Global Leader in Integrated Room Automation Systems 

 

 

 

Confidential 

Copyright © 2010 INNCOM 

e528 Smart Digital Thermostat 

Product Guide 

Overview 

INNCOM's e4 Smart Digital Thermostat is a powerful, multi-purpose Direct Digital Control (DDC) device that 
can control virtually any HVAC system found in hotel guestrooms. 

The three e4 models meet different application requirements. The e528 and e527 are 
wired and are typically used for new installation. The e529 is battery-powered and is 
designed to meet the needs of existing properties where rewiring is not practicable.  

This document describes Model e528; information on the e529 and e527 can be found 
in their respective product guides. 

Application 

In its most basic form, the e528 functions as a programmable DDC thermostat, 
automatically adjusting fan speeds and valves to achieve set temperature (

Note:

 

Guests can manually select heat or cool by pressing the OFF/AUTO button and 

cycling through OFF, AUTO, HEAT and COOL). The e528 is also an “intelligent” 
device capable of linking ancillary sensors and serving as an information gateway. 
For example, coupled with a magnetic door switch (wired or wireless), motion detectors, and other devices, the 
e528 becomes the brain of a highly effective Energy Management System (EMS) application, communicating EMS 
information requirements to central servers. It comes standard with five relays and can be equipped with an on-
board Infrared (IR) or radio frequency (RF) transceiver and Passive Infrared (PIR) motion detector.  

The e528 interfaces with all common HVAC unit voltage configurations (24 volt to 277 volt). The e528 can be 
installed in a wired or wireless INNCOM guestroom control system, which makes installation feasible and 
affordable in either new construction or retrofit installations. 

Through interfaces with other devices and sensors, the e528 supports the following functions: 

 

Remote HVAC control 

 

Guestroom HVAC diagnostics 

 

Remote room occupancy indication 

 

Automatic lighting control 

 

Remote mini-bar access reporting 

 

Remote smoke detector annunciation 

 

Central Electronic Lock control 

 

Humidity control 

 

Remote drape control 

 

Outside temperature display 

 

Peak demand load shedding 

 

Property/Building Management System (PMS/BMS) interface 

 

Figure 1 e528 Digital Thermostat

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   2   o f   1 8

 

 

 

A centrally controlled EMS package is created when the e528 is connected to the property's Central Interface 
Network (CINET) with a pair of low voltage wires or by the property’s high-speed TCP/IP network with the 
addition of a TCT (an Ethernet gateway device). RF networking is possible with radio equipped models. 

The e528 features a guest-friendly graphic interface with intuitive controls (Figure 2). A user guide for the e528, 
written primarily for installers and facility management personnel, is available (see References below). 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless Communication 

2.4Ghz wireless RF 

Table 1 e528 RF Characteristics 

Performance 

0dB 

20dB 

RF Data Rate 

250kbps 

250kbps 

Antenna Type 

SMT 

SMT 

Indoor Range  

70ft 

100ft 

Outdoor/ RF line-of-sight range 

540ft 

1000ft+ 

Transmit Power 

1mW  

10mW  

Receive Sensitivity 

-94.6dBm 

-94.6dBm 

Frequency Band 

2.4Ghz 

2.4Ghz 

Encryption 

AES-128 

AES-128 

Protocol 

802.15.4 

802.15.4 

Frequency Channels 

11-26 

11-26 

Ranges are determined by performing an RF link quality test using two identical e528 thermostats containing 
radios as defined in tables 2 and 3. The maximum distance threshold is based on a 95% overall link quality. 
Outdoor ranges were conducted in a low noise, free air environment. Indoor ranges are for reference. Indoor 
ranges are impacted by the ambient environmental noise floor, and building construction materials.  

Figure 2 e528 Graphic Interface

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   3   o f   1 8

 

 

 

IR5 (Infrared) 

Table 2 e528 IR5 Characteristics 

Performance 

IR5 

Indoor Range 

Up to 80ft 

IR Data Rate 

2500 bps 

The  IR  Eye5  works  within  INNCOM's  System-5  protocol  and  can  be  used  in  a  fluorescent  light  environment. 
However, it may be subject to interference from plasma televisions, and care must be taken in situating the device 
if a plasma television is present. 

Installation Requirements 

Location: 

The e528 must be located on a partitioning interior wall, approximately 1.5 m (5 ft) above the floor, in a 

site of average temperature. It is important to ensure that the thermostat is located away from direct sunlight or 
radiant heat, air discharge grills, stairwells, outside doors, steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical or radio interference. The unit should not be placed on an outside 
wall or behind a door. It is essential that the e4 is mounted flush to the wall and mounted level in both the horizontal 
and vertical planes; incorrect mounting can degrade IR, PIR, and temperature measurement performance. 

Installation Requirements for e4 equipped with PIR Motion Detection 

The e4 thermostat can be equipped with a PIR detector to augment the energy management scheme by detecting 
motion in the guestroom. Consider the PIR’s view angle, range characteristics, and mounting position to ensure 
proper coverage. Figure 3 below shows the ranges of the flat and standard PIRs. 

 

 

 

Flat PIR Detection Range (Single Pyro) 

Standard PIR Detection Range (Dual Pyro)

 

Figure 3 PIR Detection Ranges 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   4   o f   1 8

 

 

 

 

 

Mounting: 

The e528 is usually mounted on a standard double-gang (4 x 4) junction box. If mounted on a single-

gang box, the left side (display side) of the e528 overlaps the wall area to the left of the junction box. A low-
voltage mounting plate, mud ring, or low-voltage caddy may be used for mounting 24 volt applications. 

To mount the e528: 

1)

 

Remove the two small screws at the base of the e528. 

2)

 

Pull the bottom of the back-mounting plate slightly away from the front housing and then pull the back-
mounting plate down. 

3)

 

Position the back plate insulator within the mounting plate as shown in Figure 4. 

4)

 

Attach the mounting plate to the junction box, using the mounting screws provided with the e528. Ensure 
that the plate is mounted with the raised arrow pointing UP. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
To simplify installing and removing the e528, the headers and sockets described below and shown in Figure 5 are 
located on the back of the e528. These accept pre-made wiring harnesses provided by INNCOM. (

Note:

 Take care 

to note which e528 model is being used. Each model has slightly changed headers and connectors as identified in 
the drawings below.)

 

Figure 4 Mounting Assembly

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   5   o f   1 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 Back View Showing Headers and Sockets

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   6   o f   1 8

 

 

 

Headers 

The headers for the e528.2G, 3G and 4G

*

 thermostats are substantially the same, though the layouts and labeling on 

the PCB are slightly different (see Figure 5 above). The statements and tables below detail only the headers that differ 
in function. 

Low Voltage comm / device connector

: This header accepts the provided 6-pin harness used to connect low 

voltage communication, door/window position switch, and other room devices to the e528. Table 3 shows the 
pinout for the 2G low voltage comm / device connector and lists typical functions for each pin. Table 3a shows 
pinout and function for the 3G and 4G. For specifics, refer to the as-built wiring diagrams. 

Table 3. e528 2G Low Voltage Harness (P/N 62-1462) Pinout 

Wire Color 

Female 

Connector 

Male 

Connector 

Function 

Comment 

Brown 

Common 

GND 

Red 

12VDC Out/In 

12VDC Supply 

Orange 

S5 Bus Data Tx/Rx or IN 2 

Communication Bus 

Yellow 

IN 1 

Door, Window, PIR, Other 

Green 

CINET B 

RS485 Twisted Pair 

Blue 

CINET A 

RS485 Twisted Pair 

Table 3a. e528 3G/4G Low Voltage Harness (P/N 62-1467) Pinout 

Wire Color 

Female 

Connector 

Male 

Connector 

Function 

Comment 

Brown 

Common 

GND 

Red 

12VDC Out/In 

12VDC Supply 

Orange 

S5 Bus Data  

Communication Bus 

Yellow 

Digital Input 

Door, Window, PIR, Other 

Green 

No Connection 

 

Blue 

No Connection 

 

External temperature control sensor:

 This header accepts the wiring harness from an external temperature probe 

that can be used to supply the e528 with remote temperature measurements. The e528 uses a 10K 1% thermistor 
for external temperature measurement. This external temperature sensor can be used to monitor room 
temperature at a different location from where the e528 is mounted or to monitor pipe water temperature. 

RS485 Networks: (refer to Figure 5) 

E528.2G 

can be connected to the RS485 FLN5 network by installing the 02-9496 module, then connecting the 

RS485 network to pins 5 and 6 of the low voltage comm /device connector as described in Table 3 above. 

E528.3G

 cannot act as the media gateway for in-room traffic towards the RS485 network. The most common 

way to connect the e528.3G is to connect a PC-485.S5 (P/N: 01-9905) on the S5bus. 

E528.4G 

E528.4G to 2G RS485 Networked Application: with or without door switch input (

See Figure 6 below)

 

 

Using the adapter (P/N 203-251), connect the harness from the wall box (P/N 62-1462) previously 
connected to the thermostat being replaced to H1 of the adapter. 

 

Connect the harness H3 (rainbow) of 203-251 to the low voltage comm/device connection of the e528.4G 

                                                            

*

 “2G,” “3G,” and “4G” are internal INNCOM product designations used for convenience to differentiate 

individual hardware configurations. No difference in device capability or effectiveness is implied. Due to end-of-
life for certain 2G and 3G components, the e528.4G is now the standard INNCOM install, but 2G and 3G 
installations are still supported. 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   7   o f   1 8

 

 

 

 

Connect the harness H2 (black) of 203-251 to the RS485 header of the e528.4G 

NOTE: 

Take care to not reverse the connections to the e528.4G!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E528.4G New Installation 

Stand alone application with/without door switch input 

 

Using the harness (P/N 62-1467), make the appropriate wire connections, then plug the harness into the 
low voltage comm/device connection of the e528.4G  

RS485 Networked Application with/without door switch input 

(See Figure 7)

 

 

Using the harness (P/N 62-1467), make the appropriate wire connections, then plug the harness into the 
low voltage comm/device connection of the e528.4G.  

 

Using the adapter (P/N 203-250) and P/N 62-1532-B.12 cables, connect the RS485 A pair to the two pin 
RS485 In header and the RS485 B pair going to the next thermostat to RS485 Out header on the 203-250. 

 

Connect the harness of 203-250 to the RS485 network header of the e528.4G. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7 E528.4G New RS485 Networked Application 

Figure 6 4G to 2G RS485 Networked Application

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   8   o f   1 8

 

 

 

E528.4G Retrofit Installation 

The e528.4G can be used to retrofit an application where a legacy e528 was used. Follow the procedure below: 

4G to 2G Standalone application: with/without door switch input (no backhaul network) 

 

Using the adapter (P/N 203-013) connect the harness from the wall box (P/N 62-1462) previously 
connected to the thermostat being replaced to H1 of the adapter (see Figure 8). 

 

Connect the harness of 203-013 to the low voltage comm/device connection of the e528.4G. 

 

 

 

 

 

 

 

 

 

 

 

Molex 10-position female socket

: This female socket accepts the provided 10-pin Molex connector pre-wired 

with 8-inch, color-coded wiring leads. These leads should be connected to the 24VAC or 100–277VAC power, 
valve/fan control wiring from the FCU, or other HVAC device with wire nuts inside in the wall junction box in 
accordance with the wiring diagram provided by INNCOM. 

Note: For installations in which all leads are not required, the extraneous leads should be cut off at the Molex connector. 

Figure 8 shows the pinout for the 10-position Molex male connector supplied with all relay output models of the 
thermostat. The end view of the male connector from the wire insertion side with the pin numbers is indicated. 
This is the same as looking at the female connector point on the back of the e528. 

Typical functions for each wire are listed in Tables 4 and 5. For specifics, refer to the as-built wiring diagrams. 

 

 

 
 
 
 
 
 
 
 
 
 
 

 
 

Table 4. 24VAC Harness Color Code, Pinout, and Typical Functions 

Figure 8 e528.4G to 2G Standalone application

 

Figure 9 10-Pin Molex Connector (Part No. 62.1455 or 62.1464.R)

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   9   o f   1 8

 

 

 

24VAC harness (INNCOM Part # 62-1464 R) 

Pin 

Color 

Typical Function 

Green 

Ground 

Red 

24VAC 

Black 

Common 

Blue 

High Fan 

Brown 

Medium Fan or Second Stage Heat 

Yellow 

Cold Water Valve (FCU) or Compressor Signal 
(Heat Pump) 

White 

Hot Water Valve (FCU) or Reversing Valve 
(Heat Pump) 

Grey 

Valve Power 

Violet 

Fan Power 

10 

Orange 

Low Fan 

Table 5. 100-277VAC Harness Color Code, Pinout, and Typical Functions 

100-277VAC harness (INNCOM Part # 62-1455) 

Pin 

Color 

Typical Function 

Green 

Ground 

Black 

Line 

White 

Neutral 

Yellow 

High Fan 

Orange 

Medium Fan or Second Stage Heat 

Red 

Cold Water Valve (FCU) or Compressor Signal (Heat 
Pump) 

Brown 

Hot Water Valve (FCU) or Reversing Valve (Heat 
Pump) 

Grey 

Valve Power 

Violet 

Fan Power 

10 

Blue 

Low Fan 

Wiring:

 The steps below provide an overview of the wiring process. Refer to the as-built wiring diagrams 

provided for exact details. 

1.

 

If applicable, use wire nuts to connect the 6-pin low-voltage harness wires to the applicable low-voltage 
communication (if e528 is part of a wired RS485 centrally controlled system), door/window switch, or 
external PIR wiring within the electrical box (Figure 8). Plug the 6-pin low voltage harness onto the e528 low 
voltage comm. / device connection header. 

2.

 

Use wire nuts to connect the 10-pin Molex wiring harness to the power and valve/fan control signal wires 
within the electrical box. 

3.

 

Plug the pre-wired 10-pin connector into the female receptacle at the back of the e528. 

4.

 

Hook the tabs at the top rear of the e528 housing into the matching depressions at the top of the mounting 
plate and rotate the bottom of the housing toward the wall until it snaps into place on the mounting plate. 

5.

 

Secure the housing to the mounting plate with the two small screws removed in Step 1 of the 

Mounting

 

section. 

6.

 

Apply power to the e528 by closing the applicable supply breaker. Verify that the e528 powers up. Several 
values should begin appearing on the LCD display. 

7.

 

Once installed and connected to power, the e528 Digital Thermostat typically requires some configuration, 
specifically: 

 

If installing the e528 as part of a networked, centrally controlled EMS, a unique network address must be 
assigned to the e528. This is done by entering Service Parameter mode on the e528 and changing the 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 0   o f   1 8

 

 

 

values of Parameters 10, 11, and 12, which hold the 5-digit network address of the e528. This 5-digit 
number is typically the room number in most applications. A “Room List” document is typically 
available that lists all rooms and the associated values to set into Parameters 10, 11, and 12. Refer to 
Reference A, Section 5.1, for complete instructions for setting the e528 network address. 

 

If the particular HVAC equipment installed was not known when the e528 was shipped, the fan and 
heat/cool control outputs of the e528 must be configured to correctly operate the installed HVAC 
equipment. Setting the appropriate HVAC control parameters of the e528 to the required values and 
resetting the device reconfigures the e528 to properly control most HVAC units. Refer to Reference A, 
Section 5.2, for instructions on changing the e528 HVAC related parameters, if required. 

NOTE:  If  installing  01-9560  64K  memory  e528  Digital  Thermostats,  be  aware  that  these  devices  support  the 
INNCOM  ES-1  Flash  Memory  Module.  The  ES-1  provides  the  ability  to  copy  HVAC  related  parameter  settings 
from  a  “golden”  e528  that  has  previously  been  installed  in  a  room  and  had  its  HVAC  related  parameters  set 
correctly  and  verified  operationally  with  the  HVAC  equipment.  Once  these  settings  are  copied  to  the  ES-1 
module, plugging the ES-1 into a new thermostat automatically uploads the settings. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 7 Electrical Box Connections Line and Low Voltage

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 1   o f   1 8

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Load Specifications 

The following load specification table (Table 6) describes the submitted load characteristics for testing and UL 
certification of UL 873. The device complies with the requirements of CAN/CSA C22.2 No. 24-93. 

Table 6. Load Specifications 

MODEL 

e528-A2L2-I0P0-

00WH 

e528-A3L2-I0P0-

00WH 

e528-A1L2-

I0P0-00WH 

e528-B0L2-

I0P0-00WH 

e528-C0L2-

I0P0-

00WH 

e528-B1L2-I0P0-

00WH 

Voltage 

24VAC 

24VAC 

24VAC 

100-240VAC 

220-
277VAC 

100-277VAC 

Heat 
Relay K4-5 

3 amps 
125-277VAC 
General purpose 

3 amps 
125-277VAC 
General purpose 

240 VA PD 

240 VA PD 

240 VA PD 

3 amps 
125-277VAC 
General purpose 

Cool 
Relay K4-5 

3 amps 
125-277VAC 
General purpose 

3 amps 
125-277VAC 
General purpose 

240 VA PD 

240 VA PD 

240 VA PD 

3 amps 
125-277VAC 
General purpose 

High Fan 
Relay K1 

3 amps 
125-277VAC 
General purpose 

3 amps 
125-277VAC 
General purpose 

2.2 FLA 
13.2 LRA 

3.6 FLA 
21.6 LRA 

3.6 FLA 
21.6 LRA 

3.6 FLA 
21.6 LRA 

Medium Fan 
Relay K2-3 

3 amps 
125-277VAC 
General purpose 

3 amps 
125-277VAC 
General purpose 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

Low Fan 
Relay K2-3 

3 amps 
125-277VAC 
General purpose 

3 amps 
125-277VAC 
General purpose 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

2.2 FLA 
13.2 LRA 

 

Figure 8 Electrical Box Connections 24VAC

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 2   o f   1 8

 

 

 

Technical Specifications 

Table 7. Technical Specifications 

Power Requirements 

24 VAC at 50/60 Hz, 24 VDC nominal, 2.4 VA

 

(e528-3xx/7xx and e528-4xx) 

100 to 277 VAC at 50/60 Hz, 2.4 VA (e528-8xx)

 

Relay Contact Rating 

See Table 4.

 

Triac Relay Contact Rating 

50 m at minimum, 250 m at maximum (e528-4xx)

 

Recommended Wire Size 

18 gauge

 

Thermostat Measurement Range 

33 to 99 degrees F (1 to 37 degrees C) 

Outdoor Air Temperature 

0 to 99 degrees F (-18 to 37 degrees C) 

Display Resolution 

Whole degree F, 0.5 degree C (0.1 degree F in test mode) 

Standard Deadband 

2 degrees F (1 degree C) between heating and cooling 

Degrees C/Degrees F Display 

Toggle Button located on front display 

Ambient Operating 

41 to 149 degrees F (5 to 65 degrees C), 0-95% RH noncondensing 

Ambient Storage 

33 to 149 degrees F (1 to 65 degrees C) 

Dimensions 

(H x W x D) 4.7 x 4.7 x 1.2 in. (120 x 120 x 30 mm) 

Shipping Weight 

0.6 lb (0.27 kg) 

Approvals 

UL listed #873, CAN/CSA C22.2 No. 24-93 File #E202540/Part 15 of the FCC Rules 

RF Specifications 

See TXR RF Datasheet 

 

Warning

:  Power supply MN PS564 must be used to provide power. 

 
FCC ID: GTC202150TXR, or GTC202152TXR  
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a 
residential installation. This equipment generates uses and can radiate radio frequency energy and, if not 
installed and used in accordance with the instructions, may cause harmful interference to radio communications. 
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does 
cause harmful interference to radio or television reception, which can be determined by turning the equipment off 
and on, the user is encouraged to try to correct the interference by one of the following measures:  
— Reorient or relocate the receiving antenna.  

— Increase the separation between the equipment and receiver.  

— Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.  

— Consult the dealer or an experienced radio/TV technician for help.  
 
Any changes or modifications not expressly approved by the party responsible for compliance could void the 
user's authority to operate this equipment.  
IC ID: 1609A-202150TXR, or 1609A-202152TXR 

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two 
conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference 
that may cause undesired operation of the device. 

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 3   o f   1 8

 

 

 

Le présent appareil est conforme aux CNR d’industrie Canada applicables aux appareils 
radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) 
l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter 
tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en 
compromettre le fonctionnement.

 

 

Ordering Specifications 

Note: Ordering schemes are based on the latest PCB revision. The tables and examples in this section are correct 
only to the date of this document version. Verify part numbers and inventory availability before ordering. 

The IR-only e4 ordering part number (OPN) scheme uses only 3 digits to indicate power supply and options: 

 

 

 

 

 

 

 

The 

“X”

 number is the first of the three digits and designates the power supply type 

Table 8. IR only e528 Power Supply Ordering 

 

 

 

 

 

 

Power Supply Type 

12VDC S5BUS (Power Supply removed, powered by external X06 or X05 

24VAC 50/60 Hz 

24VAC Triac  

Nominal Voltages:  100–240VAC 50/60 Hz w/ 3.6 FLA High Fan Relay 

Nominal Voltages:  265–277VAC 50/60 Hz w/ 3.6 FLA High Fan Relay 

24VAC 50/60 Hz (02-9561) 

100-277VAC Hz (02-9560) 

24VAC 50/60 Hz (02-9565) 

Figure 9 IR Only E528.2G OPN Scheme

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 4   o f   1 8

 

 

 

The “YY” numbers are the second and third digits and designate the option or combination of options. When 
more than one option is selected, the “YY” option numbers are added, as in Examples B and C shown below. 

YY Option # 

Option 

Description 

00 

None 

No Options 

01 

IR3 
 

02-9464.1 IR3 PCBA option 

02 

IR5 

02-9467 IR5 PCBA option 

03 

IR3+ 

02-9464.3 IR3+ PCBA option 

04 

Humidity Sensor 

08 

PIR 

Passive IR Motion Sensor 

16 

DM 

Do-Not-Disturb & Make-Up-Room Buttons 

32 

P2 

Flat PIR 

Example A 

100V-277VAC e

4

 with no options  =  Model e

4

-800 [X = 8, YY = 00]

 (with 2.2 FLA high fan relay)

 

Example B 

100-277V e4 with H + PIR options  =  Model e4-812 [X = 5, YY = (04 {H} + 08 {PIR}) = 12] 

(with 3.6 FLA high fan relay)

 

Example C 

OLD 24V e4 with IR5 + PIR options  = 

Model e4-310 

[X = 3, YY = (02 {IR5} + 08 {PIR} = 10] 

NOTE: This assembly would be 01-9560.310 and calls for a 03-9460 which uses old P supply and 9496. 

For the RF capable thermostats, the complexity engendered by the multiplicity of power supplies, logic boards, 
and communications and other option call for a larger OPN incorporating a more granular scheme (Figure 13, 
below). Table 9 lists the options available for the RF E528: 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9. RF capablee528 Ordering Options 

Model 

This character set defines the model name for the e528. 

OP/N Code 

Description 

Part Number 

e528 

DDC Thermostat 

01-9911 

Figure 10 e528 3G OPN

 

Figure 11 RF Capable e528 OPN

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 5   o f   1 8

 

 

 

Power Supply 

This character set defines the power supply options available for the e528. 

OP/N Code 

Power Supply Type 

Part Number 

A0 

No power supply 

A1 

24VAC 50/60Hz power supply (300 series) 

02-9461 

A2 

24VAC 50/60Hz power supply (700 series) 

02-9561 

A3 

24VAC 50/60Hz power supply (900 series*) 

02-9565.C1 

B0 

110-240VAC 50/60Hz w/ 3.6FLA high fan relay (500 series) 

02-9460.5 

B1 

120-277VAC 50/60Hz w/ 2.2FLA high fan relay (800 series) 

02-9560 

C0 

265-277VAC 50/60Hz w/ 3.6FLA high fan relay 

02-9460.6 

Logic Board 

This character set defines the logic board options available for the e528. 

OP/N Code 

Logic Board Type 

Part Number 

L0 

No logic board 

L3 

e528 3G hermetic enclosure w/ 0dB radio 

02-9911.L1 

L4 

e528 3G hermetic enclosure w/ 20dB radio 

02-9911.L2 

L6 

E528 4G logic board with 0dB radio 

202-150 

L7 

E528.4G logic board with 20dB radio 

202-152 

Communication 

This character set defines the auxiliary communication options for the e528. 

OP/N Code 

Auxiliary Communication Type 

Part Number 

I0 

No auxiliary communication device 

I5 

IR5 only 

02-9467.e8d 

Motion Detection/Output 

This character set defines the motion detection/output options for the e528s (

Note:

 photos are for reference only. 

Actual product models may differ slightly in appearance). 

OP/N Code 

Motion Detection/Output Type 

Part Number 

P0 

 

Blank 

53-0446 

P1 

 

Standard PIR 

02-9465-B 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 6   o f   1 8

 

 

 

OP/N Code 

Motion Detection/Output Type 

Part Number 

P2 

 

Flat PIR 

02-9499 

Q0 

 

DND/MUR only 

53-0448 

Q1 

 

Manual heat/cool selection only 

TBD 

Q2 

 

ecoMODE only 

53-9209 

R0 

 

Standard PIR with DND/MUR 

53-0448 

R1 

 

Standard PIR with heat/cool 
output 

TBD 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 7   o f   1 8

 

 

 

OP/N Code 

Motion Detection/Output Type 

Part Number 

R2 

 

Standard PIR with ecoMODE 

53-9210 

R4 

 

Flat PIR with ecoMODE 

53-9211 

Humidity Sensor 

This character set defines the humidity sensor options for the e528. 

OP/N Code 

Humidity Sensor Option 

Part Number 

No humidity sensor 

Humidity sensor 

02-9463 

Logo/Housing 

This character set defines the housing logo for the e528. 

OP/N Code 

Logo Option 

Part Number 

No logo 

INNCOM logo 

JCI logo (Johnson Controls) 

Color 

This character set defines the housing color options for the e528. 

OP/N Code 

Housing Color Option 

Part Number 

WH 

White 

EA 

Eagle Almond 

BK 

Black 

XX 

Custom 

Ordering Example: 

e528-A1-L2-I5-P2-1-O-WH = An e528 with a 24VAC 50/60Hz power supply (300 series), 64K logic board, IR5 
auxiliary communication device, flat PIR motion detector, humidity sensor, no logo, manufactured in white. 

Figure 14 indicates the area of the thermostat that has options VISIBLE to the guest. 

 

 


background image

E 5 2 8   P r o d u c t   G u i d e  

P a g e   1 8   o f   1 8

 

 

 

 

 

References 

e528 Operation Manual, INNCOM Document 3000, Version 2.0, Dated April 29, 2005 

Document Revision History 

REVISION 

DATE ISSUED 

REASON FOR CHANGE 

First issue 

26-Apr-2006 

 

v1 

30-Jul-2007 

Reformatted for consistency with other product guides. Information 
about the other e4 models added to the Overview section. Information on 
all ordering options and new features added to the Ordering section. 

v2 

Not issued 

Product photos updated. Part number corrected. Figure 3 redrawn. 

v3 

27-Jun-2008 

New Figure 2 added (PIR range figures) and figure numbers changed to 
accommodate the added figure. 

v4 

30-Jun-2008 

Switched to new document format. 

v5 

30-Jun-2008 

Error in Figure 4 corrected; font discrepancies corrected. 

v6 

18-Feb-2010 

Reformatted to new template, RF data updated 

v6.1 

22-Apr-2010 

OP/N rewritten to include old scheme; photos updated. 

v6.2 

28-Oct-2010 

Added 3G pinout note  

v7.0 

05-Apr-2012 

Added 4G information 

 

Figure 12 Area of Thermostat with Options Visible to the Guest