame supervision»

Mounting notes

·

 

Ensure that the relevant safety regulations are complied with

 


background image

4/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Installation notes

·

 

Installation work must be carried out by qualified staff

·

 

Live and neutral conductors may not be mixed up

Electrical connection of the flame detector

It is important to achieve practically disturbance-free signal transmission:

·

 

Never run the detector cable together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate low-capacitance cable

·

 

Observe the permissible cable lengths (refer to «Technical data»)

·

  Always run high-voltage ignition cables separately, with the greatest possible dis-

tance to the unit and to other cables

Commissioning notes

·

 

Commissioning work must be carried out by qualified staff

·

  When commissioning the plant or when doing maintenance work, make the follow-

ing safety checks:

Safety check

Anticipated response

a)

Burner startup with flame detector
darkened

Lockout at the end of «TSA»

b)

Burner startup with flame detector
exposed to extraneous light

Lockout after 40 seconds at the
latest

c)

With wire strap «B»:
Simulation of loss of flame during
operation. For that purpose, darken
the flame detector during operation
and maintain this state

Lockout

d)

Without wire strap «B»:
Simulation of loss of flame during
operation. For that purpose, darken
the flame detector during operation
and maintain this state

Repetition followed by lockout at the
end of «TSA»

Standards

Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)

89 / 336 EEC

- Low-voltage directive

73 / 23 EEC

Service notes

·

 

Maintenance work must be carried out by qualified staff

·

  Each time a unit has been replaced, check to ensure that wiring is in an orderly

state and that the wires are firmly connected

Disposal notes

The unit contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.

 


background image

5/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Mechanical design

-

 Plug-in 

design

-

 

Exchangeable unit fuse (including spare fuse)

Difference to LAL1... / LAL2... / LAL4...:

-

 

Extraneous light does not initiate lockout
– during burner off times
– during the prepurge time

-

 

Extraneous light prevents burner startup

-

 

Made of impact-proof and heat-resistance black plastic

-

 

Lockout reset button with viewing window; located behind it:
– Lockout warning lamp
– Lockout indicator
   - coupled to the spindle of the sequence switch
   - visible in the transparent lockout reset button
   - uses easy-to-remember symbols to indicate the type of fault and the point
     in time lockout occurred

-

 

Base and plug-in section of the LAL... are designed such that only burner controls
of the LAL... family can be plugged in

-

 24 

connection 

terminals

-

 

Auxiliary terminals «31» and «32»

-

 

3 earth terminals terminating in a lug for earthing the burner

-

 

3 neutral conductor terminals
– prewired to terminal 2

-

 

14 knockout holes for cable entry by means of cable glands
– 8 at the side
– 6 in the bottom of the base

-

 

6 lateral threaded knockout holes for cable entry glands Pg11 or M20

Type summary

Switching times are given in the order of the startup sequence, valid for 50 Hz mains frequency. At 60 Hz frequency, switching times
are about 17 % shorter.

Flash steam generators

Universal use

Medium- or heavy-oil

burners

Flame supervision with QRB1... or QRC1... for blue-flame
burners

LAL1.25

LAL4.25A27

Flame supervision with QRB1... or RAR...
Choice of air pressure supervision
Choice of semiautomatic startup

LAL2.14

LAL2.25

LAL2.65

Same as LAL2.25 with the following exception:
No lockout, but prevention of startup in the case of extrane-
ous light

Special applications such

as incinerator plants

LAL3.25

t1

10 s

22.5 s

67.5 s

TSA

4 s

5 s

5 s

t3

2 s

2.5 s

2.5 s

t3´

From the start ¹)

t3n

10 s

15 s

15 s

t4

8 s

7.5 s

7.5 s

t5

4 s

7.5 s

7.5 s

t6

10 s

15 s

15 s

t7

2 s

2.5 s

2.5 s

t8

30 s

47.5 s

92.5 s

t10

6 s

10 s

10 s

t11

Optional

t12

Optional

t13

10 s

15 s

15 s

t16

4 s

5 s

5 s

t20

32 s

35 s

12.5 s

¹) 

With air pressure supervision: From the time the air pressure signal is received

LAL...

LAL3.25

Housing

Plug-in base

 


background image

6/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Ordering

When ordering, please give full type reference according to «Type summary».

Accessories

Plug-in base

- With Pg11 threads for cable entry glands

AGM410490500

- With M16 threads for cable entry glands

AGM13.1

Technical data

Mains voltage
- With LAL1... / LAL2... / LAL3... incl.

AC 230 V –15 / +10 %
AC 100 V –15 %...AC 110 V +10 %

Mains frequency

50...60 Hz ±6 %

Unit fuse (built-in)

T6,3H250V to DIN EN 60 127

Primary fuse (external)

max. 10 A (slow)

Weight

-

 LAL...

-

 Plug-in 

base

approx. 1,000 g
approx. 165 g

Flame detectors:

-

 QRB1...

-

 QRC1...

-

 RAR...

refer to Data Sheet 7714
refer to Data Sheet 7716
refer to Data Sheet 7713

Power consumption

approx. AC 3.5 VA

Mounting position

optional

Degree of protection

IP 40, when fitted, with the exception of the

connection area (terminal base)

Safety class

II

Perm. input current at terminal 1

max. 5 A (peaks of 20 A / 20 ms)

Perm. current rating of control terminals

3, 6, 7, 9...11 and 15...20

max. 4 A (peaks of 20 A / 20 ms)

Required switching capacity of switching

devices

-

 

Between terminals 4 and 5

-

 

Between terminals 4 and 12

-

 

Between terminals 12 and «LP»

-

 

Between terminals 4 and 14

-

 «LP»

1 A, AC 250 V
1 A, AC 250 V
1 A, AC 250 V
5 A (peaks of 20 A)
5 A

Degree of protection

IP 00

Cable connection

screw terminal
cross-sectional area of wire: 0.5...1.5 mm²

With stranded wires

use adequate ferrules

Transport

DIN EN 60 721-3-2

Climatic conditions

class 2K2

Mechanical conditions

class 2M2

Temperature range

-50...+60 °C

Humidity

< 95 % r.h.

Operation

DIN EN 60 721-3-3

Climatic conditions

class 3K5

Mechanical conditions

class 3M2

Temperature range

-20...+60 °C

Humidity

< 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

General unit data LAL...

Plug-in base AGM...

Environmental
conditions

 


background image

7/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

LAL1... with

LAL2... / LAL3... 

with

LAL4... with

QRB1...

QRC1...

QRB1...

RAR...

QRB1...

QRC1...

Min. detector current required
at AC 230 V

95 µA

80 µA

8 µA

6,5 µA

95 µA

80 µA

Max. permissible detector
current with no flame

12 µA

12 µA

0.8 µA

0.7 µA

12 µA

12 µA

Max. detector current that can
occur

160 µA

130 µA

35 µA

30 µA

160 µA

130 µA

Instrument’s +pole

To terminal

23

To terminal

23

To termi-

nal 22

To terminal 22

To terminal

23

To termi-

nal 23

Length of detector cable
In the same cable as the
control lines

Max. 30 m

---

Not per-

mitted

---

Max. 30 m

---

Separate cable in cable duct

Max. 1000 m

---

20 m

RAR7...: 30 m

Max. 1000 m

---

3-core cable

---

Max. 1 m

---

---

---

Max. 1 m

2-core cable for the detector
line (bl, sw); separate single-
core cable for the live con-
ductor (br)

---

Max. 20 m

---

---

---

Max. 20 m

Shielded cable (e.g. RG62,
shield insulated)

---

---

200 m

RAR8...: 100 m

---

---

Shield

---

---

To termi-

nal 23

---

---

---

23

LAL1...

22

µA DC

+

QRB1...

7153v01/0498

LAL4...

23

22

LAL1...
LAL4...

1

sw

bl

br

µA DC

+

QRC1...

7153v05/0498

23

LAL2...
LAL3...

22

+

µA DC

QRB1...

7153v02/0498

24

LAL2...
LAL3...

22

+

µA DC

+

RAR...

7153v03/0498

Flame supervision

 


background image

8/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Function

2-stage expanding flame burner

Modulating expanding flame burner

FS

BV2

min.

LK

0...

M

R

100%

LR

BV1

M1
M2

Z

~

M

P

R

T

t12

t4

t16

t5

A

B

C

D

t11

t13

t6

t7

t1

t3

t3n

TSA

t3´

7153a09/0498

R

LR

t5

t11

t12

t13

FS

min.

LK

0...

M

100%

RV

A

BV1

M2

Z

~

M

P

R

M1

T

t4

t3

t7

t1

TSA

B

t6

C

D

7153a10/0498

BV...

Fuel valve

M...

Fan or burner motor

FS

Flame signal amplifier

R

Control thermostat or pressurestat

LK

Air damper

RV

Modulating fuel valve

LR

Load controller

Z

Ignition transformer

The following features of the LAL... afford a high level of safety:

-

 

Detector and flame simulation test are restarted on completion of the afterburn time
«t13». Open or not fully closed fuel valves immediately initiate lockout at the end of
«t13». The test ends on completion of the prepurge time «t1» of the next startup
sequence

-

  The correct functioning of the flame supervision circuit is automatically checked

during each burner startup sequence

-

 

The control contacts for the release of fuel are checked to ensure they have not
welded «t6»

-

 

A built-in unit fuse protects the control contacts against overloads

-

 

Burner operation with or without postpurge

-

 

Fan motors with a current draw of up to 4 A can be connected directly 

®

 starting

current max. 20 A (for max. 20 ms)

-

 

Separate control outputs for
– preignition from start command
– postignition until shortly before the burner startup sequence is completed
– short preignition with postignition up to the end of «TSA»

-

  Separate control outputs for the actuator’s positioning directions OPEN, CLOSE

and MIN

-

 

Checked air damper operation to ensure prepurging with the nominal air volume

-

 Checked 

positions:

- CLOSED or MIN on startup 

®

 low-fire position

- OPEN at the beginning of prepurging
-  MIN on completion of prepurging
If the actuator does not drive the air damper to the required position, the burner
startup sequence will be stopped

-

 

2 control outputs for the release of the second and third output stage or for load
control

-

 

When load control is enabled, the control outputs for the actuator will be galvani-
cally separated from the burner control’s control section

-

 Connection 

facilities 

for

– remote lockout warning device
– remote reset
– remote emergency shutdown

-

 

In addition, with LAL2... / LAL3... / LAL4...:
– possibility of air pressure supervision with functional test of the air pressure
   monitor on startup
– possibility of semiautomatic burner startup

Legend

General

Control of the burner

 


background image

9/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

-

 

Flame detector and flame simulation test are made automatically during burner off
times and the prepurge time «t1»

-

 

If loss of flame occurs during operation, the burner control will initiate lockout

-

 

If automatic repetition of the startup sequence is required, the clearly marked wire
link on the plug-in section of the LAL... must be cut away 

®

 start repetition

-

 

Burner control is not in the lockout position

-

 

Sequence switch is in its start position

®

 with LAL1..., voltage is present at terminals 4 and 11

®

 with LAL2... / LAL3... / LAL4..., voltage is present at terminals 11 and 12

-

 

Air damper is closed

-

 

End switch «z» for the CLOSED position must feed power from terminal 11 to ter-
minal 8

-

  Contact of the limit thermostat or pressure switch «W» and the contacts of any

other switching devices in the control loop between terminals 4 and 5 must be
closed 

®

 e.g. a control contact for the oil preheater’s temperature

With the exception of LAL1...

-

 

Normally closed contact of the air pressure switch must be closed 

®

 «LP» test

Startup sequence

A

Start command by «R»:

®

 «R» closes the start control loop between terminals 4 and 5

-

 

The sequence switch starts to run
  - Only prepurging, fan motor at terminal 6 receives power
  - Pre- and postpurging, fan motor or flue gas fan at terminal 7 receives
    power on completion of «t7»

-

 

On completion of «t16», the control command for opening the air damper is
delivered via terminal 9

-

 

Terminal 8 receives no power during the positioning time

-

 

The sequence switch continues to run only after the air damper has fully
closed

t1

Prepurge time with air damper fully open:

-

 

The correct functioning of the flame supervision circuit is checked during
«t1»

-

 

The burner control will initiate lockout if correct functioning is not ensured

With 

LAL2... / LAL3... / LAL4...

:

Shortly after the beginning of «t1», the air pressure switch must change over
from terminal 13 to terminal 14

®

 otherwise, the burner control will initiate lockout

®

 start of the air pressure check

t3

Short preignition time:
«Z» must be connected to terminal 16, release of fuel via terminal 18

Flame supervision

Preconditions for
burner startup

 


background image

10/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

t3´

Long preignition time:
«Z» connected to terminal 15.

With 

LAL1...

:

«Z» is switched on when start command is given.

With 

LAL2... / LAL3... / LAL4...

:

«Z» is switched on when «LP» changes over

®

 no later than at the end of «t10»

-

 

On completion of «t1», the LAL... drives the air damper to the low-fire posi-
tion via terminal 10

®

 the low-fire position is defined by the changeover point of auxiliary switch

    «m» in the actuator

-

 

During the positioning time, the sequence switch maintains its position

®

 until terminal 8 receives power via «m»

-

 

The motor of the sequence switch is switched to the control section of the
LAL...

®

 positioning signals delivered to terminals 8 now have no impact on the

    further startup sequence and on subsequent burner operation

TSA

Ignition safety time:
On completion of «TSA», a flame signal must be present at terminal 22. It must
be available until controlled shutdown occurs

®

 otherwise, the burner control will initiate lockout and lock itself in the lockout

position

t3n

Postignition time:

-

 

«Z» must be connected to terminal 15

-

 

With short preignition, «Z» remains on until «TSA» has elapsed

®

 connection to terminal 16

t4

Interval «BV1 – BV2» or «BV1 - LR»:

-

 

On completion of «t4», voltage is present at terminal 19

-

 

The voltage is required to power «BV2» connected to auxiliary switch «v» in
the actuator

t5

Interval:

-

 

On completion of «t5», terminal 20 receives power. At the same time, con-
trol outputs 9 to 11 and input 8 are galvanically separated from the LAL...’s
control section

®

 LAL... is now protected against reverse voltages from the load control

     circuit

-

 

With the release of «LR» at terminal 20, the startup sequence of the LAL...
ends

-

 

After a few idle steps (steps with no contact position changes), the se-
quence switch switches itself off

B

Operating position of the burner

B-C

Burner operation:

-

 

During burner operation, «LR» drives the air damper to the nominal load or
low-fire position, depending on heat demand

-

 

Release of the nominal load takes place via auxiliary switch «v» in the ac-
tuator

-

 

In the event of loss of flame during operation, the LAL... will initiate lockout

-

 

For automatic start repetition, the clearly marked wire link «B» on the plug-
in section of the LAL... must be cut away

 


background image

11/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

C

Controlled shutdown:
In the case of controlled shutdown, «BV...» will immediately be closed. At the
same time, the sequence switch is started to program «t6»

C-D

Sequence switch travels to start position «A»

t6

Postpurge time:

-

 

Fan «M2» connected to terminal 7

-

 

Shortly after the start of «t6», terminal 10 receives power

®

 air damper is driven to the MIN position

-

 

Full closing of the air damper starts only shortly before «t6» has elapsed

®

 initiated by the control signal at terminal 11

-

 

During the following burner off time, terminal 11 is live

t13

Permissible afterburn time:
During «t13», the flame signal input may still receive a flame signal

®

 no lockout

D-A

End of control program:

®

 start position

As soon as the sequence switch has reached the start position – having thereby
switched itself off – the flame detector and flame simulation test will start again

During burner off times, the flame supervision circuit is live.

When the start position is reached:
With 

LAL1...

, a voltage signals is fed to terminal 4

With 

LAL2... / LAL3... / LAL4...

, a voltage signal is fed to terminal 12

 


background image

12/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Control sequence under fault conditions and lockout indication

Whenever a fault occurs, the sequence switch stops and with it the lockout indicator.

The symbol appearing above the reading mark indicates the type of fault:

·

 

One of the contacts is not closed (also refer to
«Preconditions for burner startup»)

3

No start

·

 Extraneous 

light:

Lockout during or after completion of the control
program
Examples:
– Nonextinguished flame
– Leaking fuel valves
– Faulty flame supervision circuit

·

 

No OPEN signal at terminal 8 from the
changeover end switch «a»

=

Interruption of startup
sequence

·

 

Terminals 6, 7 and 15 are live until fault has
been corrected

Does not apply to LAL1...:

·

 

No air pressure indication at the beginning of the
air pressure check

P

Lockout

·

 

Air pressure failure after the air pressure check

Lockout

·

 

Defect in the flame supervision circuit

·

 No 

positioning 

signal 

at 

terminal 8 from the aux-

iliary switch «m» for the low-fire position

>

Interruption of startup
sequence

·

 

Terminals 6, 7 and 15 are live until fault has
been corrected

1

Lockout

·

 

No flame signal at the end of the safety time

I

Lockout

·

 

Flame signal has been lost during operation

a-b

Startup sequence

b-b´

Idle steps
(with no contact confirmation)

b (b´)-a Postpurge program

LAL1

LAL2..., LAL3..., LAL4...

·

 

Burner control can immediately be reset after lockout:
– Do not press the lockout reset button for more than 10 seconds

·

 

The sequence switch always travels to the start position first
– After resetting
– After rectification of a fault that led to shutdown
– After each power failure
During this period of time, power is only fed to terminals 7 and 9...11.

·

 

Then, the LAL.... will program a new burner startup sequence

Lockout indicator

 


background image

13/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection diagrams 

(for variants, refer to «Connection examples»)

LAL1...

H

N

t3

n

t3

´

C

D
A

L

EK2

AL

21

1

A

S

2

1(3)

3

W

R

4

5

6

7

t6

B

A

t7

BV2

BV1

Z

SA

15

16 17 18

a

z

M

20

19

9

LR

t4

t3

T

S

A

t5

t1

t12

t16

t11

ma

z

23

m

11 10

8

22

B

t1

3

1

v

7153a01/0398

LK

S

QRB1...

sw

bl

br

QRC1...

23

22

1

SB

M1

M2

LAL2... / LAL3...

H

N

t3

n

t3

´

C
D
A

L

EK2

AL

21

1

A

S

2

1(3)

3

R

4

5

6

7

t6

B

A

t7

BV2

BV1

Z

SA

15 16 17 18

a

z

M

20

19

9

LR

t4

t3

T

S

A

t5

t1

t12

t16
t11

ma

z

7153a02/0498

24

m

LK

11 10

8

22

B

t1

3

1

v

LP

14

12

13

t1

0

P

23

S

QRB1...

SB

M1

M2

W

24

22

+

RAR...

 


background image

14/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection diagrams 

(for variants, refer to «Connection examples»)

LAL4...

H

N

t3

n

t3

´

C
D
A

L

EK2

AL

21

1

A

S

2

1(3)

3

R

4

5

6

7

t6

B

A

t7

BV2

BV1

Z

SA

15 16 17 18

a

z

M

20

19

9

LR

t4

t3

T

S

A

t5

t1

t12

t16

t11

ma

z

7153a04/0498

24

m

LK

11 10

8

22

B

t1

3

1

v

LP

14

12

13

t1

0

P

23

S

QRB1...

SB

M1

M2

W

sw

bl

br

QRC1...

23

22

1

 


background image

15/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection diagrams

L

H

1

AS

br1

a b

I

a

b

ar1

4

W

R

5

B

fr1

a

b

IX

XI

b

a

a

b

XIII

XII

L1

br2

AR

BR

M

E

A

IV

II

X

VIII

b

aa

b a

b

a

b

a

b

V

VI

III

SM

M

a

b

a

b

ar3

VII

a

b

XIV

fr2

FR

V

N

M1

M2

6

7

ar2

QRB1...

22

23 24

8

10

11

20

9

19

17

18

16

15

2

21

3

EK1*

N

AL

EK2*

1 (3)

H

Z

BV1

BV2

v

a

z

m

M

LK

LR

7153a07/0496

S

SA

sw

bl

br

QRC1...

23

22

1

SB

L

H

1

AS

br1

a b

ar1

4

W

R

B

5

fr1

a

b

IX

LP

XI

XIII

AR

br2

L1

EK1*

b

a

a

b

M

E

3

21

2

1 (3)

EK2*

AL

H

N

Z

BV1

15

16

18

BR

A

13

14

XII

IV

a

b

II

X

b

a a

b

M1

M2

N

6

7

12

ar2

a

b

I

fr2

a

b

b

a

VIII

V

VI

17 19 9

20

LR

M

v

a

z

BV2

m

LK

7153a08/0598

M

1110

8

SM

III

ar3

VII

a

b

b

a

b

a

a

b

XIV

FR

V

22

23 24

QRB1...

22

23 24

RAR...

+

NTC

SA

SB

Do not press the lockout reset button for more than 10 seconds!
For the connection of the safety shutoff valve, refer to the plant diagram provided by
the burner supplier.

LAL1...

LAL2... / LAL3...

 


background image

16/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection diagrams 

(cont’d)

L

H

1

AS

br1

a b

ar1

4

W

R

B

5

fr1

a

b

IX

LP

XI

XIII

AR

br2

L1

EK1*

b

a

a

b

M

E

3

21

2

1 (3)

EK2*

AL

H

N

Z

BV1

15

16

18

BR

A

13

14

XII

IV

a

b

II

X

b

a a

b

M1

M2

N

6

7

12

ar2

a

b

I

fr2

a

b

b

a

VIII

V

VI

17 19 9

20

LR

M

v

a

z

BV2

m

LK

7153a17/0498

M

1110

8

SM

III

ar3

VII

a

b

b

a

b

a

a

b

XIV

FR

V

22

23 24

QRB1...

SA

SB

sw

bl

br

QRC1...

23

1

22

Do not press the lockout reset button for more than 10 seconds!
For the connection of the safety shutoff valve, refer to the plant diagram provided
by the burner supplier.

Sequence diagram

A

t11

t7

t1

t12

t4

t3

t3n

B

C

D

t6

t3´

TSA

t5

t20

t13

t10*

t16

t8

Positions of lockout indicator

Control output
at terminal:

P

1

*

20

4

7

19

8

17

15

9

9

10

*

I

II

III

IV

V

VI

VII

VIII

IX

X

XI

XII

XIII

XIV

a
b

a
b
a
b

a
b

a
b
a
b

a
b

a
b
a
b

a
b
a
b

7153d01e/0402

*

12

16

11

18

* These data do not apply to LAL1...

LAL4...

 


background image

17/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Legend

a

Changeover end switch for air damper’s

NTC

Resistor with negative temperature coefficient

OPEN position

QRC1... Blue-flame detector

AL

Remote lockout indicator (alarm)

QRB1... Photoresistive detector

AR

Load relay with «ar...» contacts

RAR...

Selenium photocell detector

AS

Unit fuse

S

Fuse

B

Wire link

SA

Air damper actuator

bl

Blue

SM

Synchronous motor of sequence switch

br

Brown

sw

Black

BR

Lockout relay with «br...» contacts

v

In the actuator: Auxiliary changeover switch

EK... Lockout reset button

for position-dependent release of fuel

FR

Flame relay with «fr...» contacts

V

Flame signal amplifier

H

Mains isolator

W

Limit thermostat or pressure switch

L...

Lockout warning lamp

z

In the actuator: End switch for air damper’s

LP

Air pressure switch

CLOSED position

m

Auxiliary switch for air damper’s
MIN position

Control signals delivered by the LAL...

Required input signals:

Permissible input signals

If these signals are not present during   or 

,

the burner control will stop the startup sequence or
initiate lockout

TSA Ignition safety time

t8

Duration of startup sequence

t1

Prepurge time with air damper fully open

(excluding «t11» and «t12»)

t3

Preignition time, short («Z» connected to termi-
nal 16)

t10

Only with LAL2... / LAL3... / LAL4...: Interval from

t3´

Preignition time, long («Z» connected to terminal
15)

startup to the beginning of the air pressure check

t3n

Postignition time («Z» connected to terminal 15)

t11

Air damper running time to the OPEN position

t4

Interval between voltage at terminals 18

t12

Air damper running time to the low-fire position

and 19 («BV1-BV2»)

(MIN)

t5

Interval between voltage at terminals 19

t13

Permissible afterburn time

and 20 («BV2» load controller)

t16

Interval to the OPEN command for the air damper

t6

Postpurge time (with «M2»)

t20

Not with all LAL…: For self-shutdown

t7

Interval between start command and voltage

of the sequence switch

at terminal 7 (start delay time for «M2»)

 


background image

18/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection examples

Connection of actuators without
changeover end switch for the
CLOSED position

19

20

9

11

10

8

LR

SA

a

z

M

LK

BV2

N

v

7153a11/0498

«z» adjusted for low-fire air volume

Control of actuator during operation
by control signals fed to terminal 17

18

19

17

9

20

11

10

8

6

LR

N

BV1

BV2

LK

7153a12/0498

For signal path, refer to «Connection
diagrams»

Control of «BV...» via terminal 20

19

20

9

11

10

8

6

N

BV2

BV3

7153a14/0498

Relay is not required if «BV3» at
terminal 20 is hydraulically series-
connected with «BV2».
«BV2» is controlled by terminal 18 or
19.

®

 Burner with no air damper or

    with air damper not controlled
    by the LAL…

Wiring required with LAL2... for op-
eration with no air pressure supervi-
sion

13

12

14

4

5

6

R

W

d1

N

M

7

7153a15/1001

If an auxiliary contact «d1» of the fan
contactor is included in the circuit as
shown in the diagram, ignition and
release of fuel take place only when
the contact is closed.

Semiautomatic startup

3

12

13

14

4

5

AL

I

W

N

L3

LP

0

7153a16/0498

The burner is switched on manually
by pressing the «I» button.
Then, the LAL... programs startup
and flame supervision.
Burner shutdown is also made manu-
ally by pressing the «0» button, or
automatically when limit thermostat or
pressure switch «W» responds.
«L3» indicates when the burner is
ready for startup. It extinguishes
shortly after the burner is started up.
For other connections, refer to «Con-
nection diagrams».

 


background image

19/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Connection examples 

(cont’d)

2-stage expanding flame burner

M

N

SA

Z

BV1

IV

13 12

N

3

BV2

LR

11

7

1 6

4

9

LK

5

2

10 8

20

15
16

(t3´/t3n)

(t3)

17

18

19

9

11

10

8

I

II

III

7153a05/1195

LR

SA

L...

BV1

BV2

Load control with a 2-position controller.
During burner off times, the air damper is closed.

FS

BV2

min.

LK

0...

M

R

100%

LR

BV1

M1
M2

Z

~

M

P

R

T

t12

t4

t16

t5

A

B

C

D

t11

t13

t6

t7

t1

t3

t3n

TSA

t3´

7153a09/0498

Control of actuator according to the single-wire control
principle.

®

 For actuator «SA» type SQN..., refer to Data Sheet

    7808; for other connections, refer to «Connection
    diagrams»

 Pre- and postignition when the ignition

            transformer is connected to terminal 15

Modulating expanding flame burner

16

8

20

LR

N

9

11

M

10

Z

N

17

18

19

RV

LK

SA

a

m

z

BV1

7153a06/1195

L...

LR

SA

BV1

RV

Load control with modulating controller with galvanically
separated control contacts for positioning directions
OPEN and CLOSE.

R

LR

t5

t11

t12

t13

FS

min.

LK

0...

M

100%

RV

A

BV1

M2

Z

~

M

P

R

M1

T

t4

t3

t7

t1

TSA

B

t6

C

D

7153a10/0498

During burner off times, the air damper is fully closed.
When using actuators with changeover end switch «z»
for the CLOSED position, terminals 10 and 11 must be
interconnected.
For other connections, refer to «Connection diagrams».

 


background image

20/20

Siemens Building Technologies

CC1N7153en

HVAC Products

14.10.2002

Dimensions

Dimensions in mm

1,5

12

3

7

15

,5

6

18,9

25

25

7,5

5

15

15

15

27,5

27,5

37

7,

5

10

3

103

7153m02/0396

5,2x6,7

40

18,5

13,5

5,7

51,

5

40

26

,8

51

,5

5,7

12,8

51,5

40

51,5

25

15

1

12,

8

5

,7

7,5

18,9

4,4

1,5

5,2x6,7

5,2

715

3m

01

/0

39

6

31

32

N

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

LAL... with plug-in base
AGM...

Plug-in base AGM...
(Pg11 or M16 threads)

ã

2002 Siemens Building Technologies

Subject to change!